INTRODUCTION

Date: 7th July 2008


J (P342/3/4) K (P345)
Hardware Suffix:
A (P391)
Software Version: 33
Connection Diagrams: 10P342xx (xx = 01 to 17)
10P343xx (xx = 01 to 19)
10P344xx (xx = 01 to 12)
10P345xx (xx = 01 to 07)
10P391xx (xx =01 to 02)
P34x/EN IT/I76 Introduction

MiCOM P342, P343, P344, P345 & P391

IT
Introduction P34x/EN IT/I76

MiCOM P342, P343, P344, P345 & P391 (IT) 1-1

CONTENTS

(IT) 1-

1. MICOM DOCUMENTATION STRUCTURE 3


2. INTRODUCTION TO MICOM 5
3. PRODUCT SCOPE 6 IT
3.1 Functional overview 6
3.2 Ordering options 11

FIGURES

Figure 1: Functional diagram 10


P34x/EN IT/I76 Introduction

(IT) 1-2 MiCOM P342, P343, P344, P345 & P391

IT
Introduction P34x/EN IT/I76

MiCOM P342, P343, P344, P345 & P391 (IT) 1-3

1. MiCOM DOCUMENTATION STRUCTURE


The manual provides a functional and technical description of the MiCOM protection relay
and a comprehensive set of instructions for the relays use and application.
The chapter contents are summarized below:
P34x/EN IT Introduction
A guide to the MiCOM range of relays and the documentation structure. General safety
aspects of handling Electronic Equipment is discussed with particular reference to relay
safety symbols. Also a general functional overview of the relay and brief application
summary is given. IT
P34x/EN TD Technical Data
Technical data including setting ranges, accuracy limits, recommended operating conditions,
ratings and performance data. Compliance with norms and international standards is quoted
where appropriate.
P34x/EN GS Getting Started
A guide to the different user interfaces of the protection relay describing how to start using it.
This chapter provides detailed information regarding the communication interfaces of the
relay, including a detailed description of how to access the settings database stored within
the relay.
P34x/EN ST Settings
List of all relay settings, including ranges, step sizes and defaults, together with a brief
explanation of each setting.
P34x/EN OP Operation
A comprehensive and detailed functional description of all protection and non-protection
functions.
P34x/EN AP Application Notes
This chapter includes a description of common power system applications of the relay,
calculation of suitable settings, some typical worked examples, and how to apply the settings
to the relay.
P34x/EN PL Programmable Logic
Overview of the programmable scheme logic and a description of each logical node. This
chapter includes the factory default (PSL) and an explanation of typical applications.
P34x/EN MR Measurements and Recording
Detailed description of the relays recording and measurements functions including the
configuration of the event and disturbance recorder and measurement functions.
P34x/EN FD Firmware Design
Overview of the operation of the relays hardware and software. This chapter includes
information on the self-checking features and diagnostics of the relay.
P34x/EN CM Commissioning
Instructions on how to commission the relay, comprising checks on the calibration and
functionality of the relay.
P34x/EN MT Maintenance
A general maintenance policy for the relay is outlined.
P34x/EN TS Troubleshooting
Advice on how to recognize failure modes and the recommended course of action. Includes
guidance on whom within AREVA T&D to contact for advice.
P34x/EN IT/I76 Introduction

(IT) 1-4 MiCOM P342, P343, P344, P345 & P391

P34x/EN SC SCADA Communications


This chapter provides an overview regarding the SCADA communication interfaces of the
relay. Detailed protocol mappings, semantics, profiles and interoperability tables are not
provided within this manual. Separate documents are available per protocol, available for
download from our website.
P34x/EN SG Symbols and Glossary
List of common technical abbreviations found within the product documentation.
P34x/EN IN Installation
IT Recommendations on unpacking, handling, inspection and storage of the relay. A guide to
the mechanical and electrical installation of the relay is provided, incorporating earthing
recommendations. All external wiring connections to the relay are indicated.
P34x/EN VH Firmware and Service Manual Version History
History of all hardware and software releases for the product.
Introduction P34x/EN IT/I76

MiCOM P342, P343, P344, P345 & P391 (IT) 1-5

2. INTRODUCTION TO MiCOM
MiCOM is a comprehensive solution capable of meeting all electricity supply requirements.
It comprises a range of components, systems and services from AREVA T&D.
Central to the MiCOM concept is flexibility.
MiCOM provides the ability to define an application solution and, through extensive
communication capabilities, integrate it with your power supply control system.
The components within MiCOM are:

P range protection relays; IT


C range control products;

M range measurement products for accurate metering and monitoring;

S range versatile PC support and substation control packages.


MiCOM products include extensive facilities for recording information on the state and
behavior of the power system using disturbance and fault records. They can also provide
measurements of the system at regular intervals to a control center enabling remote
monitoring and control to take place.
For up-to-date information on any MiCOM product, visit our website:
www.areva-td.com
P34x/EN IT/I76 Introduction

(IT) 1-6 MiCOM P342, P343, P344, P345 & P391

3. PRODUCT SCOPE
The MiCOM P342/3/4/5 generator protection relays have been designed for the protection of
a wide range of generators. The MiCOM P342 is suitable for protection of small to medium
size generators (1-10MVA) or can be used as back-up protection for larger generators. The
MiCOM P343 is suitable for protection of medium to large size generators (>10MVA) or more
important generators, providing generator differential, 100% stator earth fault via a 3rd
harmonic measuring technique, pole slipping and unintentional energization at standstill
protection in addition to the features of the P342. The P344 is similar to the P343 but
includes a second neutral voltage input for earth fault/interturn protection. The MiCOM P345
is suitable for protection of large generators (>50MVA) providing 100% stator earth fault
IT protection via a low frequency injection technique in addition to the features of the P344.
The P345 also includes 10 function keys for integral scheme or operator control functionality
and tri-color (red/yellow/green) LEDs. Rotor earth fault protection is provided by the P391
low frequency square wave injection, coupling and measurement unit connected to the rotor
circuit. The measurement of the rotor resistance is passed to the P342/3/4/5 via a current
loop output (0-20mA) on the P391 connected to one of the 4 current loop inputs on the
P342/3/4/5. The rotor ground fault protection is only available if the relay includes the CLIO
hardware option.

3.1 Functional overview


The P342/3/4/5 generator protection relays contain a wide variety of protection functions.
The protection features are summarized below:

PROTECTION FUNCTIONS OVERVIEW P34x


Phase segregated generator differential protection is provided
for high speed discriminative protection for all fault types. The
87 3/4/5
differential protection can be selected as biased or high
impedance or interturn.
Restricted earth fault is configurable as a high impedance or a
biased low impedance element. This can be used to provide
64 2/3/4/5
high speed earth fault protection and is mainly applicable to
small machines where differential protection is not possible.
Two definite time stages of power protection are provided and
each stage can be independently configured to operate as
reverse power (RP), over power (OP) or low forward power
(LFP) protection. The direction of the power measured by the
protection can be reversed by selecting the operating mode,
generating/motoring. The power protection can be used to
32R, 32L, provide simple back-up overload protection (OP), protection
2/3/4/5
32O against motoring (RP, generating mode), CB interlocking to
prevent overspeeding during machine shutdown (LFP,
generating mode) and loss of load protection (LFP, motoring
mode). The relays provide a standard 3 phase power
protection element and also a single phase power protection
element which can be used with a dedicated metering class
CT using the sensitive current input.
A two stage offset mho definite time impedance element is
provided to detect failure of the machine excitation. A power
40 2/3/4/5
factor alarm element is also available to offer more sensitive
protection.
Negative phase sequence thermal overload protection is
provided to protect against unbalanced loading which can
46T 2/3/4/5
cause overheating in the rotor. Both alarm and trip stages are
provided.
Introduction P34x/EN IT/I76

MiCOM P342, P343, P344, P345 & P391 (IT) 1-7

PROTECTION FUNCTIONS OVERVIEW P34x


A voltage dependent overcurrent (controlled or restrained) or
underimpedance protection is provided for back-up protection
of phase faults. The voltage dependent overcurrent protection
51V, 21 may be set as controlled or restrained with an Inverse Definite 2/3/4/5
Minimum Time (IDMT) or Definite Time (DT). There are 2
stages of underimpedance protection which may be set as
definite time only.
Four overcurrent protection stages are provided which can be
selected to be either non-directional, directional forward or
50/51/67 directional reverse. Stages 1 and 2 may be set Inverse 2/3/4/5 IT
Definite Minimum Time (IDMT) or Definite Time (DT); stages 3
and 4 may be set DT only.
Four definite time stages of negative phase sequence
overcurrent protection are provided for remote back-up
46OC protection for both phase to earth and phase to phase faults. 2/3/4/5
Each stage can be selected to be either non-directional,
directional forward or directional reverse.
Thermal overload protection based on I1 and I2 is provided to
protect the stator/rotor against overloading due to balanced
49 2/3/4/5
and unbalanced currents. Both alarm and trip stages are
provided.
Two stages of non-directional earth fault protection are
provided for stator earth fault protection. Stage 1 may be set
50N/51N 2/3/4/5
Inverse Definite Minimum Time (IDMT) or Definite Time (DT);
stage 2 may be set DT only.
Rotor earth fault protection can be provided by a low frequency
injection method. There are 2 stages of definite time under
resistance protection. An external injection, coupling and
measurement unit (P391) is required with this function. The
measurement of the rotor resistance is passed to the P34x via
64R 2/3/4/5
a current loop output (0-20mA) on the P391 connected to one
of the 4 current loop inputs on the P34x. The rotor ground fault
protection is only available if the relay includes the CLIO
hardware option. The injection frequency is selectable
0.25/0.5/1Hz via a jumper link in the P391
One sensitive earth fault element is provided for discriminative
earth fault protection of parallel generators. The protection
can be selected to be either non-directional, directional forward
or directional reverse. Either Zero sequence or negative
67N/67W sequence polarizing is available. 2/3/4/5
The Sensitive Earth Fault element can be configured as an
cos, Isin or Vcos (Wattmetric) element for application to
isolated and compensated networks.
Residual overvoltage protection is available for stator earth
fault protection where there is an isolated or high impedance
earth. The residual voltage can be measured from a broken
delta VT, from the secondary winding of a distribution
transformer earth at the generator neutral, or can be calculated
from the three phase to neutral voltage measurements. Two
59N independent stages of protection are provided for each 2/3/4/5
measured neutral voltage input and also for the calculated
value, each stage can be selected as either IDMT or DT. The
P342/3/4/5 have 2 measured and 2 calculated stages of
residual overvoltage protection. The P344/5 has an additional
neutral voltage input and so has an additional 2 stages of
measured residual overvoltage protection.
P34x/EN IT/I76 Introduction

(IT) 1-8 MiCOM P342, P343, P344, P345 & P391

PROTECTION FUNCTIONS OVERVIEW P34x


A 3rd harmonic voltage element is provided to detect earth fault
close to the generator star point. This element combined with
the standard stator earth fault protection (59N/50N/51N)
provides 100% stator earth fault protection.
A definite time 3rd harmonic undervoltage element is provided
27TN/59TN if neutral voltage measurement is available at the neutral of the 3/4/5
machine. This element is supervised by a 3 phase
undervoltage element and optionally by 3 phase W/VA/VAr
elements. A 3rd harmonic overvoltage element is provided if
IT neutral voltage measurement is available from the terminals of
the machine.
100% stator earth fault protection can also be provided by a
low frequency injection method. There are 2 stages of definite
64S time under resistance protection and 1 stage of definite time 5
overcurrent protection. An external 20Hz generator and
bandpass filter is required with this function.
A five stage overfluxing (V/Hz) element is provided to protect
the generator, or connected transformer, against
24 overexcitation. The first stage is a definite time alarm, the 2/3/4/5
second stage can be used to provide an inverse or definite
time trip characteristic and stages 3/4/5 are definite time.
A voltage supervised overcurrent scheme is provided for dead
machine/generator unintentional energization at standstill
50/27 3/4/5
(GUESS) protection to detect if the machine circuit breaker is
closed accidentally, when the machine is not running.
A 2 stage undervoltage protection element, configurable as
either phase to phase or phase to neutral measuring is
27 2/3/4/5
provided to back up the automatic voltage regulator. Stage 1
may be selected as either IDMT or DT and stage 2 is DT only.
A 2 stage overvoltage protection element, configurable as
either phase to phase or phase to neutral measuring is
59 2/3/4/5
provided to back up the automatic voltage regulator. Stage 1
may be selected as either IDMT or DT and stage 2 is DT only.
A definite time negative phase sequence overvoltage
protection element is provided for either a tripping or
47 2/3/4/5
interlocking function upon detection of unbalanced supply
voltages.
A 4 stage definite time underfrequency and 2 stage definite
81U/O time overfrequency protection is provided for load shedding 2/3/4/5
and back-up protection of the speed control governor.
Turbine abnormal frequency protection is provided to protect
the turbine blade from potential damage due to prolonged
81AB under/over frequency operation of the generator. Up to six 2/3/4/5
frequency bands can be programmed, each having an
integrating timer to record the time spent within the band.
10 RTDs (PT100) are provided to monitor the temperature
Option
RTD accurately in the windings and bearings of the machine. Each
2/3/4/5
RTD has an instantaneous alarm and definite time trip stage.
A 2 stage circuit breaker failure function is provided with a 3
50BF 2/3/4/5
pole initiation input from external protection.
Phase, neutral and sensitive earth fault undercurrent elements
37P/37N are available for use with for example the circuit breaker fail 2/3/4/5
function.
Introduction P34x/EN IT/I76

MiCOM P342, P343, P344, P345 & P391 (IT) 1-9

PROTECTION FUNCTIONS OVERVIEW P34x


A lens shaped impedance characteristic is used to detect loss
of synchronization (pole slipping) between the generation and
the power system. Two zones are created by a reactance line
which is used to distinguish whether the impedance centre of
78 3/4/5
the pole slip is located in the power system or in the generator.
Separate counters are used to count pole slips in the 2 zones.
A setting is also provided to determine whether the protection
operates in a generating mode, motoring mode or both.
Blocked overcurrent logic is available on each stage of the
overcurrent, earth fault and sensitive earth fault protection. IT
BOL 2/3/4/5
This consists of start outputs and block inputs that can be used
to implement busbar blocking schemes for example.
Voltage transformer supervision is provided (1, 2 & 3 phase
VTS fuse failure detection) to prevent mal-operation of voltage 2/3/4/5
dependent protection elements upon loss of a VT input signal.
Current transformer supervision is provided to prevent
CTS mal-operation of current dependent protection elements upon 2/3/4/5
loss of a CT input signal.
4 analog (or current loop) inputs are provided for transducers
(vibration, tachometers etc.). Each input has a definite time
trip and alarm stage and each input can be set to operate for
Over or Under operation. Each input can be independently Option
CLIO selected as 0-1/0-10/0-20/4-20mA. 2/3/4/5
4 analogue (or current loop) outputs are provided for the
analogue measurements in the relay. Each output can be
independently selected as 0-1/0-10/0-20/4-20mA.
Phase rotation - the rotation of the phases ABC or ACB for all
3 phase current and voltage channels can be selected. Also,
for pumped storage applications where 2 phases are swapped 2/3/4/5
the swapping of 2 phases can be emulated independently for
the 3 phase voltage and 3 phase current channels.
10
Programmable function keys
(P345)
18
(P345) 8
Programmable LEDs (tri-color P345, red P342/3/4)
(P342/3/
4)
Digital inputs (order option) 7 to 32
Output relays (order option) 8 to 32
Front communication port (EIA(RS)232) 2/3/4/5
Rear communication port (KBUS/EIA(RS)485). The following
communications protocols are supported; Courier, MODBUS, 2/3/4/5
IEC870-5-103 (VDEW) and DNP3.0.
Rear communication port (Fiber Optic). The following
Option
communications protocols are supported; Courier, MODBUS,
2/3/4/5
IEC870-5-103 (VDEW) and DNP3.0.
Second rear communication port (EIA(RS)232/EIA(RS)485). Option
Courier protocol. 2/3/4/5
Rear IEC61850 Ethernet communication port. Option
2/3/4/5
Option
Time synchronization port (IRIG-B)
2/3/4/5
P34x/EN IT/I76 Introduction

(IT) 1-10 MiCOM P342, P343, P344, P345 & P391

The P34x supports the following relay management functions in addition to the functions
illustrated above.

Measurement of all instantaneous & integrated values

Circuit breaker status & condition monitoring

Trip circuit and coil supervision

4 Alternative setting groups

Programmable function keys (P345)


IT Control inputs

Programmable scheme logic

Programmable allocation of digital inputs and outputs

Sequence of event recording

Comprehensive disturbance recording (waveform capture)

Fault recording

Fully customizable menu texts

Multi-level password protection

Power-up diagnostics and continuous self-monitoring of relay

Commissioning test facilities

Real time clock/time synchronization - time synchronization possible from IRIG-B input,
opto input or communications
Application overview

Figure 1: Functional diagram


Introduction P34x/EN IT/I76

MiCOM P342, P343, P344, P345 & P391 (IT) 1-11

3.2 Ordering options


Information Required with Order

MiCOM P342 GENERATOR PROTECTION RELAY NOMENCLATURE

Character Type (A=Alpha, N=Numeric, X=Alpha-numeric)


A N N N A X X X A X X N N X A
Character Numbering (Maximum = 15)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

P 3 4 2 * * * * * M 0 * * 0 *

Vx Aux Rating
IT
24-48 Vdc 1
48-110 Vdc, 30-100 Vac 2
110-250 Vdc, 100-240 Vac 3

In/Vn Rating
In=1A/5A, Vn=100/120V 1
In=1A/5A, Vn=380/480V 2

Hardware Options
Nothing 1
IRIG-B only (modulated) 2
Fiber Optic Converter Only 3
IRIG-B (modulated) + Fiber Optic Converter 4
Ethernet (100Mbps)** 6
nd
2 Rear Comms. Board* 7
IRIG-B* (modulated) + 2nd Rear Comms Board 8
Ethernet (100Mbps) + IRIG-B (modulated)** A
Ethernet (100Mbps) + IRIG-B (de-modulated) ** B
IRIG-B (de-modulated) ** C

Product Specific
Size 40TE Case, No Option (8 Optos + 7 Relays) A
Size 40TE Case, 8 Optos + 7 Relays + RTD B
Size 40TE Case, 8 Optos + 7 Relays + CLIO* C
Size 40TE Case, 16 Optos + 7 Relays* D
Size 40TE Case, 8 Optos + 15 Relays* E
Size 40TE Case, 12 Optos + 11 Relays* F
Size 60TE Case, 16 Optos + 16 Relays* G
Size 60TE Case, 16 Optos + 16 Relays + RTD* H
Size 60TE Case, 16 Optos + 16 Relays + CLIO* J
Size 60TE Case, 24 Optos + 16 Relays* K
Size 60TE Case, 16 Optos + 24 Relays* L
Size 60TE Case, 16 Optos + 16 Relays + RTD + CLIO* M
Size 60TE Case, 24 Optos + 16 Relays + RTD* N
Size 60TE Case, 16 Optos + 24 Relays + RTD* P
Size 40TE Case, 8 Optos + 7 Relays + 4 Relays HB** Q
Size 60TE Case, 16 Optos +16 Relays + 4 Relays HB** R
Size 60TE Case, 16 Optos + 8 Relays + 4 Relays HB + S
RTD**
Size 60TE Case, 16 Optos + 8 Relays + 4 Relays HB + T
CLIO**
Size 60TE Case, 16 Optos + 8 Relays + 4 Relays HB + U
RTD + CLIO**

Note: HB = High Break, CLIO required for Rotor EF

Protocol Options
K-Bus 1
MODBUS 2
IEC870 3
DNP3.0 4
IEC 61850 + Courier via rear EIA(RS)485 port 6

Mounting
Panel Mounting M

Language Options 0
Multilingual English, French, German, Spanish 5
Multilingual English, French, German, Russian

Software 33

Setting Files
Default 0
Customer 1

Design Suffix
Original A
Phase 2 Hardware C
Phase 2 CPU J

Note Design Suffix


A = Original hardware (48V opto inputs only, lower contact rating, no I/O expansion available)
C = Universal optos, new relays, new power supply
J = Phase 2 CPU and front panel with 2 hotkeys and dual characteristic optos

* Not available in design suffix A relays


** Not available in design suffix A,B, C

Note Mounting
For rack mounting assembled single rack frames and blanking plates are available
P34x/EN IT/I76 Introduction

(IT) 1-12 MiCOM P342, P343, P344, P345 & P391

MiCOM P343 GENERATOR PROTECTION RELAY NOMENCLATURE

Character Type (A=Alpha, N=Numeric,


X=Alpha-numeric) A N N N A X X X A X X N N X A
Character Numbering (Maximum = 15)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

P 3 4 3 * * * * * M 0 * * 0 *

Vx Aux Rating
24-48 Vdc 1
IT 48-110 Vdc, 30-100 Vac
110-250 Vdc, 100-240 Vac
2
3

In/Vn Rating
In=1A/5A, Vn=100/120V 1
In=1A/5A, Vn=380/480V 2

Hardware Options
Nothing 1
IRIG-B only (modulated) 2
Fiber Optic Converter Only 3
IRIG-B (modulated) + Fiber Optic Converter 4
Ethernet (100Mbps)** 6
2nd Rear Comms. Board* 7
IRIG-B (modulated) + 2nd Rear Comms Board* 8
Ethernet (100Mbps) + IRIG-B (modulated)** A
Ethernet (100Mbps) + IRIG-B (de-modulated) ** B
IRIG-B (de-modulated) ** C

Product Specific
Size 60TE Case, No Option (16 Optos + 14 Relays) A
Size 60TE Case, 16 Optos + 14 Relays + RTD B
Size 60TE Case, 16 Optos + 14 Relays + CLIO* C
Size 60TE Case, 24 Optos + 14 Relays* D
Size 60TE Case, 16 Optos + 22 Relays* E
Size 80TE Case, 24 Optos + 24 Relays* F
Size 80TE Case, 24 Optos + 24 Relays + RTD* G
Size 80TE Case, 24 Optos + 24 Relays + CLIO* H
Size 80TE Case, 32 Optos + 24 Relays* J
Size 80TE Case, 24 Optos + 32 Relays* K
Size 80TE Case, 24 Optos + 24 Relays + RTD + CLIO* L
Size 80TE Case, 32 Optos + 24 Relays + RTD* M
Size 80TE Case, 24 Optos + 32 Relays + RTD* N
Size 80TE Case, 32 Optos + 16 Relays + RTD + CLIO* P
Size 80TE Case, 16 Optos + 32 Relays + RTD + CLIO* Q
Size 60TE Case, 16 Optos + 14 Relays + 4 Relays HB** R
Size 60TE Case, 16 Optos + 7 Relays + 4 Relays HB + S
RTD**
Size 60TE Case, 16 Optos + 7 Relays + 4 Relays HB + T
CLIO**
Size 80TE Case, 16 Optos + 16 Relays + 8 Relays HB U
Size 80TE Case, 16 Optos + 16 Relays + 8 Relays HB + V
RTD**
Size 80TE Case, 16 Optos + 16 Relays + 8 Relays HB + W
CLIO**
Size 80TE Case, 16 Optos + 16 Relays + 8 Relays HB + X
RTD + CLIO**

Note: HB = High Break, CLIO required for Rotor EF

Protocol Options
K-Bus 1
MODBUS 2
IEC870 3
DNP3.0 4
IEC 61850 + Courier via rear EIA(RS)485 port 6

Mounting
Panel Mounting M
Rack Mounting (80TE case only) N

Language Options 0
Multilingual English, French, German, Spanish 5
Multilingual English, French, German, Russian

Software 33

Setting Files
Default 0
Customer 1

Design Suffix
Original Universal A
Phase 2 Hardware C
Phase 2 CPU J
Introduction P34x/EN IT/I76

MiCOM P342, P343, P344, P345 & P391 (IT) 1-13

Note Design Suffix


A = Original hardware (48V opto inputs only, lower contact rating, no I/O expansion available)
C = Universal optos, new relays, new power supply
J = Phase 2 CPU and front panel with 2 hotkeys and dual characteristic optos

* Not available in design suffix A relays


** Not available in design suffix A,B, C

Note Mounting
For rack mounting in the 60TE case size assembled single rack frames and blanking plates are available

IT
P34x/EN IT/I76 Introduction

(IT) 1-14 MiCOM P342, P343, P344, P345 & P391

MiCOM P344 GENERATOR PROTECTION RELAY NOMENCLATURE

Character Type (A=Alpha, N=Numeric,


X=Alpha-numeric) A N N N A X X X A X X N N X A
Character Numbering (Maximum = 15)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

P 3 4 4 * * * * * M 0 * * 0 *

Vx Aux Rating
24-48 Vdc 1
IT 48-110 Vdc, 30-100 Vac
110-250 Vdc, 100-240 Vac
2
3

In/Vn Rating
In=1A/5A, Vn=100/120V 1
In=1A/5A, Vn=380/480V 2

Hardware Options
Nothing 1
IRIG-B only (modulated) 2
Fiber Optic Converter Only 3
IRIG-B (modulated) + Fiber Optic Converter 4
Ethernet (100Mbps) 6
2nd Rear Comms. Board 7
IRIG-B (modulated) + 2nd Rear Comms Board* 8
Ethernet (100Mbps) + IRIG-B (modulated A
Ethernet (100Mbps) + IRIG-B (de-modulated) B
IRIG-B (de-modulated) C

Product Specific
Size 80TE Case, No Option (24 Optos + 24 Relays) A
Size 80TE Case, 24 Optos + 24 Relays + RTD B
Size 80TE Case, 24 Optos + 24 Relays + CLIO C
Size 80TE Case, 32 Optos + 24 Relays D
Size 80TE Case, 24 Optos + 32 Relays E
Size 80TE Case, 24 Optos + 24 Relays + RTD + CLIO F
Size 80TE Case, 32 Optos + 24 Relays + RTD G
Size 80TE Case, 24 Optos + 32 Relays + RTD H
Size 80TE Case, 32 Optos + 16 Relays + RTD + CLIO J
Size 80TE Case, 16 Optos + 32 Relays + RTD + CLIO K
Size 80TE Case, 24 Optos + 16 Relays + 4 Relays HB L
Size 80TE Case, 24 Optos + 16 Relays + 4 Relays HB + M
RTD
Size 80TE Case, 24 Optos + 16 Relays + 4 Relays HB + N
CLIO
Size 80TE Case, 24 Optos + 16 Relays + 4 Relays HB + P
RTD + CLIO
Size 80TE Case, 16 Optos + 16 Relays + 8 Relays HB Q
Size 80TE Case, 16 Optos + 16 Relays + 8 Relays HB + R
RTD
Size 80TE Case, 16 Optos + 16 Relays + 8 Relays HB + S
CLIO
Size 80TE Case, 16 Optos + 16 Relays + 8 Relays HB + T
RTD + CLIO

Note: HB = High Break, CLIO required for Rotor EF

Protocol Options
K-Bus 1
MODBUS 2
IEC870 3
DNP3.0 4
IEC 61850 + Courier via rear EIA(RS)485 port 6

Mounting
Panel Mounting M
Rack Mounting N

Language Options 0
Multilingual English, French, German, Spanish 5
Multilingual English, French, German, Russian

Software 33

Setting Files
Default 0
Customer 1

Design Suffix
Phase 2 CPU J

Note Design Suffix


J = Original hardware (phase 2 CPU and front panel with 2 hotkeys and dual characteristic optos)
Introduction P34x/EN IT/I76

MiCOM P342, P343, P344, P345 & P391 (IT) 1-15

MiCOM P345 (GENERATOR RELAY WITH SIGMA-DELTA INPUT MODULE) NOMENCLATURE

Character Type (A=Alpha, N=Numeric,


X=Alpha-numeric) A N N N A X X X A X X N N X A
Character Numbering (Maximum = 15)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

P 3 4 5 * * * * * M 0 * * 0 *

Vx Aux Rating
24-48 Vdc 1
48-110 Vdc, 30-100 Vac
110-250 Vdc, 100-240 Vac
2
3 IT
In/Vn Rating 1
In = 1A/5A, Vn=100/120V 2
In = 1A/5A, Vn=380/480V

Hardware Options
Nothing 1
IRIG-B only (modulated) 2
Fiber Optic Converter Only 3
IRIG-B (modulated) + Fiber Optic Converter 4
Ethernet (100Mbps) 6
2nd Rear Comms. Board 7
IRIG-B (modulated) + 2nd Rear Comms Board* 8
Ethernet (100Mbps) + IRIG-B (modulated) A
Ethernet (100Mbps) + IRIG-B (de-modulated) B
IRIG-B (de-modulated) C

Product Specific
Size 80TE Case, No Option (24 Optos + 24 Relays) A
Size 80TE Case, 24 Optos + 24 Relays + RTD B
Size 80TE Case, 24 Optos + 24 Relays + CLIO C
Size 80TE Case, 32 Optos + 24 Relays D
Size 80TE Case, 24 Optos + 32 Relays E
Size 80TE Case, 24 Optos + 24 Relays + RTD + CLIO F
Size 80TE Case, 32 Optos + 24 Relays + RTD G
Size 80TE Case, 24 Optos + 32 Relays + RTD H
Size 80TE Case, 32 Optos + 16 Relays + RTD + CLIO J
Size 80TE Case, 16 Optos + 32 Relays + RTD + CLIO K
Size 80TE Case, 24 Optos + 16 Relays + 4 Relays HB L
Size 80TE Case, 24 Optos + 16 Relays + 4 Relays HB + M
RTD
Size 80TE Case, 24 Optos + 16 Relays + 4 Relays HB + N
CLIO
Size 80TE Case, 24 Optos + 16 Relays + 4 Relays HB + P
RTD + CLIO
Size 80TE Case, 16 Optos + 16 Relays + 8 Relays HB Q
Size 80TE Case, 16 Optos + 16 Relays + 8 Relays HB + R
RTD
Size 80TE Case, 16 Optos + 16 Relays + 8 Relays HB + S
CLIO
Size 80TE Case, 16 Optos + 16 Relays + 8 Relays HB + T
RTD + CLIO

Note: HB = High Break, CLIO required for Rotor EF

Protocol Options
K-Bus 1
MODBUS 2
IEC870 3
DNP3.0 4
IEC 61850 + Courier via rear EIA(RS)485 port 6

Mounting
Panel Mounting M
Rack Mounting N

Language Options 0
Multilingual English, French, German, Spanish 5
Multilingual English, French, German, Russian

Software 33

Setting Files
Default 0
Customer 1

Design Suffix
Extended Phase 2 CPU with 10 function keys and K
tri-color LEDs

* Note Design Suffix


K = Extended phase 2 CPU (phase 2 CPU and front panel with 10 function keys and tri-color LEDs and dual characteristic optos)
Separately ordered P345 accessories for low frequency injection 100% stator earth fault protection
1. 20Hz generator (Surface/Flush/Rail Mounted)
2. Bandpass Filter (Surface/Flush/Rail Mounted)
3. 400/5A Tripping CT
P34x/EN IT/I76 Introduction

(IT) 1-16 MiCOM P342, P343, P344, P345 & P391

MiCOM P391 (GENERATOR ROTOR EARTH FAULT MODULE) NOMENCLATURE

Character Type (A=Alpha, N=Numeric,


X=Alpha-numeric) A N N N A X X X A X X N N X A
Character Numbering (Maximum = 15)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

P 3 9 1 9 0 1 A 0 M 0 0 0 0 A

IT Vx Aux Rating
60-250 Vdc, 100-230V ac 9

In/Vn Rating 0
N/A

Hardware Options 1
None

Product Specific
None A

Protocol Options
N/A 0

Mounting P
Panel Mounting R
Rack Mounting W
Wall Mounting

Software 33

Setting Files
N/A 0

Design Suffix
Original hardware A

Você também pode gostar