Escolar Documentos
Profissional Documentos
Cultura Documentos
8 August 1982
DEVELOPMENT OF A NEW TYPE FAULT LDCATOR
USING THE ONE-TERMINAL VOLTAGE AND CURRENT DATA
Abstract A new type fault locator has been The digital fault locator (DFL), described in
developed, that calculates the reactance of a faulty this paper, uses a micro-processor and reduces errors
line, with a micro-processor, using the one-terminal by an ef f icient use of sof tware.
voltage and current data of the transmission line.
Errors caused by various factors such as load flow,
fault resistance, and the unsymmetrical arrangement of PRINC IPLE
the transmission line, are automatically corrected.
The equipment is now under field test, and during the Fundamental Equation
nine months of the field test, the equipment has
operated satisfactorily. The method to calculate the distance to a fault
point is based on the following equation, that
expresses a fault point voltage VF and current IF
INTRODUCTION using the one-terminal data.
Fault Locators, that measure the distance to a VF =
VS cosh yx -
ZSIS sinh yx
fault point on a transmission line, conventionally use .... (1)
the following methods. One is to detect the surge ISF = Vs/ ZS sinh yx - I" cosh Yx
x =
Im (VR1l * Rl)
Effect of Fault Current in an Overhead Ground Wire
In (VLRl 'cRl)
.... (3)
VLR1 = E (z Between each tower of the transmission line, an
overhead ground wire is stretched that has the same
k = Rl, Sl, Tl, R2, S2, T2 voltage to the tower, and each tower is grounded
through a tower-footing resistance.
Where Rl, Sl, Tl means each phase of No.1 line
R2, S2, T2 means each phase of No.2 line Transmission Line 'SF 'PF"
VRp: NO.1 line R phase voltage
IctRl: c component of No.1 line R-phase Overhead ground W-lire
current
ZRlk: Mutual impedance concerning No.1 line
R phase
For No.1 line S phase to T phase fault
Im (VSlTl * ISlTl*)
Im (VLSlTl * ISlTl*)
B+tRtIF'm groundQ F
1 IRT RTpRt} -.
The grourid
-
-k
VLSlTl =
(ZSlSl ZSlTl) IS1 - (ZTlTl ZSlTl) IT1
- -
lb S-TerminalL To R-Terminal
+ (ZRlSl ZRlTl) IR1 + KZ (ZSlk ZTlk) Ik
- -
[kn]
2.0
JI
Printer
CONFIGURATION
_Setting -
I
F : Filter DMA : Direct memory Access
S/H : Sample & Elold CPU : Central Processing Unit
MPX : Multiplexer ROUM : Read only Memory
A/D : Analogue to Digital D/O : Digital output
Converter
The DFL Locating Results (A) The inspection Results Error Error
Case (B) (A-B) (%)
Date Time | Line
N.
Kind of
Fault Locating No.
Reisult Tower Distance No. Faulty
Tower Phase Km
1 '81-Jan-18 11057' iL S-1G 25.7Km 109 Not found *
2 '81-Jan-19 1058' 2L R-18 41.8Km 71 41.3Km 72 2L-R 0.5Km 1.2%
3 '81-Jan-20 11034' 1L S-1G 54.7Km 38 55.lKm 37 1L-S -0.4Km 0.7%
4 '81-Jan-21 90301 2L RiT-G 32.8Km 91 32.6Km 92 2L-RT 0.2Km 0.6%
5 '81-Jan-21 19042' 2L I-I 44.9Km 61 45.3Km 60 2L-T -0.4Km 0.5%
6 '81-Jan-22 160061 2L RT-2JG (46.6Km) (56) 49.OKm 51 2L-R
34.2Km 88 2L-T
7 '81-Jan-31 130021 1L 71 31.OKm 96 30.2Km 98 1L-T 0.8Km 2.6%
8 '81-Feb-3 180311 1L S-1G (40.9Km) 73 38.5Km 77 lL-S *
9 '81-Jul-12 16035' 2L T-l G 70.7Km 3 69.8Km 5 2L-T 0.9Km 1.3%
APPENDIX I
[kmn]
A single phase circuit with a fault as shown in
Fig. A1.1 (a) can be separated into two equivalent
60e ,~j~ase 3 circuits: The pre-fault load flow component shown in
Fig. A1.1 (b) and the fault current component shown in
A -- ..Converged Fig. A1.1 (c). From the fault point
sI S
'SIRFI
IS I
(a) A single phase circuit (b) Woad flow Component (c) Fault Canponent
with a fault
From (Al.4), ' can be eliminated. Neglecting the higher order term, then:
Define f (x) to be the left term of (A1.5) in by (A3.2), (A3.1) are solved:
Appendix I. xl means approximate solution by (2)
and x2 means correct solution by (A1.5). Then, I ISF + (I, - I SF
error by approximation Ax is expressed as follows:
.... (A3.3)
X2 = X1 + Ax .... (A2.1) E-Yx/S + 'Y(x-2xo)/S
or 1 + F-2Yxo/S
Ax = -f (xI) /f ' (x1) .... (A2.2)
The fundamental equation (2) covers only the first
Approximation is expressed using small value 6 1, term of the right hand of (A3.3), and the second term
62, as follows: of (A3.3) becomes the error factor. The effect of
this error factor is shown in Fig. 4.
tanhyx = Yx + 61
.... (A2.3)
S= jXBIS, XB/ZS = 62 J S-terminal Transmission Line
I~~~~
I ISF 1;4 + IrFL
where XB: Back impedance of the transmission line 'Overhead Cm [I
From (A2.3) and (Al.5), f(xl) and f'(xl) can be ground Wire I Ii
obtained using the next approximation: