peo eotogell Guwaia ap Al-Rada Engineering Oo. WLLL, M/S: General Administration of Civil Defense Date 15/01/2017 Fire Prevention Deprt ment. Project Name: AL KHOR ACCOMMODATION G+3 floor Building 2 ; Location UM BERKA , Doha, Qatar Owner : KHALID CEMENT COMPLEX W.LL. Consultant: CEC CCD File No. Subject : HYDROSTATIC TEST HYDROSTATIC test prior tested by : Al Roda Engineering Services Wet System Type Size | Test pressure | Test time | Test passing | Remarks FIRE HOSE REEL ae 200Psi__| 2HOURS YES oa MAIN PIPE 4" 2o0rsi | 2HOURS Yes = SUB MAIN PIPE 2" 200Psi | 2HOURS YES = Notes:- * Test Pressure Should Be 200 Psi or 50 Psi Above Normal Pressure If Normal Pressure Exceeds 150 Psi * The Min Flow Should Be 750 GPM 160 PSI Residual Pressure For Class 1 or 111 Systems and 100 GPM at 65 Psi For Class 11 System . * At this Pressure a close inspection done in all grooved joints and highiy stressed parts . And the hydrostatic test results are acceptable that there is no leak in the pressure boundary of the system . * There are no Defect found during the test . gla = Aa gill - WVAEN : ogge = VEPOAL Giga = OOO VINT : Sige = EEMANVTTY « uSlB- ££01 0081: paul Tel : 44510543 - Fax : 44681731 - Mob : 55501162 - C.R :14358 - P.O.Box : 17841 - Doha -Qatar