Escolar Documentos
Profissional Documentos
Cultura Documentos
higher-level control. Q1 Q2 Qn
... Q0 (12)
Q1max Q2 max Qn max
Ui where 0 [ P0 , Q0 ]T is the given output ratio for the
Pi active and reactive power for all the PV generators,
~ ~ ~ i ~ Qi ~ respectively; Pi max and Qi max are the instantaneous
n maximum capacity of Pi and Qi , respectively; and all
Control ... Control ... Control the Pi max are assumed to have the same sign, and so do all
(a) the Qi max .
Ui
The ratios in (11)-(12) are the utilization percentages of
all the PV units and they are commanded to be the same at
Pi the steady state. Accordingly, the control objective of (11)
~ ~ ~ ~ Qi ~ -(12) is referred to as the fair utilization profile. In general,
i n a distribution network can dictate any specific utilization
Info.
profile. For instance, utilization ratio i may be desired
exchange
Centralized control to converge to i* for different i. In this case, the
(b) designer can introduce the gain of ki * i* so that the
transformed utilization ratio of ki i needs to converge to
Ui
the common ratio * . In other words, any specific
Pi utilization profile can be converted into the fair utilization
~ ~ ~ ~ Qi ~ profile in (11)-(12) for which the proposed cooperative
i n control is designed. It should be noted that a balanced
distribution network is considered in problem 1. If the
Group
High level Control distribution network is unbalanced, the energy
(Distributed Control)
management should be different because the output power
(c) contains a periodic part resulting from the negative current
Figure 1. Three different control modes in a distribution network and voltage. For this case, the power in (11)-(12) should
(the dash arrows represent information flow): (a) a decentralized be replaced by the positive output power.
mode; (b) a centralized mode; (c) a distributed control mode. By introducing the utilization profile (11)-(12), each of
the PVs can be controlled by comparing its operation to
Once the power output of each group is dispatched, the
that of any or some of its neighboring units, and there is
proposed cooperative control coordinates all the outputs of
no need for every PV unit to communicate with every
PV generators in the same group so that, even though the
other unit or the high-level control. Accordingly, the
output capacity of individual PVs may have large swings,
proposed distributed control for each PV generator is of
a given profile is achieved for their utilization and the sum
the general form
of their outputs converges to the dispatched value. This
ui wi ( si 0 y 0 , si1y1 , si 2 y 2 ,..., sin y n ) , i 1, 2,...n (13)
feature makes it possible for all the active PVs to
self-organize themselves and be controlled. The local where y 0 denotes the output of the high level control;
th
information sharing within one group of PVs may be y i represents the output of the i PV generator
intermittent, asynchronous, and of varying topology. In (for i 1, 2,...n ); S ( sij ) is the matrix defined below to
other words, the proposed control is robust with respect to
describe the instantaneous communication topology:
possible variations and limitations of communication
networks. The utilization profile for PVs in the group can s10 (t ) s11 s1n (t )
s (t ) s (t ) s2 n (t )
s22
be determined according to such considerations as S 20 21
R n( n 1) . (14)
economic and regulatory policies. In what follows, the
proposed distributed cooperative control is designed for snn
sn 0 (t ) sn1 (t ) sn 2 (t )
the case of the fair utilization profile, that is, that all of the In (14), sii (t ) 1 for all i ; sij 1 if the output of the
PVs in a designated group are to be run at the same active
and reactive power output ratios. Mathematically, this jth PV generator is known to the ith PV generator at time
control problem can be stated as follows. t , and sij (t ) 0 if otherwise; si 0 (t ) 1 if the ith PV
Problem 1: Design controls u1i and u2i ( i 1, 2,..., n ) generator receives information from the high level control
for system (7)-(10) such that, at the equilibrium operating at time t , and si 0 (t ) 0 if otherwise. As shown in Figure
point, the utilization profile of PVs is described by the 1(c), the proposed control utilizes certain neighboring
following ratios: information but does not assume any global information.
P1 P P In the extreme case that the high level control collects
2 ... n P0 (11)
P1max P2 max Pn max information from and sends command to all the PVs,
and matrix S in (14) has 1 as its entries in the first column, and
the corresponding control becomes the centralized control
4
configuration in Figure 1(b). The other extreme case is equilibrium point is piecewise-constant, and its stability
that none of the PVs exchange information with each other has to be analyzed in terms of convergence of matrix
or the high-level control, then matrix S has entries sij 0 sequences. In other words, the proposed control can be
for any i j , and the proposed control reduces to a designed by using the state-of-the-art approach from
cooperative control of networked systems rather than
decentralized control.
traditional methods such as eigen-analysis and pole
The specific expression of the control (13) will be
placement.
synthesized in subsection IV.A. In both the control (13)
Upon the solutions to Problems 1 and 2 are found, all
and matrix S of (14), the identity of sii 1 means that the
the PVs are organized into a number of groups and, within
control at every PV generator can and should utilize its each group, the PV generators are controlled to satisfy the
own output as one of the feedback. Whether or not the given utilization profile. Accordingly, each group of the
high-level command or information from other PV PVs can be viewed as a virtual generator of a larger
generators is available at the ith generator is determined by capacity and with an aggregated output. The aggregated
the current status of its communication network outputs of these virtual generators would be dispatched
represented by the ith row of communication matrix S . and in turn the operating ratios in groups utilization
Intuitively, it would be sufficient for all the PV generation profiles are determined, which results in much less
units to be controlled properly if each of the PVs can long-distance communication and also a much simpler
receive some information from some of its neighboring design for a high level control (see that in Figure 1 (c)) to
units and if the command of the total dispatched power is address ancillary service issues, given a large numbers of
sent to some of the PVs in a group. This brings out the PVs in the distribution network.
problem of determining the minimum information sharing Thus, depending upon the needs of the particular
that must exist among the group of PV generators and distribution network of our concern, the high level control
between the group and the high-level control. That is, the can be designed according to one of several objectives.
requirement on communication network needs to be Among the possibilities, the high-level control can be
specified to ensure the proposed distributed control would designed to be either a balanced generator in the islanding
work, and it is stated as the following problem. operation, or a virtual power plant for load management
Problem 2: Determine how the local communication [20], or a smart agent for maintaining frequency or a
network among the PVs (the S matrix) should be desired voltage profile [1, 6], and so on. Relevant to this
designed in order to ensure efficiency and reliability of the paper is the study in [21] where the power at the feeder is
network while minimizing economic costs. kept constant such that all the rest of the load demands are
It should be emphasized that the proposed distributed picked up by DGs. In this case, the feeder becomes a truly
control admits time varying, intermittent and dispatchable load from the utility side, allowing
asynchronous communication networks. In fact, given any demand-side management arrangements. In this paper, the
limited bandwidth of one communication node, it would idea of making the load constant to the utility grid is
be better for the convergence of networked control that the extended; in particular the high level control is designed
node sends its information intermittently to different nodes so that the reactive power is controlled to support the
in its vicinity. This means that, in (14), communication voltage at some critical bus and to keep the active power
matrix S is time-varying in general or, more precisely, consumed by loads in an area or at a feeder to be constant.
piecewise constant. Specifically, consider This leads to the third problem to be solved in the paper.
t:0 : {t0 , t1 , t2 ,...} , S:0 : {S (t0 ), S (t1 ),...} (15) Problem 3: Based on the solutions to Problem 1 and
which means that S changes at ti ( t0 0 ), or simply, Problem 2, design a high level control (as shown in Figure
1 (c)) for the system of (7)-(10) such that, for each group
S (t ) S (tk ) S:0 for t [tk , tk 1 ) . The time-varying nature
of PVs, the voltage of a critical bus is of a specific value
of matrix S also implies that the proposed distributed and the active power flow across certain transmission line
control has inherent robustness against interruptions, data is of a fixed amount. Namely, the following set points are
loss, and other phenomena of a typical communication achieved at the equilibrium:
network. Ptran () P ref , (16)
Problem 2 defined above arises naturally from the fact
that both the communication network topology and the Vc () V , ref
(17)
availability of PVs are time varying. In addressing the where P ref
and V ref
are the given reference values;
problem, we aim to find a simple condition on feasible and Vc () and Ptran () represent the voltage of the selected bus
convergent sequences of {S (t0 ), S (t1 ),...} . The basic rule and the active power over the chosen transmission line,
for designing appropriate local communication topology respectively. Note that, in (16)-(17), variables Vc () and
will further be discussed in section IV. Through such a Ptran () are functions of the outputs of PVs and, for
design of local communication network, the candidate
simplicity, the functional dependence is denoted by () .
sequences of {S (t0 ), S (t1 ),...} can be chosen to ensure the
Several observations are worth making here regarding
convergence of the distribution network under the
the aforementioned design problems:
proposed control. Due to the time-varying nature of local
a) The design problems 1-3 are defined explicitly in
communication networks and their resulting cooperative
terms of dynamics of PV generators, and they can be
controls, the resulting closed loop system around the
extended by incorporating dynamics of other types of
5
DGs. That is, for a distribution network with other there are, the more information propagates within the
types of DGs such as wind generators, the same group, and the faster the convergence to the desired
design problems can be formulated and solved for utilization profile. However, this quickly becomes an
energy management. As argued in [21], a hierarchical uneconomical solution to the problem. It follows from
control architecture should be used to control the cooperative control theory [23] that the minimum
distribution network with many DGs. In this regard, requirement on the communication topologies is the so
Problem 3 is the high-level control, Problems 1 and 2 called sequential completeness condition. Mathematically,
are the middle-level control within each of the groups this requirement is that the sequence of communication
of DGs, and also there are low-level individual matrices S:0 {S (t0 ), S (t1 ),...} be sequentially complete in
controls (which are already embedded into equations the sense that, over an infinite sequence of finite
(7)-(10)) at each of the DGs to control the individual consecutive intervals, the composite graph over each of
output. To apply such The DGs can easily be the intervals (or the binary product of all the matrices of S
classified into groups according to their location and over the interval) has at least one globally reachable node
proximity, for instance, at a feeder, within a (in the sense that all other nodes can be reached from the
communication zone, solar/wind farms, etc. How to globally reachable node by following the directed
best partition DGs into groups is an important branches of the graph) [23]. Thus, for the purpose of
problem, but it is out of the scope of this paper. In our distributed control design, the following rule is given for
simulation study, all the PVs connected to the same designing local communication networks and scheduling
feeder are considered to belong to one group. local communications.
b) In Problems 2 and 3, a DG group is controlled to act Rule: Communication matrix S is piecewise constant,
as a virtual FACTs element supporting the voltage of and the corresponding sequence S:0 {S (t0 ), S (t1 ),...} is
a critical bus. In general, it is difficult to determine
sequentially complete.
the critical bus for a large-scale power system. The
The above sequential completeness condition is a very
common practice is by simulations or by experience.
precise method to schedule local communication, and it is
For a radial distribution network, existing simulation
also the necessary and sufficient condition for any
studies [2, 6] have shown that the bus at the end of a
properly-designed cooperative system to converge [18, 23].
feeder is typically the one subject to voltage violation
A more restrictive (sufficient but not necessary) condition
when power from DGs changes intermittently. Thus,
is that the composite graph is strongly connected (which
in our simulations, the end bus of a feeder is chosen to
implies that, by following the directed branches, every
be the critical bus.
node can be reached from any other node). To illustrate its
c) Problem 3 aims to coordinate any given DG group
application, consider communication matrix S (tk ) and
with the overall power grid. The desired active and
reactive power output (i.e., reference values P ref and construct the corresponding graph by linking the nodes
V ref ) of the PV group can be determined by either according to non-zero entries in S . One can easily
offline or online optimization approach or by one of determine whether the resulting graph has at least one
the market-based approaches [6, 13, 22]. Once P ref globally reachable node or not. For instance, consider the
graphs in Figure 2. Figure 2(a) has node 0 as the unique
and V ref are obtained, the extended power flow
globally reachable node; and none of the nodes in Figure
equations of (6) and (16)-(17) could be used to
2(b) is globally reachable because there are two isolated
determine the groups aggregated power output
groups of nodes.
(which in turn yields the actual output ratios of the
active and reactive power, P0 and Q0 ). Could the
high level control collect enough information
(including the parameters of the power system
network with virtual DG generators), the desired
output ratios of every PV group can be calculated
directly. Otherwise, the high-level control for system Figure 2: Sample graphs of communication topology: (a) existence of
one globally reachable node; (b) absence of globally reachable node
coordination needs to be designed as prescribed in
subsection IV.B. The above general method can be used to verify or
establish the sequential completeness condition, and the
III. Rule of Communication Topology Design details can be found in [18, 23]. In designing distributed
control for PVs in a distribution network, we choose to
As outlined in the previous section, the topology of the focus our attention to the following very special case of
local communication network among the PVs in one local communication topology: If matrix S (tk ) has at least
group can be intermitted (time varying) and asynchronous,
in which case the communication matrix S describing the one globally reachable node for every k 0 , then
topology becomes piecewise constant. To ensure that a sequence S:0 is guaranteed to be sequentially complete.
given utilization profile is achieved among one group of The following example further explains this special case
PVs, there need to be local information sharing among the for the sequential completeness condition. Consider a
DGs. Heuristically, the more communication channels matrix sequence {S (t0 ), S (t1 ),...} defined by S (tk ) Si for
6
k 3 i where i 0,1, 2 and N is an integer; and sij is the generic entry of matrix S defined in (14)
1 0 0 0 1 0 0 0 1 0 0 0 for ui1 . Similarly, S can be defined for ui 2 and sij is
1
1 0 0 1
1 0 1 1 1 0 1
S0 , S1 , S2 . its generic entry.
1 0 1 0 0 0 1 1 1 0 1 1 Without loss of any generality, lets choose for simplicity
0 0 1 1 1 0 0 1 0 1 0 1 that
Figure 3 plots the graphs corresponding to those K d 1 K q1 K dn K qn K 0 (23)
communication topologies. It follows from Figure 3 that Then, it follows from (18)-(21) and (23) that the closed
the information can propagate from node 0 to nodes 1, 2 loop system becomes
and 3. Therefore, all of the communication matrices are Pi P n D P
K 0 i Di 0 P 0 ,
ij j
complete by themselves, and so are their sequences.
Pi max Pi max j 1 Pj max
(24)
Q i Q n D Q
K 0 i Di0 Q 0 . (25)
ij j
Qi max Qi max
j 1 Q j max
V. Simulation Study chosen for a radial network with intermittent DGs); active
power control is to keep a constant amount of power move
In this section, the standard IEEE 34-bus distribution downstream of the feeder (line 1 and its positive direction
network is used to illustrate effectiveness of the proposed are shown in figure 6).
distributed two-level controls. The network has its main Matrix of communication topology:
voltage at 24.9kV. Its topology is shown in Figure 6. Its The local communication network is represented by
DGs include 16 PV generators and one gas turbine matrix S in (34) where Gi denotes the ith PV generator
generator. Simulations are done using Digsilent, and
(i=1,2,16) and G0 is the high-level controller (which
balanced distribution networks are considered.
coordinates the aggregated power and hence is considered
to be a virtual PV generator in the lead). Unless mentioned
otherwise, matrix S of (34) is the one used in the
simulation.
G0 G1 G2 G3 G6
1 0 0 0 0 0 0 0 G0
1 1 1 1 1 0 0 0 G1
1 1 1 1 1 0 0 0 G2
0 1 1 1 1 0 0 0 G3 (34)
S
0 1 1 1 1 0 0 0 G6
0 0 1 1 1 1 0 0 G4
0 0
0 0 1 1 1 0 0 1 G16
As specified by (34), the 1st and the 2nd PV generators
receive the information from the high-level control;
generators G1, G2, G3 and G6 are closely coupled, and
the rest of generators follow G2 up to G6 by receiving
information from them.
It is easy to verify that the aforementioned
communication topology satisfies the communication rule
presented in section III. In fact, the communication
topology is intentionally chosen to be redundant so that, if
some of the entries in matrix S were to switch from 1 to 0
intermittently, the communication rule should still be
observed unless many of the communication channels stop
working at the same time. This shows that the local
communication network can be designed to be robust.
In this distribution network, the distributed generators
Figure 6. Diagram of the IEEE 34-bus network (including the gas turbine generator) provide power to not
The parameters of the system can be founded at the link only the local loads but also the external main grid. In the
http://ewh.ieee.org/soc/pes/dsacom/testfeeders.pdf. Basic simulation, total penetration levels of DGs and PVs are to
operational conditions, dynamical models and other be increased up to about 360% and 220%, respectively.
settings are: The corresponding voltages at the PV terminal buses are
PV parameters: The initial maximums of active and shown in Table 1 with different PV penetration levels
reactive power are set to 1 MW and 1MVAR, respectively. (provided that all the PVs are run according to the fair
Loads: 1.45MW+j0.85MVAR. Their model is utilization profile and their power factors are also kept to
composite (a dynamical part and a constant impedance be same). From this table, one can see that, if the
part of 50% each). penetration level of PVs is raised further, the bus voltage
Gas turbine generator: Its active power is 2MW and shall go out of the feasible range (0.9p.u.-1.1p.u.). Thus,
the terminal voltage is set to 1.0 p.u.; the default model in unless being controlled appropriately, operations of this
Digsilent is used with IEEE Type 1 control for AVR, system will have voltage problems under certain
PSS_ostab1 model for the PSS, and the IEEE-G1 model disturbances.
for the governor. The subsequent simulation study is to verify that, under
PV generators: 3.2MW+j0.16Mvar ( cos 1.0 ). disturbances and interruptions, the proposed distributed
two-layer control can make the system operate well and all
External grid: An infinite bus (1.0 p.u.).
the PV generators outputs converge according to the
The parameters in the aforementioned dynamical models
desired utilization profile. The following cases are
are included in the appendix.
simulated:
High-level controls: The voltage is controlled for the
A) Short-circuit faults;
critical bus to which PV 1 is connected (Recall that, as
B) Changes in sunlight;
discussed in section IV, the last bus in a feeder is typically
9
C) Load changes and intermittent communication It can also be observed that, at the time that the fault
interruptions. occurs, the active power generated by the PV generators
decreases, so does the active power across line 1.
Table 1. PVs terminal bus voltage for different levels of PV penetration
Accordingly, the high-level control commands PV 1 and
PV 0% 50% 100% 220%
PV 2 to increase their power output ratios and, as the
1 0.912 0.947 0.978 1.046
2 0.912 0.947 0.978 1.046 result of the proposed cooperative control, all the rest of
3 0.950 0.969 0.986 1.023 PV generators follows. At the end, all the PV generators
4 0.924 0.955 0.983 1.043 asymptotically reach the fair utilization profile. This
5 0.919 0.950 0.979 1.039 transient process is plotted in figure 7(3). Reactive power
6 0.912 0.947 0.978 1.046 is controlled in a similar way, as shown in figure 7(4).
7 0.912 0.947 0.978 1.046
8 0.912 0.946 0.978 1.045 B. Dynamic responses to rapid changes in sunlight
9 0.912 0.946 0.977 1.044 Next, sudden changes of available power due to weather
10 0.950 0.969 0.966 1.021 conditions are considered. In the simulation, the maximum
11 0.951 0.969 0.986 1.021 active power capacity of PV 1, PV 3 and PV 5 are to vary
12 0.966 0.976 0.985 1.002 between 10% and 100%, as shown in figure 8(1).
13 0.916 0.949 0.978 1.042 Figure 8 shows the dynamical responses of the system.
14 0.913 0.946 0.978 1.044 In particular, the active/reactive power output ratios are
15 0.912 0.946 0.978 1.044
shown in figures 8(2) and 8(3), respectively; and the
16 0.912 0.946 0.978 1.044
power transmitted over line 1 and the bus voltages are
A. Dynamic responses to short circuit faults plotted in figures 8(4) and 8(5), respectively.
The fault location is labeled by point (a) or the When the sunlight reaching a PV generator starts to
associated red dot in figure 6. The fault at point (a) occurs decrease, the active power output ratio initially increases
at 0.0s and is cleared after 0.12s. The resulting dynamical since the maximum available power of the corresponding
responses of the network are shown in Figure 7. PV generator is decreased. This process is apparent in
Figure 7 shows that the system is asymptotically stable figure 8(2) and 8(3) in which the active power output
under this fault and the corresponding time scales are in follows the trend of changes in sunlight except for the
seconds. In comparison, dynamics of internal state transient responses due to the aforementioned reason and
variables such as those of synchronized generators are to the controls.
much faster than the changes in PV generators outputs.
Pi max1
This validates the assumption (made in section II) that, for
0.5
the power control problem, those internal dynamics can be
ignored. 0
0 10 20 30 40 [s]
1.01 0
0.99
-5 0 5 10 15 [s]
-0.8
-5 0 5 10 15 [s]
Qi 0.02
0.01
zi
0.1 0
z0 P0 z0 Q0
0.3
zi 0 10 20 30 40 [s]
0.25
0.05
2.5
0.2
0
Ptran 2
0.15
1.5
0 10 20 30 40 [s]
0.1 -0.05
-5 0 5 10 15 [s] -5 0 5 10 15 [s]
V Vc
1.15 1.05
Vc Ptran2.5
1.1
2 1
1.05 0 10 20 30 40 [s]
1
1.5 -0.25
0.95
-0.3
0.9 1
-5 0 5 10 15 [s] -5 0 5 10 15 [s]
0 10 20 30 40 [s]
Figure 7. Dynamic responses under fault (a): 1) Frequency of Figure 8. Responses under sunlight changes: 1) Sunlight changes; 2)
gas-turbine generator; 2) Angle of the gas-turbine generator; 3) Active Active power outputs of PV generators 1, 2, 3 and 5; 3) Reactive power
power output ratios for PV generators 1 to 4; 4) Active power output output ratios of PV generators 1, 3 and 5; 4) Active power across line 1; 5)
ratios for PV generators 1 to 4; 5) Critical bus voltage; 6) Active power Voltages at the critical buses; 6) Rotor angle of the gas-turbine.
transmitted over line 1.
10
As sunlight changes, the distributed cooperative control or with communication interruptions. The output ratios of
makes PV output ratios converge to new operating points representative PV generators (PVs 1-3) are plotted in
determined by the distributed high-level controls. The Figure 12. As expected, we see by comparing solid and
high-level controls do not know the current generation dashed trajectories that convergence is faster without
capacity of all the PV generators since they communicate communication interruptions.
only with PV generators 1 and 2. Nonetheless, during the 1.5
whole period of system operation, the active power sent s20 1
over line 1 and the bus voltages are maintained around 0.5
their designated values, which are shown in figures 8(4) 0
z 0.02 z0 0.2
0.05
0.01 0.1 0
z3 0 10 20 30 [s] 0 10 20 30 [s]
0 1.1
0 10 20 30 40 [s] Vc Ptran 3
(2) 1.05
2
Figure 9. Responses to sunlight changes: 1) Active power ratios of PV 1, 1
PV 3 and P ; 2) Reactive power ratios of PV 1, PV 3 and Q .
0 0
1
0.95
autonomously adjust their outputs to converge to a Figure 11. Responses to load changes with and without intermittent
prescribed utilization profile (i.e., the fair utilization communication
profile). In what follows, a case is studied to show that the
proposed control also has strong robustness against
communication interruptions and load variations. z 0.6 z 0P PV 1 PV 2 PV 3
Vmin 0.2p.u. .
Vng max
Vmgmx
V K ang
E fd
1 Tang s
0 0
H lim Vmax
Ks (1 T1 s )(1 T2 s )
1 Tw s (1 T3 s)(1 T4 s) U pss Zhihua Qu (M90, S93, and F09) received his
L min Vmin Ph.D. degree in Electrical Engineering at the Georgia Institute of
Technology in June 1990. Since then, he has been with the University of
Central Florida (UCF), currently a Professor and Interim Chair of ECE
Figure 14. Transfer function of PSS-ostab2 and the SAIC Endowed Professor of UCF. Dr. Qus areas of expertise are
nonlinear systems and control, energy and power systems, autonomous
The governor in the gas turbine generator is the vehicles and robotics. In energy systems, his research covers such
IEEE-G2 model, the transfer function is shown in Figure subjects as low-speed power generation, dynamic stability of distributed
power systems, anti-islanding control and protection, distributed
15, and the parameters are: K 5s , T1 0.5s , generation and load sharing control, distributed VAR compensation,
T2 T4 0.1s , T3 0.95s , Pmin 0p.u. , Pmax 1.0p.u. . distributed optimization and cooperative control. Dr. Qu is the author of
three books: Robust Tracking Control of Robot Manipulators by IEEE
Pmax Press (1996), Robust Control of Nonlinear Uncertain Systems by John
PM Wiley & Sons (1998), and Cooperative Control of Dynamical Systems
K (1 sT2 ) Ka 1 sT4
with Applications to Autonomous Vehicles by Springer Verlag (2009).
(1 sT1 )(1 sT3 ) 1 Ta s 1 0.5sT4
Dr. Qu is a Fellow of IEEE and currently serving on Board of Governors
P0 Pmin of IEEE Control Systems Society and as Associate Editor for Automatica,
IEEE Transactions on Automatic Control, and International Journal of
Figure 15 Transfer function of Gov-IEEEG2 Robotics and Automation.
k pu sTpu
1 sT1 1 Qext