Você está na página 1de 8

Evolution of High-rise Buildings in Vancouver, Canada

Perry Adebar, Ph.D., P.Eng., Prof., University of British Columbia, Vancouver, Canada; Ronald DeVall, Ph.D., P.Eng.,
Read Jones Christoffersen, Vancouver, Canada; James Mutrie, P.Eng., Jones Kwong Kishi, North Vancouver (retired),
Contact: adebar@civil.ubc.ca
DOI: 10.2749/101686617X14676303588670

Abstract are large enough to cause signicant


damage to buildings if they occur
The potential for a large earthquake to cause signicant ground shaking has close enough to the buildings. Figure
had a dening inuence on the evolution of high-rise buildings in the City of 2 shows the earthquakes of magnitude
Vancouver. However, unlike other major cities along the seismically active 5 or greater that have occurred within
west coast of North America, structural steel systems and reinforced concrete 500 km of Vancouver in the past
moment-resisting frame systems have rarely been used. Virtually all high-rise 30 years. These earthquakes have all
buildings in Vancouver are concrete shear wall buildings. Older buildings, con- been more than 200 km away from
structed up until the mid-1980s, typically have thin (200 mm or less) lightly Vancouver and therefore have not
reinforced concrete walls distributed throughout the buildings. A number of caused signicant damage to the
factors, such as increased seismic demands and the changing requirements of buildings in Vancouver.
the Canadian building code, caused a paradigm shift in the 1980s so that today,
almost all new high-rise buildings in Vancouver have a large central core that is The largest earthquake to occur within
designed to resist all lateral loads. Typical modern high-rise cores have three 500 km of Vancouver in the past
independent cantilever walls in one direction that are coupled together in the 30 years was the magnitude 6.8 Nisqu-
transverse direction by ductile coupling beams above the door openings on ally Earthquake, which was an intra-
each story. The City of Vancouver has recently declared that the designs of plate earthquake that occurred at a
high-rise buildings must attain a new benchmark of architectural creativity. The depth of ~50 km and at a distance of
recent designs that have been proposed for the city include very irregular build- ~240 km south of Vancouver. The
ings that are much less likely to be habitable after an earthquake. earthquake was felt in Vancouver but
did not cause any damage to buildings.
Keywords: building codes; high-rise buildings; history; seismic design; shear It caused up to USD 4 billion damage
walls. in areas up to 150 km from the epicen-
tre, and injured up to 400 people. The
two largest earthquakes ever recorded
Introduction oors in multi-story residential in Canada were interplate earthquakes
buildings. that occurred about 700 km north-west
Vancouvers history of high-rise build- of Vancouver along the Queen Char-
ings began in the early 1900s, and for Today, the city of Vancouver has
lotte FaultMagnitude 8.1 in 1949 and
many decades, Vancouver had the tal- about 700 buildings that are 12 or
Magnitude 7.8 in 2012. These earth-
lest buildings in the British Empire. more stories and at least 35 m high
quakes were too far away to cause
The very early tall buildings have (see Fig. 1). Note that multiple build-
ings with the same height and con- damage to the buildings in Vancouver.
structural steel frames with masonry
inll walls that resist lateral loads. struction start date show up as one The third type of earthquake that
Vancouver experienced a boom of data point in Fig. 1. While the city could cause signicant ground shaking
high-rise construction from the mid- currently ranks 10th in the world in Vancouver is caused by the Casca-
1960s to early 1980s, and an even lar- for the number of high-rise buildings dia subduction zone, which is located
ger building boom started in the 1990s (skyscraperpage.com), it is a much west of Vancouver Island. The Juan de
and continues to this day (Fig. 1). smaller city than all the cities in the Fuca tectonic plate is sliding (subduct-
Virtually all of these buildings are of world that have more high-rise build- ing) underneath the North American
reinforced concrete. Some of the fac- ings. With a population of just over tectonic plate; but the movement is not
tors that contributed to this are the 600 000 people, Vancouver has 1.1 continuous. The two plates are cur-
abundance of experienced (mostly high-rise buildings per 1000 people, rently locked together causing stress to
non-unionized) concrete contractors while New York City, which has the build up in the Earths crust. Every
in the city; the absence of steel mills largest number of high-rise buildings 300800 years (550 years on average),
producing rolled structural sections in in the world, has about 60% as many the two plates slip and the resulting
western Canada; and the advantages high-rise buildings per capita. movements (up to 1000 km of rupture
of using thin concrete slabs rather length and up to 25 m of slip) can
than structural steel framing for the Regional Seismicity cause a subduction earthquake of mag-
nitude 9.0 to occur.1 Such an earth-
The west coast of British Columbia is
quake may cause very signicant long-
a seismically active region where
Peer-reviewed by international ex- duration ground motions lasting sev-
more than 100 earthquakes of magni-
perts and accepted for publication eral minutes in Vancouver.
by SEI Editorial Board tude 5 (on the Richter scale) or
greater have occurred in the past While no building in Vancouver has
Paper received: April 18, 2016 70 years (Natural Resources ever been damaged by an earthquake,
Paper accepted: August 8, 2016 Canada).14 Earthquakes of this size the potential for signicant ground

Structural Engineering International Nr. 1/2017 Scientic Paper 7


60 7.0
Living Shangri-La
2001 Nisqually
50

Magnitude of earthquake
6.5
Number of stories

40 Empire Landmark hotel


6.0
30 Marine building
Sun tower
5.5
20

10 5.0
1900 1920 1940 1960 1980 2000 2020 0 100 200 300 400 500
Year of construction Distance from Vancouver (km)

F ig . 1: High-rise buildings in Vancouver (data from F i g. 2 : Earthquakes near Vancouver in the last 30 years
Skyscraperpage.com).15 (data from Natural Resources Canada).14

movement in Vancouver due to an Vancouver Building Height (CBD), as long as the building is not
earthquake has had a very dominant Restrictions within any of the designated view cor-
inuence on the structural form of ridors. Buildings in other parts of the
While Vancouver had some of the tal-
high-rise buildings in Vancouver, and CBD are limited to 180 m. Three
lest buildings one hundred years ago,
this is the primary subject of this CBD shoulder zones are limited to
today the tallest buildings in Vancou-
paper. Figure 3 summarizes how 170 m, while a fourth CBD shoulder
ver are very low in comparison to
earthquake demands on high-rise zone is limited to 150 m. The City also
other cities. The tallest building in
buildings in Vancouver has changed permits taller buildings in two promi-
Vancouver, Living Shangri-La, is only
over the past 40 years. The design nent bridge gateways that mark the
201 m high (59 oors; Fig. 1). The
spectral acceleration values specied entry into downtown from the Bur-
reason for the low building heights is
by the National Building Code of rard and Granville Bridges.
not the signicant earthquake hazard,
Canada (NBCC)2 have been trans-
as assumed by some. The City of Van-
lated into the corresponding design
couver has restricted building heights Early Canadian Building Codes
spectral displacement values for build-
in order to protect the view of the
ings with a fundamental lateral period The Canadian building code for the
North Shore Mountains, the down-
T = 2 s (about a 20-story building) design of concrete buildings refers to
town skyline and the surrounding
and T = 4 s (about a 40-story build-
water.3 combined requirements of two sepa-
ing). As shown in Fig. 3, the earth- rate documents. The rst is the
quake demands increased signicantly Recently, the City of Vancouver has NBCC2, which is adopted by the pro-
in 1985, in 1995 for tall buildings relaxed the height restrictions in cer- vinces and large cities such as Van-
(T = 4 s), and also in 2015. Today, the tain areas of the city.3 Building couver that have a legal charter to
earthquake displacements that build- heights up to 210 m are now permit- adopt their own building code. NBCC
ings must be designed for are more ted along the three primary streets of species the general design require-
than four times what they were Georgia, Burrard and Granville ments for earthquakes, while the
in 1975. within the Central Business District design and detailing requirements for
concrete buildings are specied in
Canadian Standard CSA A23.3,4
which is referenced by NBCC.
400
Early editions of NBCC required
Spectral displacement (mm)

T = 4.0 s
buildings to be designed for a lateral
300 seismic force equal to 2 or 4% of the
building weight depending only on
the type of soil supporting the build-
200
T = 2.0 s ing. In the 1960 NBCC, the ratio of
lateral seismic force to building weight
100 was reduced with number of stories.
By 1965, the type of construction
became a factorframed buildings
0 with moment-resisting connections
1975 1985 1995 2005 2015
needed to be designed for only 60%
Year
of the seismic force that other types of
F ig . 3: Summary of how earthquake demands on high-rise buildings in Vancouver have buildings had to be designed for. In
changed over the past 40 years: spectral displacements at T = 2.0 s and T = 4.0 s. the seismically active west coast of the

8 Scientic Paper Structural Engineering International Nr. 1/2017


USA, the construction of reinforced be increased by the factor 1.1 w where examined and a detailed inventory6
concrete moment-resisting frame the overstrength ratio w was equal to was developed. The summary below
buildings became very popular at this the ratio of the moment capacity of was developed from that inventory.
time; but the system was rarely used the wall at the base divided by the fac-
About 200 of the buildings are resi-
in Canada. Designers opted to pro- tored bending moment applied at the
dential buildings from the West End
vide concrete shear walls to resist the base of the wall. The quantity of hori-
residential neighbourhood near Stan-
somewhat larger seismic forces (67% zontal reinforcement required for
ley Park. Sixty of the buildings are
larger forces in the 1965 NBCC, shear resistance was determined
from downtown, and 85% of these
reduced to 50% larger forces in the neglecting the concrete contribution
are ofce buildings. The remaining
1970 NBCC). to shear resistance Vc in the lower half
buildings are a mix of residential and
In 1970, NBCC introduced the of the wall.
ofce buildings from other parts of
requirement that all buildings over In 1975, ductile exural walls were the city.
61 m high must have a moment- introduced as a system into NBCC,
resisting space frame (MRSF) that is It was found that 97% of all buildings
and at the same time the requirement
capable of resisting not less than 25% had concrete shear walls as the pri-
that buildings over 61 m high must
of the seismic forces; however this mary seismic-force-resisting system.
have a MRSF was removed. Ductile
Of these, 80% had distributed shear
requirement could be waived if evi- exural walls needed to be designed
dence was provided to show that the for only 43% larger seismic forces walls, while the remaining 20% had
building without the frame could with- than ductile MRSFs regardless of the the shear walls concentrated in a sin-
stand the design earthquake with duc- building height. Regular exural walls gle core. Many buildings have some
tility and energy absorptive capacity (not meeting the special requirements kind of grouping of walls (small core)
equivalent to the building with a for seismic design) were permitted to around the stair and elevator shafts
frame. This requirement continues to be used up to any height without a that contribute to the lateral stiffness
be prevalent in US seismic design moment-resisting frame; but needed of the building; but many of these
codes, where in the last decade, to be designed for 185% larger seis- small cores are too slender to contrib-
performance-based design (non-linear mic forces than ductile MRSFs when ute signicantly to the lateral stiffness
dynamic analysis) has been commonly over 61 m high, and 85% larger forces of the building. Figure 4 shows an
used to avoid having to provide for heights up to 61 m. example building.
moment-resisting frames in shear wall The older buildings, i.e. pre-1960,
buildings over 76 m high.5 tend to have less wall arealess than
Vancouver High-rise Buildings about 1.5% of the oor area, while
In 1973, design and detailing require-
Built Prior to Mid-1980s buildings built after 1960 tend to have
ments for ductile exural walls were
introduced into CSA A23.3. The larger wall areas. Many of the build-
The high-rise buildings in Vancouver
detailing rules included: minimum ings built from 1960 to 1980 have wall
can be categorized into those built
0.0025 distributed horizontal rein- areas equal to about 2.0% of the oor
prior to the mid-1980s and the more
forcement and 0.0015 distributed ver- area, while some have up to 2.5% or
modern buildings built after that era.
tical reinforcement (both as a portion even 3.5%.
In order to determine the features of
of the gross concrete area); maximum typical pre-1980s high-rise buildings, The height-to-length ratios of the
spacing of 450 mm for all distributed the structural drawings of about shear walls (elevation aspect ratio)
reinforcement in the upper half of the 350 buildings in Vancouver were vary from 2 to 20, however the
structure and 300 mm maximum spa-
cing in the lower half of the structure.
Concentrated reinforcement, tied as a
column, was required at the end of
each wall, and not more than 50% of
this reinforcement was to be spliced at
the same location. In the lower half of
the structure, where plastic hinging
was expected to occur, the spacing of
the ties was limited to 8 bar diameters
to prevent buckling of the concen-
trated vertical reinforcement. Suf-
cient vertical reinforcement had to be
provided across all horizontal con-
struction joints. It is interesting to
note that, while there have been some
renements, these requirements are
surprisingly similar to the current
design requirements, more than
40 years later.
In one of the earliest applications of
capacity design, the factored shear Fi g . 4: Typical oor plan of a Vancouver high-rise residential building constructed
force at every elevation over the before the mid-1980s with distributed individual shear walls plus staircase and elevator
height of a ductile exural wall had to core walls.

Structural Engineering International Nr. 1/2017 Scientic Paper 9


ratios in most walls are in the range displacement of the gravity-load 10% of the plan dimension of the
of 412. Most of the concrete walls frame. Many of the older buildings building in the direction of the com-
are 200 mm thick; however about also do not have the designated integ- puted eccentricity. During this same
25% are only 150 mm thick. More rity steel (special bottom reinforce- period of time, the analysis tools
than half the walls have a single ment in the slab that goes through the available to the designers in Vancou-
layer of reinforcement, while the columns) to prevent complete collapse ver also changedthree-dimensional
remaining walls have two layers. The of at-plate slabs due to pull-out of linear response spectrum analysis
wall length-to-thickness ratio (plan the top reinforcement in the slabs.6 became readily available. Thus,
aspect ratio) ranged from a very designers were able to include the
small number up to 50; however torsional mode of vibration into the
Factors Inuencing High-rise building analysis. The increased acci-
most walls are less than 30, and the
mean value for all the buildings is Buildings after the 1980s dental torsion and the ability to visu-
about 15. Expected failure modes for alize the torsional modes of the
Many factors inuence the architec-
such thin (up to 200 mm thick) con- building made the designers much
tural form of high-rise buildings. For
crete walls include premature crush- more aware of the importance of tor-
example, the arrangement of gravity-
ing of the exural compression load columns is dictated by suite lay- sional deformations of the building.
zones,7 overall buckling of the walls, outs and the importance of not Figure 5 summarizes the force design
and lap-splice failures in the exural restricting occupant views, while at- requirements for exural walls relative
tension zones. plate oor slabs are typically used to ductile MRSFs. In 1990, the relative
The axial load on the walls due to because of the increased speed of con- seismic design forces for regular ex-
gravity loads was estimated to vary up struction from simplied formwork. ural walls (without any special require-
to ~15% fc0 Ag ; however the mean During the 1980s a number of factors ments for seismic design) increased
values of axial load on the walls is caused a paradigm shift in the typical very dramatically. When the height of
about 5% fc0 Ag . The percentage of dis- form of high-rise concrete buildings in the building was more than 60 m, reg-
tributed vertical reinforcement typi-
Vancouver. The 1984 edition of CSA ular exural walls had to be designed
A23.3 presented signicant new for a 300% increase in force (four
cally varies between 0.1 and 0.4%,
requirements for the ductility of ex- times the force) of ductile MRSF,
with about 40% of the walls having
ural walls. These requirements made while when the building was less than
less than 0.2%. The percentage of
it difcult for ductile exural walls to 60 m high, the walls had to be design-
distributed horizontal reinforcement
have a rectangular cross-section. The ed for 167% higher seismic forces than
typically varies between 0.2 and 0.3%. ductility requirements are discussed
The horizontal wall reinforcement ductile MRSF. At the same time, the
further in Section Ductility of Flexural ductile exural walls of any height
usually extends to the ends of the Walls.
wall, but is not anchored either by were reduced to only 14% larger than
hooking around a vertical bar or A second signicant change was the ductile MRSF. This strongly encour-
extending within tied vertical rein- increased seismic demands in the aged the use of ductile exural walls in
forcement. Essentially none of the 1985 edition of NBCC. As shown in Vancouver. In 1990, a new category of
walls have any tied concentrated verti- Fig. 3, earthquake spectral displace- special wallswith nominal
cal (boundary zone) reinforcement. ment demands for all types of build- ductilitywas introduced. This had
ings went up by a factor of 2.5 in only a few seismic design require-
Two types of irregularities were com- 1985. In addition, the design eccen- ments, and had to be designed for
monly observed in the shear walls. tricity for the minimum torsional 100% higher seismic force than ductile
The rst is when a wall has a large moments in the horizontal plane of MRSF when the building was less than
opening so that the wall is essentially the building was increased. The acci- 60 m high (200% increase when the
supported on two columnsone on dental torsion increased from 5 to building was more than 60 m high).
each end of the wall. About 30% of
the buildings were found to have this
350
type of irregularity. A second com- No longer
Percent increase in seismic design forces

mon irregularity is when a shear wall H > 60 m permitted


300
above overhangs the shear wall
H 30 m
below, sometimes referred to as a 250
ag wall. The wall below is sub-
H > 60 m
jected to signicantly larger vertical 200
strain and simultaneously increased H 60 m
H 60 m
horizontal tension strain due to the 150
Regular (conventional) wall
overhang above.8
100
One characteristic that distinguishes Moderately (nominally)
Ductile wall
older buildings from newer buildings 50
is that the older buildings do not have Ductile wall
any transverse shear reinforcement in 0
the at-plate slabs around the gravity- 1965 1975 1985 1995 2005 2015
load columns in order to prevent Year
punching shear failures of the slabs F i g. 5 : Increase in factored seismic design forces (elastic base shear reduced by force-
due to the concentrated deformation reduction factors) for concrete exural walls relative to ductile moment-resisting space
of the slabs from the lateral frames for buildings with different heights (H)

10 Scientic Paper Structural Engineering International Nr. 1/2017


In 1995, ductile coupled walls, with code provisions for wall ductility is to demand is estimated directly from
ductile coupling beams interconnect- dene the maximum length of the total displacement demand, and an
ing two or more wall piers, were exural compression zone in concrete estimate of yield curvature is used
introduced as a new system in walls without connement reinforce- only to determine the small elastic
NBCC, although the detailing rules ment. The ties that are provided portion of total curvature capacity.
for coupled walls had existed in CSA around the concentrated reinforce- These provisions require an estimate
A23.3 since 1984. Ductile coupled ment at the ends of the concrete walls of the displacement demand at the top
walls were designed for the same seis- in Vancouver are to prevent buckling of the wall due to the design earth-
mic force levels as ductile MRSFs. In of the vertical reinforcement, which quake. While this added complexity to
2005, new height limits were intro- requires much less ties than are the ductility provisions, it was neces-
duced into the Canadian building needed for connement of concrete. sary in order to ensure adequate per-
code that continues to this day. Duc- formance of all concrete walls while at
The 1973 edition of CSA A23.3 was
tile exural walls have no height limit; the same time not being unnecessarily
the rst to dene special provisions for
but moderately ductile walls (previ- restrictive for concrete walls in build-
seismic design of concrete buildings. It
ously called nominally ductile) are ings with good drift control.10
required that ductile exural walls be
limited to 60 m in Vancouver and
designed to have adequate ductility Comparing the limits from the newer
conventional (regular) exural walls
and energy absorption capacity in provisions with the older provisions,
are limited to 30 m in Vancouver. In
accordance with generally accepted ductile walls with small overstrength
addition, all systems must be designed
principles but did not give any specic are now permitted to have considera-
for a minimum seismic force level cal-
requirements. The commentary sug- bly larger compression zone lengths if
culated using a fundamental lateral
gested that ductile walls be designed the drift demand is small, and ductile
period of the building equal to 2.0 s,
with a minimum curvature (sectional) walls with signicant overstrength are
which is approximately the fundamen-
ductility of 3. It became known a now required to have much smaller
tal period for a 60 m tall building.
short time later9 that this was not an compression zone lengths if the drift
That is, all buildings taller than ~60 m
adequate level of ductility because of demand is large. For moderately duc-
must be designed for about the same
the concentration of inelastic curva- tile walls, the two provisions suggest a
seismic forceas a ratio of building
tures in the plastic hinge region. similar inuence of wall overstrength;
weightas for a 60 m tall building.
however, the permitted exural com-
The 1984 edition of CSA A23.3 pre-
All of these changes strongly encour- pression zone lengths are generally
sented the rst comprehensive provi-
aged the use of ductile walls arranged much smaller according to the newer
sions for the ductility of exural walls,
in a central core, which became the provisions. Overstrength is the ratio of
and these requirements were only
prevalent seismic-force-resisting sys- the exural resistance of a wall to the
slightly modied in the 1994 edition.
tem in high-rise buildings in Vancou- reduced bending moment demand
These provisions were based on the
ver after the 1980s. Typical modern accounting for ductility.
recommendation9 that the plastic
Vancouver core wall systems are dis-
hinge length for a slender wall is The ductility requirements play a very
cussed in Section Modern Vancouver
about equal to the wall length. More important role in dictating the geome-
High-rise Corewall Buildings.
recently it has become common prac- try of the concrete walls. The evolu-
tice to use a plastic hinge length equal tion of the ductility requirements in
Ductility of Flexural Walls the Canadian code has had a signi-
to 50% of the wall length.
The ductility requirements for exural cant impact on the form of modern
The cornerstone of the 1984/1994 duc-
walls ensure that the walls will have high-rise buildings in Vancouver as
tility provisions is that an accurate
adequate exural displacement capac- discussed in the next section.
estimate of yield curvature can easily
ity, which is one of the most important
be made from the yield strain of the
requirements for the seismic design of
high-rise shear wall buildings. When
reinforcement and the assumption of Modern Vancouver High-rise
small compression strains in concrete. Corewall Buildings
the maximum compression strain
The curvature demand on concrete
demand in a wall is expected to
walls was estimated as the yield curva- As a result of the issues described in
exceed the compression strain capac-
ture times the curvature ductility Section Factors Inuencing High-rise
ity of unconned concrete, conne-
demand, where the latter is a number Buildings after the 1980s, essentially
ment reinforcement must be provided
such as 10 for ductile walls. Thus, any all high-rise buildings in Vancouver
in the ends of the wall. Alternatively,
errors in the estimation of yield curva- built since the mid-1980s have a cen-
the wall geometry can be modied
ture are increased by an order of mag- tral core that is the lateral-force-
(e.g. size of compression ange
nitude in the estimate of curvature resisting system. The core is assumed
increased) to reduce the required ex-
demand. It has subsequently become to resist 100% of the lateral load due
ural compression zone length given
known that the yield curvature that to wind or earthquake. For buildings
the level of axial compression, and
should be used to estimate curvature over 30 stories, the quantity of rein-
hence reduce the maximum compres-
demand on a wall may deviate consid- forcement in the wall is typically dic-
sion strain demand. Owing to the
erably from the value that was used to tated by wind design requirements;
increased costs and difculties associ-
develop the 1984/1994 Canadian code however the detailing of the walls is
ated with providing connement rein-
requirements.10 dictated by the ductility requirements
forcement in the walls, Vancouver
for seismic design.
designers typically avoid providing In the 2004 Canadian code provisions
connement reinforcement in walls. for wall ductility, which are identical Figure 6 shows an example core from
Thus, the primary function of the to the 2014 provisions, total curvature a typical Vancouver high-rise

Structural Engineering International Nr. 1/2017 Scientic Paper 11


8100 about a vertical axis in Fig. 6) to resist
lateral loads due to wind or earth-
950 1200 quake. The three (U or inverted-U
shaped) walls are connected together
by diagonally reinforced coupling

600
beams4 above the 950 mm wide door
openings into the stairwell and the
1200 mm wide openings into the ele-
vator lobby area. With typical clear
story heights of 2.6 m, 0.2 m thick
slabs, and 2.12.2 m high door open-
ings, the coupling beams are typically
600700 mm deep. In a typical Van-
8600

couver core of a 30-story building,


about 85% of the overturning
moment applied in the coupled-wall
direction is resisted by the axial forces
in the two outside wallscompression
in one wall and tension (uplift) in the
opposite wall.

600
The wall system is designed so that
the coupling beams above the wall
400 350 600 openings will yield prior to the verti-
cal reinforcement at the base of the
F ig . 6: Partial oor plan showing a typical core from a modern high-rise building in
wall yielding due to the uplift forces
Vancouver. (Units: [mm])
from the coupling beams. That is, the
design uplift forces in the wall piers
building. The box-shape arrangement walls is very effective in controlling
are increased to account for over-
of walls has a number of signicant the torsional deformations of the
strength of the coupling beams. In
advantages. First, the perpendicular building and for resisting the applied
order to maximize the axial compres-
walls act as compression anges that seismic accidental torsional moment. sion applied to the walls from dead
ensure the compression strain depth is load of the structure, the gravity-load
A typical Vancouver core (as shown
limited to a small portion of the wall in Fig. 6) acts as three independent columns are usually positioned as far
length. This is important in order to cantilever walls in one direction as possible away from the core. The
meet the seismic ductility require- (bending about a horizontal axis in typical oor slabs in residential build-
ments in the Canadian code described Fig. 6), and acts as three (U or ings are 190 mm reinforced concrete
in Section Ductility of Flexural Walls. inverted-U shaped) coupled walls in at plate slabs that span up to 6.6 m
Second, the box arrangement of the transverse direction (bending from the core to the columns. In ofce

(a) (b) (c)

F i g. 7: Unique design aspects of the tallest high-rise building in Vancouver: Living Shangri-La (a), three-dimensional perspectives of
core walls (b) and typical mid-level oor plan (c)

12 Scientic Paper Structural Engineering International Nr. 1/2017


buildings, prestressed concrete (post- laterally) and would overload the The seismic design requirements for
tensioned) oor slabs may be used in gravity-load columns supporting the gravity-load resisting columns and
order to increase the span of the slabs other end of the transfer girders, the bearing walls depend on the inelastic
between the core and the perimeter 3.6 m deep transfer girders were cast exural deformation demands on the
columns. monolithic with the core walls over member. When seismic demands on
only the lower 0.9 m of depth. A gap gravity-load frames are determined
Figure 7 presents some design infor-
was left over the remaining 2.5 m using a linear model of the gravity-
mation from Living Shangri-La, 1128
height of the transfer girders. That is, load frame, the requirements are
West Georgia Street, which is cur-
the transfer girders were designed determined from how much the
rently the tallest building in Vancou-
with a pin support to the core walls. induced bending moment exceeds
ver at 201 m high. The rst 15 oors
the factored bending resistance of the
of the mixed-use building are a hotel,
Recent Canadian Building member. The limit ranges from 5.0
while condominium apartment units
times the factored bending moment
occupy the remaining oors. The Code Changes
resistance for columns from special
building has an unusual triangular
As shown in Fig. 3, the seismic moment-resisting frames to 0.5 times
oor plan in part because the building
demands on tall buildings have the factored resistance for thin walls
is located at the edge of a City of
increased signicantly in 2015. This is with a single layer of reinforcement.
Vancouver view cone (see
mostly because the subduction earth- The detailing requirements for
Section Vancouver Building Height
quake actions are combined probabil- gravity-load resisting beams are also
Restrictions). Normally the core walls
istically with the two other types of based on how much the calculated
in a building are prismatic over the
earthquakes that may generate bending moment exceeds the factored
full building height (wall thicknesses
ground motions in Vancouver.1 In bending resistance. Factored resis-
may reduce in taller buildings). In the
addition, a number of other signicant tances are used as a simple way to
case of Shangri-La, the core geometry
building code changes have occurred compensate for uncertainty in dis-
changes dramatically at two elevations
that will inuence the future design of placement demands. New axial load
where a bank of elevators stop. In the
high-rise buildings in Vancouver. restrictions have been placed on col-
lower portion of the building, the core
umns and bearing walls with a mini-
consists of three rectangular boxes, Gravity-Load Frames mum dimension <300 mm to account
while at the top level, the core con-
Perhaps the largest change for the for the fact that these thin members
sists of a single approximately square
2015 Canadian building code is the can suddenly lose all vertical load car-
box similar to the typical core shown
increased requirements for the design rying capacity.7
in Fig. 6. Figure 7c shows the arrange-
ment of core walls near mid-height of structural members not considered
where the building has two sets of ele- part of the seismic-force-resisting sys-
vator banks with three elevators each. tem (SFRS). One of the most com- Foundations
The core walls are up to 1524 mm mon causes of building collapse
during an earthquake is failure of Another major change is the
thick at the base of the building.
members in the gravity-load resisting requirement to consider how the
There were a number of unique struc- frame, e.g. failure of the gravity-load movement of all unrestrained foun-
tural design aspects of the building. resisting columns. The intent of the dations will inuence the SFRS and
One example is the design of the cou- new requirements, summarized in the gravity-load frame. A simplied
pling beams at the two elevations Ref. [11], is to ensure an adequate procedure that ignores foundation
where the core transitions, i.e. the last level of strength and/or ductility for movement can be used for founda-
coupling beams at the top of the cut- all structural members subjected to tions that are restrained against
off portion of the core. The disconti- seismically induced deformations. An rotation. Foundations are either
nuity of the core walls causes a large interstorey drift envelope is dened capacity protected (CP) by having
concentration of demands in these for shear wall buildings as a function an overturning capacity larger than
coupling beams. Another challenge of the global drift demand determined the SFRS or are not capacity pro-
was the unusual arrangement of at the top of the gravity-load frame tected (NCP). A simple non-linear
gravity-load columns. Because of the from an analysis that includes the static procedure is provided for esti-
unique geometry of the building, a effect of torsion. The variation of mating the rotation of CP founda-
number of columns were located close interstorey drift over the upper stories tions from the initial shear modulus
to the core (see Fig. 7). Also, the was developed from the results of of soil and the uniform bearing
inuence of differential creep shorten- numerous non-linear dynamic ana- stress required to resist the applied
ing of the more heavily loaded col- lyses of shear wall buildings. The pre- loads.12 The results from non-linear
umns and the core walls was scribed envelope also accounts for the response history analysis were used
investigated to ensure the oor slabs non-linear shear deformation in the to develop a simple upper-bound
would not become too far out of level. plastic hinge region of shear walls as estimate of the increased drifts due
Finally, a large number of the gravity- was observed in experiments. This to NCP foundations. A new require-
load columns had to be transferred non-linear shear deformation, which ment is that the factored overturning
near grade level using 3.6 m deep currently is not accounted for in state- capacity of NCP foundations must
transfer girders that were supported of-the-art non-linear analysis of shear not be less than 75% of the nominal
at one end by the core walls. Because walls, greatly increases the interstorey overturning capacity of the SFRS.13
of concerns that the very stiff transfer drift demands on the gravity-load This is expected to inuence the
girders would act as unintentional resisting columns over the plastic design of future high-rise building
outriggers (when the core bends hinge region of the shear walls. foundations.

Structural Engineering International Nr. 1/2017 Scientic Paper 13


Future Challenges earthquake, the threat of a large as prepared for the 2015 National Building
earthquake has had a dening inu- Code of Canada. Proceedings of the 11th Cana-
The City of Vancouver has recently dian Conference on Earthquake Engineering,
ence on the evolution of high-rise
Victoria, BC, July 2015; 11 pp.
declared that all Higher Buildings buildings in the city. Today, seismolo-
must establish a signicant and recog- gists predict1 an earthquake as large [2] National Research Council of Canada.
nizable new benchmark for architec- as magnitude 9.0 could occur within Associate Com. on the National Building Code
tural creativity and excellence, while National Building Code of Canada: Ottawa,
about 100 km of Vancouver (only 2015; 1354 pp.
making a signicant contribution to the three earthquakes larger than 9.0
beauty and visual power of the citys have ever been recorded in the [3] City of Vancouver. General Policy for
skyline. The City also requires: leader- Higher Buildings, Land Use and Development
world). In the 1960s, MRSFs were the
Policies and Guidelines. Amended 25 June
ship in sustainable design, reduced preferred structural system for build- 2014.
energy consumption, carbon neutrality, ings in earthquake-prone areas of
community benets, public amenities [4] Canadian Standards Association. Design of
North America such as California.
Concrete Structures. Standard CSA-A23.314.
and minimum adverse shadowing and Canadian building codes were suf- Canadian Standards Association: Mississauga,
view impacts on the public realm.3 ciently different that shear walls were 2014; 290 pp.
The seismic resilience of buildings has used almost exclusively in Vancouver.
[5] LATBSDC. An Alternative Procedure for
not been identied as an explicit Until about the mid-1980s, these Seismic Analysis and Design of Tall Buildings
requirement by the City because of a buildings usually had thin shear walls Located in the Los Angeles Region Los Angeles
mistaken belief that the Canadian (150 or 200 mm thick) distributed Tall Building Structural Design Council: Los
building code ensures that buildings will throughout the buildings and perhaps Angeles, 2014; 53 pp.
perform adequately during an earth- one or more small cores. Owing to the [6] Yathon J, Elwood K, Adebar P. Seismic
quake. Like most building codes, the signicant axial compression applied response of pre-1980s high-rise concrete build-
current Canadian building code speci- to the walls by gravity loads, the shear ings in Vancouver. Proceedings of the 10th Nat-
es life-safety performance require- walls typically needed very little verti- ional Conference in Earthquake Engineering,
cal reinforcement to resist the over- EERI, Anchorage, 2014; 10 pp.
ments for design-level ground shaking
(2% probability of exceedance in turning moment due to lateral loads. [7] Adebar P. Compression failure of thin con-
50 years). If design-level ground shak- It is now known that such thin lightly crete walls during 2010 Chile earthquake: les-
reinforced concrete walls can be brit- sons for Canadian design practice. Can. J. Civil
ing occurs, the occupants of a building Eng. 2013; 40(8): 711721.
that meets the minimum requirements tle, particularly when there is a dis-
of the building code should be able to continuity in the geometry of the [8] Adebar P, Mahmoodi M. Compression fail-
walls. ure of thin concrete shear walls with overhan-
safely exit the building; but not neces- ging walls above. Proceedings of the 10th
sarily ever be able to re-enter the build- A number of factors in the 1980s National Conference in Earthquake Engineering,
ing. As a large proportion of high-rise together caused a paradigm shift in the EERI, Anchorage, 2014, 11 pp.
buildings in Vancouver are residential design of high-rise buildings in Vancou- [9] Paulay T, & Uzumeri SM. A critical review
buildings, a design-level earthquake ver. The seismic demands on all build- of the seismic design provisions for ductile shear
could result in many people being dis- ings increased, while at the same time, walls of the Canadian code and commentary.
placed from their homes. the relative demands on non-ductile Can. J. Civil Eng. 1975; 2: 592601.

The building code does not provide shear walls increased signicantly [10] Adebar P, Mutrie J, & DeVall R. Ductility
any requirements, or even any guid- more. There was also an increase in the of concrete walls: the Canadian seismic design
ance on how, to design a building so level of accidental torsion that buildings provision 1984 to 2004. Can. J. Civil Eng. 2005;
had to resist. At the same time, three- 32(6): 11241137.
that it is more likely to be useable after
an earthquake. Whether or not a build- dimensional structural analysis pro- [11] Adebar P, DeVall R, Mutrie JG. Design of
ing will be useable after an earthquake grams became readily available so that gravity-load resisting frames for seismic dis-
designers became fully aware of the placement demands, Proceedings of the 10th
will depend on factors such as the soil National Conference in Earthquake Engineering,
conditions beneath the building and torsional movements of the buildings.
EERI, Anchorage, July 2014; 11 pp.
the architecture of the building. Recent Finally, new ductility requirements
designs that have been motivated by required that shear walls were able to [12] Adebar P. Nonlinear rotation of capacity-
resist the applied axial compressions protected foundations: the 2015 Canadian build-
the Citys mandate for a new bench- ing code. Earthq. Spectra 2015; 31(4):
mark of architectural creativity are over a very short length of the walls.
18851907.
resulting in buildings that are more As a result of all these factors, large
central core-wall systems became the [13] Adebar P, DeVall R, Bazargani P,
likely to be damaged, and therefore Anderson D. Design of foundations: the 2015
more likely to be unusable, after an prevalent SFRS in high-rise buildings
Canadian Building Code. Proceedings of the
earthquake because of the irregularity in Vancouver and this continues to this
10th National Conference in Earthquake
of the structural systems that results day. The system has recently become Engineering, EERI, Anchorage, July 2014;
from the architectural creativity. popular in California as well. 11 pp.
[14] Natural Resources Canada. http://www.
Conclusions earthquakescanada.nrcan.gc.ca (accessed 15
References March 2016).
While the City of Vancouver has not [1] Adams J, Halchuk S, Allen, T, Rogers G. [15] http://skyscraperpage.com/ (accessed 20
yet experienced a damaging Canadas 5th Generation seismic hazard model, March 2016).

14 Scientic Paper Structural Engineering International Nr. 1/2017

Você também pode gostar