1.

11000/433 Volt oil immersed outdoor copper wound distribution transformer having vector
group Dyn11 with
2.5 % Off circuit tap changer (OCTC).
2. Voltage Ratio: No load voltage 11000/433 volts within tolerance as stipulated in IS: 2026.
3. System: 11000 volts A.C.,50 Hz supply having non effectively earthed neutral(resistively
earthed) system on HV side/ The 11kV systems shall have basic insulation level of 28 kV for
one minute/95 kVp impulse. 433 volts A.C,50 Hz supply shall be rated for 1.1 kV grade and
basic insulation of 3 kV for one minute and 7,5 kVp impulse.
4. Temperature Rise: The maximum temperature rise at the specified maximum continuous
output shall not exceed 35 degree C by thermometer in the hottest portion of the oil or 40
degree C measured by resistance of winding above ambient temperature of 50 degree C.
Temperature rise test to be performed in any one supplied transformer in presence of
representative of Sr.Mgr[EM-OPH],SgTPP,WBPDCL.
5. Connections: H.V Delta and L.V Star connected with neutral brought out on the secondary
side for connection to earth Vector group Dyn11 of IS: 2026.
6. Guarantee: All transformers shall be supplied with guarantee period of 3 years from date of
commissioning of transformer. Any deficiency during guarantee period will be made up free of
cost by the supplier either by the replacement or by repairs.
7. Cable End Boxes : The transformer shall be fitted with suitable end termination boxes on 11
kV side to terminate one 11 kV/ 3 core Aluminum conductor XLPE/PILC cable up to 300 mm2.
The transformer shall be fitted with suitable LV cable end .
Secondary: Terminals shall be provided with 1.1 kV Epoxy bushings as per IS: 3347 for heavily
polluted atmosphere having fixed palm type connectors with suitable locking arrangement to
restrict the rotation of palm assembly.
8. 9.2 Leakage of Oil: Suitable approved material Neoprene of RC 70 C grade as specified in
IS: 1866 shall be provided at all joints to prevent leakage of oil during continuous operation of
the transformer.
9. Insulation level: The transformer shall be designed to withstand the following.

Voltage Impulse Voltage(kVP) Power Frequency Voltage (kV)


11000 95 28
415 7.5 3
10. Transformer shall be designed for 11 kV non effectively earthed system.
11. Details of transformer shall be furnished in Data sheet by the bidders along with offer.
12. Transformer to be supplied within 14 weeks after approval of drawing and data sheet.
13. Oil Level gauge to have 03 marking, minimum, normal and maximum.
14. Thermometer to be fitted in thermometer pocket and to be supplied with transformers.
15. Off circuit Tap changer(OCTC) to have pad locking facility.
16. HT bushing supply to include all necessary fittings.
17. Supplied LV bushing metal parts to have integral palm connectors.
18. Rating and diagram plate drawing to be furnished.