Project : Alberta Oilsand Eng : Test

www.civilbay.com Jon No : 1234567 Chk : Test


Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

1 of 1
CALCULATION TABLE OF CONTENTS

1.0 INTRODUCTION 002


1.1 DESIGN DESCRIPTION 002
1.2 DESIGN BASIS & ASSUMPTIONS 002
1.3 INPUT 003
1.4 CONCLUSION 006

2.0 LOAD DEVELOPMENT 007

3.0 LOAD CASE 1 010


3.1 LONG SIDE WALL CHECK 012
3.2 SHORT SIDE WALL CHECK 014
3.3 BASE SLAB CHECK 016

4.0 LOAD CASE 2 018


4.1 LONG SIDE WALL CHECK 020
4.2 SHORT SIDE WALL CHECK 022

5.0 LOAD CASE 3 024

6.0 ROOF SLAB DESIGN 027

7.0 BEARING CAPACITY CHECK 029

8.0 APPENDIX SOIL REPORT & PCA TABLES 030

001
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

1.0 INTRODUCTION 1 of 4
1.1 DESIGN DESCRIPTION
Rectangular concrete tank design based on Code Abbreviation
PCA Rectangular Concrete Tanks Revised 5th Edition PCA Rect Tank
A23.3-04 Design of Concrete Structures A23.3-04
ACI 318M-08 Metric Building Code Requirements for Structural Concrete and Commentary ACI 318M-08

1.2 DESIGN BASIS & ASSUMPTIONS


Ground Water Table
Refer to CivilBay soil report page 19, the ground water level varies from 592.2m to 590.9m. It's almost the same level as tank
base elevation 592.55 (EL98.65, EL100=594.2). For design, assume water table 1.5m above tank base to be conservative.

Frost Jacking Uplift


The tank base is 595.7-592.55=3.15m below grade, thus the up heave to tank base needs not to be considered
The tank perimeter wall will be bitumen coated and applied with 100mm STYROFOAM insulation. This will reduce the
adfreeze froce to minimum and jacking due to adfreeze is not a concern in the design.

Soil Bearing Capacity


Refer to CivilBay soil report page 53, soil bearing capacity 150kPa is used in the design

Subgrade Spring Value


No subgrade modulus value is available in CivilBay soil report. From CivilBay soil report page 55, predicted settlement
for 5mx5m footing with 150kPa pressure is 25~40mm. From this we can work out subgrade 150kPa/0.03m = 5000 kN/m3

Soil Pressure Coefficient


Refer to CivilBay soil report page 57, at rest coefficient K0=0.45 is used in the design

Seismic Design
The tank is buried underground and well confined by compacted soil. The seismic is not a concern in this case.

Load Cases
There most unfavourable load cases are checked in the design. The tank top boundary is free in all these 3 cases.

002
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

2 of 4
1.3 INPUT Code Reference

Tank Data
Tank length Lx = 6.250 [m]
Tank width Ly = 3.690 [m]
Tank height h = 3.000 [m]
Tank wall thickness w = 0.300 [m]
Tank base thickness Tb = 0.300 [m]
Tank roof thickness Tr = 0.300 [m]
Tank base extension wt = 0.300 [m]
Ground water table height hw = 1.500 [m]
Tank length wall c/c b = 6.550 [m]
Tank width wall c/c c = 3.990 [m]
Tank content density w = 10.0 [kN/m3]
Soil density s = 21.0 [kN/m3]
Soil allowable bearing capacity qa = 150 [kPa]
Soil subgrade modulus k = 5000 [kN/m3]
Ground surcharge qs = 10.0 [kPa]
Soil pressure coefficient ko = 0.45

Wall Force by PCA Tables


Moment coefficient Mx, My, Mxy Case 3 in Page 3-31, 3-32
b/a = Lx / h = 2.1 c/a = Ly / h = 1.2
Long Side Wall Lx = 6.25m
Wall ver bending moment Mx + | Mxy | = 92.5 at bottom edge-midpoint
Wall hor bending moment My + | Mxy | = 53.5 at side edge-max
Short Side Wall Ly = 3.69m
Wall ver bending moment Mz + | Myz | = 39.5 at bottom edge-midpoint
Wall hor bending moment My + | Myz | = 53.5 at side edge-max

003
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

3 of 4
Roof Slab Force by PCA Tables
Moment coefficient Mx, My, Mxy Case 10 in Page 2-60 ~ 2-64 b/a = 1.6
Moment coeff. max(MX+|MXY|, MY+|MXY|) = 85.0

Wall Force by FEA


Load Case 1 Leakage Test Prior to Backfilling
Long Side Wall Lx
Bottom edge-midpoint v=max(SQX,SQY) = 113.7 [kPa]
Side edge-maximum v=max(SQX,SQY) = 82.9 [kPa]
Wall hor tensile force t=max(SX,SY) = 106.0 [kPa]
Wall ver bending moment bottom edge-max MLV=max(MX+|MXY|, MY+|MXY|) = 12.2 [kNm/m]
Wall hor bending moment side edge-max MLH=max(MX+|MXY|, MY+|MXY|) = 16.3 [kNm/m]

Short Side Wall Ly


Bottom edge-midpoint v=max(SQX,SQY) = 63.5 [kPa]
Side edge-maximum v=max(SQX,SQY) = 89.6 [kPa]
Wall hor tensile force t=max(SX,SY) = 117.6 [kPa]
Wall ver bending moment bottom edge-max MSV=max(MX+|MXY|, MY+|MXY|) = 7.3 [kNm/m]
Wall hor bending moment side edge-max MSH=max(MX+|MXY|, MY+|MXY|) = 16.8 [kNm/m]

Base Slab With Full Tank of Liquid


Base slab max shear v=max(SQX,SQY) = 73.1 [kPa]
Base slab max flexure Mb=max(MX+|MXY|, MY+|MXY|) = 22.5 [kNm/m]

Load Case 2 Empty Tank With Backfill Present


Long Side Wall Lx
Bottom edge-midpoint v=max(SQX,SQY) = 167.5 [kPa]
Side edge-maximum v=max(SQX,SQY) = 122.2 [kPa]
Wall hor tensile force t=max(SX,SY) = 110.6 [kPa]
Wall ver bending moment bottom edge-max MLV=max(MX+|MXY|, MY+|MXY|) = 25.7 [kNm/m]
Wall hor bending moment side edge-max MLH=max(MX+|MXY|, MY+|MXY|) = 21.8 [kNm/m]

Short Side Wall Ly


Bottom edge-midpoint v=max(SQX,SQY) = 106.1 [kPa]
Side edge-maximum v=max(SQX,SQY) = 96.4 [kPa]
Wall hor tensile force t=max(SX,SY) = 146.6 [kPa]
Wall ver bending moment bottom edge-max MSV=max(MX+|MXY|, MY+|MXY|) = 6.5 [kNm/m]
Wall hor bending moment side edge-max MSH=max(MX+|MXY|, MY+|MXY|) = 21.4 [kNm/m]

Load Case 3 Empty Tank With Buoyancy Force


Base slab max shear v=max(SQX,SQY) = 42.3 [kPa]
Base slab max flexure Mb=max(MX+|MXY|, MY+|MXY|) = 12.0 [kNm/m]
004
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

4 of 4
Long Side Wall Lx Reinft Data Code Reference
Ver. bar size 15 Area of one bar = 200 [mm2]
Ver. bar spacing 200 [mm] Asprov = 1000 [mm2/m]

Hor. bar size 15 Area of one bar = 200 [mm2]


Hor. bar spacing 200 [mm] Asprov = 1000 [mm2/m]

Short Side Wall Ly Reinft Data


Ver. bar size 15 Area of one bar = 200 [mm2]
Ver. bar spacing 200 [mm] Asprov = 1000 [mm2/m]

Hor. bar size 15 Area of one bar = 200 [mm2]


Hor. bar spacing 200 [mm] Asprov = 1000 [mm2/m]

Base Slab Reinft Data


Top & Bott bar size 15 Area of one bar = 200 [mm2]
Top & Bott bar spacing 200 [mm] Asprov = 1000 [mm2/m]

Roof Slab Reinft Data


Top & Bott bar size 15 Area of one bar = 200 [mm2]
Top & Bott bar spacing 200 [mm] Asprov = 1000 [mm2/m]

Conc & Rebar Data A23.3-04


Concrete strength f'c = 35 [MPa]
Rebar yield strength fy = 400 [MPa]
Concrete cover c = 75 [mm]
Exterior exposure crack control z = 25000 [N/mm] 10.6.1

Concrete resistance factor c = 0.65 8.4.2


Rebar resistance factor s = 0.85 8.4.3
Low density conc factor = 1.0

005
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

1 of 1
1.4 CONCLUSION

LOAD CASE 1 Leakage Test Prior to Backfilling


Long Side Wall Check
[The Wall Thickness Is Adequate]
[The Wall Reinft Is Adequate]
[The Wall Crack Control Is Adequate]

Short Side Wall Check


[The Wall Thickness Is Adequate]
[The Wall Reinft Is Adequate]
[The Wall Crack Control Is Adequate]

Base Slab
[The Base Slab Thickness Is Adequate]
[The Base Slab Reinft Is Adequate]
[The Base Slab Crack Control Is Adequate]

LOAD CASE 2 Empty Tank With Backfill Present


Long Side Wall Check
[The Wall Thickness Is Adequate]
[The Wall Reinft Is Adequate]
[The Wall Crack Control Is Adequate]

Short Side Wall Check


[The Wall Thickness Is Adequate]
[The Wall Reinft Is Adequate]
[The Wall Crack Control Is Adequate]

LOAD CASE 3 Buoyancy Force


[The Uplift Resistance Is Adequate]
[The Base Slab Thickness Is Adequate]
[The Base Slab Reinft Is Adequate]
[The Base Slab Crack Control Is Adequate]

ROOF SLAB DESIGN


[The Roof Slab Thickness Is Adequate]
[The Roof Slab Reinft Is Adequate]
[The Roof Slab Crack Control Is Adequate]
[The Roof Slab Deflection Is Adequate]

BEARING CAPACITY CHECK


[The Soil Bearing Capacity Is Adequate]
006
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

1 of 3
2.0 LOAD DEVELOPMENT
LOAD CASE 1 Leakage Test Prior to Backfilling

Load For FEA Input

Tank height h = 3.000 [m]


Tank content density w = 10.0 [kN/m3]
p1 = 3.0 [kPa] q1 = 1.5 [kPa]
p2 = 6.0 [kPa] q2 = 4.5 [kPa]
p3 = 9.0 [kPa] q3 = 7.5 [kPa]
p4 = 12.0 [kPa] q4 = 10.5 [kPa]
p5 = 15.0 [kPa] q5 = 13.5 [kPa]
p6 = 18.0 [kPa] q6 = 16.5 [kPa]
p7 = 21.0 [kPa] q7 = 19.5 [kPa]
p8 = 24.0 [kPa] q8 = 22.5 [kPa]
p9 = 27.0 [kPa] q9 = 25.5 [kPa]
p10 = 30.0 [kPa] q10 = 28.5 [kPa]

007
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

2 of 3
LOAD CASE 2 Empty Tank With Backfill Present

Equivalent Triangle Load For PCA Table Lookup


Tank height h = 3.000 [m]
Ground water table height hw = 1.500 [m]
Soil density s = 21.0 [kN/m3]
Ground surcharge qs = 10.0 [kPa]
Soil pressure coefficient ko = 0.45

Pressure by ground surcharge w1 = ko x qs = 4.5 [kPa]


Pressure by soil above water w2 = ko x (h-hw) x s = 14.2 [kPa]
Pressure by soil below water w3 = ko x hw x (s - w) = 7.4 [kPa]
Pressure by ground water w4 = hw x w = 15.0 [kPa]

Force by ground surcharge ps1 = w1 x h = 13.5 [kN/m]


Force by soil above water ps21 = w2 x (h-hw) / 2 = 10.6 [kN/m]
ps22 = w2 x hw = 21.3 [kN/m]
Force by soil below water ps3 = w3 x hw / 2 = 5.6 [kN/m]
Force by ground water ps4 = w4 x hw / 2 = 11.3 [kN/m]
Total lateral force ps = 62.2 [kN/m]
Equivalent triangle load q = 2 x ps / h = 41.5 [kPa]

008
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

3 of 3
Load For FEA Input

Tank height h = 3.000 [m]


Ground water table height hw = 1.500 [m]
Soil density s = 21.0 [kN/m3]
Ground surcharge qs = 10.0 [kPa]
Soil pressure coefficient ko = 0.450
h - hw = 1.500 [m]
s - w = 11.0 [kN/m3]
Pressure by ground surcharge w1 = ko x qs = 4.5 [kPa]
Pressure by soil above water w2 = ko x (h-hw) x s = 14.2 [kPa]
dist. to grade
p0 = 4.5 [kPa] 0.000
p1 = 7.3 [kPa] q1 = 5.9 [kPa] 0.300
p2 = 10.2 [kPa] q2 = 8.8 [kPa] 0.600
p3 = 13.0 [kPa] q3 = 11.6 [kPa] 0.900
p4 = 15.8 [kPa] q4 = 14.4 [kPa] 1.200
p5 = 18.7 [kPa] q5 = 17.3 [kPa] 1.500
p6 = 23.2 [kPa] q6 = 20.9 [kPa] 1.800
p7 = 27.6 [kPa] q7 = 25.4 [kPa] 2.100
p8 = 32.1 [kPa] q8 = 29.9 [kPa] 2.400
p9 = 36.6 [kPa] q9 = 34.4 [kPa] 2.700
p10 = 41.1 [kPa] q10 = 38.9 [kPa] 3.000

009
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

1 of 8
3.0 LOAD CASE 1 Leakage Test Prior to Backfilling
Tank length Lx = 6.250 [m]
Tank width Ly = 3.690 [m]
Tank height h = 3.000 [m]
Tank content density w = 10.0 [kN/m3]
q = h w = 30.0 [kN/m2]
Wall Force by PCA Tables
Long Side Wall Lx
Shear Coefficient Cs Case 3 in Page 2-17
a = 3.000 [m] b = 6.250 [m]
b/a = 2.1
Bottom edge - midpoint Cs = 0.455 VL1 = Cs x q x a = 40.9 [kN/m]
Side edge - maximum Cs = 0.280 VL2 = Cs x q x a = 25.2 [kN/m]
Side edge - midpoint Cs = 0.258 VL3 = Cs x q x a = 23.2 [kN/m]
Wall hor tensile force TL = VS2 = = 22.4 [kN/m]

Moment Coefficient Mx, My, Mxy Case 3 in Page 3-31, 3-32


b/a = Lx / h = 2.1 c/a = Ly / h = 1.2
Wall ver bending moment Mx + | Mxy | = 92.5 MLV = (Mx+|Mxy|)qa2/103 = 25.0 [kNm/m]
Wall hor bending moment My + | Mxy | = 53.5 MLH = (My+|Mxy|)qa2/103 = 14.4 [kNm/m]

Short Side Wall Ly


a = 3.000 [m] b = 3.690 [m]
b/a = 1.2
Bottom edge - midpoint Cs = 0.357 VS1 = Cs x q x a = 32.1 [kN/m]
Side edge - maximum Cs = 0.249 VS2 = Cs x q x a = 22.4 [kN/m]
Side edge - midpoint Cs = 0.248 VS3 = Cs x q x a = 22.4 [kN/m]
Wall hor tensile force TS = VL2 = = 25.2 [kN/m]

Moment Coefficient Mz, My, Myz Case 3 in Page 3-31, 3-32


b/a = Lx / h = 2.1 c/a = Ly / h = 1.2
Wall ver bending moment Mz + | Myz | = 39.5 MSV = (Mz+|Myz|)qa2/103 = 10.7 [kNm/m]
2 3
Wall hor bending moment My + | Myz | = 53.5 MSH = (My+|Myz|)qa /10 = 14.4 [kNm/m]

Wall Force by FEA


Tank wall thickness w = 0.300 [m]
Long Side Wall Lx
Bottom edge-midpoint v=max(SQX,SQY) = 113.7 [kPa] VL1 = v x w = 34.1 [kN/m]
Side edge-maximum v=max(SQX,SQY) = 82.9 [kPa] VL2 = v x w = 24.9 [kN/m]
Wall hor tensile force t=max(SX,SY) = 106.0 [kPa] TL = t x w = 31.8 [kN/m]
Wall ver bending moment bottom edge-max MLV=max(MX+|MXY|, MY+|MXY|) = 12.2 [kNm/m]
Wall hor bending moment side edge-max MLH=max(MX+|MXY|, MY+|MXY|) = 16.3 [kNm/m]

010
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

2 of 8
Short Side Wall Ly Code Reference
Bottom edge-midpoint v=max(SQX,SQY) = 63.5 [kPa] VS1 = v x w = 19.1 [kN/m]
Side edge-maximum v=max(SQX,SQY) = 89.6 [kPa] VS2 = v x w = 26.9 [kN/m]
Wall hor tensile force t=max(SX,SY) = 117.6 [kPa] TS = t x w = 35.3 [kN/m]
Wall ver bending moment bottom edge-max MSV=max(MX+|MXY|, MY+|MXY|) = 7.3 [kNm/m]
Wall hor bending moment side edge-max MSH=max(MX+|MXY|, MY+|MXY|) = 16.8 [kNm/m]

Wall Force Used for Design Take max value of above two approaches
Long Side Wall Lx
Bottom edge - midpoint shear VL1 = 40.9 [kN/m]
Side edge - maximum shear VL2 = 25.2 [kN/m]
Wall hor tensile force TL = 31.8 [kN/m]
Wall ver bending moment bottom edge-max MLV = 25.0 [kNm/m]
Wall hor bending moment side edge-max MLH = 16.3 [kNm/m]

Short Side Wall Ly


Bottom edge - midpoint shear VS1 = 32.1 [kN/m]
Side edge - maximum shear VS2 = 26.9 [kN/m]
Wall hor tensile force TS = 35.3 [kN/m]
Wall ver bending moment bottom edge-max MSV = 10.7 [kNm/m]
Wall hor bending moment side edge-max MSH = 16.8 [kNm/m]

Conc & Rebar Data


Concrete strength f'c = 35 [MPa] A23.3-04
Rebar yield strength fy = 400 [MPa]
sqrt(f'c ) = min ( sqrt(fc') , 8 ) = 5.9 [MPa] 11.3.4
Concrete cover c = 75 [mm]
Exterior exposure crack control z = 25000 [N/mm]

Tank wall thickness w = 300 [mm]


Max bar dia db = 15 [mm]
Shear effective depth dv = w -c - db/2 = 218 [mm]

Concrete resistance factor c = 0.65


Rebar resistance factor s = 0.85
Low density conc factor = 1.0
NBC05
Liquid pressure load factor F = 1.5 for pressure of liquid in container 4.1.2.1
Soil pressure load factor S = 1.5 for lateral earth/groundwater pressure 4.1.3.2

011
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

3 of 8
3.1 Long Side Wall Check Code Reference
Shear - Wall Bottom Edge A23.3-04
Bottom edge - midpoint shear Vu = F x VL1 = 61.4 [kN/m]
When no transverse reinft. = 230 / (1000 + dv) = 0.189 11.3.6.3 Eq (11-9)

Vc = c fc' b w dv = 158 [kN] 11.3.4 Eq (11-6)


> Vu OK
Shear - Wall Side Edge
Side edge - maximum shear Vu = F x VL2 = 37.8 [kN/m]
Side edge - maximum tensile Tu = F x TL = 47.7 [kN/m]
Simplified method of determing value in A23.3-04 doesn't apply to members subjected to 11.3.6.1
significant axial tension. Formula in ACI318M-08 is used
Ag = 1m x w = 0.300 [m2] ACI 318M-08
Nu = Tu x -1 = -47.7 [kN]
Vc = = 135.6 [kN] 11.2.2.3 Eq (11-8)
> Vu OK
Flexure - Wall Ver. Reinft. A23.3-04
Wall ver bending moment bottom Mu = F x MLV = 37.5 [kNm/m]
edge-max b = 1000 [mm] d = 218 [mm]
Kr = Mu / (b x d2) = 0.792
= = 0.24%
= max( , 0.2%) = 0.24% 7.8.1
Required flexure reinft per meter As = x 1000 x d = 520 [mm2/m]
Provided reinft bar = 15 at spacing = 200 [mm]
Provided reinft per meter length Asprov = 1000 [mm2/m]
> 520 OK

Flexure - Wall Hor. Reinft. A23.3-04


Wall hor bending moment side Mu = F x MLH = 24.5 [kNm/m]
edge-max b = 1000 [mm] d = 218 [mm]
Kr = Mu / (b x d2) = 0.517
= = 0.15%
= max( , 0.2%) = 0.20% 7.8.1
Required flexure reinft per meter Asf = x 1000 x d = 435 [mm2/m]

Side edge - maximum tensile Tu = F x TL = 47.7 [kN/m]


Required tension reinft per side Ast = Tu / (0.9 fy) x 0.5 = 66 [mm2/m]

Required total reinft per meter Asrq'd = Asf + Ast = 501 [mm2]
Provided reinft bar = 15 at spacing = 200 [mm]
Provided reinft per meter length Asprov = 1000 [mm2/m]
> 501 OK

012
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

4 of 8
Crack Control Code Reference
Max unfactored bending moment M = max( MLV , MLH ) = 25.0 [kNm/m] A23.3-04
Concrete modulus of elasticity Ec = = 26622 [MPa] 8.6.2.3 Eq (8-2)
n = Es / Ec = 7.5
As = 1000 [mm2/m] d = 218 [mm]
= 0.46% n = 0.0345
k = 2 n + ( n) 2 n = 0.231
j = 1 - k/3 = 0.923
fs = M / (As x j x d) = 124.4 [MPa]
dc = c + db/2 (c<=50mm) = 57.5 [mm] 10.6.1
No of bar in 1m wide strip nb = 5
A = 2 x dc x 1000 / nb = 23000 [mm2]
Exterior exposure crack control z = = 25000 [N/mm] 10.6.1
z = = 13653 [N/mm] 10.6.1 Eq (10-6)
< 25000 OK

[The Wall Thickness Is Adequate]


[The Wall Reinft Is Adequate]
[The Wall Crack Control Is Adequate]

013
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

5 of 8
3.2 Short Side Wall Check Code Reference
Shear - Wall Bottom Edge A23.3-04
Bottom edge - midpoint shear Vu = F x VS1 = 48.2 [kN/m]
When no transverse reinft. = 230 / (1000 + dv) = 0.189 11.3.6.3 Eq (11-9)

Vc = c fc' b w dv = 158 [kN] 11.3.4 Eq (11-6)


> Vu OK
Shear - Wall Side Edge
Side edge - maximum shear Vu = F x VS2 = 40.3 [kN/m]
Side edge - maximum tensile Tu = F x TS = 52.9 [kN/m]
Simplified method of determing value in A23.3-04 doesn't apply to members subjected to 11.3.6.1
significant axial tension. Formula in ACI318M-08 is used
Ag = 1m x w = 0.300 [m2] ACI 318M-08
Nu = Tu x -1 = -52.9 [kN]
Vc = = 134.9 [kN] 11.2.2.3 Eq (11-8)
> Vu OK
Flexure - Wall Ver. Reinft. A23.3-04
Wall ver bending moment bottom Mu = F x MSV = 16.0 [kNm/m]
edge-max b = 1000 [mm] d = 218 [mm]
Kr = Mu / (b x d2) = 0.338
= = 0.10%
= max( , 0.2%) = 0.20% 7.8.1
Required flexure reinft per meter As = x 1000 x d = 435 [mm2/m]
Provided reinft bar = 15 at spacing = 200 [mm]
Provided reinft per meter length Asprov = 1000 [mm2/m]
> 435 OK

Flexure - Wall Hor. Reinft. A23.3-04


Wall hor bending moment side Mu = F x MSH = 25.2 [kN/m]
edge-max b = 1000 [mm] d = 218 [mm]
Kr = Mu / (b x d2) = 0.533
= = 0.16%
= max( , 0.2%) = 0.20% 7.8.1
Required flexure reinft per meter Asf = x 1000 x d = 435 [mm2/m]

Side edge - maximum tensile Tu = F x TS = 52.9 [kN/m]


Required tension reinft per side Ast = Tu / (0.9 fy) x 0.5 = 74 [mm2/m]

Required total reinft per meter Asrq'd = Asf + Ast = 509 [mm2]
Provided reinft bar = 15 at spacing = 200 [mm]
Provided reinft per meter length Asprov = 1000 [mm2/m]
> 509 OK

014
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

6 of 8
Crack Control Code Reference
Max unfactored bending moment M = max( MSV , MSH ) = 16.8 [kN/m] A23.3-04
Concrete modulus of elasticity Ec = = 26622 [MPa] 8.6.2.3 Eq (8-2)
n = Es / Ec = 7.5
As = 1000 [mm2/m] d = 218 [mm]
= 0.46% n = 0.0345
k = 2 n + ( n) 2 n = 0.231
j = 1 - k/3 = 0.923
fs = M / (As x j x d) = 83.7 [MPa]
dc = c + db/2 (c<=50mm) = 57.5 [mm] 10.6.1
No of bar in 1m wide strip nb = 5
A = 2 x dc x 1000 / nb = 23000 [mm2]
Exterior exposure crack control z = = 25000 [N/mm] 10.6.1
z = = 9184 [N/mm] 10.6.1 Eq (10-6)
< 25000 OK

[The Wall Thickness Is Adequate]


[The Wall Reinft Is Adequate]
[The Wall Crack Control Is Adequate]

015
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

7 of 8
3.3 Base Slab Check

Base Slab Force by FEA With Full Tank of Liquid


Tank base thickness Tb = 0.300 [m]
Base slab max shear v=max(SQX,SQY) = 73.1 [kPa] Vb = v x Tb = 21.9 [kN/m]
Base slab max flexure Mb=max(MX+|MXY|, MY+|MXY|) = 22.5 [kNm/m]

Conc & Rebar Data Code Reference


Concrete strength f'c = 35 [MPa] A23.3-04
Rebar yield strength fy = 400 [MPa]
sqrt(f'c ) = min ( sqrt(fc') , 8 ) = 5.9 [MPa] 11.3.4
Concrete cover c = 75 [mm]
Exterior exposure crack control z = 25000 [N/mm]

Tank base thickness Tb = 300 [mm]


Max bar dia db = 15 [mm]
Shear effective depth dv = Tb -c - db/2 = 218 [mm]

Concrete resistance factor c = 0.65


Rebar resistance factor s = 0.85
Low density conc factor = 1.00
NBC05
Liquid pressure load factor F = 1.5 for pressure of liquid in container 4.1.2.1
Soil pressure load factor S = 1.5 for lateral earth/groundwater pressure 4.1.3.2

Base Slab Shear Check With Full Tank of Liquid A23.3-04


Max factored shear Vu = F x Vb = 32.9 [kN/m]
When no transverse reinft. = 230 / (1000 + dv) = 0.189 11.3.6.3 Eq (11-9)

Vc = c fc' b w dv = 158 [kN] 11.3.4 Eq (11-6)


> Vu OK
Base Slab Flexure Check A23.3-04
Max factored flexure Mu = F x Mb = 33.8 [kNm/m]
b = 1000 [mm] d = 218 [mm]
2
Kr = Mu / (b x d ) = 0.713
= = 0.21%
= max( , 0.2%) = 0.21% 7.8.1
2
Required flexure reinft per meter As = x 1000 x d = 468 [mm /m]
Provided reinft bar = 15 at spacing = 200 [mm]
Provided reinft per meter length Asprov = 1000 [mm2/m]
> 468 OK

016
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

8 of 8
Base Slab Crack Control Code Reference
Max unfactored bending moment M = = 22.5 [kN/m] A23.3-04
Concrete modulus of elasticity Ec = = 26622 [MPa] 8.6.2.3 Eq (8-2)
n = Es / Ec = 7.5
As = 1000 [mm2/m] d = 218 [mm]
= 0.46% n = 0.0345
k = 2 n + ( n) 2 n = 0.231
j = 1 - k/3 = 0.923
fs = M / (As x j x d) = 112.1 [MPa]
dc = c + db/2 (c<=50mm) = 57.5 [mm] 10.6.1
No of bar in 1m wide strip nb = 5
A = 2 x dc x 1000 / nb = 23000 [mm2]
Exterior exposure crack control z = = 25000 [N/mm] 10.6.1
z = = 12300 [N/mm] 10.6.1 Eq (10-6)
< 25000 OK

[The Base Slab Thickness Is Adequate]


[The Base Slab Reinft Is Adequate]
[The Base Slab Crack Control Is Adequate]

017
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

1 of 6
4.0 LOAD CASE 2 Empty Tank With Backfill Present
Tank length Lx = 6.250 [m]
Tank width Ly = 3.690 [m]
Tank height h = 3.000 [m]
Tank content density w = 10.0 [kN/m3]
Equivalent triangle load q = = 41.5 [kN/m2]

Wall Force by PCA Tables


Long Side Wall Lx
Shear Coefficient Cs Case 3 in Page 2-17
a = 3.000 [m] b = 6.250 [m]
b/a = 2.1
Bottom edge - midpoint Cs = 0.455 VL1 = Cs x q x a = 56.6 [kN/m]
Side edge - maximum Cs = 0.280 VL2 = Cs x q x a = 34.8 [kN/m]
Side edge - midpoint Cs = 0.258 VL3 = Cs x q x a = 32.1 [kN/m]
Wall hor tensile force TL = VS2 = = 31.0 [kN/m]

Moment Coefficient Mx, My, Mxy Case 3 in Page 3-31, 3-32


b/a = Lx / h = 2.1 c/a = Ly / h = 1.2
Wall ver bending moment Mx + | Mxy | = 92.5 MLV = (Mx+|Mxy|)qa2/103 = 34.5 [kNm/m]
2 3
Wall hor bending moment My + | Mxy | = 53.5 MLH = (My+|Mxy|)qa /10 = 20.0 [kNm/m]

Short Side Wall Ly


a = 3.000 [m] b = 3.690 [m]
b/a = 1.2
Bottom edge - midpoint Cs = 0.357 VS1 = Cs x q x a = 44.4 [kN/m]
Side edge - maximum Cs = 0.249 VS2 = Cs x q x a = 31.0 [kN/m]
Side edge - midpoint Cs = 0.248 VS3 = Cs x q x a = 30.9 [kN/m]
Wall hor tensile force TS = VL2 = = 34.8 [kN/m]

Moment Coefficient Mz, My, Myz Case 3 in Page 3-31, 3-32


b/a = Lx / h = 2.1 c/a = Ly / h = 1.2
Wall ver bending moment Mz + | Myz | = 39.5 MSV = (Mz+|Myz|)qa2/103 = 14.7 [kNm/m]
Wall hor bending moment My + | Myz | = 53.5 MSH = (My+|Myz|)qa2/103 = 20.0 [kNm/m]

Wall Force by FEA


Tank wall thickness w = 0.300 [m]
Long Side Wall Lx
Bottom edge-midpoint v=max(SQX,SQY) = 113.7 [kPa] VL1 = v x w = 34.1 [kN/m]
Side edge-maximum v=max(SQX,SQY) = 82.9 [kPa] VL2 = v x w = 24.9 [kN/m]
Wall hor tensile force t=max(SX,SY) = 106.0 [kPa] TL = t x w = 31.8 [kN/m]
Wall ver bending moment bottom edge-max MLV=max(MX+|MXY|, MY+|MXY|) = 12.2 [kNm/m]
Wall hor bending moment side edge-max MLH=max(MX+|MXY|, MY+|MXY|) = 16.3 [kNm/m]
018
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

2 of 6
Short Side Wall Ly Code Reference
Bottom edge-midpoint v=max(SQX,SQY) = 63.5 [kPa] VS1 = v x w = 19.1 [kN/m]
Side edge-maximum v=max(SQX,SQY) = 89.6 [kPa] VS2 = v x w = 26.9 [kN/m]
Wall hor tensile force t=max(SX,SY) = 117.6 [kPa] TS = t x w = 35.3 [kN/m]
Wall ver bending moment bottom edge-max MSV=max(MX+|MXY|, MY+|MXY|) = 7.3 [kNm/m]
Wall hor bending moment side edge-max MSH=max(MX+|MXY|, MY+|MXY|) = 16.8 [kNm/m]

Wall Force Used for Design Take max value of above two approaches
Long Side Wall Lx
Bottom edge - midpoint shear VL1 = 56.6 [kN/m]
Side edge - maximum shear VL2 = 34.8 [kN/m]
Wall hor tensile force TL = 31.8 [kN/m]
Wall ver bending moment bottom edge-max MLV = 34.5 [kNm/m]
Wall hor bending moment side edge-max MLH = 20.0 [kNm/m]

Short Side Wall Ly


Bottom edge - midpoint shear VS1 = 44.4 [kN/m]
Side edge - maximum shear VS2 = 31.0 [kN/m]
Wall hor tensile force TS = 35.3 [kN/m]
Wall ver bending moment bottom edge-max MSV = 14.7 [kNm/m]
Wall hor bending moment side edge-max MSH = 20.0 [kNm/m]

Conc & Rebar Data


Concrete strength f'c = 35 [MPa] A23.3-04
Rebar yield strength fy = 400 [MPa]
sqrt(f'c ) = min ( sqrt(fc') , 8 ) = 5.9 [MPa] 11.3.4
Concrete cover c = 75 [mm]
Exterior exposure crack control z = 25000 [N/mm]

Tank wall thickness w = 300 [mm]


Max bar dia db = 15 [mm]
Shear effective depth dv = w -c - db/2 = 218 [mm]

Concrete resistance factor c = 0.65


Rebar resistance factor s = 0.85
Low density conc factor = 1.0
NBC05
Liquid pressure load factor F = 1.5 for pressure of liquid in container 4.1.2.1
Soil pressure load factor S = 1.5 for lateral earth/groundwater pressure 4.1.3.2

019
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

3 of 6
4.1 Long Side Wall Check Code Reference
Shear - Wall Bottom Edge A23.3-04
Bottom edge - midpoint shear Vu = F x VL1 = 84.9 [kN/m]
When no transverse reinft. = 230 / (1000 + dv) = 0.189 11.3.6.3 Eq (11-9)

Vc = c fc' b w dv = 158 [kN] 11.3.4 Eq (11-6)


> Vu OK
Shear - Wall Side Edge
Side edge - maximum shear Vu = F x VL2 = 52.3 [kN/m]
Side edge - maximum tensile Tu = F x TL = 47.7 [kN/m]
Simplified method of determing value in A23.3-04 doesn't apply to members subjected to 11.3.6.1
significant axial tension. Formula in ACI318M-08 is used
Ag = 1m x w = 0.300 [m2] ACI 318M-08
Nu = Tu x -1 = -47.7 [kN]
Vc = = 135.6 [kN] 11.2.2.3 Eq (11-8)
> Vu OK
Flexure - Wall Ver. Reinft. A23.3-04
Wall ver bending moment bottom Mu = F x MLV = 51.8 [kNm/m]
edge-max b = 1000 [mm] d = 218 [mm]
Kr = Mu / (b x d2) = 1.095
= = 0.33%
= max( , 0.2%) = 0.33% 7.8.1
Required flexure reinft per meter As = x 1000 x d = 727 [mm2/m]
Provided reinft bar = 15 at spacing = 200 [mm]
Provided reinft per meter length Asprov = 1000 [mm2/m]
> 727 OK

Flexure - Wall Hor. Reinft. A23.3-04


Wall hor bending moment side Mu = F x MLH = 30.0 [kNm/m]
edge-max b = 1000 [mm] d = 218 [mm]
Kr = Mu / (b x d2) = 0.633
= = 0.19%
= max( , 0.2%) = 0.20% 7.8.1
Required flexure reinft per meter Asf = x 1000 x d = 435 [mm2/m]

Side edge - maximum tensile Tu = F x TL = 47.7 [kN/m]


Required tension reinft per side Ast = Tu / (0.9 fy) x 0.5 = 66 [mm2/m]

Required total reinft per meter Asrq'd = Asf + Ast = 501 [mm2]
Provided reinft bar = 15 at spacing = 200 [mm]
Provided reinft per meter length Asprov = 1000 [mm2/m]
> 501 OK

020
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

4 of 6
Crack Control Code Reference
Max unfactored bending moment M = max( MLV , MLH ) = 34.5 [kNm/m] A23.3-04
Concrete modulus of elasticity Ec = = 26622 [MPa] 8.6.2.3 Eq (8-2)
n = Es / Ec = 7.5
As = 1000 [mm2/m] d = 218 [mm]
= 0.46% n = 0.0345
k = 2 n + ( n) 2 n = 0.231
j = 1 - k/3 = 0.923
fs = M / (As x j x d) = 172.0 [MPa]
dc = c + db/2 (c<=50mm) = 57.5 [mm] 10.6.1
No of bar in 1m wide strip nb = 5
A = 2 x dc x 1000 / nb = 23000 [mm2]
Exterior exposure crack control z = = 25000 [N/mm] 10.6.1
z = = 18876 [N/mm] 10.6.1 Eq (10-6)
< 25000 OK

[The Wall Thickness Is Adequate]


[The Wall Reinft Is Adequate]
[The Wall Crack Control Is Adequate]

021
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

5 of 6
4.2 Short Side Wall Check Code Reference
Shear - Wall Bottom Edge A23.3-04
Bottom edge - midpoint shear Vu = F x VS1 = 66.6 [kN/m]
When no transverse reinft. = 230 / (1000 + dv) = 0.189 11.3.6.3 Eq (11-9)

Vc = c fc' b w dv = 158 [kN] 11.3.4 Eq (11-6)


> Vu OK
Shear - Wall Side Edge
Side edge - maximum shear Vu = F x VS2 = 46.5 [kN/m]
Side edge - maximum tensile Tu = F x TS = 52.9 [kN/m]
Simplified method of determing value in A23.3-04 doesn't apply to members subjected to 11.3.6.1
significant axial tension. Formula in ACI318M-08 is used
Ag = 1m x w = 0.300 [m2] ACI 318M-08
Nu = Tu x -1 = -52.9 [kN]
Vc = = 134.9 [kN] 11.2.2.3 Eq (11-8)
> Vu OK
Flexure - Wall Ver. Reinft. A23.3-04
Wall ver bending moment bottom Mu = F x MSV = 22.1 [kNm/m]
edge-max b = 1000 [mm] d = 218 [mm]
Kr = Mu / (b x d2) = 0.468
= = 0.14%
= max( , 0.2%) = 0.20% 7.8.1
Required flexure reinft per meter As = x 1000 x d = 435 [mm2/m]
Provided reinft bar = 15 at spacing = 200 [mm]
Provided reinft per meter length Asprov = 1000 [mm2/m]
> 435 OK

Flexure - Wall Hor. Reinft. A23.3-04


Wall hor bending moment side Mu = F x MSH = 30.0 [kN/m]
edge-max b = 1000 [mm] d = 218 [mm]
Kr = Mu / (b x d2) = 0.633
= = 0.19%
= max( , 0.2%) = 0.20% 7.8.1
Required flexure reinft per meter Asf = x 1000 x d = 435 [mm2/m]

Side edge - maximum tensile Tu = F x TS = 52.9 [kN/m]


Required tension reinft per side Ast = Tu / (0.9 fy) x 0.5 = 74 [mm2/m]

Required total reinft per meter Asrq'd = Asf + Ast = 509 [mm2]
Provided reinft bar = 15 at spacing = 200 [mm]
Provided reinft per meter length Asprov = 1000 [mm2/m]
> 509 OK

022
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

6 of 6
Crack Control Code Reference
Max unfactored bending moment M = max( MSV , MSH ) = 20.0 [kN/m] A23.3-04
Concrete modulus of elasticity Ec = = 26622 [MPa] 8.6.2.3 Eq (8-2)
n = Es / Ec = 7.5
As = 1000 [mm2/m] d = 218 [mm]
= 0.46% n = 0.0345
k = 2 n + ( n) 2 n = 0.231
j = 1 - k/3 = 0.923
fs = M / (As x j x d) = 99.5 [MPa]
dc = c + db/2 (c<=50mm) = 57.5 [mm] 10.6.1
No of bar in 1m wide strip nb = 5
A = 2 x dc x 1000 / nb = 23000 [mm2]
Exterior exposure crack control z = = 25000 [N/mm] 10.6.1
z = = 10917 [N/mm] 10.6.1 Eq (10-6)
< 25000 OK

[The Wall Thickness Is Adequate]


[The Wall Reinft Is Adequate]
[The Wall Crack Control Is Adequate]

023
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

1 of 3
5.0 LOAD CASE 3 Buoyancy Force

Tank Data
Tank length Lx = 6.250 [m]
Tank width Ly = 3.690 [m]
Tank height h = 3.000 [m]
Tank wall thickness w = 0.300 [m]
Tank base thickness Tb = 0.300 [m]
Tank roof thickness Tr = 0.300 [m]
Tank base extension wt = 0.300 [m]
Ground water table height hw = 1.500 [m]
Tank length wall c/c b = 6.550 [m]
Tank width wall c/c c = 3.990 [m]
Soil density s = 21.000 [kN/m3]

Uplift Resistance
Tank wall weight w1 = (b+c) x 2 x h x w x 23.5 = 445.8 [kN]
Bottom slab weight w2 = (b+w+2wt ) x (c+w+2wt ) x Tb x 23.5 = 256.8 [kN]
Top slab weight w3 = (b+w) x (c+w) x Tr x 23.5 = 207.2 [kN]
Soil above base extension wt. w4 = (b+c+2w+2wt ) x 2 x wt x h x s = 443.8 [kN]
Total weight w = = 1353.6 [kN]

Area of bottom slab A = (b+w+2wt ) x (c+w+2wt ) = 36.4 [m2]


Water pressure p = (hw+Tb) x 10 = 18.0 [kN/m2]
Buoyant force B = Axp = 655.7 [kN]
Safety factor SF = w / B = 2.1
> 1.5 OK

Tank Base Slab Design With Empty Tank and Uplift Buoyancy Force
Tank base thickness Tb = 0.300 [m]
Water net pressure on base pn = p - Tb x 23.5 = 11.0 [kN/m2]
Water net pressure on base pn used for design = 11.0 [kN/m2]

Base Slab Force by FEA


Base slab max shear v=max(SQX,SQY) = 42.3 [kPa] Vb = v x Tb = 12.7 [kN/m]
Base slab max flexure Mb=max(MX+|MXY|, MY+|MXY|) = 12.0 [kNm/m]

024
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

2 of 3
Conc & Rebar Data Code Reference
Concrete strength f'c = 35 [MPa] A23.3-04
Rebar yield strength fy = 400 [MPa]
sqrt(f'c ) = min ( sqrt(fc') , 8 ) = 5.9 [MPa] 11.3.4
Concrete cover c = 75 [mm]
Exterior exposure crack control z = 25000 [N/mm]

Tank base thickness Tb = 300 [mm]


Max bar dia db = 15 [mm]
Shear effective depth dv = Tb -c - db/2 = 218 [mm]

Concrete resistance factor c = 0.65


Rebar resistance factor s = 0.85
Low density conc factor = 1.0
NBC05
Liquid pressure load factor F = 1.5 for pressure of liquid in container 4.1.2.1
Soil pressure load factor S = 1.5 for lateral earth/groundwater pressure 4.1.3.2

Shear Check A23.3-04


Max factored shear Vu = F x Vb = 19.0 [kN/m]
When no transverse reinft. = 230 / (1000 + dv) = 0.189 11.3.6.3 Eq (11-9)

Vc = c fc' b w dv = 158 [kN] 11.3.4 Eq (11-6)


> Vu OK
Flexure Check A23.3-04
Max factored flexure Mu = F x Mb = 18.0 [kNm/m]
edge-max b = 1000 [mm] d = 218 [mm]
Kr = Mu / (b x d2) = 0.380
= = 0.11%
= max( , 0.2%) = 0.20% 7.8.1
Required flexure reinft per meter As = x 1000 x d = 435 [mm2/m]
Provided reinft bar = 15 at spacing = 200 [mm]
Provided reinft per meter length Asprov = 1000 [mm2/m]
> 435 OK

025
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

3 of 3
Crack Control Code Reference
Max unfactored bending moment M = = 12.0 [kNm/m] A23.3-04
Concrete modulus of elasticity Ec = = 26622 [MPa] 8.6.2.3 Eq (8-2)
n = Es / Ec = 7.5
As = 1000 [mm2/m] d = 218 [mm]
= 0.46% n = 0.0345
k = 2 n + ( n) 2 n = 0.231
j = 1 - k/3 = 0.923
fs = M / (As x j x d) = 59.8 [MPa]
dc = c + db/2 (c<=50mm) = 57.5 [mm] 10.6.1
No of bar in 1m wide strip nb = 5
A = 2 x dc x 1000 / nb = 23000 [mm2]
Exterior exposure crack control z = = 25000 [N/mm] 10.6.1
z = = 6560 [N/mm] 10.6.1 Eq (10-6)
< 25000 OK

[The Uplift Resistance Is Adequate]


[The Base Slab Thickness Is Adequate]
[The Base Slab Reinft Is Adequate]
[The Base Slab Crack Control Is Adequate]

026
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

1 of 2
6.0 ROOF SLAB DESIGN Code Reference
Tank Data
Tank length Lx = 6.250 [m]
Tank width Ly = 3.690 [m]
Tank wall thickness w = 0.300 [m]
Tank roof thickness Tr = 0.300 [m]
Tank length wall c/c b = 6.550 [m]
Tank width wall c/c c = 3.990 [m]
Ground surcharge qs = 10.0 [kPa]

Roof Slab Force by PCA Tables


b = 6.550 [m] a = 3.990 [m]
b/a = 1.6
Service area load q = Slab SelfWt + qs = 17.1 [kPa]
Factored area load qf = 1.25 Slab SelfWt +1.5 qs = 23.8 [kPa]
PCA Rect Tank
Shear Coefficient Cs Case 10 in Page 2-59 slab 4 edges simply supported Page 2-59
Factored max shear Cs = 0.437 V = Cs x q x a = 41.5 [kN/m]
Deflection Coefficient Cd Cd = 8.493

Moment coefficient Mx, My, Mxy Case 10 in Page 2-60 ~ 2-64


Moment coeff. m = max(MX+|MXY|, MY+|MXY|) = 85.0
Factored max flexure Mf = m qf a2 / 1000 = 32.2 [kNm/m]

Conc & Rebar Data


Concrete strength f'c = 35 [MPa] A23.3-04
Rebar yield strength fy = 400 [MPa]
sqrt(f'c ) = min ( sqrt(fc') , 8 ) = 5.9 [MPa] 11.3.4
Concrete cover c = 75 [mm]
Exterior exposure crack control z = 25000 [N/mm]

Tank roof thickness Tr = 300 [mm]


Max bar dia db = 15 [mm]
Shear effective depth dv = Tr -c - db/2 = 218 [mm]
Concrete resistance factor c = 0.65
Rebar resistance factor s = 0.85
Low density conc factor = 1.0

Shear Check
Max factored shear Vu = = 41.5 [kN/m]
When no transverse reinft. = 230 / (1000 + dv) = 0.189 11.3.6.3 Eq (11-9)
Vc = c fc' b w dv = 158 [kN] 11.3.4 Eq (11-6)
> Vu OK
027
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

2 of 2
Flexure Check Code Reference
Max factored flexure Mu = = 32.2 [kNm/m]
b = 1000 [mm] d = 218 [mm]
Kr = Mu / (b x d2) = 0.681 A23.3-04
= = 0.21%
= max( , 0.2%) = 0.21% 7.8.1
Required flexure reinft per meter As = x 1000 x d = 446 [mm2/m]
Provided reinft bar = 15 at spacing = 200 [mm]
Provided reinft per meter length Asprov = 1000 [mm2/m]
> 446 OK
Crack Control
Max unfactored bending moment M = m q a2 / 1000 = 23.1 [kNm/m] A23.3-04
Concrete modulus of elasticity Ec = = 26622 [MPa] 8.6.2.3 Eq (8-2)
n = Es / Ec = 7.5
As = 1000 [mm2/m] d = 218 [mm]
= 0.46% n = 0.0345
k = 2 n + ( n) 2 n = 0.231
j = 1 - k/3 = 0.923
fs = M / (As x j x d) = 114.9 [MPa]
dc = c + db/2 (c<=50mm) = 57.5 [mm] 10.6.1
No of bar in 1m wide strip nb = 5
A = 2 x dc x 1000 / nb = 23000 [mm2]
Exterior exposure crack control z = = 25000 [N/mm] 10.6.1
z = = 12613 [N/mm] 10.6.1 Eq (10-6)
< 25000 OK
Deflection Check
t = 0.300 [m] = 0.17

D = = 61683 [kNm]

Deflection due to live load d = Cd x qs x a4 / (1000 x D) x 1000 = 0.3 [mm]


Deflection limit = a / 180 = 22.2 [mm] Table 9.3
Assume cracked section Ie = 0.5 Ig , the deflection will be doubled
d = 2xd = 0.7 [mm]
< a/180 OK

[The Roof Slab Thickness Is Adequate]


[The Roof Slab Reinft Is Adequate]
[The Roof Slab Crack Control Is Adequate]
[The Roof Slab Deflection Is Adequate]

028
Project : Alberta Oilsand Eng : Test
www.civilbay.com Jon No : 1234567 Chk : Test
Doc No : 1234567 Date : 2013-02-14
Calculation Sheet Subject : Sump Tank Calc Rev : 0

1 of 1
7.0 BEARING CAPACITY CHECK

Tank Data
Tank length Lx = 6.250 [m]
Tank width Ly = 3.690 [m]
Tank height h = 3.000 [m]
Tank wall thickness w = 0.300 [m]
Tank base thickness Tb = 0.300 [m]
Tank roof thickness Tr = 0.300 [m]
Tank base extension wt = 0.300 [m]
Ground water table height hw = 1.500 [m]
Tank length wall c/c b = 6.550 [m]
Tank width wall c/c c = 3.990 [m]
Soil density s = 21.0 [kN/m3]
Ground surcharge qs = 10.0 [kPa]
Soil allowable bearing capacity qa = 150 [kPa]

Tank Base Compressive Pressure


Tank wall weight w1 = (b+c) x 2 x h x w x 23.5 = 445.8 [kN]
Bottom slab weight w2 = (b+w+2wt ) x (c+w+2wt ) x Tb x 23.5 = 256.8 [kN]
Top slab weight w3 = (b+w) x (c+w) x Tr x 23.5 = 207.2 [kN]
Soil above base extension wt. w4 = (b+c+2w+2wt ) x 2 x wt x h x s = 443.8 [kN]
Full tank water weight w5 = Lx x Ly x h x w = 691.9 [kN]
Ground surcharge weight w6 = (b+w+2wt ) x (c+w+2wt ) x qs = 364.3 [kN]
Total weight w = = 2409.8 [kN]

Area of bottom slab A = (b+w+2wt ) x (c+w+2wt ) = 36.4 [m2]


Tank base pressure p = w / A = 66.1 [kN/m2]
< 150 OK

[The Soil Bearing Capacity Is Adequate]

029