Você está na página 1de 42

RAC-2000PS

Two Door Control Panel


Hardware Manual
Version 1.21
Table of Contents

Chapter 1 Product Overview ...........................................................................................3


1.1 Package Contents................................................................................................3
1.2 Features...............................................................................................................4
1.3 Specifications.......................................................................................................5
Chapter 2 Physical Dimensions ......................................................................................6
2.1 Appearance..........................................................................................................6
2.1.1 Front ............................................................................................................6
2.2 Dimensions ..........................................................................................................6
2.2.1 Front / Lateral ..............................................................................................6
2.3 Board Layout........................................................................................................7
Chapter 3 System Configuration and Terminal Introduction............................................8
3.1 System Configuration...........................................................................................8
3.2 RAC-2000PS Terminal Introduction.....................................................................9
3.2.1 Controller Terminal Introduction ..................................................................9
Chapter 4 Installation ....................................................................................................11
4.1 Hardware Setup .................................................................................................11
4.1.1 Metal Housing Setup .................................................................................11
4.1.2 Control Panel Setup ..................................................................................12
4.2 Reader Setup.....................................................................................................13
4.3 Electronic Lock Setup ........................................................................................14
4.3.1 NO Mode Connection ................................................................................14
4.3.2 NC Mode Connection ................................................................................15
4.3.3 Magnetic Door Lock Connection................................................................16
4.4 Chime Bell / Alarm Connection ..........................................................................17
4.4.1 DI Input Connection ...................................................................................17
4.4.2 Relay Output Connection...........................................................................18
4.5 Communication Interface Setup.........................................................................19
4.5.1 RS-232 connection ....................................................................................19
4.5.2 RS-485 connection ....................................................................................20
4.5.3 Communication Converter Setup...............................................................20
4.6 Push Button Connection ....................................................................................21
4.7 Door Sensor Connection....................................................................................22
4.8 Power Supply Setup ..........................................................................................23
Chapter 5 Configuration ................................................................................................24

HUNDURE 1 RAC-2000PS Hardware Manual


5.1 Set NODE ID......................................................................................................24
5.2 RS-232 / RS-485 Selection (to PC)....................................................................26
5.3 Reader Power Configuration..............................................................................27
5.4 Relay NO / NC Output Configuration .................................................................28
5.5 Operation Setup.................................................................................................29
5.5.1 Function key 00 Change NODE ID............................................................30
5.5.2 Function key 01 Emergency Exit Control...................................................30
5.5.3 Function key 02 Create Single Temporary Card/ Valid Card .....................31
5.5.4 Function key 03 Delete Single Temporary Card / Valid Card ....................32
5.5.5 Function key 05 Delete All Cards ..............................................................32
5.5.6 Function key 10 Change MASTER CODE.................................................33
5.5.7 Function key 99 System Initialization.........................................................33
Chapter 6 Testing..........................................................................................................34
Chapter 7 Troubleshooting............................................................................................35
Chapter 8 Appendices...................................................................................................38
8.1 Appendix 1 (Wiring Material Requirements) ......................................................38
8.2 Appendix 2 (DIP Switch Setting) ........................................................................39

Rev. History
Ver. Revisions
V1.0 Initial Release
V1.1 Manual format revision
V1.2 Modify 1.14.1Chapter 6
V1.21 Modify 1.2 Features

HUNDURE 2 RAC-2000PS Hardware Manual


Chapter 1 Product Overview

Thank you for purchasing this high quality Two Door Control Panel & LCD Display
Reader.

Adopting a separated controller and reader design, RAC-2000PS is a truly dependable,


flexible access control solution with real time on site or remote operation, event
recording, programmable duress, multiple access modes, anti pass back functions for
entrance security. RAC-2000PS can support max. up to 15,000 card holders and can
connect 4 RS-485 readers. Operated with eNitor Management Software, RAC-2000PS
is your ideal solution for residential zone, hospital, warehouse, airport, offices, factories,
university, campus, and parking lot barrier etc. access control.

1.1 Package Contents

When you unpack your new RAC-2000PS, Two Door Control Panel & LCD Display
Reader, please make sure that all of the following items are included and are not
damaged.

Controller x 1 Quick Start Guide x 1

If any of the following items are missing or damaged, please contact your dealer
immediately.

HUNDURE 3 RAC-2000PS Hardware Manual


1.2 Features

z Control panel holder & block terminal ensure easy installation & easy
maintenance
z Provide RS232/RS485 communication interface to PC.(Able to expandable to
255 sets by RS485 interface)
z Controller and reader separate design, maximum controls 4 RS-485 Readers (2
IN / 2 OUT for 2 doors or reader IN, exit button for OUT of single door)
z Provides optical coupled isolated sensors for door sensor, exit button and reader
tamper
z Provide 2 relay outputs for electronic lock and alarm
z Stores maximum 15,000 cardholders/events
z Provide 128 time zones and schedules, 8 time conditional unlock door
schedules, 100 holiday schedules per year (Able input date through software)
z Provides blacklist and 50 sets visitor card with configurable check digits, duration,
usage time & frequency.
z Anti-passback and Duress card/code setting. When door opened in the
emergency, controller will send signal to control center at the same time for
tracing and rescue.
z Door sensor detection time function. The alarms will activation when door unlock
over detection time setting.
z ESD / Surge protection design to protect devices & enhance communication
quality.
z RTC (Real Time Clock) and Watchdog function ensures accurate date/time and
system free from halting
z Support connects external PSU-330 Uninterrupted power supply, ensure the
operation during power outages.

HUNDURE 4 RAC-2000PS Hardware Manual


1.3 Specifications

Model RAC-2000PS

Processor 8 Bit

Memory 256K

8 sensor
Input Ports
( Door Sensor x 2Exit Button x 2Case Sensor x 4 )

Output Ports 4 Relay ( Electronic Lock x 2Alarm x 2 )

Cardholders/Events 15,000 (max.)

LED Indicator Power / Output Status / Comm.

RTC Yes

ID Setting DIP switch setting

Reader Ports RS-485

Output Voltage DC 12V / 1A (excluding slave reader)

Operating Voltage 500mA (excluding slave reader)

Comm. Interface RS-232 / RS-485

Comm. Baudrate 9,600 / 19,200 / 38,400 bps-N-8-1

Operating Temp. -10~ 55 / 14~ 131

Relative Humidity 20% ~ 80% (Non-condensing)

Dimensions 210mm(L) x 150mm(W) x 29mm(H)

Weight(Device) 528g

HUNDURE 5 RAC-2000PS Hardware Manual


Chapter 2 Physical Dimensions

2.1 Appearance

2.1.1 Front

2.2 Dimensions

2.2.1 Front / Lateral

Scale: mm

HUNDURE 6 RAC-2000PS Hardware Manual


2.3 Board Layout

1 JP1-9 RS-485 / RS-232 Mode Selection

2 LED1 Communication LED for computer

3 SW1 RS-485 Reader Communication LED

4 LED4 Reset Button

5 SW2 Power LED


JP14-17
6 Node ID Configuration Switch
LED5-8
7 JP11 Relay NO/NC Selection. Relay Activation LED

8 JP12 Hardware initialization selection

9 JP13 Reserved

10 Reader Communication LED

HUNDURE 7 RAC-2000PS Hardware Manual


Chapter 3 System Configuration and Terminal Introduction

3.1 System Configuration

HUNDURE 8 RAC-2000PS Hardware Manual


3.2 RAC-2000PS Terminal Introduction

3.2.1 Controller Terminal Introduction

A1-A18 Reserved
A19 485+ RS-485 + or RS-232 TXD to PC
A20 485- RS-485 or RS-232 RXD to PC
A21 GND Ground Connection
A22-A24 Reserved
A25 TXD2 RS-485+ to Reader
A26 RXD2 RS-485- to Reader

B1 FG Frame Ground
B2 GND DC12V ground input
B3 +12V DC +12V Input

HUNDURE 9 RAC-2000PS Hardware Manual


B4 DOOR1+
Door 1 Electronic Lock Relay Output (Dry contact)
B5 DOOR1-
B6 ALARM1+
Door 1 Alarm Relay Output (Dry contact)
B7 ALARM1-
B8 DOOR2+
Door 2 Electronic Lock Relay Output (Dry contact)
B9 DOOR2-
B10 ALARM2+
Door 2 Alarm Relay Output (Dry contact)
B11 ALARM2-
B12 PUSH1 Door 1 Exit Button Input
B13 GND Ground Connection
B14 PUSH2 Door 2 Exit Button Input
B15 SENSOR1 Door 1 Sensor Input
B16 GND Ground Connection
B17 SENSOR2 Door 2 Sensor Input
B18-B23 Reserved

Note:
z The reader required to use a separate power supply to prevent power
degradation due to long transmission distance and ensure readers normal
operation.
z For optimum read range, kindly use DC Linear power for the readers power
supply.
z Please add an isolator with proper thickness on the back of the reader if you are
to install it onto a metallic object to prevent interference.
z The distance between 2 readers should be 1.5 times the read range to prevent
radio frequency interference from each other.
z TXD2 and RXD2 are designated for RAC-2000PS compatible readers; kindly
use a 20AWG aluminum foiled-double shielded twisted pair cable.
z NODE ID 1 and 2 is allocated for Door 1 while NODE ID 3 and 4 is for Door 2.

HUNDURE 10 RAC-2000PS Hardware Manual


Chapter 4 Installation

4.1 Hardware Setup

4.1.1 Metal Housing Setup

1. Install the control panel backer to the metal rail. Install the notch of backer to the
protruding of the metal rail (Indicator 1).
2. Press the backer (Indicator 2) slightly to install the control panel to the metal rail.
3. To dismount the control panel from the metal rail, press the orange button (No. 3) on top
of the backer.
4. To remove the control panel from the metal rail, please gently push and pull the backer.
(Indicator 4).
5. Take out the backer (Indicator 5), the control panel can be detached successfully.

HUNDURE 11 RAC-2000PS Hardware Manual


4.1.2 Control Panel Setup

There are two installation ways:


(A). 1. Install the control panel on the wall or suitable
locations with screws.
2. Install the control panel on the metal rail.
(B). Fix metal rail on the wall with screws. (Optional)
(C). Press the orange button on top of control panel
(D). (E) Put control panel on the metal rail

HUNDURE 12 RAC-2000PS Hardware Manual


4.2 Reader Setup

RS-485 Reader Connection

HUNDURE 13 RAC-2000PS Hardware Manual


4.3 Electronic Lock Setup

4.3.1 NO Mode Connection

Note: Please refer to Appendix 1 of Chapter 8 for the requirements of all wiring
materials.

HUNDURE 14 RAC-2000PS Hardware Manual


4.3.2 NC Mode Connection

Note: Please refer to Appendix 1 of Chapter 8 for the requirements of all wiring
materials.

HUNDURE 15 RAC-2000PS Hardware Manual


4.3.3 Magnetic Door Lock Connection

Note: Please refer to Appendix 1 of Chapter 8 for the requirements of all wiring
materials.

HUNDURE 16 RAC-2000PS Hardware Manual


4.4 Chime Bell / Alarm Connection

4.4.1 DI Input Connection

SENSOR2

SENSOR1

PUSH2

PUSH1
CASE4

CASE3

CASE2

CASE1
GND

GND

GND

GND
HUNDURE

HUNDURE

HUNDURE

HUNDURE

HUNDURE 17 RAC-2000PS Hardware Manual


4.4.2 Relay Output Connection

HUNDURE 18 RAC-2000PS Hardware Manual


4.5 Communication Interface Setup

4.5.1 RS-232 connection

HUNDURE 19 RAC-2000PS Hardware Manual


4.5.2 RS-485 connection

4.5.3 Communication Converter Setup

HUNDURE 20 RAC-2000PS Hardware Manual


4.6 Push Button Connection

HUNDURE 21 RAC-2000PS Hardware Manual


4.7 Door Sensor Connection

HUNDURE 22 RAC-2000PS Hardware Manual


4.8 Power Supply Setup

HUNDURE 23 RAC-2000PS Hardware Manual


Chapter 5 Configuration

5.1 Set NODE ID

* Controller ID Configuration

ID NO. 1=ON 0=OFF


NODE ID Switch
ON
ON
Black is DIP 001
1 2 3 4 5 6 7 8
Switchs
location 002
1 2 3 4 5 6 7 8 003
0 1 2 3 4 5 6 7
Binary 2 + 2 + 2 + 2+2+2+2+2 004
Decimal 1 + 2 + 4 + 8 + 16 + 32 + 64 + 128 005
1. DIP Switch counting is base on binary. 006
2. Up is meaning " ON ( 1 ) . Down is meaning " OFF ( 0 ) .
007
3. Kindly refer to above figure to understand how to counting the device
ID. 008
4. Above figure is show how to counting ID 5. Decimal of first place is 1, 009
third place is 4, so total will be 5.
010
5. For NODE ID 001 ~ 010, please refer to left side form. For more
Node ID information, kindly refer to appendix.
Kindly refer to appendix.

z NODE ID should be set within the range 0255. NODE ID set as 0 stands for
allowing reader to set NODE ID.

z The following is the quick configuration list of NODE ID:031, for NODE ID after
31, please refer to Appendix 2 of Chapter 8.

HUNDURE 24 RAC-2000PS Hardware Manual


NODE ID: 0~31 Quick Configuration List (Condition ON=, OFF=)

SW Configuration SW Configuration
ID No. ID No.
1~8 1~8

0 00000000 16 00001000

1 10000000 17 10001000

2 01000000 18 01001000

3 11000000 19 11001000

4 00100000 20 00101000

5 10100000 21 10101000

6 01100000 22 01101000

7 11100000 23 11101000

8 00010000 24 00011000

9 10010000 25 10011000

10 01010000 26 01011000

11 11010000 27 11011000

12 00110000 28 00111000

13 10110000 29 10111000

14 01110000 30 01111000

15 11110000 31 11111000

Note: For NODE ID : 0 ~ 255 configuration, please refer to Appendix 2 of Chapter 8.

HUNDURE 25 RAC-2000PS Hardware Manual


5.2 RS-232 / RS-485 Selection (to PC)

z For RS-232 communication, please set JUMPER on RS-232 position.


z For RS-485 communication, please set JUMPER on RS-485 position

HUNDURE 26 RAC-2000PS Hardware Manual


5.3 Reader Power Configuration

z Set jumper JP11 to +12V for connection of +12V readers.


z Set jumper JP11 to +5V for connection of +5V readers.

NOTEThe readers power supply is provided by the control panels power supply. A
reader consumes averagely 200Ma power (please refer to the readers
specification.) Supply of power should increase with respect to transmission
distance and the numbers of readers installed. It is recommended to provide
a separate power supply for the reader. When the reader uses a separate
power supply, make sure the ground is connected with the control panel.

HUNDURE 27 RAC-2000PS Hardware Manual


5.4 Relay NO / NC Output Configuration

z Set jumper to NO for connection of:


1.Electric Bolt Lock
2.Alarm output
z Set jumper to NC for connection of:
1.Electric strikes
2.Electromagnetic Lock
z Default connection is NO.

HUNDURE 28 RAC-2000PS Hardware Manual


5.5 Operation Setup

Function Key Description


Change ID (DIP Switch node ID is set to 0)

Emergency Exit Control

Create temporary card number/ Create valid card number

Delete temporary card number/ Delete valid card number

Delete all cards

Change Master Code

System initialization

z Use reader with keypads for function key input.


z Please enter Master Code for configuration mode (default: 30191000).
z The OK LED on reader blinks, waiting for function key inputs. After function key
inputs, OK LED will be lit continuously (except for key 01 and 05).
z Function key 05 will delete all card numbers. Please be careful when using this
function.
z Function key 10 is for changing Master Code, the system will use the new Master
Code.
z Follow commends only support connecting with Hundure reader.
z RAC-2000PS will resume to ready status when idling for 30 seconds during
operation.

HUNDURE 29 RAC-2000PS Hardware Manual


5.5.1 Function key 00 Change NODE ID

No. Description
1 Ready mode, the red LED of reader is lit.

2 Enter Default Master Code : 30191000(Enter  )

3 The green LED of reader blinks.

4 Enter 00 (Enter  )

5 Green LED of reader is lit continuously.

6 Enter NODE ID, the range is 1~255 (Enter  )

7 Green LED of reader goes off. Red LED blinks and beeps four times.

8 RAC-2000P/PV/G automatically restarts and red LED of reader is lit.


z Set DIP Switch NODE ID as 0, or this function will not activate.

5.5.2 Function key 01 Emergency Exit Control

No. Description

1 Ready mode, the red LED of reader is lit.

2 Enter Default Master Code : 30191000(Enter  )

3 The green LED of reader blinks.

4 Enter 01 (Enter (  ), reader beeps twice and the door opens.

5 RAC-2000P/PV/G automatically restarts and red LED of reader is lit.

HUNDURE 30 RAC-2000PS Hardware Manual


5.5.3 Function key 02 Create Single Temporary Card/ Valid Card

No. Description

1 Ready mode, the red LED of reader is lit.

2 Enter Default Master Code : 30191000(Enter  )

3 The green LED of reader blinks.

4 Enter 02 (Enter  )

5 Green LED of reader is lit continuously.

Method 1: Swipe the card to create card number.


6
Method 2: Enter the card number to add the new card.

7 Reader beeps once and green LED blinks.

Enter  to return to ready mode or go to item 4 to add another


8
card.

z Function key (02) can add only one card each time. To add another record, repeat
the same procedure.
z For card number and pin code entry mode, application software setting is required.

HUNDURE 31 RAC-2000PS Hardware Manual


5.5.4 Function key 03 Delete Single Temporary Card / Valid Card

No. Description

1 Ready mode, the red LED of reader is lit.

2 Enter Default Master Code : 30191000(Enter  )

3 The green LED of reader blinks.

4 Enter 03 (Enter  )

5 Green LED of reader is lit continuously.

Method 1: Swipe the card to delete card number.


6
Method 2: Enter the card number to delete the card.

7 Reader beeps once and green LED blinks.

Enter  to return to ready mode or go to item 4 to delete another


8
card.
z Function key (03) can delete only one card each time. To delete another record,
repeat the same procedure.

5.5.5 Function key 05 Delete All Cards

No. Description

1 Ready mode, the red LED of reader is lit.

2 Enter Default Master Code : 30191000(Enter  )

3 The green LED of reader blinks.

4 Enter 05 (Enter  ). Delete all card numbers.

Green LED of reader extinguishes.


5
Red LED blinks and beeps four times.

6 RAC-2000P/PV/G automatically restarts and red LED of reader is lit.

HUNDURE 32 RAC-2000PS Hardware Manual


5.5.6 Function key 10 Change MASTER CODE

No. Description

1 Ready mode, the red LED of reader is lit.

2 Enter Default Master Code : 30191000(Enter  )

3 The green LED of reader blinks.

4 Enter 10 (Enter  )

5 Green LED of reader lights continuously.

Method 1, Swipe card to configure new master code.


6
Method 2, enter the card number of the master code.
Green LED of reader extinguishes.
7
Red LED blinks and beeps four times.

8 RAC-2000P/PV/G automatically restarts and red LED of reader is lit.

5.5.7 Function key 99 System Initialization

No. Description

1 Ready mode, the red LED of reader is lit.

2 Enter Default Master Code : 30191000(Enter  )

3 The green LED of reader blinks.

4 Enter 99 (Enter  )

5 Orange LED of reader lights.

Enter [0] for ignore, [1] for repair, [2] for refresh.
After entering [0] or [1], the red LED blinks four times and beeps four
times. RAC-2000P/PV/G automatically restarts and red LED of
6 reader is lit.
After entering [2]. The red and green LED blinks alternatively for 5
seconds and beeps once. RAC-2000P/PV/G automatically restarts
and red LED of reader is lit.
z When the hardware installation is complete, make sure to execute system
initialization to resume system back to default settings

HUNDURE 33 RAC-2000PS Hardware Manual


Chapter 6 Testing

The above steps can be ignored if there is no keypad on reader.


Follow the steps below for hardware initialization.
Move JP12 JUMPER to the back of HW INITIAL. Restart the
HDP-100 and there will be continuous beep sound. Set JP12
JUMPER back to NORMAL and wait for 5 seconds. The HDP-100
will beep and complete hardware initialization.

HUNDURE 34 RAC-2000PS Hardware Manual


Chapter 7 Troubleshooting

QThe power indicator (LED 4) on the control panel does not blink.
AKindly check if 12V power supply is connected to the power source. Verify if the power
polarity is correct and the power input is sufficient or not.

QDoor does not open after swipe card


A
1. Please check wire connection of reader and reader interface setup is correct.
2. Make sure reader ID is correct.
3. Please check if set the authorization and if the card number is correct.
4. Please check wire connect with lock.

QThe reader beeps once after swiping card. There is no other sound and door is not
open.
A
1. Please check wire connection between reader and control panel.
2. Make sure reader ID is correct.
3. Press RESET button of control panel and try to recover the connection.

QReader displays incorrect date and time.


A
1. Please check wire connection between reader and control panel.
2. Make sure reader ID is correct
3. Pres RESET button of control panel and try to recover the connection.
4. Please synchronization from the software.

QSometimes can access, sometimes can not access the door.


A
1. Make sure if access authorization setting is correct.
2. Authorization changed but doesnt upload to control panel, kindly upload all setting to
control panel again.

HUNDURE 35 RAC-2000PS Hardware Manual


QCannot enter commend mode after input Master Code.
A
1. Please check wire connection of reader is correct.
2. Please check if Master Code is correct.

QForget Master Code.


A
1. Please connect with software and read Master Code back from the control panel.
2. Please initial the hardware. All the parameters will back to default value.

QDoor doesnt open after pressing exit button.


A
1. Make sure the exit button installed and wire connection is connected correctly.
2. Make sure the wire connection of electric door lock is connected correctly.

QDoor open generally but lock after swiping card.


AWrong door relay activate mode, please adjust the jumps and select suitable relay mode.

QSwiped door 1 reader but door 2 opens.


A
1. The wire of door relay is not connected correctly.
2. Wrong reader ID setup. Reader ID 1 (Outdoor) and 2 (Indoor) is for door 1, reader ID 3
(Outdoor) and 4 (Indoor) is for door 2.

QThe read range of reader is too short.


A
1. It is recommended to use separate linear direct current (not switching power)
2. If the reader is installed upon metallic object add proper thickness plastic separator on
back of reader for isolation and avoid interference.
3. The distance between two readers should be 1.5 times the read range to prevent radio
frequency interference from each other.

HUNDURE 36 RAC-2000PS Hardware Manual


4. The readers are installed on the slender wall, add proper thickness plastic separator on
the back of readers or change install location for isolation and avoid interference.

QDoor opened after swiping card twice.


AThe distance between reader and control panel are too far or using fishbowl connection
way. Please upgrade cable specification and change connection way as daisy chain.

QThe door opens too long time or locks too quickly.


AKindly use software to adjust door relay activate time.

QNo warning sounds when door open overtime.


A
1. Please activate door sensor and set door sensor detecting time from the software.
2. Please check install location of door sensor is sufficient or not and the wire connection
is correct or not.

QNo alarm when external forces happened


A
1. Please activate door sensor and select alarm type from the software.
2. Please check install location of door sensor is sufficient or not and the wire connection
is connected correctly.
3. Please check wire connection of alarm relay is connected correctly.

QControl panel doesnt communicate with PC.


A
1. Please select RS-232 or RS-485 communication mode from jump 1~9.
2. Make sure the control pane ID is correct and unique.
3. Please check communication wire is connected correctly.
4. Please check power, wire connection and setting of converter are correct.
5. Make sure the com port selection of PC is correct.

HUNDURE 37 RAC-2000PS Hardware Manual


Chapter 8 Appendices

8.1 Appendix 1 (Wiring Material Requirements)

Maximum
Cable Type Cable Specification Connection
Length

RAC-2000PS power cable 18-20 AWG 30M

Door Relay and its power cable 18-20 AWG 50M

Alarm Relay connection cable 18-20 AWG 50M

Door Sensor connection cable 18-22 AWG 50M

Exit Button connection cable 18-22 AWG 50M

Power: 2-conductor shielded cable

External RS-485 reader 20AWG


30M
connection cable
Signal: 2-conductor (at least) shielded
twisted pair wire 2022AWG

4-conductor shielded twisted pair wire


RS-232 cable 25M
20~22 AWG

4-conductor shielded twisted pair wire


RS-485 cable (to PC) 800 M
20~22 AWG

z Upgrade the cable specification according to transmission distance.


z Upgrade the cable specification as per environmental interference factors.
z It is advisable to purchase cables with core-wires more than what Hundure
recommends, to reserve for future use.
z It is highly recommended to use shielded twisted pair wire for readers and
communication cable to increase transmission distance and interference
resistance ability.

HUNDURE 38 RAC-2000PS Hardware Manual


8.2 Appendix 2 (DIP Switch Setting)

(Condition: ON=, OFF=)


ID SW 1~8 ID SW 1~8 ID SW1~8 ID SW1~8 ID SW1~8
0 00000000 52 00101100 104 00010110 156 00111001 208 00001011

1 10000000 53 10101100 105 10010110 157 10111001 209 10001011

2 01000000 54 01101100 106 01010110 158 01111001 210 01001011

3 11000000 55 11101100 107 11010110 159 11111001 211 11001011

4 00100000 56 00011100 108 00110110 160 00000101 212 00101011

5 10100000 57 10011100 109 10110110 161 10000101 213 10101011

6 01100000 58 01011100 110 01110110 162 01000101 214 01101011

7 11100000 59 11011100 111 11110110 163 11000101 215 11101011

8 00010000 60 00111100 112 00001110 164 00100101 216 00011011

9 10010000 61 10111100 113 10001110 165 10100101 217 10011011

10 01010000 62 01111100 114 01001110 166 01100101 218 01011011

11 11010000 63 11111100 115 11001110 167 11100101 219 11011011

12 00110000 64 00000010 116 00101110 168 00010101 220 00111011

13 10110000 65 10000010 117 10101110 169 10010101 221 10111011

14 01110000 66 01000010 118 01101110 170 01010101 222 01111011

15 11110000 67 11000010 119 11101110 171 11010101 223 11111011

16 00001000 68 00100010 120 00011110 172 00110101 224 00000111

17 10001000 69 10100010 121 10011110 173 10110101 225 10000111

18 01001000 70 01100010 122 01011110 174 01110101 226 01000111

19 11001000 71 11100010 123 11011110 175 11110101 227 11000111

20 00101000 72 00010010 124 00111110 176 00001101 228 00100111

21 10101000 73 10010010 125 10111110 177 10001101 229 10100111

22 01101000 74 01010010 126 01111110 178 01001101 230 01100111

23 11101000 75 11010010 127 11111110 179 11001101 231 11100111

24 00011000 76 00110010 128 00000001 180 00101101 232 00010111

25 10011000 77 10110010 129 10000001 181 10101101 233 10010111

26 01011000 78 01110010 130 01000001 182 01101101 234 01010111

27 11011000 79 11110010 131 11000001 183 11101101 235 11010111

28 00111000 80 00001010 132 00100001 184 00011101 236 00110111

29 10111000 81 10001010 133 10100001 185 10011101 237 10110111

30 01111000 82 01001010 134 01100001 186 01011101 238 01110111

HUNDURE 39 RAC-2000PS Hardware Manual


31 11111000 83 11001010 135 11100001 187 11011101 239 11110111

32 00000100 84 00101010 136 00010001 188 00111101 240 00001111

33 10000100 85 10101010 137 10010001 189 10111101 241 10001111

34 01000100 86 01101010 138 01010001 190 01111101 242 01001111

35 11000100 87 11101010 139 11010001 191 11111101 243 11001111

36 00100100 88 00011010 140 00110001 192 00000011 244 00101111

37 10100100 89 10011010 141 10110001 193 10000011 245 10101111

38 01100100 90 01011010 142 01110001 194 01000011 246 01101111

39 11100100 91 11011010 143 11110001 195 11000011 247 11101111

40 00010100 92 00111010 144 00001001 196 00100011 248 00011111

41 10010100 93 10111010 145 10001001 197 10100011 249 10011111

42 01010100 94 01111010 146 01001001 198 01100011 250 01011111

43 11010100 95 11111010 147 11001001 199 11100011 251 11011111

44 00110100 96 00000110 148 00101001 200 00010011 252 00111111

45 10110100 97 10000110 149 10101001 201 10010011 253 10111111

46 01110100 98 01000110 150 01101001 202 01010011 254 01111111

47 11110100 99 11000110 151 11101001 203 11010011 255 11111111

48 00001100 100 00100110 152 00011001 204 00110011

49 10001100 101 10100110 153 10011001 205 10110011

50 01001100 102 01100110 154 01011001 206 01110011

51 11001100 103 11100110 155 11011001 207 11110011

HUNDURE 40 RAC-2000PS Hardware Manual


ONE YEAR LIMITED WARRANTY

We warrants this product against defect in material or workmanship for


1 year from the date of purchase. If such a defect is discovered within this warranty
limitation, contact your dealer for repair or replacement of your unit.

When returning the product, you must ship the product in its original packaging or
packaging that gives an equal degree of protection. This warranty becomes invalid if the
factory-supplied serial number has been removed or altered on the product.

This warranty does not cover cosmetic damage or damage due to acts of God, accident,
misuse, abuse, negligence or modification of any part of the product. This warranty does
not cover damage due to improper operation or maintenance, connection to improper
equipment, or attempted repair by anyone other than .

In no event shall manufacturers liability exceed the price paid for the product from direct,
indirect, special, incidental, or consequential, damages resulting from the use of the
product, its accompanying software, or its documentation. Hundure makes no warranty
or representation expressed, implied, or statutory, with respect to its products, contents of
use of this documentation and all accompanying software, and specially disclaims its
quality, performance, merchantability or fitness for any particular purpose. Hundure
reserves the right to revise or update its product, software or documentation without
obligation to notify any individual or entity.

TECHNICAL SUPPORT

For technical questions regarding your product, please email our service and support team at

overseas@hundure.com

Você também pode gostar