Al-Rada Engineering Oo. WLLL,
M/S: General Administration of Civil Defense Date 15/01/2017
Fire Prevention Deprt ment.
Project Name: AL KHOR ACCOMMODATION G+3 floor Building 2
; Location UM BERKA , Doha, Qatar
Owner : KHALID CEMENT COMPLEX W.LL.
Consultant: CEC
CCD File No.
Subject : HYDROSTATIC TEST
HYDROSTATIC test prior tested by : Al Roda Engineering Services
Wet System Type Size | Test pressure | Test time | Test passing | Remarks
FIRE HOSE REEL ae 200Psi__| 2HOURS YES oa
MAIN PIPE 4" 2o0rsi | 2HOURS Yes =
SUB MAIN PIPE 2" 200Psi | 2HOURS YES =
Notes:-
* Test Pressure Should Be 200 Psi or 50 Psi Above Normal Pressure If
Normal Pressure Exceeds 150 Psi
* The Min Flow Should Be 750 GPM 160 PSI Residual Pressure For Class 1
or 111 Systems and 100 GPM at 65 Psi For Class 11 System .
* At this Pressure a close inspection done in all grooved joints and highiy
stressed parts . And the hydrostatic test results are acceptable that there is
no leak in the pressure boundary of the system .
* There are no Defect found during the test .