DryTypeTransformerTesting
FromOpenElectrical
Contents
1 Introduction
2 Testing
2.1 InsulationResistanceTests
2.2 DielectricLossAngleMeasurementTests
2.3 PartialDischargeTests
2.4 FrequencyResponseAnalysis
2.5 AcousticEmissionTests
2.6 ThermographicSurveys
3 References
Introduction
Theprimaryconcernwithalltransformers(andalsothekeyindicatoroflifeexpectancy)istheconditionofthe
insulationsystem.
Fordrytypetransformers,theinsulationsystemconsistsofthecastresinwindingandcoreinsulationandthe
terminationsysteminsulation(e.g.bushings).Thestructuralstrengthandinsulatingpropertiesofmaterialsusedfor
theseinsulationsystemsdegradeovertimethroughnormalageing.Theycanalsodegradeprematurelyasaresult
ofoverheatingandmechanicalandelectricalstresses(e.g.faults,overvoltages,inrushcurrents,etc).
Theinitialbreakdownofinsulationaroundthewindingscanresultininterturnfaults,especiallyonthehigh
voltagewindingswheretheelectricfieldstrengthishighenoughtoioniseairgapsandcausecoronaactivity.Inter
turnfaultsareshortcircuitsbetweencoilturnsonasinglewinding.Furtherdegradationoftheinsulationcouldsee
interturnfaultsdevelopintomoreseriousfaultssuchasinterwindingandearthfaults.
http://wiki.openelectrical.org/index.php?title=DryType_Transformer_Testing 1/5
5/1/2017 DryTypeTransformerTestingOpenElectrical
Testing
Themostfrequentmodeoffailurefordrytypetransformersisinsulationbreakdownresultingininterturnfaults
whichleadstomoreseverefaultssuchasphasetophasewindingorearthfaults.Theinsulationconditionof
componentpartsofthetransformer(i.e.windings,core,bushings,etc)canbedeterminedbyasuiteoftests.
Dissolvedgasanalysisisthemostcommonlyusedmethodfordeterminingwindinginsulationconditioninoiltype
transformers,butisnotpossiblefordrytypetransformers.
Thefollowingtestsarediscussedfurther:
Insulationresistance/polarisationindextests
Dielectriclossanglemeasurementtests
Partialdischargetests
Frequencyresponseanalysis
Acousticemissiontests(inconjunctionwithpartialdischargetests)
Thermographicsurveys
InsulationResistanceTests
Insulationresistance,measuredbyapplicationofanimpressedDCvoltage(i.e.Megger),givesageneralindication
oftheinsulationconditionbetweenthephasewindingsandearth.Themeasurementsaretypicallytakenovertime
(i.e.1minuteintervalsover10minutes)togenerateacurve,calledtheDielectricAbsorptioncurve.
ThePolarisationIndexisthesteepnessofthecurveatagiventemperatureandisdefinedasperthefollowing
equation[1]:
http://wiki.openelectrical.org/index.php?title=DryType_Transformer_Testing 2/5
5/1/2017 DryTypeTransformerTestingOpenElectrical
R 10
PI =
R1
Where
R10=megohmsinsulationresistanceat10minutes
R1=megohmsinsulationresistanceat1minute
ThePolarisationIndexindicatestherelativedrynessandlevelofmoistureingressintotheinsulation.
DielectricLossAngleMeasurementTests
Dielectriclossangletests,alsocalleddissipationfactor,powerfactorortandeltatests,determinetheinsulation
dielectricpowerlossbymeasurementofthepoweranglebetweenanappliedACvoltageandtheresultantcurrent.
Intheidealinsulator,thepoweranglewouldbe90Casitispurelycapacitiveandnonconducting.Howeverin
realinsulators,thereissomeleakagecurrentandresistivelossesthroughthedielectric.
Relativeincreasesindielectricpowerlossesareindicativeofinsulationdeteriorationandmayfurtheraccelerate
degradationduetoincreasedheating.Notethatdielectricpowerlossdoesnottranslatetodielectricstrength,
thoughthereareoftencommoncausesforincreasesinpowerlossanddecreasesindielectricstrength.
Thecosineofthepowerangle()iscalledthepowerfactor.Thecomplementofisdenotedasshowninthe
diagramabove.Thepowerfactorcanbepracticallyapproximatedbytakingthetangentof(hencethenametan
delta).Thisapproximationiscalledthedissipationfactorandisroughlyequaltothepowerfactorbetweenvalues
of0and0.08,whichcoversthemajorityoftests.
Thedissipationfactorisessentiallytheratiobetweentheresistiveandcapacitivecomponentsoftheinsulationand
canbemeasureddirectly(viaacapacitancebridgecircuit).Thelowerthequalityoftheinsulationcondition,the
moreresistiveitwillappearandthemorepowerlosswillbedissipatedthroughit(intheformofheat).
Theincreaseinthedissipationfactorvaluesasthetestvoltageisincreasediscalledthe"tipup".
Thetechnicalliteratureonthissubjecthasnotedthatthistestisusefulfordetectingmoistureingressinthe
bushingsandwindings.About90%ofbushingfailuresmaybeattributedtomoistureingressevidencedbyan
increasingpowerfactorfromdielectriclossangletestingonascheduledbasis.
PartialDischargeTests
http://wiki.openelectrical.org/index.php?title=DryType_Transformer_Testing 3/5
5/1/2017 DryTypeTransformerTestingOpenElectrical
Partialdischargesarelocalisedincipientelectricaldischargesthatonlypartiallybridgetheinsulationbetween
conductors.Partialdischargescanoccurinanylocationwherethelocalelectricalfieldstrengthissufficientto
breakdownthatportionofthedielectricmaterial(whetheritbedeterioratedinsulationorair).Indrytype
transformerstheycanoccurwithinairfilledvoidswherethesolidinsulationhasdegraded.
Partialdischargetestingcandetectthepresenceandlocationofpartialdischargeactivityinatransformer.Partial
dischargesintransformersaretypicallymeasuredbyapplyingaprespecifiedvoltagetothetransformerwindings
andmeasuringinducedchargesviaacouplingdevice(e.g.couplingcapacitors).
AS60076.11andAS60270setouttherequirements,procedure,equipmentandacceptancelevelsforpartial
dischargetesting[3][4].ItshouldbenotedthatthepartialdischargetestsspecifiedinAS60076.11areintendedas
routinetestsfornewtransformers.Thisinvolvesapplyingaprestressvoltageof1.8timesratedvoltagetothe
windings.Thismaybeexcessivefortransformersalreadyinserviceforover20years.
Analysisofthepartialdischargemeasurementsgathered(i.e.pulsewaveforms,magnitude,durationandintervals
betweenpulses)canbeusedasaguideregardingtheconditionoftheinsulation.Theresultscanbetrendedtochart
therateofinsulationdegradationbetweenconsecutivetests.
FrequencyResponseAnalysis
Frequencyresponseanalysisisadiagnostictestingtechniquethatmeasurestheimpedanceofthetransformer
windingsoverawiderangeoffrequencies.Themeasurementsarecomparedwithareferencesetandthe
differencesarehighlighted.Thedifferencesmayindicatemechanicaldamagetothewindings(e.g.winding
displacementorloosewinding)andelectricalfaults(e.g.interturnfaults).
Frequencyresponseanalysiscanbeachievedbyeitherinjectingalowvoltageimpulseintothewinding(i.e.
impulseresponsemethod)orbymakingafrequencysweepusingasinusoidalsignal(i.e.sweptfrequency
method).
Forfrequencyresponseanalysistobeuseful,abaselinereferencesetofmeasurementsneedtobedeterminedand
periodictestsneedtobeconductedtocomparethedifferences.
RefertoresearchbyS.TenbohlenetalattheUniversityofStuttgart[5].
AcousticEmissionTests
Partialdischargesintransformerscanalsobedetectedandlocalisedviaacousticemissiontesting.Acoustic
emissiontestingisbasedontheacousticdetectionofthepartialdischargepulsesandconversiontoanelectrical
signal.Sensorsarecoupledtothesurfaceofthetransformerandduringoperationofthetransformer,theoutputof
thesensorsarefedintoanelectronicmodule.Thesignalsarefilteredtoremovenoiseandprocessedtodetermine
thepresenceandlocationofanypartialdischargesinthetransformer.
ThermographicSurveys
Infraredthermographyiscommonlyusedinpreventativemaintenancetodetecthotspots,especiallyatjointsand
terminations.IRThermographycamerasmeasuresurfacetemperaturesandtheresultingthermalimagecanbeused
toidentifyoverheatingatthetransformerterminations.
Forthermographicsurveystobeconducted,thermographicwindowsneedtobeinstalledlookingatthe
terminationsandwindings.
http://wiki.openelectrical.org/index.php?title=DryType_Transformer_Testing 4/5
5/1/2017 DryTypeTransformerTestingOpenElectrical
References
1.FacilitiesInstruction,StandardsandTechniquesVolume31,TestingSolidInsulationofElectrical
Equipment,U.SDepartmentoftheInterior,ReclamationBranch,December1991(http://www.usbr.gov/po
wer/data/fist/fist3_1/vol31.pdf)
2.FacilitiesInstruction,StandardsandTechniquesVolume331,TransformerDiagnostics,U.SDepartment
oftheInterior,ReclamationBranch,June2003(http://www.usbr.gov/power/data/fist/fist3_31/fist331.pdf)
3.AS60076.11,PowertransformersPart11:Drytypetransformers,2006
4.AS60270,HighvoltagetesttechniquesPartialdischargemeasurements,2001
5.ResearchatUniversityofStuttgart(includingTenbohlen'spapers)(http://www.unistuttgart.de/ieh/forschun
g/veroeffentlichungen/index.html)
Retrievedfrom"http://wiki.openelectrical.org/index.php?title=DryType_Transformer_Testing&oldid=531"
Thispagewaslastmodifiedon18February2017,at03:47.