Você está na página 1de 2

ADDC Testing and Protection Section

Setting Calculation Protocol for IDMT Overcurrent Relay Settings


Station:

Contract:

Consultant:

Contractor:

Feeder ID: Outgoing Feeder (Typical)

Relay: Relay Type: Numerical Relay Model: Delta Relay Make: VATECH

CT Ratio Prim. Current Sec. Current Burden, VA Class Rct


CT Data:
600/400/1 600 1 15 - 10 5P15 -

Fault Current, If L-L Fault L-G Fault

Fault Data: Min. Fault Current, A 11000 8100

Max. Fault Current, A 22000 16200

FAULT SETTING CALCULATION FOR IDMT O/C

General Data:

Overload Current: 480 (125% of Full load current of Protected Object)

PMS (Plug Multiplier Setting): 0.8

Curve Selected: Normal Inverse (NI)

Operating time at TMS 1, sec '=0.14/


2.17 sec .........Eq. 1
[(PSM)0.02 - 1]:

PSM (Plus Setting Multiplier):


'=[(Ifmin/Prim.Current) * (Sec.Rated 22.92 1.06 .........Eq. 2
Current/PMS)]
Assuming Prot. Op. time, sec:
0.3 sec
(0.3sec)
Grading Margin (0.3sec) 0 sec
Hence TMS: ('= (0.3+0) / (Result
0.139 .........Eq. 3
from Eq.1)
Final TMS set at: 0.125
Operating time at TMS 0.125, sec
0.271 sec
'=0.14*0.125/[(PSM)0.02 - 1]:
Operating time at TMS 0.2, sec
0.433 sec (for Sample)
'=0.14*0.2/[(PSM)0.02 - 1]:

PMS: 0.8

Adopted Settings: TMS: 0.125


High Set
10xIn
(I>>):
Is settings co-ordinated with downstream side: Yes/No

Is settings co-ordinated with upstream side: Yes/No

348717346.xls/IDMT OC-Outgoing 1/2


ADDC Testing and Protection Section

Setting Calculation Protocol for IDMT Earth Fault Relay Settings


Station:

Contract:

Consultant:

Contractor:

Feeder ID: Outgoing Feeder (Typical)

Relay: Relay Type: Numerical Relay Model: Delta Relay Make: VATECH

CT Ratio Prim. Current Sec. Current Burden, VA Class Rct


CT Data:
600/400/1 600 1 15 - 10 5P15 -

Fault Current, If L-L Fault L-G Fault

Fault Data: Min. Fault Current, A 11000 8100

Max. Fault Current, A 22000 16200

FAULT SETTING CALCULATION FOR IDMT O/C

General Data:

Earth Fault Current: 0.2 (25% of OC PMS)

PMS (Plug Multiplier Setting): 0.2

Curve Selected: Normal Inverse (NI)

Operating time at TMS 1, sec '=0.14/


1.59 sec .........Eq. 1
[(PSM)0.02 - 1]:

PSM (Plus Setting Multiplier):


'=[(Ifmin/Prim.Current) * (Sec.Rated 67.50 1.09 .........Eq. 2
Current/PMS)]
Assuming Prot. Op. time, sec:
0.3 sec
(0.3sec)
Grading Margin (0.3sec) 0 sec
Hence TMS: ('= (0.3+0) / (Result
0.188 .........Eq. 3
from Eq.1)
Final TMS set at: 0.2
Operating time at TMS 0.2, sec
0.319 sec
'=0.14*0.2/[(PSM)0.02 - 1]:

PMS: 0.2

Adopted Settings: TMS: 0.2


High Set
8xIn
(I0>>):
Is settings co-ordinated with downstream side: Yes/No

Is settings co-ordinated with upstream side: Yes/No

348717346.xls/IDMT EF-Outgoing 2/2