Você está na página 1de 12

1

A Self Organizing Strategy for Power Flow


Control of Photovoltaic Generators in a
Distribution Network
H. Xin, Z. Qu, Fellow, IEEE, J. Seuss, A. Maknouninejad
Abstract: The focus of this paper is to develop a in sunlight due to a passing cloud/storm) could trigger a
distributed control algorithm that will regulate the power rapid disconnection of these PV generators or the reduction
output of multiple photovoltaic generators (PVs) in a of their operating capacity, resulting in a significant loss of
distribution network. To this end, the cooperative control active power support. The loss of generation can lead to an
methodology from network control theory is used to make array of problems, such as voltage variation [4, 6], transient
a group of PV generators converge and operate at certain stability issues, and even voltage collapse [7-9], making it
(or the same) ratio of available power, which is desirable to developing a practical and robust scheme of
determined by the status of the distribution network and controlling the total output of the PVs, especially in the
the PV generators. The proposed control only requires case that the distribution network is weak.
asynchronous information intermittently from neighboring The Optimal Power Flow (OPF) strategy is the standard
PV generators, making a communication network among approach to dispatch and control traditional generators in
the PV units both simple and necessary. The minimum the transmission network [10-12]. The strategy has also
requirement on communication topologies is also been applied to distribution networks that have a few
prescribed for the proposed control. It is shown that the distributed generators (DGs) [13, 14]. These results yield
proposed analysis and design methodology has the centralized controls by collecting the system-wide
advantages that the corresponding communication information and sending the command globally. For a
networks are local, their topology can be time varying, and power system whose transmission and distribution
their bandwidth may be limited. These features enable PV networks have numerous and geographically dispersed
generators to have both self-organizing and adaptive DGs, such centralized controls are too expensive to be
coordination properties even under adverse conditions. implemented and, even if they could be done, the resulting
The proposed method is simulated using the IEEE system is not robust or efficient.
standard 34-bus distribution network. 1 On the other hand, a decentralized control mode such as
the maximum photovoltaic power tracking (MPPT),
Key words: PV Generators, Power Flow Control, constant VF (Voltage and Frequency) with droop mode, or
Distribution Network, Self Organization, Network Control the feeder power flow control mode [1, 2, 15, 16], is
useful in the distribution network if there are only a few
I. Introduction DGs present.
As the level of PV penetration increases, intermittent
In recent years, there has been an increasing number of
changes of these PV outputs become too many to
distributed generators (DGs) integrated into the modern
enumerate and consider, and hence it becomes intractable
distribution network [1-3]. Among these DGs, PVs are
for either the decentralized or centralized mode to
becoming an increasingly attractive source of renewable
adequately manage a distribution network, such as
energy in certain areas, especially as they become more
maintaining the voltage profile. Instead, the practically
commercially viable to manufacture and install [4, 5].
feasible solution is a distributed control configuration [17]
However, the introduction of a large amount of PV
that uses local communication networks and hence
generation could have a negative impact on the power
combines the positive features of both centralized and
system at large if the relevant stability and control issues
decentralized controls while limiting their disadvantages.
are not properly considered.
Specifically, a PV generator should incorporate whatever
In a distribution network that contains a high level of
information is available from its neighboring generators or
penetration of PV units but has an insufficient number of
critical nodes into its control law. This distributed control
storage devices, a sudden disturbance (such as the change
configuration is in line with the concept that a future smart
grid would include communication among network
1
This work is partially supported by the US Department of Energy elements [3, 4]. This resulting control problem becomes
(under the SEGIS program) and Florida Energy Systems Consortium. the so-called network control problem which has
H. Xin is with the department of electrical engineering, Zhejiang systematically been studied in recent years and also
University, P. R. China. He was also a postdoc in the University of
Central Florida when he finished this paper. Email: xinhh@zju.edu.cn. successfully applied to such fields as cooperative robotic
Z. Qu is a professor of the department of electrical engineering and control [18, 19].
computer science, the University of Central Florida, USA. Email: The distinctive feature of an appropriately designed
qu@eecs.ucf.edu; network control is that it admits local and changing
J. Seuss and A. Maknouninejad are graduate students of the University
of Central Florida, USA. Emails: jseuss@gmail.com, communication networks, is robust with respect to
ali_maknuny@yahoo.com. intermittency and latency of its feedbacks, and also
2

tolerates connection and disconnection of network 0 g 2 ( P1 ,..., Pn , Q1 ,..., Qn , , X) (6)


components. When a distribution network contains many where (2) and (3) denote the d-loop and q-loop dynamics
groups of DGs whose output may vary in wide ranges, the through which the active and reactive power outputs can
aggregated power output of all the DGs in each group can be controlled; variables u1i and u2i are the control
be dispatched and controlled by coordinating the power
inputs to be designed; is a vector of an appropriate
output level of each DG internally within the given group.
For instance, a simple solution to the power-output dimension, and it denotes all the internal network state
coordination problem is to prescribe certain utilization variables including dynamics of the PV generators, loads,
profile for all of the PVs in a group, and the so-called fair and synchronized generators; X is a vector of algebraic
utilization profile is that the same ratio of power output variables in the distribution network such as the voltages
versus available power is imposed on all individual PV of buses; and (6) is the power flow equation of the
generators. In general, the desired control algorithm distribution network.
should be able to manage a large number of DGs but Controls u1i and u2i ( i 1, 2,..., n ) are to be designed
require only local information from neighboring units. By to control active and reactive power outputs of PV
doing so, groups of DGs can be formed autonomously generators so that the power flow of the network is
based on the presence of local communication networks, reasonable. Toward this goal, the changes of the PVs
the power in a distributed network can easily dispatched outputs can be considered to be much slower than the
and controlled, and possibly large swings in power outputs dynamics of PVs internal variables, and hence it can be
of distributed generators can be tolerated. assumed that the dynamics of (4) have been made
In this paper, a self-organizing power control method is asymptotically stable by their controls. In other words, fast
proposed by applying cooperative control theory of dynamics of can be considered negligible compared to
networked systems to power distribution networks. The the slowly changing power flow variables. Accordingly,
proposed control algorithm can effectively control a large the simplified dynamical models for the distribution
number of PVs which exchange information among their network are denoted by:
neighboring units, respectively. The control can make the Idiref u1i (7)
PVs in one group converge to any given utilization profile I ref u (8)
while providing the desired power being dispatched from qi 2i

the group. It is distinctive that the proposed control can Pi U i I di , Qi U i I qi (9)


tolerate the changes in the distribution network, its local 0 g ( P1 ,..., Pn , Q1 ,..., Qn , , X) (10)
communication network can be intermittent and have time where g () [ g1T (), g 2T ()]T , and all the other variables are
varying topologies, and its communication bandwidth can
be of minimum. Typical communication setups are the same as those in (2)-(6). In what follows, a distributed
discussed, and the necessary and sufficient condition for cooperative control will be designed for system (7)-(10).
stability and convergence is also presented. B. Problems to be Solved
In a distribution network with many PV generators, its
II. Problem Formulation operating condition needs to be adjusted due to many
varying factors, such as load and sunlight fluctuations. As
A. Dynamical Model was pointed out in the introduction, it would be impossible
Consider a distribution power system network with n to determine and maintain a feasible operating condition if
three-phase inverter-based photovoltaic generators that use all of the PV generators are independently run under the
the decoupled d-q control method via Phase Locked Loops decentralized control configuration shown in Figure 1 (a).
(PLL). Under the d-q frame, the terminal voltage of the ith The centralized control mode shown in Figure 1 (b) is
PV generator satisfies U di U i and U qi 0 , where U i neither practical nor reliable since it requires global
denotes the magnitude of the terminal voltage [15]. Thus, collection and exchange of information. To handle
output power of the ith PV generator can be expressed as: numerous PV generators in the network, we propose to
Pi U i I di , Qi U i I qi (1) implement the distributed control configuration as shown
where I di and I qi are the output currents in the d-axis in Figure 1 (c).
The basic idea of the proposed distributed control is that,
and q-axis, respectively; and Pi and Qi denote the by incorporating local communication networks that share
active and reactive power. information among neighboring units, numerous PV
If an integration control design is pursued for I diref and generators autonomously form a number of generation
I qiref , then the dynamics of the distribution system are groups and that each group is represented by a virtual
generation unit which aggregates all the power generated
described by the following differential-algebraic within. The outputs of these virtual generators can be
equations: dispatched and controlled by a high level control (which is
Idiref u1i (2) equivalent to a transmission and distribution control
Iqiref u2i (3) center). While the latter is similar to the centralized
g1 ( P1 ,..., Pn , Q1 ,..., Qn , , X) (4) control configuration, the proposed control configuration
requires much less communication since the numerous
Pi U i I di , Qi U i I qi (5) distributed generators do not communicate with the
3

higher-level control. Q1 Q2 Qn
... Q0 (12)
Q1max Q2 max Qn max
Ui where 0 [ P0 , Q0 ]T is the given output ratio for the
Pi active and reactive power for all the PV generators,
~ ~ ~ i ~ Qi ~ respectively; Pi max and Qi max are the instantaneous
n maximum capacity of Pi and Qi , respectively; and all
Control ... Control ... Control the Pi max are assumed to have the same sign, and so do all
(a) the Qi max .
Ui
The ratios in (11)-(12) are the utilization percentages of
all the PV units and they are commanded to be the same at
Pi the steady state. Accordingly, the control objective of (11)
~ ~ ~ ~ Qi ~ -(12) is referred to as the fair utilization profile. In general,
i n a distribution network can dictate any specific utilization
Info.
profile. For instance, utilization ratio i may be desired
exchange
Centralized control to converge to i* for different i. In this case, the
(b) designer can introduce the gain of ki * i* so that the
transformed utilization ratio of ki i needs to converge to
Ui
the common ratio * . In other words, any specific
Pi utilization profile can be converted into the fair utilization
~ ~ ~ ~ Qi ~ profile in (11)-(12) for which the proposed cooperative
i n control is designed. It should be noted that a balanced
distribution network is considered in problem 1. If the
Group
High level Control distribution network is unbalanced, the energy
(Distributed Control)
management should be different because the output power
(c) contains a periodic part resulting from the negative current
Figure 1. Three different control modes in a distribution network and voltage. For this case, the power in (11)-(12) should
(the dash arrows represent information flow): (a) a decentralized be replaced by the positive output power.
mode; (b) a centralized mode; (c) a distributed control mode. By introducing the utilization profile (11)-(12), each of
the PVs can be controlled by comparing its operation to
Once the power output of each group is dispatched, the
that of any or some of its neighboring units, and there is
proposed cooperative control coordinates all the outputs of
no need for every PV unit to communicate with every
PV generators in the same group so that, even though the
other unit or the high-level control. Accordingly, the
output capacity of individual PVs may have large swings,
proposed distributed control for each PV generator is of
a given profile is achieved for their utilization and the sum
the general form
of their outputs converges to the dispatched value. This
ui wi ( si 0 y 0 , si1y1 , si 2 y 2 ,..., sin y n ) , i 1, 2,...n (13)
feature makes it possible for all the active PVs to
self-organize themselves and be controlled. The local where y 0 denotes the output of the high level control;
th
information sharing within one group of PVs may be y i represents the output of the i PV generator
intermittent, asynchronous, and of varying topology. In (for i 1, 2,...n ); S ( sij ) is the matrix defined below to
other words, the proposed control is robust with respect to
describe the instantaneous communication topology:
possible variations and limitations of communication
networks. The utilization profile for PVs in the group can s10 (t ) s11 s1n (t )
s (t ) s (t ) s2 n (t )
s22
be determined according to such considerations as S 20 21
R n( n 1) . (14)
economic and regulatory policies. In what follows, the

proposed distributed cooperative control is designed for snn
sn 0 (t ) sn1 (t ) sn 2 (t )
the case of the fair utilization profile, that is, that all of the In (14), sii (t ) 1 for all i ; sij 1 if the output of the
PVs in a designated group are to be run at the same active
and reactive power output ratios. Mathematically, this jth PV generator is known to the ith PV generator at time
control problem can be stated as follows. t , and sij (t ) 0 if otherwise; si 0 (t ) 1 if the ith PV
Problem 1: Design controls u1i and u2i ( i 1, 2,..., n ) generator receives information from the high level control
for system (7)-(10) such that, at the equilibrium operating at time t , and si 0 (t ) 0 if otherwise. As shown in Figure
point, the utilization profile of PVs is described by the 1(c), the proposed control utilizes certain neighboring
following ratios: information but does not assume any global information.
P1 P P In the extreme case that the high level control collects
2 ... n P0 (11)
P1max P2 max Pn max information from and sends command to all the PVs,
and matrix S in (14) has 1 as its entries in the first column, and
the corresponding control becomes the centralized control
4

configuration in Figure 1(b). The other extreme case is equilibrium point is piecewise-constant, and its stability
that none of the PVs exchange information with each other has to be analyzed in terms of convergence of matrix
or the high-level control, then matrix S has entries sij 0 sequences. In other words, the proposed control can be
for any i j , and the proposed control reduces to a designed by using the state-of-the-art approach from
cooperative control of networked systems rather than
decentralized control.
traditional methods such as eigen-analysis and pole
The specific expression of the control (13) will be
placement.
synthesized in subsection IV.A. In both the control (13)
Upon the solutions to Problems 1 and 2 are found, all
and matrix S of (14), the identity of sii 1 means that the
the PVs are organized into a number of groups and, within
control at every PV generator can and should utilize its each group, the PV generators are controlled to satisfy the
own output as one of the feedback. Whether or not the given utilization profile. Accordingly, each group of the
high-level command or information from other PV PVs can be viewed as a virtual generator of a larger
generators is available at the ith generator is determined by capacity and with an aggregated output. The aggregated
the current status of its communication network outputs of these virtual generators would be dispatched
represented by the ith row of communication matrix S . and in turn the operating ratios in groups utilization
Intuitively, it would be sufficient for all the PV generation profiles are determined, which results in much less
units to be controlled properly if each of the PVs can long-distance communication and also a much simpler
receive some information from some of its neighboring design for a high level control (see that in Figure 1 (c)) to
units and if the command of the total dispatched power is address ancillary service issues, given a large numbers of
sent to some of the PVs in a group. This brings out the PVs in the distribution network.
problem of determining the minimum information sharing Thus, depending upon the needs of the particular
that must exist among the group of PV generators and distribution network of our concern, the high level control
between the group and the high-level control. That is, the can be designed according to one of several objectives.
requirement on communication network needs to be Among the possibilities, the high-level control can be
specified to ensure the proposed distributed control would designed to be either a balanced generator in the islanding
work, and it is stated as the following problem. operation, or a virtual power plant for load management
Problem 2: Determine how the local communication [20], or a smart agent for maintaining frequency or a
network among the PVs (the S matrix) should be desired voltage profile [1, 6], and so on. Relevant to this
designed in order to ensure efficiency and reliability of the paper is the study in [21] where the power at the feeder is
network while minimizing economic costs. kept constant such that all the rest of the load demands are
It should be emphasized that the proposed distributed picked up by DGs. In this case, the feeder becomes a truly
control admits time varying, intermittent and dispatchable load from the utility side, allowing
asynchronous communication networks. In fact, given any demand-side management arrangements. In this paper, the
limited bandwidth of one communication node, it would idea of making the load constant to the utility grid is
be better for the convergence of networked control that the extended; in particular the high level control is designed
node sends its information intermittently to different nodes so that the reactive power is controlled to support the
in its vicinity. This means that, in (14), communication voltage at some critical bus and to keep the active power
matrix S is time-varying in general or, more precisely, consumed by loads in an area or at a feeder to be constant.
piecewise constant. Specifically, consider This leads to the third problem to be solved in the paper.
t:0 : {t0 , t1 , t2 ,...} , S:0 : {S (t0 ), S (t1 ),...} (15) Problem 3: Based on the solutions to Problem 1 and
which means that S changes at ti ( t0 0 ), or simply, Problem 2, design a high level control (as shown in Figure
1 (c)) for the system of (7)-(10) such that, for each group
S (t ) S (tk ) S:0 for t [tk , tk 1 ) . The time-varying nature
of PVs, the voltage of a critical bus is of a specific value
of matrix S also implies that the proposed distributed and the active power flow across certain transmission line
control has inherent robustness against interruptions, data is of a fixed amount. Namely, the following set points are
loss, and other phenomena of a typical communication achieved at the equilibrium:
network. Ptran () P ref , (16)
Problem 2 defined above arises naturally from the fact
that both the communication network topology and the Vc () V , ref
(17)
availability of PVs are time varying. In addressing the where P ref
and V ref
are the given reference values;
problem, we aim to find a simple condition on feasible and Vc () and Ptran () represent the voltage of the selected bus
convergent sequences of {S (t0 ), S (t1 ),...} . The basic rule and the active power over the chosen transmission line,
for designing appropriate local communication topology respectively. Note that, in (16)-(17), variables Vc () and
will further be discussed in section IV. Through such a Ptran () are functions of the outputs of PVs and, for
design of local communication network, the candidate
simplicity, the functional dependence is denoted by () .
sequences of {S (t0 ), S (t1 ),...} can be chosen to ensure the
Several observations are worth making here regarding
convergence of the distribution network under the
the aforementioned design problems:
proposed control. Due to the time-varying nature of local
a) The design problems 1-3 are defined explicitly in
communication networks and their resulting cooperative
terms of dynamics of PV generators, and they can be
controls, the resulting closed loop system around the
extended by incorporating dynamics of other types of
5

DGs. That is, for a distribution network with other there are, the more information propagates within the
types of DGs such as wind generators, the same group, and the faster the convergence to the desired
design problems can be formulated and solved for utilization profile. However, this quickly becomes an
energy management. As argued in [21], a hierarchical uneconomical solution to the problem. It follows from
control architecture should be used to control the cooperative control theory [23] that the minimum
distribution network with many DGs. In this regard, requirement on the communication topologies is the so
Problem 3 is the high-level control, Problems 1 and 2 called sequential completeness condition. Mathematically,
are the middle-level control within each of the groups this requirement is that the sequence of communication
of DGs, and also there are low-level individual matrices S:0 {S (t0 ), S (t1 ),...} be sequentially complete in
controls (which are already embedded into equations the sense that, over an infinite sequence of finite
(7)-(10)) at each of the DGs to control the individual consecutive intervals, the composite graph over each of
output. To apply such The DGs can easily be the intervals (or the binary product of all the matrices of S
classified into groups according to their location and over the interval) has at least one globally reachable node
proximity, for instance, at a feeder, within a (in the sense that all other nodes can be reached from the
communication zone, solar/wind farms, etc. How to globally reachable node by following the directed
best partition DGs into groups is an important branches of the graph) [23]. Thus, for the purpose of
problem, but it is out of the scope of this paper. In our distributed control design, the following rule is given for
simulation study, all the PVs connected to the same designing local communication networks and scheduling
feeder are considered to belong to one group. local communications.
b) In Problems 2 and 3, a DG group is controlled to act Rule: Communication matrix S is piecewise constant,
as a virtual FACTs element supporting the voltage of and the corresponding sequence S:0 {S (t0 ), S (t1 ),...} is
a critical bus. In general, it is difficult to determine
sequentially complete.
the critical bus for a large-scale power system. The
The above sequential completeness condition is a very
common practice is by simulations or by experience.
precise method to schedule local communication, and it is
For a radial distribution network, existing simulation
also the necessary and sufficient condition for any
studies [2, 6] have shown that the bus at the end of a
properly-designed cooperative system to converge [18, 23].
feeder is typically the one subject to voltage violation
A more restrictive (sufficient but not necessary) condition
when power from DGs changes intermittently. Thus,
is that the composite graph is strongly connected (which
in our simulations, the end bus of a feeder is chosen to
implies that, by following the directed branches, every
be the critical bus.
node can be reached from any other node). To illustrate its
c) Problem 3 aims to coordinate any given DG group
application, consider communication matrix S (tk ) and
with the overall power grid. The desired active and
reactive power output (i.e., reference values P ref and construct the corresponding graph by linking the nodes
V ref ) of the PV group can be determined by either according to non-zero entries in S . One can easily
offline or online optimization approach or by one of determine whether the resulting graph has at least one
the market-based approaches [6, 13, 22]. Once P ref globally reachable node or not. For instance, consider the
graphs in Figure 2. Figure 2(a) has node 0 as the unique
and V ref are obtained, the extended power flow
globally reachable node; and none of the nodes in Figure
equations of (6) and (16)-(17) could be used to
2(b) is globally reachable because there are two isolated
determine the groups aggregated power output
groups of nodes.
(which in turn yields the actual output ratios of the
active and reactive power, P0 and Q0 ). Could the
high level control collect enough information
(including the parameters of the power system
network with virtual DG generators), the desired
output ratios of every PV group can be calculated
directly. Otherwise, the high-level control for system Figure 2: Sample graphs of communication topology: (a) existence of
one globally reachable node; (b) absence of globally reachable node
coordination needs to be designed as prescribed in
subsection IV.B. The above general method can be used to verify or
establish the sequential completeness condition, and the
III. Rule of Communication Topology Design details can be found in [18, 23]. In designing distributed
control for PVs in a distribution network, we choose to
As outlined in the previous section, the topology of the focus our attention to the following very special case of
local communication network among the PVs in one local communication topology: If matrix S (tk ) has at least
group can be intermitted (time varying) and asynchronous,
in which case the communication matrix S describing the one globally reachable node for every k 0 , then
topology becomes piecewise constant. To ensure that a sequence S:0 is guaranteed to be sequentially complete.
given utilization profile is achieved among one group of The following example further explains this special case
PVs, there need to be local information sharing among the for the sequential completeness condition. Consider a
DGs. Heuristically, the more communication channels matrix sequence {S (t0 ), S (t1 ),...} defined by S (tk ) Si for
6

k 3 i where i 0,1, 2 and N is an integer; and sij is the generic entry of matrix S defined in (14)
1 0 0 0 1 0 0 0 1 0 0 0 for ui1 . Similarly, S can be defined for ui 2 and sij is
1
1 0 0 1
1 0 1 1 1 0 1
S0 , S1 , S2 . its generic entry.
1 0 1 0 0 0 1 1 1 0 1 1 Without loss of any generality, lets choose for simplicity

0 0 1 1 1 0 0 1 0 1 0 1 that
Figure 3 plots the graphs corresponding to those K d 1 K q1 K dn K qn K 0 (23)
communication topologies. It follows from Figure 3 that Then, it follows from (18)-(21) and (23) that the closed
the information can propagate from node 0 to nodes 1, 2 loop system becomes
and 3. Therefore, all of the communication matrices are Pi P n D P
K 0 i Di 0 P 0 ,
ij j
complete by themselves, and so are their sequences.
Pi max Pi max j 1 Pj max

(24)
Q i Q n D Q
K 0 i Di0 Q 0 . (25)
ij j

Qi max Qi max
j 1 Q j max

The following theorem shows that, if the PV generators


S0 S1 S2 are controlled by (20) and (21), their active and reactive
Figure 3: Graphs for time-varying communication topologies power utilization profiles converge to the desired values
defined in (11) and (12), respectively.
While not necessarily required, this special case can be Theorem 1: Consider control laws (20)-(21) and
used to design and implement a redundant local suppose that the communication rule is satisfied among
communication network which satisfies the so-called rule the PVs. Then, the output ratios of their active and reactive
of N-n. Namely, when n communication channels cannot power converge uniformly and asymptotically to the
work properly in some amount of time, the common values of P0 and q0 , respectively.
communication matrix corresponding to the remaining
communication channels should be kept to be complete. It Proof: System (24) can be rewritten as
should be also noted that the convergence rate of the
zi K 0 zi Di 0 P0 Dij z j (26)
closed loop system depends upon connectivity of the j 1,..., n
communication network, so it is important to design a P
reasonably connected local communication network where zi i . On the other hand, constant P0 is the
Pi max
within certain physical and economic constraints.
trajectory of the following virtual system
z0 0 , z0 (0) P0 . (27)
IV. Cooperative Control Strategy
Therefore, stability of system (26) is identical to that of
A. Control Strategy for Fair Utilization the following extended system consisting of (26)-(27):
In this subsection, the high level control is assumed to z0 0, z0 (0) P0
have sufficient information, such as the exact parameters
n . (28)
zi K 0 zi Dij z j
and the (aggregated) states of the distribution network, so
that the desired output ratios P0 and q0 can be j 0
computed directly using the expanded power flow It follows from theorem 5.4 in [23] that, if communication
equations. This assumption will be removed in the matrix D defined by (22) is sequentially complete,
subsequent subsection. system (28) uniformly asymptotically converges to c1 ,
It follows from (7)-(9) that where 1 [1,1,...,1]T and c R is the constant
U determined by the initial state and topology changes. It
Pi U i I diref U i Idiref i Pi U i u1i (18)
Ui follows from z0 P0 that c P0 . Thus, z [ z1 ,..., zn ]T
U uniformly asymptotically converges to P0 1 . Similarly,
Q i U i I qiref U i Iqiref i Qi U iu2i . (19)
Ui reactive power ratios also converge to the common value
The cooperative control laws for the ith PV generator are of q0 .
K di Pi max P n D P U i Pi Theorem 1 provides the solution to both Problems 1 and
u1i Di 0 P i 2 (20)
0 ij j

Ui Pi max j 1 Pj max 2. The salient features of the proposed distributed control


Ui
have been described in sections II and III, and they will be
K qi Qi max Q n D Q U i illustrated in section V.
u2 i Di0 Q i Qi (21)
0 ij j

Ui Qi max j 1 Q j max Ui B. Control Design for System Coordination


where K di and K qi are the gains; Since the high-level control may not have enough
sij sij information to determine the desired utilization ratios, we
Dij n
, Dij n
, i 1, 2,...n (22) propose the following distributed control (also shown in
sij
j 0
sij
j 0
Figure 4) to adjust the reactive power ratio:
7

z0 K v (Vref Vc ) with respect to any disturbance in terms of | zi z j | for


0 (29)
Q z0 every pair of {i, j} . Accordingly, theorem 5.4 in [23] can
be used to conclude that, due to the separation of time
where Vc is the critical bus voltage of interest; Q0 is the
scales, system (24)-(25) remains to be asymptotically
updated value which is used as the input for (25); and convergent (to the common desired utilization ratios) and
Vadditional is an input for achieving additional objectives so is the closed loop system under the entire set of
(to be explained shortly). In parallel, the active power distributed control (33). This result provides the solution
control over a specified transmission line is controlled to Problems 1, 2 and 3.
according to Figure 5 and as The following two remarks are worth noting about the
z0 K P [ Pref Ptran ] distributed high-level controls. (a) PVs can also be used to
0 (30) damp possible oscillations existed in a power system
P z0
network or to improve the long-term stability by designing
where Ptran is the desired active power over the given the additional control inputs Padditional and Vadditional
transmission line; P0 is the resulting utilization ratio that (shown in Figure 4 and Figure 5) in a way similar to the
drives (24); and Padditional is an input for other PSS and AVR controls for synchronous generators. This
considerations. Intuitively, the physical meanings of subject will be studied in future research, but in this paper
controls (29)-(30) are that, if the bus voltage (or real these additional inputs are set to zero. (b) The high-level
power transmission) is less than its reference value, the controls can also be implemented discretely, that is, the
proposed distributed high-level control is to command following updating laws can be used instead:
some of the PVs (through its local communication z0 (tk 1 ) z0 (tk ) z0 sign(Vref (tk ) Vc (tk ))
0 (32)
network) to increase their reactive (or real) power ratio Q z0
and that the rest of PVs will also cooperate toward the
same goal under their distributed cooperative controls. z0 (tk 1 ) z0 (tk ) z0 sign( Pref (tk ) Ptran (tk ))
0 (33)
Hence, an increase of P0 in (30) should result in an P z0
increase of Ptran until Ptran reaches its desired reference where z0 and z0 are the step sizes in adjusting the
value of Pref . utilization ratios; sign() is the standard sign function; ti .
( i 1, 2,3,... ) are the time instants of updating.
Vref 1
Vc z0 C. Further Discussions on Distributed Control
1 In addition to the distinct features already described in
Kv
s sections II and III, the following observations are also
Vadditional Ka worth noting about the proposed distributed controls:
1 (a) In the distributed controls, Pi max is assumed to be
Figure 4. Control for determining the desired ratio of Q nonzero. In the event that some of the PV generators are
out of service (due to weather or otherwise), the apparent
Pref 1 singularity of Pi max 0 can be avoided by using the simple
Ptran z0 rule that, if Pi max 0 , the ith column of communication
1
KP matrix S is set to zero. That is, a PV generator in any
s
group is ignored unless it has meaningful power
Padditional Ka
1 generation capacity.
Figure 5. Control determining the desired ratio of P
b) It has been shown that si 0 (t ) 1 is not required for
all the PVs. This means that the interaction between the
Combining (20)-(21) and (29)-(30) yields the complete distributed high-level controls and distributed cooperative
set of distributed control laws: controls can also be intermittent and time varying. In
u10 K v (Vref Vc ) particular, when the dispatched power over certain
transmission lines is changed or critical bus voltages are
u20 K P [ Pref Ptran ]
adjusted, only their reference values in the high-level
u K di Pi max D 0 Pi
n D P
U P controllers need to be modified
1i
Ui
i0 P
ij j
i 2i

Pi max j 1 Pj max U i
(31)
These two features imply that the proposed two-level

distributed controls are very flexible and effective, which
u K qi Qi max D z Qi
n D Q
U
2i Ui i0 0 ij j
i Qi
Qi max j 1 Q j max U i
enable the groups of PVs to be truly self-organizing
according to their capacity and local communication
Mathematically, by choosing gains K p and K v to be networks. Should more paths be added into the local
communication networks, the faster the system converges,
small enough, then the desired utilization issued by the
high-level controls changes much slower than the outputs which will be illustrated in the simulation study.
of the PVs. It is known [23] that the system in the form of
(28) is exponentially convergent to P0 1 and it is robust
8

V. Simulation Study chosen for a radial network with intermittent DGs); active
power control is to keep a constant amount of power move
In this section, the standard IEEE 34-bus distribution downstream of the feeder (line 1 and its positive direction
network is used to illustrate effectiveness of the proposed are shown in figure 6).
distributed two-level controls. The network has its main Matrix of communication topology:
voltage at 24.9kV. Its topology is shown in Figure 6. Its The local communication network is represented by
DGs include 16 PV generators and one gas turbine matrix S in (34) where Gi denotes the ith PV generator
generator. Simulations are done using Digsilent, and
(i=1,2,16) and G0 is the high-level controller (which
balanced distribution networks are considered.
coordinates the aggregated power and hence is considered
to be a virtual PV generator in the lead). Unless mentioned
otherwise, matrix S of (34) is the one used in the
simulation.
G0 G1 G2 G3 G6
1 0 0 0 0 0 0 0 G0
1 1 1 1 1 0 0 0 G1

1 1 1 1 1 0 0 0 G2

0 1 1 1 1 0 0 0 G3 (34)
S
0 1 1 1 1 0 0 0 G6

0 0 1 1 1 1 0 0 G4
0 0

0 0 1 1 1 0 0 1 G16
As specified by (34), the 1st and the 2nd PV generators
receive the information from the high-level control;
generators G1, G2, G3 and G6 are closely coupled, and
the rest of generators follow G2 up to G6 by receiving
information from them.
It is easy to verify that the aforementioned
communication topology satisfies the communication rule
presented in section III. In fact, the communication
topology is intentionally chosen to be redundant so that, if
some of the entries in matrix S were to switch from 1 to 0
intermittently, the communication rule should still be
observed unless many of the communication channels stop
working at the same time. This shows that the local
communication network can be designed to be robust.
In this distribution network, the distributed generators
Figure 6. Diagram of the IEEE 34-bus network (including the gas turbine generator) provide power to not
The parameters of the system can be founded at the link only the local loads but also the external main grid. In the
http://ewh.ieee.org/soc/pes/dsacom/testfeeders.pdf. Basic simulation, total penetration levels of DGs and PVs are to
operational conditions, dynamical models and other be increased up to about 360% and 220%, respectively.
settings are: The corresponding voltages at the PV terminal buses are
PV parameters: The initial maximums of active and shown in Table 1 with different PV penetration levels
reactive power are set to 1 MW and 1MVAR, respectively. (provided that all the PVs are run according to the fair
Loads: 1.45MW+j0.85MVAR. Their model is utilization profile and their power factors are also kept to
composite (a dynamical part and a constant impedance be same). From this table, one can see that, if the
part of 50% each). penetration level of PVs is raised further, the bus voltage
Gas turbine generator: Its active power is 2MW and shall go out of the feasible range (0.9p.u.-1.1p.u.). Thus,
the terminal voltage is set to 1.0 p.u.; the default model in unless being controlled appropriately, operations of this
Digsilent is used with IEEE Type 1 control for AVR, system will have voltage problems under certain
PSS_ostab1 model for the PSS, and the IEEE-G1 model disturbances.
for the governor. The subsequent simulation study is to verify that, under
PV generators: 3.2MW+j0.16Mvar ( cos 1.0 ). disturbances and interruptions, the proposed distributed
two-layer control can make the system operate well and all
External grid: An infinite bus (1.0 p.u.).
the PV generators outputs converge according to the
The parameters in the aforementioned dynamical models
desired utilization profile. The following cases are
are included in the appendix.
simulated:
High-level controls: The voltage is controlled for the
A) Short-circuit faults;
critical bus to which PV 1 is connected (Recall that, as
B) Changes in sunlight;
discussed in section IV, the last bus in a feeder is typically
9

C) Load changes and intermittent communication It can also be observed that, at the time that the fault
interruptions. occurs, the active power generated by the PV generators
decreases, so does the active power across line 1.
Table 1. PVs terminal bus voltage for different levels of PV penetration
Accordingly, the high-level control commands PV 1 and
PV 0% 50% 100% 220%
PV 2 to increase their power output ratios and, as the
1 0.912 0.947 0.978 1.046
2 0.912 0.947 0.978 1.046 result of the proposed cooperative control, all the rest of
3 0.950 0.969 0.986 1.023 PV generators follows. At the end, all the PV generators
4 0.924 0.955 0.983 1.043 asymptotically reach the fair utilization profile. This
5 0.919 0.950 0.979 1.039 transient process is plotted in figure 7(3). Reactive power
6 0.912 0.947 0.978 1.046 is controlled in a similar way, as shown in figure 7(4).
7 0.912 0.947 0.978 1.046
8 0.912 0.946 0.978 1.045 B. Dynamic responses to rapid changes in sunlight
9 0.912 0.946 0.977 1.044 Next, sudden changes of available power due to weather
10 0.950 0.969 0.966 1.021 conditions are considered. In the simulation, the maximum
11 0.951 0.969 0.986 1.021 active power capacity of PV 1, PV 3 and PV 5 are to vary
12 0.966 0.976 0.985 1.002 between 10% and 100%, as shown in figure 8(1).
13 0.916 0.949 0.978 1.042 Figure 8 shows the dynamical responses of the system.
14 0.913 0.946 0.978 1.044 In particular, the active/reactive power output ratios are
15 0.912 0.946 0.978 1.044
shown in figures 8(2) and 8(3), respectively; and the
16 0.912 0.946 0.978 1.044
power transmitted over line 1 and the bus voltages are
A. Dynamic responses to short circuit faults plotted in figures 8(4) and 8(5), respectively.
The fault location is labeled by point (a) or the When the sunlight reaching a PV generator starts to
associated red dot in figure 6. The fault at point (a) occurs decrease, the active power output ratio initially increases
at 0.0s and is cleared after 0.12s. The resulting dynamical since the maximum available power of the corresponding
responses of the network are shown in Figure 7. PV generator is decreased. This process is apparent in
Figure 7 shows that the system is asymptotically stable figure 8(2) and 8(3) in which the active power output
under this fault and the corresponding time scales are in follows the trend of changes in sunlight except for the
seconds. In comparison, dynamics of internal state transient responses due to the aforementioned reason and
variables such as those of synchronized generators are to the controls.
much faster than the changes in PV generators outputs.
Pi max1
This validates the assumption (made in section II) that, for
0.5
the power control problem, those internal dynamics can be
ignored. 0
0 10 20 30 40 [s]

1.01 0

1.005 -0.2 Pi 0.2


1 -0.4
0.1
0
0.995 -0.6 0 10 20 30 40 [s]

0.99
-5 0 5 10 15 [s]
-0.8
-5 0 5 10 15 [s]
Qi 0.02
0.01

zi
0.1 0
z0 P0 z0 Q0
0.3
zi 0 10 20 30 40 [s]
0.25
0.05
2.5
0.2
0
Ptran 2
0.15
1.5
0 10 20 30 40 [s]
0.1 -0.05
-5 0 5 10 15 [s] -5 0 5 10 15 [s]

V Vc
1.15 1.05
Vc Ptran2.5
1.1
2 1
1.05 0 10 20 30 40 [s]
1
1.5 -0.25
0.95
-0.3
0.9 1

-5 0 5 10 15 [s] -5 0 5 10 15 [s]
0 10 20 30 40 [s]
Figure 7. Dynamic responses under fault (a): 1) Frequency of Figure 8. Responses under sunlight changes: 1) Sunlight changes; 2)
gas-turbine generator; 2) Angle of the gas-turbine generator; 3) Active Active power outputs of PV generators 1, 2, 3 and 5; 3) Reactive power
power output ratios for PV generators 1 to 4; 4) Active power output output ratios of PV generators 1, 3 and 5; 4) Active power across line 1; 5)
ratios for PV generators 1 to 4; 5) Critical bus voltage; 6) Active power Voltages at the critical buses; 6) Rotor angle of the gas-turbine.
transmitted over line 1.
10

As sunlight changes, the distributed cooperative control or with communication interruptions. The output ratios of
makes PV output ratios converge to new operating points representative PV generators (PVs 1-3) are plotted in
determined by the distributed high-level controls. The Figure 12. As expected, we see by comparing solid and
high-level controls do not know the current generation dashed trajectories that convergence is faster without
capacity of all the PV generators since they communicate communication interruptions.
only with PV generators 1 and 2. Nonetheless, during the 1.5
whole period of system operation, the active power sent s20 1
over line 1 and the bus voltages are maintained around 0.5
their designated values, which are shown in figures 8(4) 0

and 8(5). This confirms the features claimed in the -0.5


-5 0 5 10 15 20 25 30 35 [s]
previous discussions.
Under the proposed power flow control method, the 1.5

feeder can be considered from the viewpoint of bus (b) to


s31 1
0.5
be a virtual emulated load of constant active power, and 0
the inner voltage of this feeder can be controlled by -0.5
reactive power control of the PV generators. Figure 9 -5 0 5 10 15 20 25 30 35 [s]
shows the changes of real and reactive power output ratios. 1.5
Therefore, the effects due to the fluctuations of the PV real s10,2 1
power generation can be reduced or minimized by 0.5
implementing local information sharing and cooperative 0
controls. It is believed that the proposed method can be -0.5
-5 0 5 10 15 20 25 30 35 [s]
applied to solve voltage regulation problems.
0.4 Figure 10. Intermittent interruptions in communication channels
z z1
0.3
no commu. fault commu. fault constant PQ
0.2
z0 z3 P1 0.5
Q1 0.15
0.1
0 10 20 30 40 0.4
[s] 0.1
(1) 0.3

z 0.02 z0 0.2
0.05

0.01 0.1 0
z3 0 10 20 30 [s] 0 10 20 30 [s]

0 1.1
0 10 20 30 40 [s] Vc Ptran 3
(2) 1.05
2
Figure 9. Responses to sunlight changes: 1) Active power ratios of PV 1, 1
PV 3 and P ; 2) Reactive power ratios of PV 1, PV 3 and Q .
0 0
1
0.95

C. Load changes and communication interruptions 0.9 0


0 10 20 30 0 10 20 30
The previous simulations show that PV generators can [s] [s]

autonomously adjust their outputs to converge to a Figure 11. Responses to load changes with and without intermittent
prescribed utilization profile (i.e., the fair utilization communication
profile). In what follows, a case is studied to show that the
proposed control also has strong robustness against
communication interruptions and load variations. z 0.6 z 0P PV 1 PV 2 PV 3

Consider the following severe case that local 0.4


communication network is interrupted intermittently and
the loads vary simultaneously: 0.2

1) The simulated communication interruptions are


0
chosen as follows: the communication channels of 0 2 , -5 0 10 20 30 [s] 40
1 3 and 2 10 are intermittent and the time instants
of their changes are random (whose changes are shown in z 0.2 z 0Q PV 1 PV 2 PV 3
figure 10(1), in which 1 means that the corresponding 0.15
channel is working; and 0 if otherwise).
0.1
2) All loads ramp to 200% of the base levels within one
second, and 10% loads of the base loads are cleared at 5s 0.05
and 10s, respectively. 0
Dynamical responses of the gas-turbine generator and -5 0 10 20 30 [s] 40
the PV generators are shown in Figure 11 in which the Figure 12. Responses to intermittent communication and load changes: 1)
dashed and solid trajectories represent the results without Active power ratios of PVs 1-3; 2) Reactive power ratios of PVs 1-3.
11

VI. Conclusion [14] C. Dent, L. Ochoa, and G. Harrison, "Network Distributed


Generation Capacity Analysis Using OPF With Voltage Step
A distributed two-level control scheme is proposed for Constraints," IEEE Transactions on Power Systems, vol. 25, no. 1,
pp. 296-304, Feb 2010.
power control of groups of PV generators in a distribution [15] G. Diaz, C. Gonzaalez-Moran, J. Gomez-Aleixandre, et al.,
network. The proposed control guarantees that the "Complex-Valued State Matrices for Simple Representation of
distribution network can autonomously adjust itself to a Large Autonomous Microgrids Supplied by PQ and V f
feasible operating point (after disturbances occur) and that Generation," IEEE Transactions on Power Systems, vol. 24, no. 4,
pp. 1720-1730, Nov 2009.
all the PV generators in one group converge to a [16] J. M. Kwon, B. H. Kwon, and K. H. Nam, "Three-Phase
prescribed utilization profile. The proposed controls Photovoltaic System With Three-Level Boosting MPPT Control,"
require only intermittent information sharing among IEEE Transactions on Power Electronics, vol. 23, no. 5, pp.
neighboring generators, and topologies of local 2319-2327, Sep 2008.
[17] P. Massioni and M. Verhaegen, "Distributed Control for Identical
communication networks can be time varying. As long as Dynamically Coupled Systems: A Decomposition Approach,"
the communication networks meet the minimum IEEE Transactions on Automatic Control, vol. 54, no. 1, pp.
information exchange requirement (of the matrix sequence 124-135, Jan 2009.
[18] Z. Qu, J. Wang, and R. Hull, "Cooperative control of dynamical
being sequentially complete), the proposed controls
systems with application to autonomous vehicles," IEEE
ensures convergence. Simulations of the IEEE benchmark Transactions on Automatic Control, vol. 53, no. 4, pp. 894-911,
distribution network are used to validate the features and May 2008.
effectiveness of the proposed method. The proposed [19] Y. Zhang and Y. Tian, "Consentability and protocol design of
design methodology is also applicable to distribution multi-agent systems with stochastic switching topology,"
Automatica, vol. 45, no. 5, pp. 1195-1201, May 2009.
networks with different types of DGs including solar-, [20] N. Ruiz, I. Cobelo, and J. Oyarzabal, "A Direct Load Control
wind- and ocean-energy power generators. Model for Virtual Power Plant Management," IEEE Transactions
on Power Systems, vol. 24, no. 2, pp. 959-966, May 2009.
[21] R. H. Lasseter and P. Piagi, Control and design of microgrid
Reference components. University of Wisconsin-Madison: PSERC
Publication 06-03, 2006.
[1] F. Katiraei and M. Iravani, "Power management strategies for a
[22] G. A. Jimenez-Estevez, R. Palma-Behnke, R. Torres-Avila, et al.,
microgrid with multiple distributed generation units," IEEE
"A competitive market integration model for distributed
Transactions on Power Systems, vol. 21, no. 4, pp. 1821-1831,
generation," IEEE Transactions on Power Systems, vol. 22, no. 4,
Nov 2006.
pp. 2161-2169, Nov 2007.
[2] A. Kashem and G. Ledwich, "Multiple distributed generators for
[23] Z. Qu, Cooperative Control of Dynamical Systems. London:
distribution feeder voltage support," IEEE Transactions on Energy
Springer, 2009.
Conversion, vol. 20, no. 3, pp. 676-684, Sep 2005.
[24] P. Kundur, Power System Stability and Control. New York:
[3] G. Strbac, "Electric power systems research on dispersed
McGraw-Hill, 1994.
generation - Preface," Electric Power Systems Research, vol. 77,
no. 9, pp. 1143-1147, Jul 2007.
[4] J. Lopes, N. Hatziargyriou, J. Mutale, et al., "Integrating
distributed generation into electric power systems: A review of
drivers, challenges and opportunities," Electric Power Systems
Research, vol. 77, no. 9, pp. 1189-1203, Jul 2007. Appendix
[5] W. El-Khattam and M. Salama, "Distributed generation
technologies, definitions and benefits," Electric Power Systems The parameters for the gas turbine generator are:
Research, vol. 71, no. 2, pp. 119-128, Oct 2004. S B 5MVA , H 1.5s , Damp 0.02p.u. , x1 0.1p.u. ,
[6] M. E. Baran and I. M. El-Markabi, "A multiagent-based
dispatching scheme for distributed generators for voltage support xd 2.062p.u. , xq 2.062p.u. , Td0 5.51s , Tq0 0.8s ,
on distribution feeders," IEEE Transactions on Power Systems, Td0 Tq0 0.1s , xd xq 0.171p.u. .
vol. 22, no. 1, pp. 52-59, Feb 2007.
[7] T. Nguyen and M. Pai, "A sensitivity-based approach for studying The AVR model in the gas turbine generator is the IEEE
stability impact of distributed generation," International Journal type 1 [24]. Its transfer function is shown in Figure 13 and
of Electrical Power & Energy Systems, vol. 30, no. 8, pp. 442-446, the parameters are: Tr 0.02s , K a 200p.u. , Ta 0.03s ,
Oct 2008.
[8] V. Calderaro, J. Milanovic, M. Kayikci, et al., "The impact of K e 1p.u. , Te 0.2 s , K f 0.05p.u. , Tf 1.5s ,
distributed synchronous generators on quality of electricity supply
and transient stability of real distribution network," Electric
Vr min 10p.u. , Vr max 10p.u. .
Power Systems Research, vol. 79, no. 1, pp. 134-143, Jan 2009. E fd
[9] H. Hedayati, S. Nabaviniaki, and A. Akbarimajd, "A method for
V 1 Ka 1
placement of DG units in distribution networks," IEEE 1 Tr s 1 Ta s K e Te s
Transactions on Power Delivery, vol. 23, no. 3, pp. 1620-1628, Jul
2008. U pss
Tf s
[10] D. Gan, R. Thomas, and R. Zimmerman, "Stability-constrained
optimal power flow," IEEE Transactions on Power Systems, vol. 1 Tf s
15, no. 2, pp. 535-540, May 2000. Figure 13. Transfer function of IEEE-1 exciter
[11] C. Dent, L. Ochoa, G. Harrison, et al., "Efficient Secure AC OPF
for Network Generation Capacity Assessment," IEEE
The PSS in the gas turbine generator is the PSS_ostab2
Transactions on Power Systems, vol. 25, no. 1, pp. 575-583, Feb
2010. model provided by the Digsilent. The transfer function is
[12] H. Xin, D. Gan, Z. Huang, et al., "Applications of shown in Figure 14, in which the parameters are:
Stability-constrained Optimal Power Flow in the East China K 200p.u. , T1 T2 0.125s , T3 T4 0.025s ,
System," IEEE Transaction on Power Systems, p. In press, 2010.
[13] A. Tsikalakis and N. Hatziargyriou, "Centralized control for K ang 8p.u. , Tang 0.5p.u. , Tw 0.021s , L min 0.2p.u. ,
optimizing microgrids operation," IEEE Transactions on Energy Vngmax 0.29p.u. , Vmg max 0.05p.u. , Vmax 0.2p.u. ,
Conversion, vol. 23, no. 1, pp. 241-248, Mar 2008.
12

Vmin 0.2p.u. .
Vng max
Vmgmx
V K ang
E fd
1 Tang s
0 0
H lim Vmax
Ks (1 T1 s )(1 T2 s )
1 Tw s (1 T3 s)(1 T4 s) U pss Zhihua Qu (M90, S93, and F09) received his
L min Vmin Ph.D. degree in Electrical Engineering at the Georgia Institute of
Technology in June 1990. Since then, he has been with the University of
Central Florida (UCF), currently a Professor and Interim Chair of ECE
Figure 14. Transfer function of PSS-ostab2 and the SAIC Endowed Professor of UCF. Dr. Qus areas of expertise are
nonlinear systems and control, energy and power systems, autonomous
The governor in the gas turbine generator is the vehicles and robotics. In energy systems, his research covers such
IEEE-G2 model, the transfer function is shown in Figure subjects as low-speed power generation, dynamic stability of distributed
power systems, anti-islanding control and protection, distributed
15, and the parameters are: K 5s , T1 0.5s , generation and load sharing control, distributed VAR compensation,
T2 T4 0.1s , T3 0.95s , Pmin 0p.u. , Pmax 1.0p.u. . distributed optimization and cooperative control. Dr. Qu is the author of
three books: Robust Tracking Control of Robot Manipulators by IEEE
Pmax Press (1996), Robust Control of Nonlinear Uncertain Systems by John
PM Wiley & Sons (1998), and Cooperative Control of Dynamical Systems
K (1 sT2 ) Ka 1 sT4
with Applications to Autonomous Vehicles by Springer Verlag (2009).
(1 sT1 )(1 sT3 ) 1 Ta s 1 0.5sT4
Dr. Qu is a Fellow of IEEE and currently serving on Board of Governors
P0 Pmin of IEEE Control Systems Society and as Associate Editor for Automatica,
IEEE Transactions on Automatic Control, and International Journal of
Figure 15 Transfer function of Gov-IEEEG2 Robotics and Automation.

The parameters for the PV generators are: K P 0.1p.u. ,


KV 0.5p.u. , K di K qi 8.0p.u. , i 1,...,16 .
The dynamical model for the loads is shown in Figure
16, and the parameters are: T1 0.1s , k pf kqf 1.0p.u. ,
k pu kqu 1.0p.u. , Tpf Tqf 0.05s , Tpu Tqu 0.05s .
f k pf sTpf P Pout
John Seuss obtained a BS degree in electrical
1 sT1
engineering from Georgia Institute of Technology in Atlanta, USA in
2006. He is currently seeking his MSEE at UCF and his research
kqf sTqf 1 Pext interests include power system stability analysis and control.
1 sT1

k pu sTpu
1 sT1 1 Qext

kqu sTqu Q Qout


1 sT1

V
Figure 16. Transfer function of load dynamics

Biographies Ali Maknouninejad obtained a MS degree in Iran


University of Science and technology. Currently he is a Ph.D. student in
the University of Central Florida and his research interests include
inverter design and control.

Huanhai Xin was born in Jiangxi, China in


1981. He has been with the faculty, currently an associate professor in
the department of Electrical Engineering, Zhejiang University, China,
after he obtained the Ph.D. degree from the same department in June
2007. He was a post-doctor in the EECS department of the University of
Central Florida from June 2009 to July 2010. His research interests
include power system stability analysis, and renewable energy.

Você também pode gostar