Você está na página 1de 4

G1D

Ratings
Type G1D
Rated voltage 550kV
Rated lightning impulse withstand voltage 1675kV
Rated switching impulse withstand voltage 1175kV
Rated power frequency withstand voltage 680kV
Rated frequency 50/60Hz
Rated current 2000/3150/4000 A
Rated short time withstand current 63kA-3sec.
Rated gas pressure (abs.) 0.7 MPa(GCB)/0.6 MPa(GIS)
Applied standards IEC
Typical Construction of 550kV GIS

SF6gas
Insulators
Live parts
CT/PT
Eathed parts Busbar disconnector and
Earthing switch, disconnector and
maintenance earthing switch maintenance earthing switch
(HS-ES/DS/M-ES) (DS/M-ES)

Current transformer Disconnector and maintenance Busbar


(CT) earthing switch(DS/M-ES)

Gas circuit breaker


(GCB)

One and a half circuit breaker system

Arrangement of Air Compressor


Abundant experience and high reliability
Reliable connector (Bite type)

Arrangement
Individual Type Semi Central Type Central Type

Gas Circuit Resistor(GCB)

Air compressor
Gas Circuit Breaker Disconnector and Earthing Switch
Principle of advanced hybrid puffer Integrated construction (DS, HS-ES, M-ES in one
(A) Initial stage of current interruption enclosure).....Minimization of size
Arcing contact Puffer cylinder All contacts (DS, HS-ES, M-ES) are straight moving
Puffer piston type with proper wipe
Nozzle
.....Simplification of arrangement, long life
Arcing contact

Moving contact of ES

Earthing switch Maintenance


(HS-ES) earthing switch
(M-ES)

(B) Final stage of current interruption Exhaust hole Disconnector

Design phyrosophy for interrupting chanber

Effective arc energy transfer to pressure rise

Fixed contact of DS Driving rod of DS


Optimum puffer cylinder dimensions

Insulating Moving contact of DS


spacer
Reduce the driving energy

Closing Resistor of GCB GIS with Long Busbar


Resistor : 400600 Long busbar is used
considering displacement
of foundation and
Closing
resistor thermal expansion

Arcing contact Closing contact

YACYRETA P/S (Argentina)


Total length of busber:
Closing resistor Closing contact Approx.700m
Typical Arrangement

, ,
B g B g

12000
VT

VT HS-ES

DS
HS-ES/
ES
DS/ES
BUSBAR2 BUSBAR1
CT

GCB

6500
CT
CT
ES CT
00
55

DS DS
ES
Width of a bay GCB DS
DS

Double Busbar System BUSBAR1

BUSBAR2

28000 28000

,
B g

BUSBAR1

DS
BUSBAR1 HS-ES ES
CT
DS
GCB

CT
ES ES
DS

DS
LCP BUSBAR2 ES
CT

GCB

CT
ES
DS
28000 28000
DS
ES ES
CT
DS/ES/HS-ES
DS GCB
DS/ES BUSBAR2
CT
BUSBAR1 HS-ES
6700

ES
CT CT DS

BUSBAR2
GCB ,
B g
26400

One and a half Circuit Breaker System Single Line Diagram

Industrial and Power Systems & Services Company


1-1, Shibaura 1-chome, Minato-ku, Tokyo 105-8001, Japan
Tel. +81-3-3457-3759 Fax. +81-3-5444-9169

The data given in this catalog are subject to change without notice. 5404-1 '06-02T1