Model TS-203B
FRONT VIEW FUNCTION
INSTRUCTION MANUAL On application of power front panel display shows
the Real Time Clock and if preprogrammed start
TS-203B TIME SWITCH time matches with RTC, relay comes ON and
www.eaplindia.com
remains on till the set duration time.
DIMENSIONS
NOTE: ALL DIMENSION ARE IN MM Manual Override Facility: By pressing the manual
button provided on the front panel the user can
toggle the output relay status there by flashing of
RTC.
This facility is conditional and gets terminated
during
a) Power failure
b) Altering the RTC
c) Completion of original intended program.
d) Changes in program settings.
Terminal Details
CONNECTIONS SIDE VIEW A1, A2 : Source voltage
Contact Rating
16Amps@250V AC Resistive
d) Keep the Mode switch in the reqd. position. Press program HRS HINTS ON CORRECT USAGE
or program MIN button to set reqd. timing. Repeate the same for
other settings. After setting 4 programs the mode switch must be After programming the time switch
brought to either 0 or 9 to save the program. remove the shorting across the CONTACT
terminals E1 & E2 where ever
RTC SETTING applicable. This facility will prevent Electronic Automation Pvt.
the tampering of program setting. Ltd
Short terminals E1 & E2, this shorting shall be potential free. # 20, KHB Industrial area
Apply power to source terminals to display the real time clock. Newtown Yelahanka
To alter Hrs. press Hrs. button on the front panel. The display rolls Bangalore -106
b/w 00 to 23.
Ph : +91-80-28567561/2 /42802345
To alter Min. press Min. button on the front panel. The display rolls
b/w 00 to 59. Email : info@eaplindiamail.com
The required RTC can be set by altering the above said buttons. www.eaplindia.com
In case of power failure the RTC display goes off. However, the
clock continues to run with the battery back up provided in the
unit. The display comes ON after a small delay when power is
resumed.