CALCULATION TABLE OF CONTENTS
001
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
1.0 INTRODUCTION 1 of 4
1.1 DESIGN DESCRIPTION
Rectangular concrete tank design based on Code Abbreviation
PCA Rectangular Concrete Tanks Revised 5th Edition PCA Rect Tank
A23.3-04 Design of Concrete Structures A23.3-04
ACI 318M-08 Metric Building Code Requirements for Structural Concrete and Commentary ACI 318M-08
Seismic Design
The tank is buried underground and well confined by compacted soil. The seismic is not a concern in this case.
Load Cases
There most unfavourable load cases are checked in the design. The tank top boundary is free in all these 3 cases.
002
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
2 of 4
1.3 INPUT Code Reference
Tank Data
Tank length Lx = 6.250 [m]
Tank width Ly = 3.690 [m]
Tank height h = 3.000 [m]
Tank wall thickness w = 0.300 [m]
Tank base thickness Tb = 0.300 [m]
Tank roof thickness Tr = 0.300 [m]
Tank base extension wt = 0.300 [m]
Ground water table height hw = 1.500 [m]
Tank length wall c/c b = 6.550 [m]
Tank width wall c/c c = 3.990 [m]
Tank content density w = 10.0 [kN/m3]
Soil density s = 21.0 [kN/m3]
Soil allowable bearing capacity qa = 150 [kPa]
Soil subgrade modulus k = 5000 [kN/m3]
Ground surcharge qs = 10.0 [kPa]
Soil pressure coefficient ko = 0.45
003
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
3 of 4
Roof Slab Force by PCA Tables
Moment coefficient Mx, My, Mxy Case 10 in Page 2-60 ~ 2-64 b/a = 1.6
Moment coeff. max(MX+|MXY|, MY+|MXY|) = 85.0
4 of 4
Long Side Wall Lx Reinft Data Code Reference
Ver. bar size 15 Area of one bar = 200 [mm2]
Ver. bar spacing 200 [mm] Asprov = 1000 [mm2/m]
005
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
1 of 1
1.4 CONCLUSION
Base Slab
[The Base Slab Thickness Is Adequate]
[The Base Slab Reinft Is Adequate]
[The Base Slab Crack Control Is Adequate]
1 of 3
2.0 LOAD DEVELOPMENT
LOAD CASE 1 Leakage Test Prior to Backfilling
007
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
2 of 3
LOAD CASE 2 Empty Tank With Backfill Present
008
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
3 of 3
Load For FEA Input
009
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
1 of 8
3.0 LOAD CASE 1 Leakage Test Prior to Backfilling
Tank length Lx = 6.250 [m]
Tank width Ly = 3.690 [m]
Tank height h = 3.000 [m]
Tank content density w = 10.0 [kN/m3]
q = h w = 30.0 [kN/m2]
Wall Force by PCA Tables
Long Side Wall Lx
Shear Coefficient Cs Case 3 in Page 2-17
a = 3.000 [m] b = 6.250 [m]
b/a = 2.1
Bottom edge - midpoint Cs = 0.455 VL1 = Cs x q x a = 40.9 [kN/m]
Side edge - maximum Cs = 0.280 VL2 = Cs x q x a = 25.2 [kN/m]
Side edge - midpoint Cs = 0.258 VL3 = Cs x q x a = 23.2 [kN/m]
Wall hor tensile force TL = VS2 = = 22.4 [kN/m]
010
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
2 of 8
Short Side Wall Ly Code Reference
Bottom edge-midpoint v=max(SQX,SQY) = 63.5 [kPa] VS1 = v x w = 19.1 [kN/m]
Side edge-maximum v=max(SQX,SQY) = 89.6 [kPa] VS2 = v x w = 26.9 [kN/m]
Wall hor tensile force t=max(SX,SY) = 117.6 [kPa] TS = t x w = 35.3 [kN/m]
Wall ver bending moment bottom edge-max MSV=max(MX+|MXY|, MY+|MXY|) = 7.3 [kNm/m]
Wall hor bending moment side edge-max MSH=max(MX+|MXY|, MY+|MXY|) = 16.8 [kNm/m]
Wall Force Used for Design Take max value of above two approaches
Long Side Wall Lx
Bottom edge - midpoint shear VL1 = 40.9 [kN/m]
Side edge - maximum shear VL2 = 25.2 [kN/m]
Wall hor tensile force TL = 31.8 [kN/m]
Wall ver bending moment bottom edge-max MLV = 25.0 [kNm/m]
Wall hor bending moment side edge-max MLH = 16.3 [kNm/m]
011
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
3 of 8
3.1 Long Side Wall Check Code Reference
Shear - Wall Bottom Edge A23.3-04
Bottom edge - midpoint shear Vu = F x VL1 = 61.4 [kN/m]
When no transverse reinft. = 230 / (1000 + dv) = 0.189 11.3.6.3 Eq (11-9)
Required total reinft per meter Asrq'd = Asf + Ast = 501 [mm2]
Provided reinft bar = 15 at spacing = 200 [mm]
Provided reinft per meter length Asprov = 1000 [mm2/m]
> 501 OK
012
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
4 of 8
Crack Control Code Reference
Max unfactored bending moment M = max( MLV , MLH ) = 25.0 [kNm/m] A23.3-04
Concrete modulus of elasticity Ec = = 26622 [MPa] 8.6.2.3 Eq (8-2)
n = Es / Ec = 7.5
As = 1000 [mm2/m] d = 218 [mm]
= 0.46% n = 0.0345
k = 2 n + ( n) 2 n = 0.231
j = 1 - k/3 = 0.923
fs = M / (As x j x d) = 124.4 [MPa]
dc = c + db/2 (c<=50mm) = 57.5 [mm] 10.6.1
No of bar in 1m wide strip nb = 5
A = 2 x dc x 1000 / nb = 23000 [mm2]
Exterior exposure crack control z = = 25000 [N/mm] 10.6.1
z = = 13653 [N/mm] 10.6.1 Eq (10-6)
< 25000 OK
013
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
5 of 8
3.2 Short Side Wall Check Code Reference
Shear - Wall Bottom Edge A23.3-04
Bottom edge - midpoint shear Vu = F x VS1 = 48.2 [kN/m]
When no transverse reinft. = 230 / (1000 + dv) = 0.189 11.3.6.3 Eq (11-9)
Required total reinft per meter Asrq'd = Asf + Ast = 509 [mm2]
Provided reinft bar = 15 at spacing = 200 [mm]
Provided reinft per meter length Asprov = 1000 [mm2/m]
> 509 OK
014
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
6 of 8
Crack Control Code Reference
Max unfactored bending moment M = max( MSV , MSH ) = 16.8 [kN/m] A23.3-04
Concrete modulus of elasticity Ec = = 26622 [MPa] 8.6.2.3 Eq (8-2)
n = Es / Ec = 7.5
As = 1000 [mm2/m] d = 218 [mm]
= 0.46% n = 0.0345
k = 2 n + ( n) 2 n = 0.231
j = 1 - k/3 = 0.923
fs = M / (As x j x d) = 83.7 [MPa]
dc = c + db/2 (c<=50mm) = 57.5 [mm] 10.6.1
No of bar in 1m wide strip nb = 5
A = 2 x dc x 1000 / nb = 23000 [mm2]
Exterior exposure crack control z = = 25000 [N/mm] 10.6.1
z = = 9184 [N/mm] 10.6.1 Eq (10-6)
< 25000 OK
015
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
7 of 8
3.3 Base Slab Check
016
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
8 of 8
Base Slab Crack Control Code Reference
Max unfactored bending moment M = = 22.5 [kN/m] A23.3-04
Concrete modulus of elasticity Ec = = 26622 [MPa] 8.6.2.3 Eq (8-2)
n = Es / Ec = 7.5
As = 1000 [mm2/m] d = 218 [mm]
= 0.46% n = 0.0345
k = 2 n + ( n) 2 n = 0.231
j = 1 - k/3 = 0.923
fs = M / (As x j x d) = 112.1 [MPa]
dc = c + db/2 (c<=50mm) = 57.5 [mm] 10.6.1
No of bar in 1m wide strip nb = 5
A = 2 x dc x 1000 / nb = 23000 [mm2]
Exterior exposure crack control z = = 25000 [N/mm] 10.6.1
z = = 12300 [N/mm] 10.6.1 Eq (10-6)
< 25000 OK
017
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
1 of 6
4.0 LOAD CASE 2 Empty Tank With Backfill Present
Tank length Lx = 6.250 [m]
Tank width Ly = 3.690 [m]
Tank height h = 3.000 [m]
Tank content density w = 10.0 [kN/m3]
Equivalent triangle load q = = 41.5 [kN/m2]
2 of 6
Short Side Wall Ly Code Reference
Bottom edge-midpoint v=max(SQX,SQY) = 63.5 [kPa] VS1 = v x w = 19.1 [kN/m]
Side edge-maximum v=max(SQX,SQY) = 89.6 [kPa] VS2 = v x w = 26.9 [kN/m]
Wall hor tensile force t=max(SX,SY) = 117.6 [kPa] TS = t x w = 35.3 [kN/m]
Wall ver bending moment bottom edge-max MSV=max(MX+|MXY|, MY+|MXY|) = 7.3 [kNm/m]
Wall hor bending moment side edge-max MSH=max(MX+|MXY|, MY+|MXY|) = 16.8 [kNm/m]
Wall Force Used for Design Take max value of above two approaches
Long Side Wall Lx
Bottom edge - midpoint shear VL1 = 56.6 [kN/m]
Side edge - maximum shear VL2 = 34.8 [kN/m]
Wall hor tensile force TL = 31.8 [kN/m]
Wall ver bending moment bottom edge-max MLV = 34.5 [kNm/m]
Wall hor bending moment side edge-max MLH = 20.0 [kNm/m]
019
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
3 of 6
4.1 Long Side Wall Check Code Reference
Shear - Wall Bottom Edge A23.3-04
Bottom edge - midpoint shear Vu = F x VL1 = 84.9 [kN/m]
When no transverse reinft. = 230 / (1000 + dv) = 0.189 11.3.6.3 Eq (11-9)
Required total reinft per meter Asrq'd = Asf + Ast = 501 [mm2]
Provided reinft bar = 15 at spacing = 200 [mm]
Provided reinft per meter length Asprov = 1000 [mm2/m]
> 501 OK
020
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
4 of 6
Crack Control Code Reference
Max unfactored bending moment M = max( MLV , MLH ) = 34.5 [kNm/m] A23.3-04
Concrete modulus of elasticity Ec = = 26622 [MPa] 8.6.2.3 Eq (8-2)
n = Es / Ec = 7.5
As = 1000 [mm2/m] d = 218 [mm]
= 0.46% n = 0.0345
k = 2 n + ( n) 2 n = 0.231
j = 1 - k/3 = 0.923
fs = M / (As x j x d) = 172.0 [MPa]
dc = c + db/2 (c<=50mm) = 57.5 [mm] 10.6.1
No of bar in 1m wide strip nb = 5
A = 2 x dc x 1000 / nb = 23000 [mm2]
Exterior exposure crack control z = = 25000 [N/mm] 10.6.1
z = = 18876 [N/mm] 10.6.1 Eq (10-6)
< 25000 OK
021
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
5 of 6
4.2 Short Side Wall Check Code Reference
Shear - Wall Bottom Edge A23.3-04
Bottom edge - midpoint shear Vu = F x VS1 = 66.6 [kN/m]
When no transverse reinft. = 230 / (1000 + dv) = 0.189 11.3.6.3 Eq (11-9)
Required total reinft per meter Asrq'd = Asf + Ast = 509 [mm2]
Provided reinft bar = 15 at spacing = 200 [mm]
Provided reinft per meter length Asprov = 1000 [mm2/m]
> 509 OK
022
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
6 of 6
Crack Control Code Reference
Max unfactored bending moment M = max( MSV , MSH ) = 20.0 [kN/m] A23.3-04
Concrete modulus of elasticity Ec = = 26622 [MPa] 8.6.2.3 Eq (8-2)
n = Es / Ec = 7.5
As = 1000 [mm2/m] d = 218 [mm]
= 0.46% n = 0.0345
k = 2 n + ( n) 2 n = 0.231
j = 1 - k/3 = 0.923
fs = M / (As x j x d) = 99.5 [MPa]
dc = c + db/2 (c<=50mm) = 57.5 [mm] 10.6.1
No of bar in 1m wide strip nb = 5
A = 2 x dc x 1000 / nb = 23000 [mm2]
Exterior exposure crack control z = = 25000 [N/mm] 10.6.1
z = = 10917 [N/mm] 10.6.1 Eq (10-6)
< 25000 OK
023
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
1 of 3
5.0 LOAD CASE 3 Buoyancy Force
Tank Data
Tank length Lx = 6.250 [m]
Tank width Ly = 3.690 [m]
Tank height h = 3.000 [m]
Tank wall thickness w = 0.300 [m]
Tank base thickness Tb = 0.300 [m]
Tank roof thickness Tr = 0.300 [m]
Tank base extension wt = 0.300 [m]
Ground water table height hw = 1.500 [m]
Tank length wall c/c b = 6.550 [m]
Tank width wall c/c c = 3.990 [m]
Soil density s = 21.000 [kN/m3]
Uplift Resistance
Tank wall weight w1 = (b+c) x 2 x h x w x 23.5 = 445.8 [kN]
Bottom slab weight w2 = (b+w+2wt ) x (c+w+2wt ) x Tb x 23.5 = 256.8 [kN]
Top slab weight w3 = (b+w) x (c+w) x Tr x 23.5 = 207.2 [kN]
Soil above base extension wt. w4 = (b+c+2w+2wt ) x 2 x wt x h x s = 443.8 [kN]
Total weight w = = 1353.6 [kN]
Tank Base Slab Design With Empty Tank and Uplift Buoyancy Force
Tank base thickness Tb = 0.300 [m]
Water net pressure on base pn = p - Tb x 23.5 = 11.0 [kN/m2]
Water net pressure on base pn used for design = 11.0 [kN/m2]
024
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
2 of 3
Conc & Rebar Data Code Reference
Concrete strength f'c = 35 [MPa] A23.3-04
Rebar yield strength fy = 400 [MPa]
sqrt(f'c ) = min ( sqrt(fc') , 8 ) = 5.9 [MPa] 11.3.4
Concrete cover c = 75 [mm]
Exterior exposure crack control z = 25000 [N/mm]
025
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
3 of 3
Crack Control Code Reference
Max unfactored bending moment M = = 12.0 [kNm/m] A23.3-04
Concrete modulus of elasticity Ec = = 26622 [MPa] 8.6.2.3 Eq (8-2)
n = Es / Ec = 7.5
As = 1000 [mm2/m] d = 218 [mm]
= 0.46% n = 0.0345
k = 2 n + ( n) 2 n = 0.231
j = 1 - k/3 = 0.923
fs = M / (As x j x d) = 59.8 [MPa]
dc = c + db/2 (c<=50mm) = 57.5 [mm] 10.6.1
No of bar in 1m wide strip nb = 5
A = 2 x dc x 1000 / nb = 23000 [mm2]
Exterior exposure crack control z = = 25000 [N/mm] 10.6.1
z = = 6560 [N/mm] 10.6.1 Eq (10-6)
< 25000 OK
026
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
1 of 2
6.0 ROOF SLAB DESIGN Code Reference
Tank Data
Tank length Lx = 6.250 [m]
Tank width Ly = 3.690 [m]
Tank wall thickness w = 0.300 [m]
Tank roof thickness Tr = 0.300 [m]
Tank length wall c/c b = 6.550 [m]
Tank width wall c/c c = 3.990 [m]
Ground surcharge qs = 10.0 [kPa]
Shear Check
Max factored shear Vu = = 41.5 [kN/m]
When no transverse reinft. = 230 / (1000 + dv) = 0.189 11.3.6.3 Eq (11-9)
Vc = c fc' b w dv = 158 [kN] 11.3.4 Eq (11-6)
> Vu OK
027
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
2 of 2
Flexure Check Code Reference
Max factored flexure Mu = = 32.2 [kNm/m]
b = 1000 [mm] d = 218 [mm]
Kr = Mu / (b x d2) = 0.681 A23.3-04
= = 0.21%
= max( , 0.2%) = 0.21% 7.8.1
Required flexure reinft per meter As = x 1000 x d = 446 [mm2/m]
Provided reinft bar = 15 at spacing = 200 [mm]
Provided reinft per meter length Asprov = 1000 [mm2/m]
> 446 OK
Crack Control
Max unfactored bending moment M = m q a2 / 1000 = 23.1 [kNm/m] A23.3-04
Concrete modulus of elasticity Ec = = 26622 [MPa] 8.6.2.3 Eq (8-2)
n = Es / Ec = 7.5
As = 1000 [mm2/m] d = 218 [mm]
= 0.46% n = 0.0345
k = 2 n + ( n) 2 n = 0.231
j = 1 - k/3 = 0.923
fs = M / (As x j x d) = 114.9 [MPa]
dc = c + db/2 (c<=50mm) = 57.5 [mm] 10.6.1
No of bar in 1m wide strip nb = 5
A = 2 x dc x 1000 / nb = 23000 [mm2]
Exterior exposure crack control z = = 25000 [N/mm] 10.6.1
z = = 12613 [N/mm] 10.6.1 Eq (10-6)
< 25000 OK
Deflection Check
t = 0.300 [m] = 0.17
D = = 61683 [kNm]
028
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0
1 of 1
7.0 BEARING CAPACITY CHECK
Tank Data
Tank length Lx = 6.250 [m]
Tank width Ly = 3.690 [m]
Tank height h = 3.000 [m]
Tank wall thickness w = 0.300 [m]
Tank base thickness Tb = 0.300 [m]
Tank roof thickness Tr = 0.300 [m]
Tank base extension wt = 0.300 [m]
Ground water table height hw = 1.500 [m]
Tank length wall c/c b = 6.550 [m]
Tank width wall c/c c = 3.990 [m]
Soil density s = 21.0 [kN/m3]
Ground surcharge qs = 10.0 [kPa]
Soil allowable bearing capacity qa = 150 [kPa]