Gate City Ohsaki, East Tower, 11-2, Osaki 1-chome, Shinagawa-ku, Tokyo 141-0032, Japan
Phone : (03)5435-7111
world, because of the advantages: Small overall dimensions The modular design principle
Small space requirement make for minimum space requirements applied Voltage
High reliability Maintenance
and very low profile needs very little permits quantity production and the use of earthing switch transformer
Safety vertical clearance. standard parts, which increase reliability
Current Line disconnector
Environment compatibility Hence the costs of foundations and and simplifies stock-keeping. transformer
Make-proof
Long maintenance intervals buildings can be reduced. earthing switch
Minimum erection period at site The fully earthed enclosure
The steel enclosure used protects the operating personnel and
Fuji alone has installed a great number of
is highly resistant to arcing and affords the prevents HF interference.
switch bays for 72.5 kV to 300 kV since
personnel optimum protection. A further There is no risk of touching live parts and
1970, both at home and abroad. Circuit
advantage of the steel enclosure is their also atmospheric pollution.
The three phase encapsulated switchgear breaker
high mechanical strength.
for 72.5 kV was developed in 1975
Unified SF6 gas pressure
and since then the installation of SF6 Bus disconnector Bus disconnector
Long service life throughout the switchgear makes Control
switchgear has increased rapidly. After box for GIS
of the switchgear is expected due to non- simplified gas maintenance work.
three years in 1978, Fuji has put into
oxidizing of SF6 gas in enclosure and oil
operation the first three phase
in electro-hydraulic operating mechanism.
encapsulated SF6 switchgear for 170 kV
in the world.
On the excellent experience of SF6 Cable
sealing end
switchgear, Fuji has a compact and
reliable three phase encapsulated SF6 Surge
Operating box Maintenance
switchgear : type SDF. for curcuit earthing arrester
Technical data breaker switch
Busbar Busbar
1 2
Circuit Breaker Hydraulic Operating Mechanism
Thousands of Fuji SF6 circuit breakers with hydraulic operating Oil pump, oil tank, main valve, auxiliary valves, pressure switches
Circuit breaker Hydraulic operating mechanism
mechanism were delivered into all over the world and have been and gauges are incorporated as one block unit and connected
in satisfactory operation since 1973. directly to main cylinder.
The SF6 switchgear SDF is equipped with the single pressure Hence a compact, very reliable and pipeless hydraulic operating
puffer type gas circuit breaker with hydraulic operating mechanism Upper connecting conductor mechanism was realized.
which is used uniformly also for outdoor circuit breakers. Earthed housing The valve seal of oil system is made of metal seat and metal ball,
Fuji gas circuit breakers have the advantages: which is good for permanent use without necessity of replacement.
Three phase interrupters
Low noise level during operation But the valve seal of air system is made of rubber, which degrades
Nozzle
Excellent interrupting performance its quality and requires replacement periodically.
Arcing contacts Interrrupter
Long maintenance intervals
Main contact
Individual energy supply, no air-compressor necessary
Moving contact
Lower connecting conductor
The earthed housing accommodates three phase interrupters Puffer cylinder
Support
fixed on supporting mounts. At the lower part of circuit breaker, Insulating rod
the operating box is arranged, which accommodates hydraulic Control box for GIS
operating mechanism and monitoring unit for the circuit breaker. Closing
Supporting mounts
The interrupter has a double-flow system and the compressed SF6 Closing coil energized
gas, which is produced by the downward movement of the puffer Pilot valve opens.
cylinder at opening, flows into both directions in order to distinguish Main valve opens.
effectively the arc generated at arcing contacts. Main cylinder moves.
The moving section is composed of nozzle, moving contact, and
a moving cylinder connected to hydraulic operating mechanism Opening
Cylinder rod Trip coil energized Accumulator
through insulating rod and cylinder rod mechanically.
The current path is composed of upper connecting conductor, Pilot valve closes.
fixed contact support, main contact, moving contact, support and Operating box for Main valve closes. N2
circuit breaker Main cylinder moves.
lower connecting conductor.
31.5 Mpa
Pilot valve Trip coil
0MPa Closing coil
Opening
Principle of arc quenching
Closing
Closed position Opening Opening (arc quenching) Open position
Main cylinder
M P
Aux.switch
Main valve
3 4
Other Components SF6 Gas System
Rated SF6 gas pressure is unified at 0.5 MPa for all components. The gas system for the circuit breaker is independent of the
Disconnectors and earthing switches Busbar SF6 gas pressure changes depending on the ambient temperature other parts of the switchgear. The SF6 gas filled disconnector/bus
There are two kinds of disconnectors employed in the switchgear: The three phase conductors made of aluminum or copper, as shown in pressure-temperature characteristic curve. chamber is sealed off from the adjacent bays by gastight and arc-
the linear type disconnector provided in a linear current passage, depending on the current rating, are supported by gas tight The monitoring of SF6 gas is carried out by means of temperature proof disconnectors. A similar insulator seals off this chamber from
and the right-angled type disconnector provided at right-angle insulator (for standard bay bus) or individual supporting insulators compensated pressure switches in the manner as tabled below. the circuit breaker.
of the current passage. Line disconnector is of linear type and is (for extended bus). [at 20 ] All gas zones are monitored by gas density relays. The switchgear
incorporated together with earthing switch in one housing as a The three phase conductors are arranged in a rational disposition has a very low gas leakage rate. Guaranteed gas loss is less than
SF6 gas pressure Rated Low Operation
combined disconnector/earthing switch. Bus disconnector is of to reduce the intensity of electric field on the surface of lower part SF6 gas alarm lockout 0.5 % per annum.
right-angled type and is assembled in each bus enclosure. of enclosure and hence be reliable against the metallic dust, which pressure pressure pressure
Disconnectors and earthing switches are normally motor-and can possibly enter during site erection. Components [MPa] [MPa] [MPa]
SF6 gas system
manual-operated. When disconnectors are specified to have Circuit breakers 0.5 0.45 0.4
a switching capability of small current as charging current and Disconnectors 0.5 0.45 (Note)
transformer magnetizing current, they are operated by the motor- Extended bus earthing switches
VT
Pressure
0.4
compact and economical.
0.3 : Gas tight disconnector : Stopping valve(N.O.)
Conductor Rated pressure0.5 MPa at 20 : Stopping valve(N.C.)
Voltage transformer 0.2
Alarm pressure0.45 MPa at 20 PS : Temperature compensated pressure switch
Supporting insulator (low alarm, operation lockout)
0.1 Lockout pressure0.4 MPa at 20
The voltage transformer is of the inductive type. SF6 gas provides PS : Temperature compensated pressure switch
the high-voltage insulation. 0 (low alarm)
The high-voltage winding discs are well insulated by plastic foils. 30 20 10 0 10 20 30 40 50 60 : Gas pressure gauge : Gas port
Temperature
The SF6 gas provides permanent impregnation for the foil
insulation.
Surge arrester
The surge arrester consists of zinc oxide (ZnO) element with
excellent low residual voltage characteristics and long service life.
5 6
Typical Arrangement Application Examples
Dimension: mm The first three phase encapsulated SF6 switchgear for 170 kV SDF120 for mobile substation for 170 kV 1250 A 40 kA
Cable feeder unit with single bus (mass : 13 t including VT, LA) Single line diagram
1400
4400
3400
Layout
3400
N99-2029-12
7 8
Three Phase Encapsulated Type
SF6 Gas Insulated Switchgear
Type SDF for 170 kV