Você está na página 1de 4

ASIC/2-7040

ASI Controls Configurable System Controller

The ASIC/2-7040 is a configurable unitary controller designed for energy


ASIC/2-7040 Features management and control systems for a wide range of building systems
including air handlers, chillers, cooling towers, pumps, lighting, etc.
16 Universal Inputs Applications range from autonomous control of retail stores, branch banks,
and telephone company buildings to networked control of very large
12 Binary relay outputs buildings.
8 analog outputs. The controller is easily configured using Windows based ASI Visual Expert
configuration software that links ready-made objects for scheduling, PID
10 Year hardware clock control, alarming, optimum start, trending, run-time accumulation, event
logging and electrical demand management. The ASIC/2-7040 has an on-
System bus for board battery-backed calendar clock and allows special events, holidays, and
communication access schedules to be defined in advance. Configuration data is stored in non-
volatile memory that is retained through power loss. Comprehensive product
Local bus for supervision documentation is available on-line while using ASI Expert software.
of terminal controllers In stand-alone applications a modem may be connected to allow dial-in from a
remote location to review conditions and/or to modify schedules or setpoints.
Direct RS-232 communication Under selected alarm conditions the controller can dial-out and send notify
user access messages to a pager, printer, or computer running ASI Monitor software.
Similarly, an ASI EtherLink can be attached to receive and send information
Compatible with ASI WebLink via Ethernet TCP/IP network.
& ASI Data Server products
The controller has separate RS-485 system and local buses. The system bus is
used to network multiple ASIC/2 controllers. The controllers may be polled or
be configured for peer-to-peer communication using token passing. On a
separate local bus the ASIC/2-7040 can poll ASIC/1 terminal controllers and
make control decisions based on the data received. No central system is
needed to supervise the controller. Red and green LEDs indicate the
controller receive and transmit communications.
The ASIC/2-7040 can operate as part of a larger communicating control
network with other ASI controllers.
Communication at speeds up to 19,200
baud means rapid access to information.
This enables integrated control of the
complete mechanical system to ensure
optimum building performance.
Temperatures, setpoints, and other
controller information may be easily
reported to ASI WebLink, or any
Windows based software that is a client for
OLE for Process Control (OPC) or
Dynamic Data Exchange (DDE).
The twelve 24 Vac relay outputs are ideal
for driving contactors and starters. Four
yellow LEDs may be configured to
indicate specific alarm or other conditions.
The eight analog outputs are used for
modulated actuators, electronic-pneumatic
transducers, variable speed drives and
other analog signal devices. The 16
universal inputs may be used for counting
pulses, for reading thermistors and contact
closures directly, and for reading 4 to 20
mA, 0 to 5 Vdc or 1 to 5 Vdc input signals.

DOC-1381 (03/17/2003) 2202 Camino Ramon, San Ramon, CA 94583 925 866-8808
http://www.asicontrols.com
ASIC/2-7040
ASI Controls Configurable System Controller

Features Specifications Continued


Analog Input Monitoring Binary Input Monitoring Connections
Maintained Outputs Pulsed Outputs Power: Molex 3 pin plug connector
Tristate Outputs Analog Outputs Input: 2 Molex 15 pin plug connector
Binary Output: 2 Molex 12 pin plug connector
Scheduled Start/Stop Afterhour Override Analog Output: Molex 15 pin receptacle connector
Calendar Events Special Day Schedules Communications: 2, 3 Position, screw terminals
Multiple Control States Multiple PID Loop Mini-Molex 8 pin connector for DAK-002-E
Counters and Timers Optional Demand Limit 9 position DE-9 female for RS-232
Conditional Logic Display and Keypad Other
Alarm Configuraiton Value Trending Microprocessor: Intel 80C196 microcontroller
Memory: Firmware, 512 kbits EPROM
Polling Communications Optional Token Passing Volatile, 32kbytes RAM
Local Bus Polling Local Bus Broadcast Non-volatile, 32 kbytes EEPROM
Hardware Clock Brownout Protection Indication: 1 Red LED, Power
2 Red LED Receive, 2 Green LED Transmit
Specifications 4 Amber LED programmable.
12 Red LED, Binary Outputs
Control Power Overall Dimensions with base:
Supply Voltage: 24 Vac +/- 15%, 50/60 Hz 7.7" x 10.2" x 2.5" (WxLxH)
Power Consumption: 24 VA (plus loads) 196 mm x 259 mm x 64 mm
Protection: 1 A Fuse with mounting holes on center
Binary Outputs 12 7.2" x 7.2" (183 mm x 183 mm )
Type: Form "A" Relay SPST N.O. Weight: 4.4 lb (2.0 kg )
Dry Contacts Environmental
Voltage Rating: 24 Vac or 24 Vdc, 2 A
Operating: 0 to 40 oC (32 to 104 oF)
Analog Outputs 8 10 to 95% rh non-condensing
Type: Analog 0-10Vdc
Resolution: 0.4% full scale Storage: -37 to 80 oC (-35 to +180 oF)
Current Rating: 5.0 mA at 10Vdc 5 to 95% rh non-condensing
Optional Transient Voltage Suppressor Kit UL Listing
Inputs 16 UL 916, Open Energy Management
Type: Universal Analog/Binary E123287 11PK
Range: 0 to 5 Vdc ASIC/2-7040
Accuracy: 0.1% full scale
Communications Rated as a Class 2 Device, Pilot Duty
Format: RS-485 1/2 duplex Includes MCK-003 Molex connector kit with wiring instructions
RS-232 DB-9 Connector Use provided connectors. Meets CE requirements.
Baud Rate: 1200, 2400, 4800, 9600, 19200
Protection: 1/8 A pico fuse, How to Order: Order Number
Transient Protection: 500 mW-s Transorb
Maximum Length: 4000 ft (1.2 km) RS-485 Configurable Controller with enclosure ASIC/2-7040
Repeater: ASI Converter/Repeater
every 32 devices Accessories: Order Number
System Bus Communication Three Input Multiplex Kit MUX-124
Address Range: 32,001 to 32,255
Maximum Size: Up to 255 devices with repeaters Transient Voltage Suppressor Kit, 10 Vdc TVS-10
Baud Rate: Up to 19,200 baud
Local Bus Communication Software & Documentation: Order Number
Address Range: 1 to 32,000 ASI Expert Configuration Software ASI Expert
Maximum Size: Up to 64 devices with repeaters
Maximum Baud Rate: Up to 9600 baud ASIC/2-7040 Object Definitions 7040 OBJ DEF
ASIC/2-7040 Users Manual 7040 Manual

925 866-8808 2202 Camino Ramon, San Ramon, CA 94583 DOC-1381 (03/17/2003)
http://www.asicontrols.com
ASIC/2-7040
Configurable System Controller
ASI Controls
Power J4-9 J5-1
Binary Out-2 BO-01 Binary Out-1 BO-03
1
24 Vac Hot J6-1 J4-12 J5-4
Ground J6-2 J4-3 J5-7
2
3 2 1 BO-02 3 2 1 BO-04
24 Vac Common J6-3 J4-6 J5-10
6 5 4 J4-8 6 5 4 J5-2
3
BO-09 BO-05
9 8 7 J4-11 9 8 7 J5-5
IN-1 J2-1 J4-2 J5-8
Common 12 11 10 BO-10 12 11 10
BO-06
J6 J2-4 J4-5 J5-11
IN-2 J2-7 J4-7 J5-3
Common J2-10
BO-11 J4-10
BO-07 J5-6
J4 J5
IN-3 J2-9 J4-1 J5-9
Input-1 Common
BO-12 BO-08
J2-12 J4-4 J5-12

3 2 1 IN-4 J2-2
Common J2-5
Indicator Lights System Bus Communication
6 5 4 IN-5 J2-8 Amber 3 Common TB2-3
Common A BO-13 LED 1
9 8 7 J2-11 2 System Bus - TB2-2
IN-6 J2-3 Amber System Bus + TB2-1
12 11 10 Common A BO-14 LED 2 1
J2-6
TB2
IN-7 J2-13 Amber DAK Communication
15 14 13
Common A BO-15 LED 3
J2-14
Local Bus+(DAK) J8-1
IN-8 J2-15 Amber
Common A BO-16 LED 4 Local Bus-(DAK) J8-2
J2 J2-14
8 7 6 5 RS-485 Monitor (+) J8-3
RS-485 Monitor(-) J8-4
IN-9 J1-1 AO-1 J3-1
Common Analog Outputs J8-5
J1-4 AO Common J3-4
4 3 2 1 J8-6
IN-10 J1-7 AO-2 J3-7 J8
3 2 1 + 12 Vdc (DAK) J8-7
Common J1-10 AO Common J3-10
Common (DAK) J8-8
Input-2 IN-11 J1-9 6 5 4 AO-3 J3-9
Common J1-12 AO Common J3-12
9 8 7 Local Bus Communication
3 2 1 IN-12 J1-2 AO-4 J3-2 3
Common J1-5 12 11 10 AO Common J3-5 Common TB1-3
6 5 4 2
IN-13 J1-8 AO-5 J3-8 Local Bus - TB1-2
15 14 13
9 8 7 Common J1-11 AO Common J3-11 1 Local Bus + TB1-1

IN-14 J1-3 AO-6 J3-3 TB1


12 11 10
Common J1-6 J3 AO Common J3-6
15 14 13 J7 - RS-232 Local/System Monitor DE9
IN-15 J1-13 AO-7 J3-13
Common J1-14 AO Common J3-14 Tx Transmit J7-2

IN-16 J1-15 AO-8 J3-15 Rx Receive J7-3


J1 Common Common J7-5
J1-14 AO Common J3-12

F1 1 A
24 Vac Power
24 Vac Power R DS21 Power
24 Vac Power J6-1
Common J6-2 Ground
24 Vac Common
24 Vac Common J6-3
Building Ground
R DS1- DS12 Binary Outputs

R DS20 System Rx R DS18 Local Rx

G DS19 Sytem Tx G DS17 Local Tx


RS-485 System Bus RS-485 Local Bus

(+) TB2-1 Active TB1-1 (+)


F4 1/8 A F2 1/8 A
(-) TB2-2 Circuit TB1-2 (-)
TB2-3 TB1-3
F5 1/8 A F3 1/8 A

123
J8 DAK Access Local Bus W3,4=1-2
W3
Local Bus+(DAK) J8-1 System Bus W3,4=2-3
RS-485
Local Bus-(DAK) J8-2 J7 RS-232 Monitor
RS-485 Monitor(+)J8-3 RS-232 J7-2 Rx
Convert
RS-485 Monitor(-)J8-4 J7-3 Tx
System Bus (+) J8-5 J7-5 Common
123 W4
System Bus (-) J8-6
+ 12 Vdc(DAK) J8-7
Common(DAK) J8-8

DOC-1381 (03/17/2003) 2202 Camino Ramon, San Ramon, CA 94583 925 866-8808
http://www.asicontrols.com
ASIC/2-7040
ASI Controls Configurable System Controller

To other ASIC controllers

To 4th floor ASIC/1s

System Bus
ASIC/2-7040
Make-up To 3rd floor ASIC/1s
Air ASIC/1-8X55 Local Bus

Local Bus
Control Local Polling
& Broadcast

To 2nd floor ASIC/1s


System Bus
ASIC/2-7040

Cooling
To 1st floor ASIC/1s
Tower ASIC/1-8X55 Local Bus
Local Bus

Control Local Polling


& Broadcast
System Bus Up to 19,200 baud
System Bus
ASIC/2-7040

Modem (Dial-in/out)
Chiller
Modem or
Control
Local Bus

EtherLink (TCP/IP)
232 TCP/IP
Power
Link

EtherLink
SINC/3-3000

Local
RS-485

System
Modem
Modem
RS-232

Direct
Access

ASI Software
SINC/3 Multi-port System Interface

Typical ASIC/2-7040 System Layout

Modem (Dial-in/out)
Modem or
System Bus

EtherLink (TCP/IP)
ASIC/2-7040

AHU
Control
232 TCP/IP
Local Bus

Power
Link
EtherLink

Single ASIC/2-7040 Layout

925 866-8808 2202 Camino Ramon, San Ramon, CA 94583 DOC-1381 (03/17/2003)
http://www.asicontrols.com