Escolar Documentos
Profissional Documentos
Cultura Documentos
bbranch switching
D.C. Pinhheiro, and C.A Castro, Senior Member, IEEE
University of Campinas (UNICAMP)
Campinas, Brazil
dpinhheir@dsee.fee.unicamp.br, ccastro@ieee.org
Abstract This paper aims to contribute to the development of best control variables to be used. Another
A approach is based
methods for alleviating overloads in the traansmission system. on the application of linear or nonlinear programming, as in
Among the several possible alternatives to achieve this goal, [3]-[4]. In [5], generation redispattch and/or load shedding
branch (transmission lines and transformers)) switching will be were used to decrease line currents based on sensitivity
the focus in this work. Even though this p possibility is well-
factors. In [3] the idea of local optimization (LO) was
known, a very interesting branch switch hing method was
proposed recently in the literature to identtify the candidate introduced. A fixed sized region (n named working region) in
branches to be switched. In this work the iidea is to propose the neighborhood of the overload ded branch is previously
improvements to this method in such a way itt becomes efficient defined and corrective control action ns are defined within this
enough to be used in real time monitorring and control region. Recently, the utilization of diistribution factors (derived
environments. Those improvements are b based on specific from sensitivity analysis) along witth a very simple and fast
calculation techniques and information aboout the nature of technique to identify the candidate branches to be switched
power systems operation. was proposed [6].
Index Terms -- Power system security analyysis, power system
operation, violations elimination, DC Power fl
flow, overload, line
outage.
I. INTRODUCTION
where | is the distribution factor (senssitivity factor that Fig. 2. Physical interpretation of corollary I:I reciprocity in power flow ( )
relates the power flow change in b and the ooutage of a), is variation in branches verified by sensitivity an
nalysis.
the power flow through a before its outage, aand , , are the Based on this corollary, the prooposed algorithm will be
reactances of branches a and b respectively. AAlso described ahead, along with the swittching strategies in case of
, (3) line overloads.
where is a n-element vector with alll zeroes but the III. ADAPTIVE LOCAL SEARCH AND HEURISTIC RULES
terminal buses of branch a, which are equual to 1 and 1.
Finally, In general, the consequences of a topological change in a
large system are restricted to a relativ
vely small area around the
, (4) change itself. It has already been observed in practice that the
further the control variable is from the overloaded branch, the
where is a n-element vector with alll zeroes but the
smaller the sensitivity between them m will be. Fig. 3 shows this
terminal buses of branch b, which are equal to 1 and 1. Eqs.
situation, where the sensitivity of a control
c variable from area
[2]-[4] are very well-known [1].
A1 to overloaded branch (OV) iss larger than of control
In [6], rather than considering the effectss of the outage of
variables in area A2, and so on. Theerefore, the inclusion of a
branch a over the remaining branches, the iidea is to evaluate
local search procedure in an allgorithm for eliminating
the possibility of eliminating the overload aat a by switching
overloads results in precise and more efficient results,
off other branches. Let b|a the power flow tthrough branch b
especially for large systems.
after the outage of a, and a|b the power floow through a after
the outage of b. These power flows are givenn by
b|a = + | (5)
and
a|b = + | . (6)
The following theorem [6]-[10] suggestss an algorithm for
eliminating the overload at branch a.
Theorem: Given a power system modeled by the linearized
load flow, | | > 0 always hold. Fig. 3. Sensitivity levels of control variables to overloaded branch OV: large
When a is outaged, the power flow variaation in b is given (A1); moderate (A2); small (A3).
by
Besides, it is important that thee new operating point be
| | (7) obtained by the least amount forr control changes in the
neighborhood of the overloaded branch. In this sense, the
Similarly, when b is outaged, the power flow in a is given concept of local optimization intro oduced here is extremely
by relevant, with the objective of findin ng close control variables
that result in smaller topological chan
nges as possible.
In addition to the local search procedure, heuristic rules E C EC
(11)
have also been applied seeking the selection of control O R P %
variable candidates that provide the largest overload relief,
with the least changes in the systems operating state, where
avoiding undesirable side effects such as new overloads. R (cost-benefit relationship): cost associated to power flow
increase in neighbor branches of the candidate branch (to be
IV. PROPOSED ALGORITHM switched off) and benefit associated to the relief of
Fig. 4 shows a flowchart with the basic steps of the overloaded branch OV.
proposed switching algorithm. EC (estimated changes in the operating condition): refers to
the undesired power flow increase in the neighbor branches of
the candidate branch. These power flow increases are
estimated by equations similar to (8), applied to the neighbor
branches. The values of EC are actually weighted averages
resulting from the estimated power flow variations in the
region around the candidate branch. Table I shows the criteria
and respective weights adopted in this work.
V. SIMULATION RESULTTS
The algorithm was implemented with MA
ATLAB using the
load flow from MATPOWER [11]. The simuulations presented Fig. 5. One line diagram of the 30-bus sysstem: (OV) overloaded branch;
here involve: (BC) candidate branches for switching. BC*
* is the branch recommended to
be switched off. (adapted from [12]).
The application of sensitivity analyysis to the 30-bus
system [12], and The process is initiated by runn ning a load flow and all
The application of the proposed alggorithm to the full power flows are determined. Then, thet overload of branch 6-8
interconnected Brazilian power syystem with 4,526 is detected ( ). Sensitivity analysis is used to determine
buses [13]. for all other branches of the system m. Finally, the condition
. 0 defines the candidate brranches to be switched off
A. 30-bus system - Sensitivity analysis to alleviate overload OV.
By applying this procedure to the 30-bus system, six
The simulation presented here aims to cclarify the process branches were identified as candid dates to be switched off.
of searching for candidate branches, which is the basis for the Table III shows the results of thiis search. The rightmost
algorithm proposed in this paper. column shows the estimated pow wer flow change at the
The data from this system can be oobtained in [12]. overloaded branch 6-8 for each switcching.
Overload at branch 6-8 was defined as shownn in Table II.
TABLE III: SEARCH FOR CANDIDATE BRAN
NCHES (POWER FLOWS IN MW)
20
TABLE VI: OVERLOAD AT THE SIN
Overloaded From To Branch Rated Amount of
branch bus bus flow limit Overload
Pow er flow [M W ]
15
Branch 150 134 396 251MW 239MW 12 MW
10
The one-line diagram shown in Fig. 8 illustrates the details
of the overloaded branch (OV) as well as its neighborhood.
The figure also shows the candidate branches (BC) to be
5
switched off.
0
6- 8 6- 9 9-10 28-27 6-28
Branch
Fig. 6. Switching of branch (24-25) eliminates the overload of (6-8) but
results in new overloads at (6-9), (9-10), (28-27), and (6-28).
VII. REFERENCES
[1] A.J. Wood, B.F. Wollenberg, Power generation, operation and control,
John Willey and Sons, 1984.
[2] C.A. Castro, A. Bose, Correctability of voltage violations in on-line
contingency analisys, IEEE Transactions on Power Systems, vol.9, n.3,
pp. 16511657, 1994.
[3] A. Shandilya, H. Gupta, J. Sharma, Method for generation rescheduling
and load shedding to alleviate line overloads using local optimization,
IEE Proceedings C, vol.140, n.5, pp. 337342, 1993.
[4] H.D. Abrantes, C.A. Castro, A new efficient nonlinear programming
based method for branch overload elimination, Controle & Automao,
vol.14, n.1, pp. 7683, 2003.
[5] T.K.P. Medicherla, R. Billinton, M.S. Sachadev, Generation
rescheduling and load shedding to alleviate line overloads, IEEE
Transactions on Power Apparatus and Systems, vol.98, n.6, pp. 1876
1884, 1979.
[6] H. Zhang, B. Gou, A new algorithm of corrective control to relieve
overloads, IEEE PES General Meeting, San Diego, CA, USA, 2012.
Fig. 9. Power flows through branch (134-396) before and after the switching [7] Energy Expansion Decennial Plan 2023 / Ministry of Mines and
of candidate branch (213-216). Energy. EPE, Braslia: MME/EPE, 2013 (in Portuguese).
[8] E.B. Makram, K.P. Thornton, H.E. Brown, Selection of lines to be
Additionally to Fig. 9, Table VIII shows the main switched to eliminate overloaded lines using a Z-matrix method, IEEE
information on the operation of branch (134-396) after the Transactions on Power Systems, vol.4, pp. 653661, 1989.
[9] A.J. Monticelli, Load flow in electric energy networks, Edgard Blcher,
control action. 1983. (in Portuguese)
[10] H. Zhang, B. Gou, A Fast Online Corrective Control Strategy for
TABLE VIII: POWER FLOW RESULTS AFTER THE SWITCHING OF Relieving Overloads, published in IET Generation, Transmission &
CANDIDATE BRANCH (213-216) Distribution, 2013.
[11] R.D. Zimmerman, C.E. Murillo-Snchez, R.J. Thomas, MATPOWER:
Overloaded From To Branch Rated Security Steady-State Operations, Planning and Analysis Tools for Power
branch bus bus flow limit Margin Systems Research and Education, IEEE Transactions on Power
150 134 396 238MW 239MW 1MW Systems, vol. 26, no. 1, pp. 12-19, Feb. 2011.
[12] O. Alsac, B. Stott, Optimal Load Flow with Steady State Security,
VI. CONCLUSIONS IEEE Transactions on Power Apparatus and Systems, Vol. PAS 93, No.
3,1974, pp. 745-751.
This paper presented a procedure for the elimination of [13] Brazilian ISO (ONS - Operador Nacional do Sistema Eltrico),
available on http://www.ons.org.br/.
overloads in transmission systems based on branch switching [14] Wei Shao, Vijay Vittal, A New Algorithm for Relieving Overloads and
defined by sensitivity analysis. The overload elimination is Voltage Violations by Transmission Line and Bus-bar Switching,
achieved without the need of expensive control actions as Proceedings of Power System Conference & Exposition, NY, 2004.