Ventilation System in Car Park
Purging of Smoke and Heat based on Induced Jet Fans
Air Jet Fan Normal ventilation is used during normal traffic operation to maintain acceptable levels
Ventilation System of contaminants (CO and CO2) in the car park areas. A 6 ACH (Air Change per Hour) is
recommended for the normal ventilation purpose.
A ventilation system that is based on Emergency Ventilation is introduced during a fire mode to remove, control and dilute of
the utilisation of induced air jet fans is smoke and contaminants particles. The major purpose of emergency ventilation is to
an alternative to the conventional duct provide a car park environment sufficiently clear of smoke and hot contaminant gases to
system. The air in one region can be permit safe evacuation. Building regulations state the requirement for 10 ~ 12 ACH (Air
transported through a long distance by Change per Hour) in the event of fire operation.
the induction of the air through the fan
units in a series mode. However there
are many factors such as the allocated
number of units and the volume flow
rate of each of these units that affect an
optima arrangement of fans to provide
good ventilation. In addition, there are
also flow barriers and obstacles in an
architectural facility such as pillars and
beams that will affect the air flow of the
system. Such an arrangement is also
dependent on the structural
configuration of the building. Kruger has Illustration of system velocity profile using Surface response curves for z-
the expertise of presenting effective colour plot. 500 monitor points scattered vector velocity
ventilation under fire conditions. An over 1819 meters (represented by black
operational example of the vehicle dots) measure the localised z-velocity in the
tunnel ventilation during a fire outbreak (x, z) spatial grid
is shown below.
Tunnel
Entrance
and
Fresh air
inlet
3
Kruger Jet Fan Ventilation System
Integrating our fans to design the perfect ventilation system
Higher efficiency:
Reduce system loss of complicated ductwork. Thus, reduce motors power,
sound level, and finally electrical consumption reduction.
4
Smoke Control Using Jet Fans
Looking into the modern smoke control system
Kruger Smoke Control System + ch7 ch6 ch5 ch4 ch3 ch2 ch1 ch0
Frequency Inverter
Control Signal Exhaust Fans
-
Exhaust Fan Controller Activation Smoke, Heat
CO
The control system typically consists of smoke, heat and Smoke Control System
5
An Effective Ventilation System
Our system design methodology
Systematic approach for the design of Kruger Jet Fan Ventilation System in a car park
6
Computational Fluid Dynamics
A powerful tool in our organisation
A fire is typically simulated within the facility and the fans are
Computational Fluid Analysis activated to the full power mode. The volume flow rate of
each fan is doubled and smoke concentration plots are
prepared for the fire situation. For both the normal and
emergency operational modes, the CFD model of a ventilation
Computational Fluid Dynamics (CFD) analysis has been system is sometimes verified using experimental results.
undertaken to provide an effective method of determining Useful deduction on the performance of the system is made.
the optimum placement of induce air jet fan units in an Steady and transient state solutions provide insights on the
enclosure, so as to achieve the best ventilation. The most effective smoke control using our designed ventilation
examination of the air circuitry is important in ensuring system.
that the distribution of air and its movement properties are
sufficient to provide the enclosure for both general and
emergency ventilation cases. In a car park, the general
Fire simulation in car park from isometric
ventilation of carbon monoxide (CO) and carbon dioxide view
(CO2) is achieved by the daily and periodic operation of the
induce jet fans. During a fire outbreak when smoke is
produced at high rates, all the fans are activated at full
power to push the dangerous contaminants out of the
building. Therefore, it is vital that jet fans are positioned
strategically throughout the car park to maintain a
distribution of air that covers sufficient areas to remove
potential stagnant air regions known as dead spots and
which moves fast enough to transport any contaminants
produced within the enclosure.
CFD has been used to illustrate the effectiveness of CFD simulation outputs enables us to predict the
positioning fans based on our specialists proposed distribution of smoke and heat from a fire source
configuration. The degree of ventilation is analysed and how air flows through the spatial region in
using the speed, smoke concentration, and the car park
temperature contour plots of the ventilation system
that is operating at normal and emergency modes
from the front, plan and side views
Air jets from fans at fan height Smoke Concentration Level (ppm)
level
7
General Information
Contacting our organisation
SINGAPORE SINGAPORE
KRUGER VENTILATION INDUSTRIES PTE LTD KRUGER ENGINEERING PTE LTD
No. 17, Tuas Avenue 10 No. 17, Tuas Avenue 10
Singapore 639141 Singapore 639141
Tel. +65 68611577 - Fax +65 68613577 Tel. +65 68631191 - Fax +65 68631151
Email: mktg@krugerasia.com Email: mktg@krugerasia.com
MALAYSIA THAILAND
KRUVENT INDUSTRIES (M) SDN BHD KRUGER VENTILATION IND. (THAILAND) CO. LTD
Lot 8, Jalan Perusahaan 2 Batu Caves 1/19 Moo 2 Rama II Rd, Tasai
Industrial Area, 68100 Batu Caves Selangor Mueng Samuthsakorn 74000, Thailand
Tel. +603 61888293 - Fax +603 61898843 Tel. +66 34-490164-9/375-6 - Fax +66 34-490170/377
Email: mktg@kruger.com.my Email: mktg@kruger.co.th
BEIJING GUANGZHOU
BEIJING KRUGER M&E EQUIPMENTS CO. LTD GUANGZHOU KRUGER M&E INDUSTRIES LTD
No. 1A Fuyuan South Road No. 1270 Maogang Road, Huangpu
Beijing Economical And Technological Guangzhou, P.R. China 510700
Development Area, Beijing China 100176 Tel. +86 20-82287634 - Fax +86 20-82287624
Tel. +86 10-67881366 - Fax +86 10-67880566 Email: gzkruger@krugerchina.com
Email: krugerbj@krugerchina.com
WUHAN TAIPEI
WUHAN KRUGER INDUSTRIES CO. LTD KRUGER VENTILATION (TAIWAN) CO. LTD
No. 12 Heping Tieji Industries Parden Hongshan No. 157, Ping-an Rd, Hengfeng Village,
Economic Zone, Wuhan P.R.China 430063 Dayuan Shiang Taoyuan County 337, Taiwan(ROC)
Tel. +86 27- 86718165 - Fax +86 27- 86825719 Tel. +886 3-3859119 - Fax +886 3-3859118
Email: whkruger@krugerchina.com Email: kruger@ms27.hinet.net
PHILIPPINES AUSTRALIA
KRUGER M&E INDUSTRIES CORPORATION KRUGER VENTILATION (AUSTRALIA) PTY LTD
FAPI Compound, E. Rodriguez Ave. 4 Blackfriar Place, Wetherill Park
Tunasan, Muntinlupa City, Philippines 1773 NSW 2164, Australia
Tel. +63 2-8622891-97 - Fax +63 2-8621287 Tel. +61 2-97562008 - Fax +61 2-97560808
Email: mktg@krugerph.com Email: auscheng@tig.com.au
INDONESIA INDIA
P.T. KRUGER VENTILATION INDONESIA KRUGER M&E INDUSTRIES (INDIA) PVT LTD
Ruko Mahkota Mas Blok C No. 20 Pardhy House 1st Floor
JL. M.H. Thamrin Cikokol Tangerang 15117 Junction of Hanuman Road & MG Road
Tel. +62 21-5543107/8 - Fax +62 21-5543016 Vile Parle (East) Mumbai 57
Email: kia@krugerindo.co.id Tel. +91 22-56926095/6/7 - Fax +91 22-56926098
Email: sales@krugerindia.com
KOREA
NEOMATE TECHNOLOGY & CONSULTING CO. LTD
#A-407-1, Ansung B/D, 410-13, Shindorim-Dong,
Kuro-Gu, Seoul, Korea
Tel. +82 02-2679-2052/3 - Fax +82 02-2679-2174
Email: neomatetnc@chol.com