R.L (M&E) CHECKLIST Project No. : eS Project Title: es FIRE PROTECTION - DRY RISER SYSTEM BREECHING INLET : Location according to plan/within 18m from fire engine access 2 way inlet provided (100 mm diameter riser pipe) 4 way inlet provided (50 mm diameter riser pipe) About 760 mm above finished floor level Tnlets housed in glass fronted box Rigidly supported Labelled “DRY RISER BREECHING INLET” and differentiated (if ‘more than 1 stack) Clear of obstruction Inlet painted yellow colour RISER Pipe size in order 2a. | Diameter 100 mm (ht of bldg < 45mm) 2,_ | Diameter 150 mm (ht of bldg > 6Om but > 45m) 3. _| Not passing through unprotected area/fre ated 4. _| Airtelease valve provided 5.__| Barthing provided ¥(F- compy, x des nat comply, NA not appicabIy we] so] Inspected By : Signature: Date : estas) »WSP-Ng Project No. Project Title RL (M&E) CHECKLIST FIRE PROTECTION - DRY RISER SYSTEM (Cont'd) LANDING VALVE SS 1 760 mm to 1m above finished floor level Condition of handwheel satisfactory Cap provided Strapped & padlocked in closed position Labelled / Numbered Clear of obstruction Landing valve painted yellow colour 2 3. 4 5. 6 7. D ‘TESTING OF HYDROSTATIC PRESSURE Pressure constant at 300 psi /20.7 bar at more than 30 mins 3200p fr Ahes a Air release valve functioning * (7 eoimy, X= does not comply, NA not appicabley Inspected By : Date Signature uc st99sRMs() BWSP-Ng