Você está na página 1de 5

Protection Technology

Challenges of protection power grids with distributed generating units

Technical Article
The energy transition changes power grids
Challenges of protecting power grids
with distributed generating units
The energy transition implies a paradigm shift in the energy system and has an impact on the
generation, transmission and distribution of electricity. An increasing number of distributed
generating units based on renewable energies have to be integrated. Wind energy and
photovoltaics systems are the fastest growing suppliers. This calls for a protection concept that is
tailored to the new conditions, the selection of appropriate protection devices including the
functions and protective settings adjusted to the changed grid conditions. This essay presents
possible consequences for the protection technology.
As the energy transition is being put into Guidelines for generating units at the The contribution of
practice, energy is generated at all voltage medium-voltage grid 2008; EEC converter-controlled generating units to
levels which entails a change of classic grid generating units at the high- and extra the short-circuit current is low and is
tasks. A distribution grid contributes high-voltage grid 2004 and their within the range of the generating
significantly to the generation of electricity update in the technical connection unit's rated current (1 Irated) and in
and assumes transport tasks. The protection conditions TAB [2, 3] some cases even below, for example
system makes a major contribution to the System service provision ordinance on under weak wind conditions. This has
supply security. wind energy farms (SDLWindV) [4]. an impact on the selection of protection
principles and protective settings. It is
Marginal conditions General requirements for the recommended to make sample
protection technology calculations to distribute the
Distributed generating units have to short-circuit fault during a fault.
observe guidelines and they are subject to Power grid studies found the following: In case of unbalanced faults, the fault
certification. The following guidelines have current contribution depends on
to be complied with: Existing protection principles and control procedures of the inverter or
schemes are basically suitable. frequency converter (for example only
Gridcode (for example transmission However, protective settings have to be feed-in of a positive-sequence
code TC 2007) which specifies the adjusted to the changed grid current). To cope with unbalanced
feed-in conditions (for example, also conditions. faults, a negative-sequence current
feed-in during a fault fault ride
has to be injected. The inverter
through, reactive power provision for
voltage stabilization)) [1] operating principle has to be inquired
with the manufacturer.
Due to the distributed feed-ins, the
distribution grid's topology and tasks
are similar to the transmission grid. For
example, there are multi-end feed-ins
or intermediate feed-ins. This requires
established protection concepts and
graded protection principles from the
transmission grid to be implemented.
In addition to protection tasks, grid
disconnection and load shedding have to be
implemented, taking the feed-in conditions
into account.

Digital protection devices are the


optimum solution for many
applications

The multifunctional digital device


technology and the functions including
state-of-the-art communication features are
designed to enable solutions tailored to the
application.
Figure 1. single-pole earth fault and no infeed of short circuit through wind farm

The energy transition changes power grids / Energy Automation 08-2015


x

Figure 2. example of additional infeed of synchronous generator into the medium-voltage grid
a) situation of infeed and failure; b) impedance trajectory depending on duration of failure

They are supported by a powerful Feed-in of a wind farm Additional feed-in of synchronous
engineering tool (for example Digsi 5 from Figure 1 shows a wind farm connected to generators in a medium-voltage grid
Siemens). Siprotec 5, the new family of the grid with a phase-to-ground fault In this example, a synchronous generator
protection devices from Siemens, combines occurring in the grid. The individual wind (biomass, hydro-electric power plant)
protection, control, automation, energy units feed energy to the grid additionally feeds energy into the grid. The
measurement, regulation and through the frequency converter. No grid connection design is depicted in Figure
communication in one device [5] and has zero-sequence system is transmitted in case 2a. The busbar is fed through a strong grid.
the following typical properties: of a transformer in the star delta vector The protection in the outgoing feeders is
group. A phase-to-ground fault at the star implemented as a directional time
A modular hardware and software side results in a 2-phase short circuit with a overcurrent protection. The selected delay
concept enables the devices to be distinct negative-sequence current. But time t results from the grading time. Now if
tailored to the grid conditions (for since the wind farm in its present design a short-circuit occurs on the line of
example free selection of the measuring does not feed in any negative-sequence protection equipment A, this fault is fed
points, of the I/O quantity structure, the current (no negative-sequence impedance both by the grid and by the synchronous
protection functions and the available), the wind farm neither supplies a generator. Upon fault inception, a forward
communication infrastructure). fault current. This is equivalent to an open fault is recognized in A and timing element t
Identical functions are used in various circuit breaker in the wind farm. The fault is started. Protection device B, in contrast,
devices, increasing the flexibility of current is solely fed through the remaining recognizes the reverse direction. In the
application (communication of grid. The behavior (open circuit breaker at event of a fault, the synchronous generator
protection data between the devices). the transformer delta side) is known as the is relieved in terms of active power, causing
High-precision measurements (class 0.2 Bauch phenomenon in protection the generator to accelerate and the angular
for U, I and class 0.5 for P, Q, S) make technology. Figure 1 depicts the situation displacement to change. The
additional measuring transducers and shows the currents and voltages at the current/voltage vector will thus offset over
redundant and additionally enable a measuring point at the transformer star time.
wide setting range of the protection side. The distinct zero-sequence current in
functions. all three phases is typical of the Bauch In line B that is feeding the fault current, the
Powerful fault recording and evaluation phenomenon. A distance protection must protection device will recognize the reverse
tools support fault recovery. recognize this situation, select the proper fault as a forward fault after a certain period
measuring loop and trip selectively. of time and also start the timing element.
Different protocols and communication Depending on the fault duration and the set
infrastructures provide for the optimal As feed-ins through inverters or frequency grading time, the outgoing feeder B may
connection to the substation control and converters will increase, these also have to also trip. To prevent this non-selective
protection system. The devices support IEC be capable of supplying a tripping, the tripping time in outgoing
61850 Edition 1 and 2. negative-sequence current during a fault feeder A has to be reduced. This can be
from a protection perspective [6, 7]. achieved by replacing the so far directional
Applications Simulations have shown that when inverter overcurrent protection with a distance
controllers are not set correctly, inverters protection.
We have selected some representative are capable of delivering harmonics during
examples from the application options. a fault as a result. When the setting is
They give an overview of possible correct, the feeding quantities are
changes: sinusoidal (fundamental component). As
faults cannot be ruled out entirely, the
protection has to be resistant towards
harmonics.

The energy transition changes power grids / Energy Automation 08-2015


Figure 4 shows a connection example, the
most important protection and
disconnection functions and their settings.
Other well-known disconnection criteria
such as the phase angle jump of the voltage
vector (vector jump) and the frequency rate
of change function df/dt) are not
recommended, because they require
complex settings (grid calculations with
variant consideration) and involve the risk of
over- or underfunctioning (practical
experience). The threshold values of the
frequency functions correspond to the
requirements from [1] and are identical to
those of conventional power plants
(type 1 acc. to [1]).

Different variants of the plant design and


special cases to be considered were
discussed in detail in [10]. For this reason,
we will go into Figure 4 by way of example.
It depicts a typical constellation: Supply to a
medium-voltage grid and connection to the
high-voltage grid through a radial-line
connection.
The solutions to protect the tapped line on
the high-voltage side are sufficiently known.
There is one special aspect in this
application. If faults occur in the
Figure 3. load shedding by taking into account infeed conditions high-voltage grid, the circuit-breaker in the
radial-line connection remains closed.
But there are other approaches to reducing This automation environment in particular But the circuit-breaker of the feed-in into
the tripping time: contains modern, digital devices that offer the medium-voltage grid will be
Using the line differential protection various possibilities, such as the function intertripped by distance protection A. The
that needs an additional backup itself, high-precision measurements and goal is to assure the supply reliability of the
protection to respond when the flexible communication. Adaptive load consumers in the medium voltage, since
upstream protection device fails. shedding becomes reality. most faults in high voltage can be cleared
Possible backup protection functions by automatic reclosing. In medium-voltage
include a time overcurrent protection Grid disconnection faults, distance protection A assumes the
(also directional depending on the Given the rapid increase of distributed function of a backup protection.
application) and a distance protection feed-ins (in particular type 2 according to
at higher voltage levels [8]. [1]), the disconnection strategy has Distance protection B fulfils the same
Expanding the directional time changed over the years. The goal is to keep function with the reverse zone. The forward
overcurrent protection to ensure generating units connected to the grid for zone of distance protection B clears faults
protection data communication and as long as possible. Besides grid on the line towards the generating unit. It is
implementation of directional disconnection specifications, the guidelines crucial for the distance protection setting
comparison protection. The latter has to also define marginal conditions for the that fault currents inside or below the rated
be designed so as to require no infeed feed-in behavior. For example, the fault current range have to be mastered. A U/I
from the remote end. This means that if ride-through capability is required. This and Z pickup is a mandatory requirement.
the infeed side protection device picks means that during a 3-pole short-line fault The overvoltage disconnection function
up and the opposite side is not blocked, generating units have to stay connected to protects a grid against overvoltage and in
the device will trip short time [9]. the grid for at least 150 ms and feed in doing so contributes to the power quality.
again once the fault has been cleared by the The undervoltage function protects the grid
Load shedding protection device (e.g. the differential against inadmissible undervoltage and is
If consumed and generated active power protection). Moreover, the systems have to the backup protection of the distance
are out of balance, the previous solution contribute to voltage stabilization resulting protection if the latter fails to pick up.
has been to shed loads with from the requirement to inject reactive
underfrequency based on a fixed frequency power in the event of a fault. The grid connection U< stage assures the
stage plan (5-stage plan [1]). If, however, grid disconnection and it is the backup
distributed generating units supply at the A pragmatic approach was chosen for the protection for the undervoltage protection
grid connection point, these are lost. This definition of the disconnection criteria. In of the generating unit.
exacerbates the situation between addition to overfrequency and The U< stage assures the grid disconnection
generation and consumption. Therefore, underfrequency (f>, f<), overvoltage and in the event of undervoltage conditions and
the international and national guidelines undervoltage (U>, U<) are required. The simultaneously assumes a backup function
were adapted accordingly without any directional reactive power function with for the short-circuit protection of the
further development towards more additional undervoltage release in all three generating unit (for type 2) and the U<<
flexibility [8]. phases is a new feature (evaluation of the stage. The U<< stage is the main protection
If there are distributed feed-ins besides phase-to-phase voltage). This function aims for low-current faults. The QU protection
loads at the grid connection point, the to prevent the voltage from being reduced monitors the appropriate post-fault
circuit breaker must not open when energy further when reactive power is imported. behavior and performs the separation at the
is fed back (Figure 3). The frequency The selectivity of the disconnection grid connection point.
protection has to be connected to the functions is implemented by different
power directional protection. threshold values and timer settings.

The energy transition changes power grids / Energy Automation 08-2015


Summary References Author

[1] Transmission Code 2007: Netz-und Systemregeln Dipl. Ing. habil.


We have used examples to show that the
der deutschen bertragungsnetzbetreiber. VDN Hans-Joachim Herrmann,
energy transition with its distributed Product Lifecycle Manager,
Berlin, Version 1.1, August 2007.
generating units has an impact on the [2] Technische Richtlinie Erzeugungsanlagen am Protection and Substation Automation,
protection technology. Existing protection Mittelspannungsnetz. Regelungen und Principa Key Expert
principles still have a right to exist. The bergangsfristen fr bestimmte Anforderungen Energy Management Division,
significant changes in the feed-in situation in Ergnzung zur technischen Richtlinie. BDEW, Energy Automation,
call for a reassessment of existing Berlin, January 2013 edition. Siemens AG, Nuremberg
protection concepts and settings. Hence, it [3] EEG-Erzeugungsanlagen am Hoch- und
Hchstspannungsnetz. VDN Berlin, August 2004
is insufficient to simply connect the
und TAB Hochspannung, VDE-AR-N 4120, VDN
generating unit (as certified). A holistic Berlin, January 2015.
consideration of the system has to be [4] Verordnung zu Systemdienstleistungen durch
performed at any rate. Windenergieanlagen (SDLWindV). German
In this context, generating units are not all Federal Environment Ministry, Berlin, 3 July
the same. Type 1 units, feed-in via 2009, and amendments in 2014.
synchronous generators, behave in the [5] Siprotec 5 Schutz, Automatisierung und
well-known way. In contrast, type 2 units, berwachung. bersichtskatalog
C1000G220-A221, Siemens AG, Nrnberg, 2014.
such as feed-in via frequency
[6] Erlich, I.; Schegner, P.: Wind Turbine Negative
converter/inverter, exhibit a different Sequence Current Control and its Effect on Power
behavior. In particular, the low short-circuit System Protection. IEEE PES GM, Vancouver
current has to be coped with in the event of 2013.
a fault. As a result, distance or differential [7] Khn, H.: Der Einfluss regenerativer
protection schemes and modified settings Erzeugungsanlagen auf den Kurzschlussstrom. 7.
(pickup and rated current) are required. ETG/FNN-Tutorial Schutz- und Leittechnik, Mainz,
February 2012.
Modern digital protection devices have the
[8] Hlshorst, H.-G.: Auswirkung der dezentralen
potential to tackle the new challenges. Einspeisung auf das Lastabwurfkonzept.
Future solutions will be based not only on ETG-Tagung Schutz- und Leittechnik, Dsseldorf,
the implementation of new functions, but February 2014.
also on flexible communication features [9] Siprotec-5-Distanzschutz,
including high-precision measurement Leitungsdifferentialschutz und
technology. It is crucial that both grid Schaltermanagement fr einpolige und
operators and device manufacturers dreipolige Auslsung 7SA87, 7SD87, 7SL87,
7VK87. Handbuch C53000G5000-C011-6,
exchange their experiences and work
Siemens AG, 2014.
together on developing a new and reliable [10] Siprotec 5 berstromzeitschutz 7SJ82,7SJ85,
electrical energy system. Handbuch C53000G5000-C017-5, Siemens AG,
2014.
[11] Hinz., K.; Schossig, W.: Schutzkonzeptionen fr
Verteilnetze dezentrale
Energieerzeugungsanlagen. Anwendertagung
Omicroncamp, Ulm, June 2013.

The energy transition changes power grids / Energy Automation 08-2015

Você também pode gostar