Utility Networks
Contents
Empty Cabinets 28
Bus Bars 32
KS-Design 2002 36
Ensto is an international industrial Ensto Utility Networks develops, Our product line includes both
Group, founded in 1958, developing, manufactures and markets products overhead line and underground
manufacturing and marketing for transmission and distribution cable accessories. We can offer our
electrical solutions and accessories. networks within a voltage range of customers high quality and reliable
At the moment, Ensto operates in 14 0.4 400 kV, underground cable products by combining our know-
countries with a staff of over 1,000 accessories within a voltage range how, experience and customer-
and exports to over 70 countries. of 0.4 36 kV as well as special oriented product development.
products.
The range of Enstos low voltage Since the joint includes easy-to-use The kits include connectors with
underground cable accessories has screw connectors, no special tools shear head bolts, so no pressing
expanded signicantly. Our product are needed and cable joining is tools are needed. Moreover, every
range includes heat shrink tube kits easier. kit covers a large range of cross-
for joining 3, 4 and 5-core cables. sections, which reduces warehousing
Accessories for 1kV cables also costs. It is easy to choose the right
include spreader caps, end caps, 1 kV Joint Kits and Accessories kits with the Jatsekko program,
cast resin joints and cable repair Enstos 1 kV joint kits cover all 3, which nds the correct kits upon
sleeves. The new SJKK joint kits with 4 and 5-core cable joints within entry of the cable type.
repair sleeves make cable joining a cross-sectional range of 6-300
possible, even in conned spaces. mm. With these accessory kits,
papercable joints can also be made.
7
Enstos SJK joint kits include four inner heat shrink tubes with adhesive, and one outer heat shrink tube with adhesive for the cable
sheath, four connectors with shear head bolts, an abrasive band, a cleaning towel and a tting tool for installing the connectors. It
is safe to join Cu cables to Al cables with the joint kit because the connectors are tin-plated and have middle wall, which prevents
corrosion of the Al/Cu joint.
End Caps
The end cap seals the head of the disconnected cable, protecting it from humidity and water penetration. The cap should be
used when storing the cable in outdoor conditions. End caps are provided with adhesive.
Cast Resin EG
EG cast resin is meant for installations with a maximum voltage of 1kV and for mechanical protection for medium voltages. It is
suitable for both paper and plastic cables. The same bag includes a separate curing agent and polyurethane cast resin, which
are mixed by pulling out a separating stick from between the compartments. The cast resin and curing agent are mixed and
poured into the casting mould, forming effective insulation with a compact and water-tight layer. Within a few hours the cast
resin hardens, and the voltage can be immediately connected. The resins storage period is 40 months.
LG 500
Bushing sealant is used for sealing cable bushing. The sealant adheres to concrete, wood, steel and various plastics, and is
spread with a wooden stick provided with the kit. It can be stored for 20 months.
Terminations and
Joints for MV Cables
CHE
Our MV terminations and joints
combine the advantages of heat UCHE
and cold shrink technologies. CHEP
The semi-conductive insulation
CAE
screen is covered with a stress
control tube which is easy to install
and extremely reliable, effectively
preventing damage to this most
vulnerable section of the joint.
The stress control tube evens out
and controls the electrical eld,
preventing the formation of uneven
and high-intensity electrical elds,
which might stress the cable at the
end of the semi-conductive screen.
The medium voltage terminations
and joints are packaged into kits that
are as complete as possible, making UCHMP UCHM
on-site installation easier. Joint UCHMPL CHM
kits include connectors with shear
CHM3
head bolts, and correspondingly,
CAM
termination kits include cable lugs
with shear head bolts. Kits are also
available without connectors.
Ensto MV Joint System
10 kV and 20 kV
UCHM
AHXAMK-W AHXAMK-W
UCHMP
AHXAMK-W APYAKMM
UCHMP+UCHMPL1
AHXAMK-W PYLKVJ
UCHM+UCHML1,2,3
AHXAMK-W AHXCMK-WTC, AHXCMKM,
UCHM AXCEL, AXCES, AXLJ, AXCLIGHT
AHXAMK-W (A)HXCMK
CHMPR3-1+SJEW
AHXAMK-W PLKVJ 10 kV
14
Use
UCHE cable terminations are compatible with plastic insulated AHXAMK-W, AHXAMK-WM, AHXAMK-WP and SAXKA-W cables.
The terminations are for both outdoor and indoor use, and can be used for installing cables into ring main units, transformers,
motors and SF6 switchgear. The terminations suit Cu and Al cables with a cross-section of 25...300 mm. Terminations are
also easy to install on a pole together with a SH 536 surge arresterbracket and SO 75.1 raised bracket. Since the cable lugs
with shear head bolts included in the basic kits are waterproof longitudinally, they are ideally suited to outdoor use. The
slip-on silicone sheds are quick and easy to install and provide effective cover for the cable. The cable can be connected to the
mains immediately after installation.
UCHM Joint for AHXAMK-W Cables, 10-20 kV, AHXAMK-W -> AHXAMK-W
Joint Structure
AMV cable joints include some elements that are identical to those of cable terminations, i.e. the electrical eld is controlled
with a stress control tube. Enstos UCHM cable joint consists of a stress control tube, heat shrink tube, cable connectors with
shear head bolts and sealing mastic. The reliability and safety of the cable joint is ensured by a stress control tube, which is
easy to install using the tool and GM 1 lubricant/ller included in the kit. The kit also includes a tubular, tin-plated Cu grid and
earth springs for joining the cables Al shroud. Joint kits are also available without cable connectors, when e.g. pressed cable
connectors can be used.
Use
The UCHM cable joint is compatible with AHXAMK-W (Wiski, Dryrex), AHXAMK-WM (Multiwiski), AHAMK-WP (Pikkuwiski)
and SAXKA-W cables. It is used for joining MV underground cables, which can be connected to the mains immediately after
installation.
Joint Kit with Shear Head Bolt Connectors
VOLTAGE CROSS-SECTION TYPE EAN
kV mm
10 16-25 UCHM 10/0 6418677432651
10 35-95 UCHM 10/1 6418677417689
10 95-240 UCHM 10/2 6418677417696
10 150-300 UCHM 10/3 6418677417702
20 16-35 UCHM 20/1 6418677432811
20 50-95 UCHM 20/2 6418677417719
20 95-240 UCHM 20/3 6418677417474
20 150-300 UCHM 20/4 6418677417733
UCHMP Transition Joint from the APYAKMM to AHXAMK-W with Shear Head Bolt
Connectors
Heat shrink transition joints are suitable for APYAKMM to AHXAMK-W and APYAKMT to AHXAMK-W joints. Kits are available
both with and without shear head bolt connectors. The kit includes a silicone stress control tube, red insulating heat shrink
tubes, surface semi-conductive tube, semi-conductive tape and sealing mastic. In addition to these, the kit includes connection
accessories for Al sheath and Al laminate, and an earthing tapping point from an APYAKMM cable to an AHXAMK-W earthing Cu.
UCHML1 AHXAMK-W > 3-core common wire screen cable Accessory Kit
This accessory kit is intended for connecting the AHXAMK-W - AHXCMK-WTC transition joint. The joint requires the UCHM
basic kit and UCHML1 accessory kit. The accessory kit includes a spreader cap and heat shrink tubes for the protection of
the phase conductors corona shield (for AHXCMK-WTC). In addition, the kit includes a shroud, a plated Cu bridle needed for
connecting Cu wires (AHXCMK-WTC) and Cu earthing conductor (AHXAMK-W), a Cu connector and constant force springs.
Note! The same accessory kit is also suitable for connecting AHXAMK-W to cable types AHXCMKM, AXCES, AXCEL, AXCLIGHT,
AXLJ and AXQJ.
CHE-I Indoor Terminations and CHE-F Outdoor Terminations for single core
plastic Cables, 10-20 kV
Termination Structure
Heat shrink termination includes accessories for all three phase conductors. The termination consists of an insulating and
antitrackingheat shrink part, stress control tube and slip-on silicone sheds.
Use
The CHE-I termination is intended for indoor use for single-core Cu and Al cables. Correspondingly, the CHE-F termination is
intended for outdoor use.
CHM Joint for single core cables with copper wire screen, 10-20 kV
Joint Structure
The CHM cable joint consists of a stress control tube, insulating heat shrink tubes and a surface semi-conductive heat shrink
tube, an outer tube covering the cable mechanically . In addition, the basic joint kit includes a tubular tin-plated Cu grid
for shroud and constant force springs. Note! The kit is available with or without shear head bolt connectors. The reliability
and safety of the cable joint is ensured by a stress control tube, which is easy to install using the tool and GM 1 lubricant/
ller included in the kit. The cable joint has been tested according to the German DIN VDE 0278 standard, and fullls all
requirements for MV cables with a voltage range of 6-36 kV. The kit includes all accessories needed for one phase.
Use
The CHM joint is compatible with single core plastic cablescables which have a layer of Cu wires as a shroud, and is used for
joining underground cable. The cable can be connected to the mains immediately after installation.
The termination consists of an insulating heat shrink tube, a stress control tube, a spreader cap, heat shrink tubes, slip-on
silicone sheds and sealing mastic (on the outdoor termination). The reliability and safety of the termination is ensured by a
silicone stress control tube, which is easy to install using the tool and GM1 lubricant/ller included in the kit. With the outdoor
termination, it is possible to select the length of the peeled phase conductor, ranging from 100.1000mm, depending on
installation and use.
The termination consists of an insulating and surface current resistant heat shrink tube, a stress control tube, a spreader
cap, heat shrink tubes and slip-on silicone anges. The reliability and safety of the termination is ensured by a silicone stress
control tube, which is easy to install using the tool and GM11 lubricant/ller included in the kit. With the indoor termination, it
is possible to select the length of the peeled phase conductors (black) protective tube, ranging from 100350mm, depending
on installation and use.
Termination Structure
CAE terminations have an integrated, reliable stress control tube inside and anges for the outer surface, so they do not need
to be installed separately. The termination is made of exible silicone and has a smooth surface which cleans itself when in
contact with water (forming a water drop on the termination, not a homogenous water coating). Terminations are available
with shear head bolt cable lugs and without cable lugs.
Use
The CAE-I termination is intended for indoor use for single-core Cu and Al cables such as (A)HXCMK. Correspondingly, the
CAE-F termination is intended for outdoor use. CAE terminations are also suitable for AHXAMK-W, AHXAMK-WM, AHXAMK-
WP and SAXKA-W cables. The termination kit does not include the AHXAMK-W cables Al shroud earthing set, which must be
ordered separately using the product code SJCW70240.1.
CAE-3F Outdoor Termination and CAE-3I Indoor Termination for 3-Core Cables
The CAE-3I and CAE-3F cold shrink terminations can be used when terminating AHXCMK-WTC, AHXAMKM, AXCEL, EXCEL,
AXLJ, AXQJ, AXCLIGHT and AXCLIGHT H cables.
The cable termination consists of a cold shrink SLIP ON termination, which is otherwise the same as the CAE-I and CAE-F
single-core terminations. In addition, it has a cold shrink spreader cap and a cold shrink cover tube for covering the corona
shield and sealing mastic. Stress control and anges are integrated into the same termination tube.
Insulation Tape No 62
For repair and bonds between insulating and sheathing materials. Can be used for temporary insulation or protection until 69
kV.
Sealant Tape No 64
Self-vulcanizing sealant tape can be used as cables dampfproof course.
Pressure Springs
For connections between screen, armouring and metal sheath and earthing elements.
The same xing points can be used barrier can be installed in the
with the marking bar. cabinets. The ventilation of the
cabinets has been improved by
ventilation holes in the front
panel.
900
900
25
26
850 mm 850 mm
900 mm 900 mm
KSE 26 KSE 44 KSE 50 KSE 72 KSE 94 KSE 117 KSE 149 KSE 183 KSE 216
Empty Cabinets
The empty cabinets are suitable for tele or instrument cabinets, e.g. a street lighting or a measuring cabinet. The empty
cabinets are externally similar to the cabinets with bus bar, see page 4 and 14. It is possible to install a mounting plate
or a C-mounting bracket into the mounting bars inside the cabinet. The roof of the cabinet can be removed during
installation of the mounting plate or the C-bar bracket. Mounting plates have to be ordered separately.
Cabinet E-KSTA 44.2 is suitable also for pole installation. Pole mounting box E-SF6-44.
29
Mounting plates, Al 2 mm
TYPE EAN FOR CABINET HEIGHT WIDTH
mm mm
E-MPAL 44 5702662518156 E-KST_44 700 252
E-MPAL 60 5702662518217 E-KST_60 700 380
E-MPAL 94 5702662518279 E-KST_94 700 583
E-MPAL 117 5702662518330 E-KST_117 700 781
E-MPAL 183 5702662518385 E-KST_183 700 1177
C-mounting brackets
The mounting brackets are made of C-form aluminium prole. The mounting bracket includes vertical and horizontal bars,
xing parts and an earthing set with connectors. E-CKV bar set includes 2 pcs of xed length horizontal bars and xing parts
into the cabinet.
C-mounting brackets
TYPE EAN FOR CABINET HEIGHT WIDTH
mm mm
E-CKS 44 6418677410413 E-KST_44 700 252
E-CKS 60 6418677410420 E-KST_60 700 380
E-CKS 94 6418677410437 E-KST_94 700 583
E-CKS 117 6418677410444 E-KST_117 700 781
E-CKS 183 6418677410451 E-KST_183 700 1177
C-bar sets
TYPE EAN FOR CABINET RAIL REST WIDTH
mm
E-CKV 44 6418677410468 E-KST_44 E-CKS 44 252
E-CKV 60 6418677410475 E-KST_60 E-CKS 60 380
E-CKV 94 6418677410482 E-KST_94 E-CKS 94 583
E-CKV 117 6418677410499 E-KST_117 E-CKS 117 781
E-CKV 183 6418677410505 E-KST_183 E-CKS 183 1177
The E-DZ2x63A fuse-switch The E-KLB2 400 A fuse-switch The connectors have to be ordered
disconnector includes two outputs disconnector can be used with one separately. Every disconnector unit is
(max 63 A DZ II-III fuses) with spring max 300 mm2 cable with E-KK240- voltage tested at the factory.
operated fuse holders. The breaking 300 connectors or with two 50...185 All phases of the cable including
operation of the load is made with mm2 cables having the same the PEN conductor are connected
knives, not with fuses. The EDZ2x63A cross-section with E-KK2x50-185 directly to all the switches in the
is ideal for renewing projects and connectors. same level, which makes the
private house areas because each The E-FSD disconnector unit installation easy. There is no need
consumer can be connected with includes visible clearance between to bend the PEN conductor into
ones own output. Connectors are open contacts. The switch is one pole a separate earthing bar. All the
integrated into the construction, operated. The utilisation category switches and components are
so there no need for separate of the unit is AC21 with rated values suitable for live line work without
connectors. The right fuse size is of 500 V, 400 A. The cabinet can be any special tools or working
limited with fuse adapters. bypassed by connecting two E-FSDs methods. The installation of all the
The E-KLB00 160 A fuse-switch together. components and switches is done
disconnector can be used with one The unit can be used as a with 5 mm allen key E-IN5 or E-
max 95 mm2 cable or two max 35 disconnecting device in a ring MIN5.
mm2 cables having the same cross- network instead of e.g. short The bus bar and cables can be
section, when E-KK25-95 connectors circuiting knives. earthed with earthing covers.
are used. Connectors, which are
delivered in sets of 4, have to be
ordered separately for E-KLB00 and
E-KLB2 switches.
Bus Bars
The renewing bus bars are ideal for renewing of old, existing cable distribution
cabinets and transformer substations. If an old cabinet body is in good
condition, there is no need to change the whole cabinet and a lot of money and
time is saved. The bus bar is mounted into an old cabinet and old switches and
open fuse bases can be replaced with new ones. The protection class of the
bus bars is IP20. E-SS bus bars are suitable for old cable distribution cabinets,
E-SS1600 bus bars for LV side of transformer substations and E-STS bus bars
for the branch off cabinets.
Covered bus bars (630A, IP20) for renewing of old cable distribution cabinets
TYPE EAN HEIGHT WIDTH LENGTH OF BUS BAR WEIGHT
mm mm mod kg
E-SS 6-50 5702665989885 580 330 49 4,5
E-SS 6-61 5702665989878 580 395 60 4,8
E-SS 6-72 5702665989892 580 460 71 5,2
E-SS 6-83 5702665989915 580 526 82 7,2
E-SS 6-94 5702665989939 580 565 93 9,8
E-SS 6-117 5702665989946 580 763 117 12,5
E-SS 6-183 5702665989953 580 1159 183 18,0
Covered bus bars (630A, IP20) for the branch off cabinets
TYPE EAN FOR CABINET WEIGHT
kg
E-STS 6-26 5702665989601 E-KSE 26.2 2,5
E-STS 6-44 5702665989618 E-KSE 44.2 3,0
E-HP 2 bracket
Bracket is used to connect two switches E-KLB2 parallel to each other.
Keys
Insulated allen keys are used for installation of all the switches and connectors. The keys are approved for live line work up to
1000 VAC and they fulll EN 60900 standard requirements. E-MIN5 allen key can be used with 3/8 torque wrench. Triangle key
E-TN is used for opening and closing the door.
Brackets
The protective tubes can be xed into a pole with bracket E-RH3 (place for 3 tubes) or with E-RH7 (place for 7 tubes).
Connection sets
The cabinets can be mounted together with E-SK connection sets or by connecting the roofs together.
Marking rods
Marking rod can be xed to the side of the cabinet.
Identication plates
External identication can be done with identication plates. The identication plates are xed to an identication bar, in which
there is place for 8 plates.
KS-Design 2002
Branching connector KE 10
The connectors can be used for aluminium and copper conductors. Tightening torque is 10 Nm. The
connectors are used either inside metal poles or in separate boxes.