Escolar Documentos
Profissional Documentos
Cultura Documentos
K Y Yow
Director, Technical Center of Excellence
HVAC & Transport , Climate Sector
API , Ingersoll Rand
Energy efficient HVAC
systems are the key
Every Building can be a High Performance Building
Tracer Summit
VPF CTO
Chiller KWI
lvg condenser water
pressure
KWI reduces if LIFT
Compressor
CHW reset higher ?
Reduce Tower temp ? Evaporator
VSD 3
pumps
DP
(typical)
Tracer Summit
propeller fan
louvers
outdoor air fill
Tracer Summit
Fan Laws: sump
Cfm a rpm
Strategies
Dp a rpm VSD control ( tower optimisation)
a cfm Select Smaller Tower ( retrofit)
=> Lower CFM/CMH
Hp a rpm VPF => Smaller Motor HP
Good maintenance practice
100% Flow
GPM reduction of 37.6%
#
Interactions amongst the Components-
Opportunities of Trade-offs.
KWI
Strategies Chiller Evp Pump Cds Pump C/Tower Cost
Tracer Summit
(Low Flow)
Tower
Pumps Trane Optimisation
EARTHWISE
SYSTEM
CTO
VPF Cooling Tower
(Var Pri Flow)
VPF
scroll
<75 tons
4.0
reciprocating
<125 tons
2.0
0.0
ASHRAE Standard 90 best
90-75 90-75 90.1-89 90.1-99 90.1-2010 available
(1977) (1980)
#
Low Flow Design
Capacity Expansion
Electrical Load
#
Scenario of Retrofit Challenge
Situation
Chiller needs to be
replaced
Cooling needs have
increased by 50%
Cooling tower and
pipes were replaced
two years ago
Pipes run under the
parking lot and
nobody wants to dig
them up!
#
Power of Low Flow Design
- Upgrading Existing Plant
Present facility Desired facility
2,000 RT 3,000 RT(50% More)
Chilled water: 6.7C ; 5.6C T
4,800 gpm (302 L/S) Solution ?
#
Power of Low Flow Design
- Upgrading Existing Plant
Present facility Desired facility Low Temp
2,000 tons 3,000 tons Low Flow
#
Use the existing infrastructure
to satisfy new requirements
Use existing
Use existing Pipe Coils
Evap
Lo Flow/ Lo Temp
Use existing
Use existing Cooling Towers
Cond pumps
Lo Flow/ Hi Temp
#
Case Study
Location: SINGAPORE
Building type: Office, no economizer
Peak cooling load: 1500tons (5275kw), 2 x 750
ton chiller in plant
Cooling tower: Fan with VSD,12ft (3.7m)
static lift
System: Variable primary chilled
water flow in parallel
configuration and constant
condenser flow
#
Three alternatives
CHW
6.67/12.2C(44/55F) 6.67/12.2C(44/55F) 6.67/12.2C(44/55F)
(Chilled
CHWP: 30m (100ft) CHWP: 30m(100ft) CHWP: 30m (100ft)
water)
CNW
32/37C (89.6/98.6F) 32/40C (89.6/104F) 31/39C(86.9/101.3F)
(Condenser
CNP: 23m(75ft) CNP: 12m(40ft) CNP: 12m (40ft)
water)
Notes:
1. Same chillers are used in all alternatives
#
Low Flow Condenser system:
System KWI comparison
Conventional Green 1 Green 2
Alt 1 (6.67/12.2C, 32/37C) Alt 2 (6.67/12.2C, 32/40C) Alt 3 (6.67/12.2C, 31/39C)
867kw 828kw
798kw
44kw 74kw
74kw
CT Kw 74 44 74
CNW pump Kw 92 30 30
CHW pump Kw 85 85 85
Best , how about annualised Kwh?
#
Annualised KWH
Conventional 1,553,994
Green 1
Winner (smaller CT) 1,443,325 7.1 % 110,669
Condenser
Water Temp Chiller kW Tower kW Total kW
?
?
#
Chiller Tower
Optimsiaiton
350 Total
300
Chiller
250
Optimal Pt Chiller kW
200
Tower kW
150 Total kW
kW
100
50 Tower
0
72 73 74 75 76 77 78 79 80 81 82 83 84 85
( 22.5 C) Condenser Water Temperature ( 29.5 C)
#
Variable Primary Flow
#
Variable Primary Flow
1 1
2 2
3 VSD 3
pumps
Constant speed DP
(typical)
primary pumps
Bypass (decoupler)
VS secondary
pumps
DP
Placeholder for
Manifolded P-S
System picture (Beth
T to supply)
#
Variable Primary Flow
#
Low PD piping
Conventional
No Balancing
valves
15 HP pump
Raised Foundation
for pumps
#
System Controls Optimization
System Controls
Pump pressure
optimization
Chiller Sequencing
Chiller-tower optimization
# of towers to operate
Variable Primary flow
tube
bundle