Você está na página 1de 11

www.ietdl.

org

Published in IET Power Electronics


Received on 3rd September 2008
Revised on 2nd May 2009
doi: 10.1049/iet-pel.2008.0281

ISSN 1755-4535

Control strategy and space vector modulation


for three-leg four-wire voltage source inverters
under unbalanced load conditions
A. Mohd1 E. Ortjohann1 N. Hamsic1 W. Sinsukthavorn1
M. Lingemann1 A. Schmelter1 D. Morton2
1
University of Applied Sciences South Westphalia/Division Soest, Luebecker Ring 2, Soest D-59494, Germany
2
Bolton University, Deane Road, Bolton, UK
E-mail: AlaaMohd@gmail.com

Abstract: One of the desirable characteristics of inverters in three-phase systems is the ability to feed unbalanced/
non-linear loads with voltage and frequency nominal values. Therefore three-leg four-wire inverters are expected
to play an essential role in future power systems because of their ability to handle the neutral current caused by
unbalanced or non-linear loads. This study introduces an original control method in combination with three-
dimensional space-vector modulation (3D-SVM) strategy. The steps for the 3D-SVM implementation are
identied. The switching vectors, 3D-SVM diagrams and the boundary planes equations, as well as the
matrices for the duty cycles and symmetric switching sequences are discussed in detail. Experimental results
including different loads are presented to validate the proposed SVM control strategy for three-leg four-wire
voltage source inverters. The experimental results of this study show that the developed control scheme in
combination with three-leg four-wire inverters can carry out the grid feeding requirements and supply good
power quality to loads under extreme unbalanced conditions efciently.

1 Introduction However, all of these sources need power electronic devices


to connect them to the grid. These units are multifunctional
Fossil fuels are currently the major source of energy in and should be well controlled to do many utility functions.
the world today. However, as the world is considering An essential component at the grid side of such systems
more economical and environmentally friendly alternative is the inverter due to the wide range of functions it has
energy generation systems, the global energy mix is to perform. It has to convert the DC voltage to sinusoidal
becoming more complex. Factors forcing these current for use by the grid in addition to act as the
considerations are (a) the increasing demand for electric interface between the energy converting systems (ECSs),
power by both developed and developing countries, the local load and the grid. It also has to handle the
(b) many developing countries lacking the resources to variations in the electricity it receives due to varying levels
build power plants and distribution networks, (c) some of generation by the RESs, loads and grid voltages [3 7].
industrialised countries facing insufcient power generation
and (d) greenhouse gas emission and climate change The necessity of feeding three-phase unbalanced loads,
concerns. Renewable Energy Sources (RESs) such as wind irregularly distributed single-phase loads or balanced three-
turbines, photovoltaic solar systems, solar-thermo power, phase loads running at fault condition [8] leads to
biomass power plants, fuel cells, gas micro-turbines, investigate different methods to handle the neutral current.
hydropower turbines, combined heat and power micro- If the phases are unequally loaded, they produce undesired
turbines and hybrid power systems will be part of future negative and zero sequence currents. The negative sequence
power generation systems [1, 2]. will cause excessive heating in machines, saturation of

IET Power Electron., 2010, Vol. 3, Iss. 3, pp. 323 333 323
doi: 10.1049/iet-pel.2008.0281 & The Institution of Engineering and Technology 2010
www.ietdl.org

transformers and ripple in rectiers. The zero sequence


currents cause not only excessive power losses in neutral
lines but also affect protection [9]. Past research shows that
there are mainly three ways to provide neutral current
compensation: using zigzag transformers, using four-wire
voltage source inverter topology while tying the neutral
point to the mid-point of the fourth neutral leg [10]
or using split DC-link capacitors while tying the neutral
point to the mid-point of the DC-linked capacitors [8].
Figure 1 Three-phase three-leg inverter with a neutral
point
Several modulation strategies, differing in concept and
performance, have been developed for these topologies in
order to achieve variety of aims, including wide linear
modulation range, less switching loss, less total harmonic single-phase ones. Three half-bridge single-phase inverters
distortion (THD) in the spectrum of switching waveform, joined together can be seen as a three-phase four-wire
easy implementation and less computation time [11]. inverter, see Fig. 1, where each output feeds one phase.
With the development of microprocessors, space-vector This topology can be used to feed balanced/unbalanced
modulation (SVM) has become one of the most important loads. In case of unbalanced loads, the sum of the output
pulse-width modulation (PWM) methods for three-phase currents ia , ib and ic will not be zero and the neutral
inverters because of its ability to reduce the commutation current will ow in the connection between the neutral
losses and the harmonic contents of the output voltage, point and the mid-point of the capacitive divider [21 23].
as well as obtaining higher amplitude modulation indexes To maintain symmetrical voltage across the two capacitors,
[12, 13]. an adequate power electronics and voltage stage
management are needed. However, this will not be taken
While the use of three-dimensional SVM (3D-SVM) further into discussion since it is out of scope of this paper.
with four-leg inverter was explored by many authors using The additional neutral inductor Ln is optional, as it can
different approaches, on the other hand, the use of 3D- reduce switching frequency ripple [24]. Furthermore, the
SVM with three-leg four-wire got less attention. It was high unbalanced current owing through the DC-link
discussed briey in [14 18]. In [19], a discussion about capacitors of the three-leg four-wire inverter requires higher
the 3D-SVM for three-leg four-wire voltage source capacitance [25, 26]. However, compared with the four-leg
inverters was made including theory, implementation and inverters, the three-leg four-wire inverter has a lower
application examples. In a recent paper [20], a discrete number of semiconductor switches and the control function
sliding mode control with modied SVM was discussed. can be built like three individual single-line inverters
which makes it an attractive option.
In this paper, SVM in combination with advanced control
strategy based on symmetrical components for three-leg four-
wire topology is presented and validated using experimental
results. It will be shown that the developed 3D-SVM 3 Sequence decomposition
control schemes in combination with three-leg four-wire Symmetrical sequence decomposition (SSD) is used mainly
inverters can perform the feeding requirements of grid in power electric fault analysis. In [27] a controller based
under extreme unbalanced load conditions efciently. on symmetrical components for handling unbalanced
conditions with a multi-level inverter was introduced. In
This paper will start in Section 2 with discussion of the present work, sequence decomposition is used in the
the used inverter topology. In the next step, a detailed implementation of the three-leg four-wire inverter control.
description of the sequence decomposition used to transfer The SSD is able to represent asymmetrical three-phase
the asymmetrical voltage/current into the dq 0 symmetrical signal (voltage/current) as a sum of positive, negative and
components will be given in Section 3. From there, the zero sequence. The positive and negative components are
paper will introduce the developed control strategy in three-phase symmetrical signals, whereas the zero sequence
Section 4. In Section 5, the proposed 3D-SVM will be is a single-phase one.
described in detail. Experimental results to validate the
introduced method are presented in Sections 6. In dq0-coordinates, the negative sequence appears as a
disturbance in d and q variables at a frequency of 2v [28,
29]. This is because the dq reference frame is rotating in
2 Three-phase four-wire inverter the positive direction at an angular frequency of v, whereas
the negative sequence disturbance rotates at an angular
topologies frequency of v in the opposite direction. The zero sequence
Three-phase four-wire voltage source inverters (three-phase appears at a frequency of v, because the zero-axis is
inverters with neutral point) are an evolution from the stationary [30].

324 IET Power Electron., 2010, Vol. 3, Iss. 3, pp. 323 333
& The Institution of Engineering and Technology 2010 doi: 10.1049/iet-pel.2008.0281
www.ietdl.org

Asymmetrical three-phase signals va , vb and vc (the transformation process is done, each line is represented in
following method applies to currents in exactly the same detach dq-components. These signals in the dq-plane can
way) can be decomposed into two symmetrical three-phase be interpreted as complex values
waves: the positive component
Va dq = Va d + jVa q (6)
vp = {va p , vb p , vc p } (1) Vb dq = Vb d + jVb q (7)

and the negative components, that is Vc dq = Vc d + jVc q (8)

vn = {va n , vb n , vc n } (2) These asymmetrical complex dq-values for each line can
now be decoupled by the use of SSD. The relationship
and the zero-component v0 . The asymmetrical signals can be between the symmetrical dq-components corresponding
rearranged by the sums to the three-phase asymmetrical dq signals is given by (9)

va = va p + va + v0 (3)
n Vp dq 1 a a2 Va dq
Vn dq
= 11 a2 a V b dq
(9)
vb = vb p + vb n + v0 (4) V0 3 Vc
dq 1 1 1 dq

vc = vc p + vc n + v0 (5)
where
The general idea is shown in Fig. 2a. Therefore voltage of a = e j(2p/3) and a2 = e j(4p/3) (10)
each line is transformed by an ideal selective lter into va and
v components [31 33]. Then, a Park transformation is The phasors are dened in complex dq-plane. The back
performed to obtain the vd and vq components. When this transformation into a, b and g components is easier since

Figure 2 Sequence decomposition and composition


a Sequence decomposition
b Sequence composition

IET Power Electron., 2010, Vol. 3, Iss. 3, pp. 323 333 325
doi: 10.1049/iet-pel.2008.0281 & The Institution of Engineering and Technology 2010
www.ietdl.org

no transformation to the complex domain is needed. and the units own qualications. An inverter in
Summing up vp and vn as they are both in the ab-plane, grid-parallel mode is a power production unit that is not
while taking into account that the negative component is controlled according to the requirements of the electrical
rotating anticlockwise, we obtain system. RESs such as wind energy converters and
photovoltaic systems may be used to feed their maximum
va = vp a + vn a (11) power into the grid (standard applications in conventional
grids). In such a case, these systems are considered as
vb = vp b vn b (12) grid parallel units. Advanced control strategies based on
symmetrical components in combination with four-leg or
vg = v0 a (13) three-leg four-wire inverter were developed by the authors
in [34, 35] and will be briey discussed here.
From the last equation, it can be pointed out that the
zero-component v0_a equals the g-component and both of As a grid forming unit, the inverter has to provide the
them are single-phase signals. The complete transformation voltage and the frequency of the grid (voltage source). This
starting from dq-plane of each line is shown in Fig. 2b. is done as following: the voltage and the current sensed
values are transformed from the abc-frame to the positive
The composed a, b and g components can be used for the negative zero dq sequence components.
SVM to produce the pulse pattern for the power electronic
switches [24]. In the following section, the control strategy The controller block comprises current and voltage PI
based on the symmetrical components will be discussed. controllers for each component. Six controllers are needed
for the voltage and the current components of the load.
4 Proposed control method For the controller only the d-component of the positive
sequence Vp_d_ref is considered. The other reference values
A general feeding philosophy to supply electric energy are set to zero since the inverter has to supply symmetrical
through power electronic inverters is discussed in [21]. In three-phase voltage. The output reference values from the
this philosophy, the power ow from an ECS into the control unit are transformed to the abg-space and the
grid may be driven by the grid or by the ECS itself, as SVM block uses them to calculate the pulse pattern for
summarised in Fig. 3 and Table 1. An inverter in grid- the switches. Fig. 4 shows an inverter in grid forming
forming mode is responsible for establishing the voltage mode for unbalanced loads. The control functions can be
and the frequency of the grid and maintaining them. described as vectors according to the following denition
An inverter in grid-supporting mode produces predened
amounts of power which are normally specied by a
management unit. The management system may change
Vp d ref Vp d act
the reference values according to the systems requirements Vp Vp
q ref q act

Vn Vn act
= , = ,
d ref d
V pn0 dq ref V V pn0 dq act V
n q ref n q act

V0 d ref V0 d act
V0 q ref V0 q act

Vp d Ip d act
Vp Ip
q q act

Vn d In act
= , =
d
V pn0 dq V I pn0 dq act I
n q n q act

V0 d I0 d act
V0 q I0 q act

Figure 3 Feeding modes at the grid-side (14)

Table 1 Control modes denition

Inverter mode Type Function


forming voltage source establish and control grid voltage and frequency
supporting voltage/current source power balance based on voltage and frequency
parallel current source none

326 IET Power Electron., 2010, Vol. 3, Iss. 3, pp. 323 333
& The Institution of Engineering and Technology 2010 doi: 10.1049/iet-pel.2008.0281
www.ietdl.org

Figure 4 Inverter in grid forming mode for unbalanced loads

The control strategies of asymmetrical grid supporting be approximated as


and parallel are detailed in [35] and will not be repeated here.
V ref = da va + db vb + dc vc (16)
5 SVM for three-leg four-wire
inverters in which da , db and dc are the duty cycles of vectors va , vb
and vc . In [36], 3D-SVM algorithm based on generating a
SVM is based on vector selection in the abg (stationary) or
zero-vector was introduced. Still, the proposed algorithm
in the dq 0 (rotating) reference frame. A set of three vectors
has a drawback of stressing the insulated gate bipolar
va , vb and vc in the abg-frame can generate a normalised
transistors (IGBTs) unequally. In this paper, another SVM
reference vector Vref in the same plane using PWM-
algorithm without using a zero-vector is launched. This
averaged approximation. The average reference vector can
algorithm based on vectors compensation (compensated
be obtained by sequentially applying these vectors in a
vectors approach) is more practical as it is not only stressing
modulation period in accordance with
the IGBTs equally but less as well. The proposed SVM
algorithm can be achieved through the following steps:
TS T1 T2 TS
1 1 1 1
V ref dt = V a dt + V b dt + V c dt 1. Determining the switching combinations and the
TS TS TS TS
0 0 T1 T1 +T2 corresponding vectors.

(15) 2. Calculating the voltage drop related to each vector.

where TS is the modulation period and T1 + T2 TS . Since 3. Identifying the position for each vector in the abg-space
Vref remains constant during the modulation period, (15) can vector diagram.

IET Power Electron., 2010, Vol. 3, Iss. 3, pp. 323 333 327
doi: 10.1049/iet-pel.2008.0281 & The Institution of Engineering and Technology 2010
www.ietdl.org

4. Identifying the reference vector position.

5. Calculating the duty cycles.

6. Building a vector sequence.

7. Computing pulse patterns.

These steps are described in detail in the following


paragraphs.

5.1 Steps one, two and three


In similar way to two-level three-phase inverters, there
are eight different switching combinations where the output
terminals will be connected to +1/2 or 21/2 of the
input DC voltage. However, unlike two-level three-leg
inverters none of these switching combinations is
Figure 5 3D space vectors
generating zero voltage at the output terminals, which make
the implementation of its SVM more difcult. Table 2
presents the eight possible switching vectors and the 5.2 Step four: reference vector position
corresponding output voltages related to the DC-voltage as identication
reference voltage. The switching vectors can be represented
Given that 12 tetrahedrons exist, there are 12 possibilities for
in the abg-coordinates using Clarkes transformation.
the reference vector position. We can identify the position
Table 2 shows the normalised abg-values of each switching
of the reference vector using the boundary planes limiting
vector.
the tetrahedron. Each tetrahedron is limited by three
planes. The boundary planes can be determined by means
The representation for these switching vectors in abg-
of the following linear equations
space is shown in Fig. 5. The vectors are taking place in
layers according to the value of their g component. Three 1
E71 : Vb = 0 (17)
vectors (V2 , V4 and V6) are located at the layer 3
Vg 1/6(VDC). The vectors (V1 , V3 and V5) are lying at
E12 :Va 3Vb + 4Vg = 0 (18)
the layer Vg 21/6(VDC). The vectors V7 and V0 are
located at the g-axis at Vg 1/2(VDC) and Vg 21/
3 1
2(VDC), respectively. The projection of the vectors in the E27 : V V =0 (19)
6 a 6 b
ab-frame is shown in Fig. 5 which is divided into six
prisms. The six prisms in the abg-space are shown in E23 : 2Va + 2Vg = 0 (20)
Fig. 6. Each prism is divided into two tetrahedrons, upper
and lower tetrahedron. Each tetrahedron is characterised by 3 1
E37 : Va + Vb = 0 (21)
three vectors. 6 6

Table 2 Switching states, the corresponding output voltages and normalised components of each switching vector

Switches (on) Vectors Normalised output voltage Normalised abg-components


Va /VDC Vb /VDC Vc /VDC Va /VDC Vb /VDC Vg /VDC
S4 S6 S2 V0 21/2 21/2 21/2 0 0 21/2
S1 S6 S2 V1 1/2 21/2 21/2 2/3 0 21/6

S1 S3 S2 V2 1/2 1/2 21/2 1/3 1/ 3 1/6

S4 S3 S2 V3 21/2 1/2 21/2 21/3 1/ 3 21/6
S4 S3 S5 V4 21/2 1/2 1/2 22/3 0 1/6

S4 S6 S5 V5 21/2 21/2 1/2 21/3 1/ 3 21/6

S1 S6 S5 V6 1/2 21/2 1/2 1/3 1/ 3 1/6
S1 S3 S5 V7 1/2 1/2 1/2 0 0 1/2

328 IET Power Electron., 2010, Vol. 3, Iss. 3, pp. 323 333
& The Institution of Engineering and Technology 2010 doi: 10.1049/iet-pel.2008.0281
www.ietdl.org

Figure 6 3D prisms for three-leg four-wire inverters

the intermediate circuit voltage, the duty cycles in matrix


E34 :Va + 3Vb + 4Vg = 0 (22) form can be written as following
The zero-vector is compensated by the vectors V0 and V7 ,
da Varef
both lying against each other direction on the g-axis. The
d 1
reference vector can be expressed as following b= [v v v ]1 Vbref (26)
VDC a b c
V ref = da V a + db V b + dg V c (23) dg Vgref
where for the upper tetrahedron (24) applies and for the The duty cycles for the vectors V7 and/or V0 can be
lower tetrahedron (25) applies determined according to the position of the reference
vector. For the upper tetrahedron using (27) and for the
V c = V 7 and dg = d7 d0 (24)
lower tetrahedron using (28)
V c = V 0 and dg = d0 d7 (25)
1 (da + db ) + dg
d7 = where d0 = d7 dg (27)
5.3 Step ve: duty cycles calculation 2

Once the target tetrahedron is dened the nearest three 1 (da + db ) + dg


d0 = where d7 = d0 dg (28)
vectors are chosen. By normalising the standard vectors at 2

IET Power Electron., 2010, Vol. 3, Iss. 3, pp. 323 333 329
doi: 10.1049/iet-pel.2008.0281 & The Institution of Engineering and Technology 2010
www.ietdl.org

Table 3 Vector sequence for the upper and lower Table 4 Inverter parameters
tetrahedrons in each prism
Parameters Values
Prism Sequence
line frequency 50 Hz
1 v0-v1-v2-v7-v7-v2-v1-v0
DC-link voltage 650
2 v0-v3-v2-v7-v7-v2-v3-v0
switching frequency 10 kHz
3 v0-v3-v4-v7-v7-v4-v3-v0
lter inductance (Lf) 3 mH
4 v0-v5-v4-v7/-v7-v4-v5-v0
lter capacitance (Cf) 10 mF
5 v0-v5-v6-v7-v7-v6-v5-v0
output power 10 kVA
6 v0-v1-v6-v7-v7-v6-v1-v0
PWM output mode symmetrical PWM

5.4 Steps six and seven: building vector polarity) [11]. Table 3 shows the vector sequence for the
sequence and pulse pattern computation upper and lower tetrahedrons in each prism.
In order to reduce the current ripple, switching vectors
adjacent to the reference vector should be selected since An example for determining the switching sequence for
they produce non-conicting voltage pulses (same voltage the rst prism is shown in Fig. 7a. The pulse sequence can

Figure 7 Building vector sequence and pulse pattern computation


a Steps for the modulation in the rst prism
b Symmetric modulation in the rst prism

Figure 8 Experimental results


a Voltage under asymmetrical resistive load
b Current under asymmetrical resistive load

330 IET Power Electron., 2010, Vol. 3, Iss. 3, pp. 323 333
& The Institution of Engineering and Technology 2010 doi: 10.1049/iet-pel.2008.0281
www.ietdl.org

Figure 9 Experimental results


a Transient response, load step down, current under asymmetrical resistive load
b Transient response, load step up, voltage under asymmetrical resistive load

Table 4. Different scenarios were tested experimentally.


In the rst case, an unbalanced resistive load was placed.
The resistance at phase a and b has been kept at 50 V
and the resistance of phase c is set to 25 V. The output
voltage is a constant three-phase signal in amplitude and
phase while the current is different due to the load
unbalance, see Fig. 8. The voltage THD 2.12% and the
current THD 2.40%.

In the second case, balanced resistive load was placed. The


resistance at all phases was set to 50 V initially. Afterwards,
a load step was done from 50 to 25 V at phase a. The
Figure 10 Current transient response under resistive- output voltage is a constant three-phase signal in amplitude
inductive load, load step down at one phase and phase while the current is increasing to compensate for
the load step, see Fig. 9.
be achieved by comparing the duty cycles with a carrier signal.
The pulse sequence for phase a, b and c are shown in Fig. 7b In the third case, an unbalanced resistive-inductive load
for the same mentioned case. was placed. The resistance at all phases was set to 50 V
initially, except phase a which includes a 3 mH inductance
in series as well. Afterwards, a load step down was done
from 50 to 25 V at phase a. The output voltage is a
6 Experimental results constant three-phase signal in amplitude and phase, while
A 10 kW experimental prototype using IGBTs was the current is increasing to compensate for the load step,
successfully built to validate the 3D-SVM PWM see Figs. 10 and 11. The voltage THD 2.29% and the
algorithm. The inverter main parameters can be seen in current THD 2.47%.

Figure 11 Voltage transient response under resistive-inductive load, load step down at one phase

IET Power Electron., 2010, Vol. 3, Iss. 3, pp. 323 333 331
doi: 10.1049/iet-pel.2008.0281 & The Institution of Engineering and Technology 2010
www.ietdl.org

7 Conclusion [8] ZHANG R., PRASAD V.H., BOROYEVICH D. , LEE F.C. : Three-
dimensional space vector modulation for four-leg
This paper introduces control functions for three-leg four- voltage-source converters, IEEE Trans. Power Electron.,
wire inverters. These functions are capable of providing 2002, 17, (3), pp. 314 326
good power quality to loads even under extreme unbalanced
conditions. These control strategies are based on sequence [9] CHAGHI A., BENOUDJIT A.G.: Four legged active power lter
decomposition where asymmetrical three-phase signals compensation for a utility distribution system, J. Electr.
(voltage/current) can be represented as sum of positive, Engng., 2004, 55, pp. 31 35
negative and zero-sequence. As part of this control strategy,
a new approach of 3D-SVM for three-leg four-wire voltage [10] PERALES M.A. , PRATS M.M. , PORTILLO R. , MORA J.L. , LEO N J.I. ,
source inverters is introduced. The steps for the 3D-SVM FRANQUELO L.G.: Three-dimensional space vector modulation
implementation are identied. The switching vectors, in abc coordinates for four-leg voltage source converters,
3D-SVM diagrams and the boundary planes equations, as IEEE Power Electron., 2003, 1, (4), pp. 104 109
well as the matrices for the duty cycles and symmetric
switching sequences are discussed in detail. Experimental [11] ZHOU K., WANG D. : Relationship between space-
results including different loads are presented to validate vector modulation and three-phase carrier-based
the proposed novel SVM control strategy for three-leg PWM: a comprehensive analysis, IEEE Trans. Ind.
four-wire voltage source inverters. Electron., 2002, 49, (1), pp. 186 196

Experimental results show that the proposed 3D-SVM [12] PINHEIRO H., BOTTERON F., RECH L.S.C., ET AL .: Space vector
control schemes for three-leg four-wire inverters can carry modulation for voltage-source inverters: a unied
out the feeding requirements of unbalanced loads in an approach. Presented at IEEE 28th Annual Conference of
efcient way. It can supply good quality balanced regulated the Industrial Electronics Society, 2002
three-phase voltage in the presence of unbalanced loads.
[13] DAI N.-Y., WONG M.-C., HAN Y.-D.: Application of a three-level
NPC inverter as a three-phase, four-wire power quality
8 References compensator by generalized 3DSVM, IEEE Trans. Power
Electron., 2006, 21, (2), pp. 440 449
[1] LOPES J.A.P., MOREIRA C.L., MADUREIRA A.G.: Dening control
strategies for MicroGrids islanded operation, IEEE Trans. [14] VERDELHO P.: Space vector based current controller
Power Syst., 2006, 21, pp. 916 924 in ab coordinate system for the PWM voltage
converter connected to the AC mains. Presented at
[2] PIAGI P., LASSETER R.H. : Autonomous control of PESC97, 1997
microgrids. Presented at IEEE PES Meeting, Montreal,
June 2006 [15] VERDELHO P., MARQUES G.D.: Four-wire current-regulated
PWM voltage converter, IEEE Trans. Ind. Electron., 1998,
[3] PRODANOVIC M., GREEN T.C.: High-quality power generation 45, pp. 761 770
through distributed control of a power park microgrid, IEEE
Trans. Ind. Electron., 2006, 53, pp. 1471 1482 [16] ZHAN C., RAMACHANDARAMURTHY V.K., ARULAMPALAM A., ET AL .:
Dynamic voltage restorer (DVR) based on voltage-space-
[4] KEYHANI A., DAI M., JUNG J.W.: Parallel operation of power vector PWM control, IEEE Trans Ind. Appl., 2001, 37,
converters for applications to distributed energy systems. pp. 1855 1863
Presented at 2nd IASTED Int. Conf. Power and Energy
Systems, Greece, 2002 [17] ZHAN C., ARULAMPALAM A., RAMACHANDARAMURTHY V.K., FITZER C.,
BARNES M., JENKINS N.:
Dynamic voltage restorer based on 3-D
[5] GUERRERO J.M., DE VICUNA L.G., MATAS J., CASTILLA M., MIRET J.: A voltage space vector PWM algorithm. Presented at IEEE
wireless controller to enhance dynamic performance of PESC, Vancouver, Canada, 2001
parallel inverters in distributed generation systems, IEEE
Trans. Power Electron., 2004, 19, pp. 1205 1212 [18] ZHAN C., ARULAMPALAM A., JENKINS N.: Four-wire dynamic
voltage restorer based on a three-dimensional voltage
[6] SAO C.K., LEHN P.W.: Autonomous load sharing of voltage space vector PWM algorithm, IEEE Trans. Power
source converters, IEEE Trans. Power Deliv., 2005, 20, Electron., 2003, 18, pp. 1093 1102
pp. 1009 1016
[19] VILLALVA M.G., RUPPERT E.F.: 3-d space vector PWM for
[7] MARWALI M.N., JUNG J.-W., KEYHANI A.: Control of distributed three-leg four-wire voltage source inverters. Presented at
generation systems. Part II: Load sharing control, IEEE IEEE Annual Power Electronics Specialists Conference
Trans. Power Electron., 2004, 19, (6), pp. 1551 1561 PESC, 2004

332 IET Power Electron., 2010, Vol. 3, Iss. 3, pp. 323 333
& The Institution of Engineering and Technology 2010 doi: 10.1049/iet-pel.2008.0281
www.ietdl.org

[20] DAI M., MARWALI M.N., JUNG J.-W., KEYHANI A.: A three-phase [29] SONG H.-S., NAM K.: Dual current control scheme for
four-wire inverter control technique for a single PWM converter under unbalanced input voltage
distributed generation unit in island mode, IEEE Trans. conditions, IEEE Trans. Ind. Electron., 1999, 46,
Power Electron., 2008, 23, pp. 322 331 pp. 953 959

[21] OMARI O.: Conceptual development of a general supply [30] VECHIUM I., CAMBLONG H. , TAPIA G. , CUREA O., DAKYO B.:
philosophy for isolated electrical power systems, PhD Modelling and control of four-wire voltage source
Thesis, South Westphalia University of Applied Sciences, inverter under unbalanced voltage condition for hybrid
Soest, Germany, 2005 power system applications. Presented at 2005 European
Conf. Power Electronics and Applications, 2005
[22] SEGUIER G., LABRIQUE F.: Power electronic converters, DC-
AC conversion (Springer, Heidelberg, Germany, 1993) [31] ENGLER A. : Control of parallel operating battery
inverters. Presented at Photovoltaic Hybrid Power
[23] EL-BARBARI S., HOFMANN W.: Digital control of a four leg Systems Conference, Aix-en-Provence, 2000
inverter for standalone photovoltaic systems with
unbalanced load. Presented at IECON 2000. 26th Annual [32] LASSETER R., PIAGI P. UNIVERSITY OF WISCONSIN-MADISON: Control
Conference of the IEEE, 2000 and design of microgrid components. Final Project Report,
January 2006
[24] ZHANG R.: High performance power converter systems
for nonlinear and unbalanced load/source, PhD Thesis, [33] MATTHIAS H., HELMUT S.: Control of a three-phase inverter
Faculty of the Virginia Polytechnic Institute and State feeding an unbalanced load and working in parallel with
University, Virginia, 1998 other power sources. Presented at EPE-PEMC Dubrovnik,
2002
[25] ZHANG R. , BOROYEVICH D. , PRASAD V.H. , MAO H.C. , LEE F.C. ,
DUBOVSKY S.:
A three-phase inverter with a neutral leg with [34] ORTJOHANN E. , MORTON D., MOHD A. , HAMSIC N., OMARI O. :
space vector modulation. Presented at Twelfth Annual Grid-forming three-phase inverters for unbalanced loads
Applied Power Electronics Conference and Exposition, 1997 in hybrid power systems. Presented at IEEE 4th World
Conf. Photovoltaic Energy Conversion, Waikoloa, Hawaii,
[26] BRUCOLI M. , GREEN T.C. : Fault response of inverter 2006
dominated microgrids. Presented at 2nd Int. Conf.
Integration of Renewable and Distributed Energy [35] ORTJOHANN E. , MOHD A., HAMSIC N., MORTON D., OMARI O. :
Resources, Napa, California, USA, 2006 Advanced control strategy for three-phase grid inverters
with unbalanced loads for PV/hybrid power systems.
[27] HOCHGRAF C., LASSETER R.: StatCom controls for Presented at 21th European PV Solar Energy Conf.,
operation with unbalanced voltages, IEEE Trans. Power Dresden, 2006
Deliv., 1998, 13, (2), pp. 538 544
[36] ORTJOHANN E., MOHD A., HAMSIC N., AL-DAIB A., LINGEMANN M.:
[28] SACCOMANDO G., SVENSSON J.: Transient operation of grid- Three-dimensional space vector modulation algorithm for
connected voltage source converter under unbalanced three-leg four-wire voltage source inverters. Presented at
voltage conditions. Presented at IEEE Industry the First Int. Conf. Power Engineering, Energy and
Applications Conf., Chicago, USA, 2001 Electrical Drives (POWERENG), Portugal, 2007

IET Power Electron., 2010, Vol. 3, Iss. 3, pp. 323 333 333
doi: 10.1049/iet-pel.2008.0281 & The Institution of Engineering and Technology 2010

Você também pode gostar