Issues with Solar photovoltaic (PV) power supply systems | 17

Solar
photovoltaic (PV)
power supply
systems
This article looks to aid the understanding of
some of the complex issues associated with PV
installations.

By Mark Coles
Photovoltaic (PV) systems are Requirements for Photovoltaic
unique. Common logic used in (PV) Generators (currently in
other methods of electricity development by IEC TC 82) Best in the
generation, such as motor will set out general business
generators, wind turbines, UPS installation and safety
and Stirling Engines cannot be requirements for the PV
applied. Significant changes equipment.
are occurring in
standardisation at international Systems NICEIC TechTalks are
standard level where PV The Scope of Section 712 in BS the best place to get
technical updates
systems are concerned. 7671:2008 includes PV power
supply systems including
Standards
Section 712 of BS 7671:2008
systems with a.c. modules but,
currently, excludes any form of
and new product
is Solar photovoltaic (PV) battery storage. There are many information.
power supply systems; the systems across the world Tony Cable, Industry Legend
and TechTalk presenter
section is likely to remain that feature battery storage
largely unchanged in the first but no single standard has
amendment of the standard, as yet been developed to At NICEICs new series of
TechTalks you will learn about:
due for publication in June reflect this.
Proposed amendments
2011. The origins of Section to PIRs
712 of BS 7671:2008 can be System components Microgeneration
found in IEC 60364-7-712 as There are many possible Technologies for smart
no CENELEC HD currently configurations of PV systems homes and buildings
Proposed amendments
exists. Note that IEC 60364-7 but, first well look at the
to BS 7671
712 is intended to provide components and their
requirements for the function.
installation of PV systems. To find a venue click or call:
Requirements for the Modules www.niceicdirect.com
equipment IEC 62548 Photovoltaic or PV cells 0843 290 3483
Installation and Safety convert sunlight directly into

Winter 10 | IET Wiring Matters


18 | Issues with Solar photovoltaic (PV) power supply systems

PV system on open ground

electricity and generate d.c. A this produces an open


typical single PV cell is a thin circuit voltage of around
semiconductor wafer made of 0.6 volts.
highly purified silicon;
crystalline silicon is the most PV cells are interconnected to
widely used. During form a PV module. The
manufacture, the wafer is module is manufactured with
doped: boron on one side, the cells laminated between
producing a surplus of a transparent front sheet PV system incorporated into a building
electrons; phosphorous on (usually glass) to allow
the other side, which has a sunlight to pass and a Strings can, of course, be Depending on the location and
deficit of electrons. When the protective waterproof material connected in a parallel land available, PV arrays are
wafer is bombarded by on the back. A module is the formation to create an frequently roof-mounted,
sunlight, photons in the smallest commercially array. sometimes integrated directly
sunlight knock off some of available unit bought as a into the fabric of a building,
the excess electrons creating panel. Optimum operation is but they can also be fixed to
a voltage difference between achieved when modules are framework on open ground.
the two sides as the excess Modules can be linked in direct sunlight but
electrons try to move to the together to create a electricity is still generated Figures 712.1 and 712.2 of
deficit side. In silicon cells string, i.e. connected in series. on cloudy days. BS 7671:2008 show bypass

Fig 1 First fault on a PV array Fig 2 Second fault on a PV array

IET Wiring Matters | Winter 10


20 | Issues with Solar photovoltaic (PV) power supply systems

and blocking diodes and some are effectively floating. flow and, as shown in Figure 2, Blocking diodes can be
reference is made to blocking Note that Figures 1 and 2 modules can be driven into a installed in series with each
diodes in Regulation show a floating system as reverse current situation. Each string and are sometimes
712.512.1.1. Diodes, which neither conductor (L+ or L-) is module will have a maximum suggested as a method of
pass d.c. in one direction only, connected to Earth. The permitted reverse current as preventing reverse currents
are used to bypass or block modules metallic framework is stated by the manufacturer that could result in such fires.
reverse currents caused by shown to feature protective but, of course, the Blocking diodes are prevalent
faults. bonding as may be required in manufacturer has no idea in systems installed in Japan
certain installations where the fault will occur. High but evidence demonstrates
Consider the scenario where a reverse currents will overstress that such diodes can fail to
fault has developed on one d.c. Unlike a TN-S electrical and overheat the units which short-circuit (through voltage
module connecting a current supply, for example, where the can result in fire if overcurrent transients), which negates the
carrying part with the modules neutral or star point of a protection is not fitted. reverse current protection
metallic framework, shown as generator is connected to without anyone being aware of
first fault (Fig 1). Earth, a PV system is For a design where the the failure. Therefore, blocking
effectively floating, hence, this number of parallel connected diodes should not be used as a
There are many PV first fault doesnt affect the strings is such that the replacement for overcurrent
configurations, for example, for operation of the array nor does potential reverse fault current protection in PV strings.
functional reasons, some are it present any great risk of exceeds the manufacturers
earthed on the positive side electric shock. The problems permitted reverse current, Bypass diodes are installed
whilst some on the negative . arise when a second fault some form of overcurrent in parallel with modules to
Some are referenced to the occurs. protection is required. This is prevent reverse voltage
mains supply through a usually achieved by the use of conditions that could develop
non-separated Depending on where the faults string fuses. on modules as a result of
(transformerless) inverter and occur, circulation currents will shading, caused by, for

In-house training

to keep your company ahead


Your employees are your biggest asset so ensure they are
working to the highest standards.
The IET, home of electrical excellence and experts in the wiring regulations, offers professional
training courses, on your premises and tailored to meet your companys needs.

Our training courses


cover BS 7671, inspection & testing and all aspects of electrical safety

save you money in your training budget and travel/accommodation costs

will motivate and upskill your workforce

can be designed to match the skills and abilities of your workforce

are flexible enough to cater for small classes or large groups

Companies taking advantage So whatever your training


requirements, why not chat with one
of our training courses include of our short course experts?
BBC For friendly advice call us on 01438
767289 or email coursesreg@theiet.org
British Sugar

Debenhams

Network Rail

London Underground

www.theiet.org/company-training
The Institution of Engineering and Technology (the IET) is registered as a Charity in England and Wales (No. 211014)
and Scotland (No. SC038698). Michael Faraday House, Six Hills Way, Stevenage, SG1 2AY, UK.

IET Wiring Matters | Winter 10


Issues with Solar photovoltaic (PV) power supply systems | 21

research on very large arrays by basic insulation of live parts sinusoidal currents up to
has shown that, particularly on or by barriers or enclosures in 1,000Hz, pulsating direct
thin film modules, low accordance with Section 416, residual currents and
resistance readings, e.g. and smooth direct residual
500k on systems circa (ii) fault protection is provided currents.
1,000 modules, are common by simple separation of the
at daybreak. Module cracking separated circuit from other One other issue regarding
and delamination can occur circuits and from Earth. RCDs is pertinent here. In a
under some conditions, which domestic installation which
compromises the modules Simple separation can be will not be under the
insulation leading to opinions provided by having separate supervision of a skilled or
that modules are not class II. windings within a transformer instructed person, Regulations
Once a first fault is found or or, particularly for PV 522.6.6 and 522.6.7 would
detected it is paramount that installations, the manufacturer require that additional
owners of the system repair/ may state that the inverter protection by an RCD
replace/remove the faulty provides this function. meeting the requirements of
module immediately as Regulation 415.1 is installed.
Manufacturers label fixed to a research has shown that a The current standard for type This differs from the RCD
module second fault on that module B RCDs, which will be requirement in Regulation
is not far off. reflected in Section 712 of 712.411.3.2.1.2 which calls
example, buildings obstructing BS 7671:2008(2011), is IEC for a type B RCD to provide
direct sunlight, a covering of Inverters 62423:2009; note that there fault protection.
snow or array loading Inverters are used to change is not an EN or BS version of
conditions. d.c. generated by PV modules this standard as yet. L Further reading
into a.c for use on a.c. Regulation 712.411.3.2.1.2 BS 7671:2008 Requirements for
The design of some types of systems. The output of the does not state an operating Electrical Installations
modules require that one of inverter may, in some cases, time or residual operating IEC 62423:2009 - Type F and type
the live conductors is be connected and current; refer to Section 411 B residual current operated
connected to the main synchronised to the local and Table 41.1 of BS circuit breakers with or
earthing terminal of the a.c. electrical distribution network 7671:2008. without integral overcurrent
electrical system (functional and operate under the UKs protection for household and
earthing) as they need to be feed-in tariff scheme (see The concern is that d.c. fault similar uses
electrically biased in order to Wiring Matters Autumn currents can feed into the a.c. Guidance Note 1 Selection and
operate correctly. Such a 2010 Issue 36 for more side of the electrical Erection, The IET, 5th Edition
conductor may carry current in information) and also the installation and corrupt Electricity, Safety, Quality and
the event of a first fault. To Electricity, Safety, Quality and upstream devices, such as Continuity Regulations 2002 (as
mitigate this issue, some Continuity Regulations 2002 type A and type AC RCDs. amended)
manufacturers require that the (as amended) (ESQCR). Type B RCDs will provide L Thanks
functional earthing of their protection against d.c. Martin Cotterell Sundog Energy,
equipment is through a BS 7671:2008 has a earth fault currents; see co-convenor IEC TC 82 WG3
protective device which would particular requirement for Guidance Note 1 - Selection Ted Spooner University of New
operate upon detection of the inverters in Regulation and Erection for more South Wales, co-convenor IEC
first fault. 712.411.3.2.1.2. The information. Type B RCDs are TC 82 WG3
Regulation requires that if able to provide protection Eur.Ing Leon Markwell Ecovert
Much discussion has taken simple separation is not against alternating residual Bob Cairney SELECT
place within PV committees on provided between the a.c.
how to deal with module and d.c. side of the system
failures and faults. Some then a type B RCD is to be
inverters are pre-programmed installed to provide fault
to run an insulation resistance protection. Simple separation
test initiated at sunrise just as is a component part of
the modules begin to generate. Electrical Separation in
This is compounded by Regulation 413.1.1:
debates over the class of PV
modules, i.e. whether they are 413.1.1 Electrical separation
class I or class II. Many is a protective measure in
manufacturers state that which:
modules are class II but (i) basic protection is provided Large array installation

Winter 10 | IET Wiring Matters