Prepared by
Martin Gough and Colin Rees
IES Ltd
Lord Hope Building
141 St James Road
Glasgow G4 0LT
UK
Tel: +44 (0)141 552 8368
2
Table of contents
1 Introduction................................................................................................................ 3
2 Description of tests ................................................................................................... 3
3 ApacheSim Models.................................................................................................... 7
4 ApacheSim Results ................................................................................................... 7
5 Observations on ApacheSim Results ...................................................................... 7
Heating load.................................................................................................................... 7
Cooling load .................................................................................................................... 8
Annual free-floating temperature output.......................................................................... 8
Basic sensitivity tests cases 600-960........................................................................... 8
Low-mass in-depth sensitivity tests cases 195-320 ..................................................... 9
Low-mass in-depth sensitivity tests cases 395-440 ................................................... 10
High mass in-depth sensitivity tests cases 800-950................................................... 10
Solar radiation tests ...................................................................................................... 11
6 Conclusions ............................................................................................................. 11
References ...................................................................................................................... 11
Appendix A. Apache simulation settings ..................................................................... 12
Figures............................................................................................................................. 15
3
1 Introduction
ANSI/ASHRAE Standard 140-2001, Standard Method of Test for the Evaluation of
Building Energy Analysis Computer Programs[1], defines a series of tests for building
energy simulation programs.
This standard method of test (SMOT) which has its origin in the IEA 12B/21C BESTEST
diagnostic tests[2], requires the simulation of a number of variants of a test building. The
test cases increase in complexity from a simple building shell without glazing, infiltration or
internal gains to comparatively realistic building types.
The aim of the tests is to identify and diagnose differences in predictions that may be
caused by software errors. The ways in which they can be used are listed in Standard
140-2001:
(a) comparing the predictions from other building energy programs to the example
results provided in the informational Annex B8 and/or to other results that were
generated using this SMOT,
(b) checking a program against a previous version of itself after internal code
modifications to ensure that only the intended changes actually resulted,
(c) checking a program against itself after a single algorithmic change to understand
the sensitivity between algorithms,
(d) diagnosing the algorithmic sources of prediction differences; diagnostic logic flow
diagrams are included in the informational Annex B9.
While the text of the Standard emphasises that all building models are simplifications of
reality, and full validation cannot be achieved by a single series of tests, the ASHRAE 140
tests provide a valuable benchmark by which the predictions of a simulation program may
be compared with those of its peers, as means to establishing a degree of confidence in
the correctness of its algorithms and their implementation.
This report presents the results of these tests applied to the simulation program
ApacheSim[3], as required by ASHRAE Standard 90.1-2001, Addendum p[4].
A brief outline of the tests is provided. This is followed by a description of the modelling
assumptions and settings used to run the tests in the ApacheSim program. The
ApacheSim results are then presented and discussed.
2 Description of tests
A full description of the tests, including input data, output reporting conventions and
terminology, is provided in the ASHRAE Standard. Here it will suffice to enumerate and
briefly describe the cases.
Figure 1 shows a sketch of the building which forms the subject of Case 600. This is
referred to in the Standard as the Base Case, of which all other cases are variants.
4
The building is a cuboid with one of its longer sides facing south. In Case 600 it has two
south-facing windows each of area 6m2.
Two groups of cases are identified: basic tests (cases 600-650 and 900-960) and in-
depth tests (the remainder).
Each case consists of simulating a variant of the test building over a year using a Denver,
Colorado weather dataset. The cases explore different combinations of the following
parameters and settings:
Glazing: none, high conductance opaque panel or double glazed window
Glazing orientation: south or east/west
Glazing shading devices: none, overhang (south), overhang + side-fins (E/W)
Fabric: low-mass or high-mass construction
Infra-red emissivity of internal ( i) and external ( e) surfaces: 0.1 or 0.9
Solar-spectrum absorptance of internal ( i) and external ( i) surfaces: 0.1, 0.6, 0.9
Internal gains: 0 or 200W
Infiltration: 0.0, 0.5 or 1.0 ach
Heating and cooling: different setpoint combinations or no heating/cooling
Venting: an option using night ventilation and free cooling
Sunspace: Case 960 examines the effect of an attached sunspace
In all the tests the issue of heat transfer with the ground is largely eliminated by the
inclusion of a thick layer of insulation in the floor construction.
Table 1 provides a summary of the test cases. The basic cases are indicated by
underlining. Bold text indicates salient differences from previously listed cases. The table
is divided into sections covering different heating and cooling control regimes. For
example, Setpoints 20, 27 means heating to 20C and cooling to 27C. Setback means
heating to 10C overnight (2300-0700) and to 20C at other times, with cooling to 27C.
Venting means continuous night ventilation between 1800 and 0700, cooling to 27C
during the rest of the day, and no heating.
Cases including the letters FF test free-floating conditions with no heating or cooling.
Case 960 is a version of Case 600 with an attached sunspace. The outputs tested are
heating and cooling loads in the room and the temperature in the sunspace.
6
3 ApacheSim Models
Modelling options used in ApacheSim are set out in Appendix A, using the format
specified in the Standard.
4 ApacheSim Results
The ApacheSim results are presented graphically in Figures 1-326, alongside the results
for other programs reported in ANSI/ASHRAE Standard 140-2001[1]. Results provided for
other programs in the earlier BESTEST report[2] but omitted from the ANSI/ASHRAE
Standard are indicated with a striped fill pattern. Results from the program EnergyPlus
version 1.1.0.020[6] are also included.
The results are presented in tabular form in the file ASHRAE 140 ApacheSim.xls, as
required by the Standard. This file contains certain additional data not included in this
report, including time series comparisons and binned temperature data for Case 900FF.
Heating load
CIBSE Guide A[5] algorithm for this process, which gives somewhat cooler sky
temperatures than some other methods.
Finally, in case 920, where the windows have shading devices, ApacheSim heating loads
will have been increased by the inclusion of diffuse shading in ApacheSims solar
calculations. ApacheSim, unlike most of the programs involved in the study, performs a
calculation of the obscuration of both short-wave and long-wave sky radiation by shading
objects. The inclusion of diffuse shading will have reduced the solar gain, causing an
increase in heating load.
The comparison of peak heating loads shows that ApacheSims predictions fall
consistently within the range of values calculated by the other programs.
Cooling load
solar heat transfer to the air point. The result is a small increase in annual cooling load for
case 230, but not for case 220, which has a fixed, and low, room moisture content.
These effects would of course not occur in realistic modelling situations where there is
always some degree of infiltration.
ApacheSim predicts the highest figure for the increase in annual cooling load between
cases 250 and 220. Case 250s annual cooling load has already been discussed.
The only other extreme ApacheSim value is that for the difference in peak cooling load
between cases 220 and 270, where, in a closely grouped set of results, ApacheSim
predicts the lowest increase by a small margin.
6 Conclusions
The tests set out in ANSI/ASHRAE Standard 140-2001 have been applied to the program
ApacheSim. The ApacheSim results are in good agreement with those from the reference
programs. Out of 326 tests. Apache predicted a value outside the range set by the other
programs in only 13. In each of these cases a satisfactory explanation has been found for
the difference. In most of these the difference can be accounted for in terms of modelling
refinements incorporated in ApacheSims algorithms. The tests did not reveal any bugs in
the software.
References
1. ANSI/ASHRAE Standard 140-2001, Standard Method of Test for the Evaluation of
Building Energy Analysis Computer Programs. ASHRAE Inc., 1791 Tullie Circle NE
Atlanta, GA 30329. www.ashrae.org
2. Judkoff, R., and J. Neymark. (1995). International Energy Agency Building Energy
Simulation Test (BESTEST) and Diagnostic Method. NREL/TP-472-6231. Golden, CO:
National Renewable Energy Laboratory.
3. ApacheSim Building Thermal Simulation Program. IES Ltd. 141 St James Road,
Glasgow G4 0LT. www.iesve.com
4. ASHRAE Standard 90.1-2001, Addendum p. ASHRAE Inc., 1791 Tullie Circle NE
Atlanta, GA 30329. www.ashrae.org
5. CIBSE Guide A Environmental Design. The Chartered Institution of Building Services
Engineers, London, 1999.
6. EnergyPlus Testing with ANSI/ASHRAE Standard 140-2001 (BESTEST). EnergyPlus
Version 1.1.0.020. May 2003. Ernest Orlando Lawrence Berkeley National Laboratory,
Berkeley, California. Prepared by Robert H. Henniger and Michael J, Witte, GARD
Analytics, 1028 Busse Highway, Park Ridge, Illinois 60068, USA. www.gard.com
12
SOFTWARE: ApacheSim
VERSION: 5.2
Simulated Effect:
Solar radiation model.
Simulated Effect:
Internal Heat Transfer
Simulated Effect:
Initial temperature
Simulated Effect:
Time step
Simulated Effect:
Reporting interval
Simulated Effect:
Preconditioning period
Simulated Effect:
Direct solar shading and internal solar tracking calculated by the SunCast program
Simulated Effect:
Diffuse shading calculated by the SunCast program
Simulated Effect:
Infiltration
Figures
Figures 1-35
Annual Heating Load
16
Figure 1: Annual Heating - Case 195 Figure 2: Annual Heating - Case 200
10.000 10.000
9.000 9.000
8.000 8.000
6.882
7.000 ESP 7.000 6.683 6.636 ESP
6.559 6.555
6.395
BLAST BLA ST
5.871 DOE2 DOE2
6.000 6.000
5.324 SRES 5.252 SRES
4.968 4.973
MWH
H
4.895 4.871 4.921 4.892 SERIRES SERIRES
MW
5.000 5.000
S3PA S S3PA S
4.167 4.2218
TRNSY S TRNSYS
4.000 TA SE 4.000 TA SE
EnergyPlus EnergyPlus
2.000 2.000
1.000 1.000
0.000 0.000
Figure 3: Annual Heating - Case 210 Figure 4: Annual Heating - Case 215
8.000 10.000
7.169
6.967 9.000
7.000 6.794 6.735
6.559 6.554
6.456
7.943
8.000
7.281 7.319 7.375
6.000 7.215 7.130
ESP 7.000 ESP
BLA ST BLAST
5.000
DOE2 6.000 DOE2
5.547
SRES SRES
H
MWH
SERIRES SERIRES
MW
4.000 5.000
S3PAS S3PA S
TRNSYS TRNSY S
TA SE 4.000 TA SE
3.000
Energy Plus EnergyPlus
APACHE 3.000 APA CHE
2.000
2.000
1.000
1.000
0.000 0.000
Figure 5: Annual Heating - Case 220 Figure 6: Annual Heating - Case 230
10.000 14.000
MWH
SERIRES SERIRES
MW
5.000
S3PA S S3PA S
TRNSY S 6.000 TRNSY S
4.000 TASE TASE
EnergyPlus EnergyPlus
3.000 A PA CHE A PA CHE
4.000
2.000
2.000
1.000
0.000 0.000
Figure 7: Annual Heating - Case 240 Figure 8: Annual Heating - Case 250
10.000 10.000
9.000 9.000
8.000 8.000
7.448
7.024
7.000 6.769 6.786 6.806 7.000
ESP 6.608 6.653 6.562 ESP
6.194 6.234 BLAST BLA ST
6.009 6.076 5.974
6.000 5.649 DOE2 6.000 5.739 5.764 5.738 DOE2
SRES SRES
MWH
H
SERIRES SERIRES
MW
2.000 2.000
1.000 1.000
0.000 0.000
Figure 9: Annual Heating - Case 270 Figure 10: Annual Heating - Case 280
10.000 10.000
9.000 9.000
8.000 8.000
4.930
MWH
SERIRES SERIRES
MW
2.000 2.000
1.000 1.000
0.000 0.000
17
Figure 11: Annual Heating - Case 290 Figure 12: Annual Heating - Case 300
10.000 10.000
9.000 9.000
8.000 8.000
MWH
SERIRES SERIRES
5.000 5.000 4.761
4.577 S3PA S S3PA S
TRNSYS TRNSYS
4.000 TA SE 4.000 TA SE
EnergyPlus EnergyPlus
2.000 2.000
1.000 1.000
0.000 0.000
Figure 13: Annual Heating - Case 310 Figure 14: Annual Heating - Case 320
10.000 10.000
9.000 9.000
8.000 8.000
7.135
7.000 ESP 7.000 ESP
6.165 6.154 6.095 BLAST BLAST
5.937
6.000 DOE2 6.000 DOE2
5.610
5.221 5.327 SRES SRES
5.141
MWH
SERIRES
MWH
4.840 4.835 SERIRES
5.000 5.000 4.764
S3PA S S3PA S
4.343 4.348
4.209
TRNSYS TRNSYS
3.859
4.000 TA SE 4.000 TASE
EnergyPlus Energy Plus
3.000 APACHE 3.000 APA CHE
2.000 2.000
1.000 1.000
0.000 0.000
Figure 15: Annual Heating - Case 395 Figure 16: Annual Heating - Case 400
10.000 10.000
2.000 2.000
1.000 1.000
0.000 0.000
Figure 17: Annual Heating - Case 410 Figure 18: Annual Heating - Case 420
12.000 10.000
9.151
10.506 9.000
8.365 8.373 8.424
10.000 9.726 9.734 9.724
7.774 7.863
8.000 7.610 7.697
9.019 8.936 9.085
8.873 7.298
8.596
MWH
SERIRES SERIRES
6.000 5.000
S3PA S S3PA S
TRNSYS TRNSYS
TA SE 4.000 TA SE
EnergyPlus EnergyPlus
4.000
A PACHE 3.000 APACHE
2.000
2.000
1.000
0.000 0.000
Figure 19: Annual Heating - Case 430 Figure 20: Annual Heating - Case 440
10.000 10.000
9.000 9.000
MWH
SERIRES SERIRES
5.000 5.000
S3PA S 4.449 S3PAS
TRNSYS TRNSY S
4.000 TASE 4.000 TA SE
EnergyPlus EnergyPlus
3.000 APA CHE 3.000 A PACHE
2.000 2.000
1.000 1.000
0.000 0.000
18
Figure 21: Annual Heating - Case 600 Figure 22: Annual Heating - Case 610
8.000 8.000
7.000 7.000
MWH
SERIRES SERIRES
4.000 4.000
S3PA S S3PA S
TRNSYS TRNSYS
TA SE TA SE
3.000 3.000
EnergyPlus EnergyPlus
A PACHE A PACHE
2.000 2.000
1.000 1.000
0.000 0.000
Figure 23: Annual Heating - Case 620 Figure 24: Annual Heating - Case 630
8.000 8.000
7.018
7.000 7.000
6.469
MWH
SERIRES SERIRES
4.000 4.000
S3PA S S3PA S
TRNSYS TRNSYS
TA SE TASE
3.000 3.000
EnergyPlus EnergyPlus
APACHE APA CHE
2.000 2.000
1.000 1.000
0.000 0.000
Figure 25: Annual Heating - Case 640 Figure 26: Annual Heating - Case 650
8.000 8.000
7.000 7.000
6.000 6.000
ESP ESP
BLA ST BLA ST
5.000 5.000
DOE2 DOE2
SRES SRES
MWH
MWH
SERIRES SERIRES
4.000 3.803 4.000
3.543 3.501 S3PAS S3PA S
3.255 3.309 3.237 TRNSY S TRNSYS
3.065 3.043
2.888 TA SE TA SE
3.000 2.751 3.000
EnergyPlus A PACHE
A PACHE EnergyPlus
2.000 2.000
1.000 1.000
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
0.000 0.000
Figure 27: Annual Heating - Case 800 Figure 28: Annual Heating - Case 810
8.000 8.000
7.228
6.161
5.953 5.940 5.861
6.000 6.000
ESP ESP
MWH
SERIRES SERIRES
4.000 4.000
S3PA S S3PA S
TRNSYS TRNSYS
3.004 2.962 2.963
TA SE 2.828 TA SE
3.000 3.000 2.722
EnergyPlus 2.567 EnergyPlus
2.446
A PACHE APACHE
1.000 1.000
0.000 0.000
Figure 29: Annual Heating - Case 900 Figure 30: Annual Heating - Case 910
8.000 8.000
7.000 7.000
6.000 6.000
ESP ESP
BLAST BLA ST
5.000 5.000
DOE2 DOE2
SRES SRES
MWH
MWH
SERIRES SERIRES
4.000 4.000
S3PA S S3PAS
TRNSYS TRNSY S
TASE TA SE
3.000 3.000
EnergyPlus EnergyPlus
2.254 2.282 2.333
APA CHE 2.174 2.220 APACHE
2.041 2.063 2.097
1.897 1.988 1.947
1.872 1.862
2.000 1.730 2.000 1.734
1.610 1.655 1.575
1.437
1.170
1.000 1.000
0.000 0.000
19
Figure 31: Annual Heating - Case 920 Figure 32: Annual Heating - Case 930
8.000 8.000
7.000 7.000
6.306
6.000 6.000
MWH
SERIRES SERIRES
4.000 3.752 3.776 4.000
S3PA S S3PA S
3.448
3.313 TRNSYS TRNSYS
TA SE TA SE
3.000 3.000
EnergyPlus EnergyPlus
A PACHE A PACHE
2.000 2.000
1.000 1.000
0.000 0.000
Figure 33: Annual Heating - Case 940 Figure 34: Annual Heating - Case 950
8.000 8.000
7.000 7.000
6.000 6.000
ESP ESP
BLAST BLAST
5.000 5.000
DOE2 DOE2
SRES SRES
MWH
SERIRES
MWH
SERIRES
4.000 4.000
S3PA S S3PA S
TRNSYS TRNSYS
TA SE TASE
3.000 3.000
EnergyPlus APA CHE
APACHE Energy Plus
2.000 2.000
1.411 1.323 1.322
1.239 1.231 1.179
1.021 1.080
0.968
1.000 0.793 1.000
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
0.000 0.000
8.000
7.000
6.000
ESP
BLA ST
5.000
DOE2
SRES
MWH
SERIRES
4.000
S3PAS
3.373
TRNSY S
2.928 2.943 3.008
2.884 2.851 2.816 TA SE
3.000 2.664 2.765
EnergyPlus
2.311
A PACHE
2.000
1.000
0.000
20
Figures 36-70
Peak Heating Load
21
Figure 36: Peak Heating - Case 195 Figure 37: Peak Heating - Case 200
5.000 5.000
4.000 4.000
3.382
ESP ESP
BLA ST 3.047 BLA ST
2.973 2.999 2.969 2.997
3.000 DOE2 3.000 DOE2
SRES 2.651 SRES
MWH
H
SERIRES SERIRES
MW
2.385
2.320 2.263
2.235 2.221 2.218 S3PA S S3PA S
2.186 2.186
2.004 2.0565 TRNSYS TRNSYS
2.000 TA SE 2.000 TA SE
EnergyPlus EnergyPlus
APA CHE A PACHE
1.000 1.000
0.000 0.000
Figure 38: Peak Heating - Case 210 Figure 39: Peak Heating - Case 215
5.000 5.000
4.000 4.000
3.650
3.458
3.325 ESP 3.386
3.280 3.307 3.294 ESP
3.077 BLAST BLAST
2.973 3.020 2.981 3.021
3.000 DOE2 3.000 DOE2
2.787
2.701 SRES SRES
H
MWH
SERIRES SERIRES
MW
S3PAS S3PA S
TRNSYS TRNSY S
2.000 TASE 2.000 TA SE
Energy Plus EnergyPlus
A PA CHE APA CHE
1.000 1.000
0.000 0.000
Figure 40: Peak Heating - Case 220 Figure 41: Peak Heating - Case 230
5.000 6.000
5.279 5.293
5.159 5.107
4.984 4.994 4.929
5.000 4.892
4.000
3.695 3.709 4.386
3.465 3.520
3.423
3.348 3.336 ESP ESP
3.280
4.000
BLAST BLAST
MWH
SERIRES SERIRES
MW
3.000
S3PA S S3PA S
TRNSY S TRNSY S
2.000 TA SE TASE
EnergyPlus EnergyPlus
2.000
APA CHE A PA CHE
1.000
1.000
0.000 0.000
Figure 42: Peak Heating - Case 240 Figure 43: Peak Heating - Case 250
5.000 5.000
4.000 4.000
3.695 3.709
3.495 3.509 3.465 3.525
3.422
3.333 ESP 3.341 3.336 ESP
3.282 3.239 3.279
3.100 3.159 3.153 BLAST BLA ST
SERIRES
H
SERIRES
MW
S3PA S S3PAS
TRNSYS TRNSY S
2.000 TASE 2.000 TA SE
Energy Plus EnergyPlus
A PA CHE APACHE
1.000 1.000
0.000 0.000
Figure 44: Peak Heating - Case 270 Figure 45: Peak Heating - Case 280
5.000 5.000
4.000 4.000
3.714 3.738 3.714 3.759
3.661 3.685
3.441 3.444
3.340 3.336 ESP 3.341 3.336 ESP
3.277 3.278
BLA ST BLA ST
MWH
SERIRES SERIRES
MW
S3PAS S3PAS
TRNSY S TRNSY S
2.000 TASE 2.000 TASE
EnergyPlus EnergyPlus
APACHE APACHE
1.000 1.000
0.000 0.000
22
Figure 46: Peak Heating - Case 290 Figure 47: Peak Heating - Case 300
5.000 5.000
4.000 4.000
3.714 3.738 3.714 3.770
3.670 3.681
3.599
3.432 3.446
3.340 3.328 ESP 3.328 ESP
3.277 3.276
BLA ST BLAST
3.014
3.000 2.863 DOE2 3.000 DOE2
SRES SRES
MWH
MWH
SERIRES SERIRES
S3PA S S3PA S
TRNSYS TRNSY S
2.000 TA SE 2.000 TASE
EnergyPlus EnergyPlus
APA CHE A PA CHE
1.000 1.000
0.000 0.000
Figure 48: Peak Heating - Case 310 Figure 49: Peak Heating - Case 320
5.000 5.000
4.000 4.000
3.714 3.771 3.714 3.735
3.672 3.661
3.599
3.439 3.438
3.328 ESP 3.340 3.336 ESP
3.277 3.275
BLAST BLA ST
3.015
3.000 DOE2 3.000 2.861 DOE2
SRES SRES
MWH
SERIRES
MWH
SERIRES
S3PA S S3PAS
TRNSYS TRNSYS
2.000 TA SE 2.000 TA SE
EnergyPlus Energy Plus
APACHE APACHE
1.000 1.000
0.000 0.000
Figure 50: Peak Heating - Case 395 Figure 51: Peak Heating - Case 400
5.000 4.000
3.695 3.709
3.476 3.520
3.423
3.342 3.336
3.280
4.000
3.000 2.867
ESP ESP
BLA ST BLA ST
3.000 DOE2 DOE2
SRES SRES
MWH
SERIRES
MWH
SERIRES
2.328 2.385 2.391 2.000
2.263 2.270 2.285 S3PAS S3PA S
2.209 2.221
2.062 TRNSY S TRNSYS
2.000 TA SE TA SE
EnergyPlus EnergyPlus
A PACHE A PACHE
1.000
1.000
0.000 0.000
Figure 52: Peak Heating - Case 410 Figure 53: Peak Heating - Case 420
5.000 5.000
4.487 4.501
4.314 4.500 4.301
4.233 4.287
4.227
4.124 4.114 4.157 4.126
4.050 4.044
3.944 3.931 3.975
4.000 4.000
3.625
3.443
ESP 3.500 ESP
BLA ST BLAST
MWH
SERIRES SERIRES
2.500
S3PA S S3PA S
TRNSYS TRNSYS
2.000 TA SE 2.000 TA SE
EnergyPlus EnergyPlus
A PACHE 1.500 APACHE
1.000 1.000
0.500
0.000 0.000
Figure 54: Peak Heating - Case 430 Figure 55: Peak Heating - Case 440
5.000 5.000
4.376
4.287 4.301 4.277 4.306
4.137
4.050 4.044 4.041 3.996
3.944 3.931 3.975 3.942 3.931
4.000 4.000
3.442 3.439
ESP ESP
BLAST BLA ST
3.000 DOE2 3.000 DOE2
SRES SRES
MWH
MWH
SERIRES SERIRES
S3PA S S3PAS
TRNSYS TRNSY S
2.000 TASE 2.000 TA SE
Energy Plus EnergyPlus
APA CHE A PACHE
1.000 1.000
0.000 0.000
23
Figure 56: Peak Heating - Case 600 Figure 57: Peak Heating - Case 610
5.000 5.000
3.437 3.437
ESP ESP
BLA ST BLAST
MWH
SERIRES SERIRES
S3PA S S3PA S
TRNSYS TRNSY S
2.000 TA SE 2.000 TA SE
EnergyPlus EnergyPlus
A PACHE APA CHE
1.000 1.000
0.000 0.000
Figure 58: Peak Heating - Case 620 Figure 59: Peak Heating - Case 630
5.000 5.000
4.379 4.379
4.277 4.306 4.277 4.280 4.306 4.278
4.046 3.998 4.025 3.992
3.941 3.922 3.941 3.922
4.000 3.866 4.000 3.840
3.591 3.592
ESP ESP
BLAST BLAST
SERIRES
MWH
SERIRES
S3PA S S3PA S
TRNSYS TRNSYS
2.000 TA SE 2.000 TASE
EnergyPlus Energy Plus
APACHE A PA CHE
1.000 1.000
0.000 0.000
Figure 60: Peak Heating - Case 640 Figure 61: Peak Heating - Case 650
9.000 5.000
8.078
8.000
7.290
6.954 4.000
7.000
6.530 6.436
6.347
5.943 ESP BLA ST
6.000 5.722
5.486 BLA ST DOE2
5.232 DOE2 SRES
3.000
5.000 SRES SERIRES
MWH
S3PA S
MWH
SERIRES
S3PAS TRNSYS
4.000 TRNSY S TA SE
TA SE 2.000 A PACHE
EnergyPlus ESP
3.000
A PACHE EnergyPlus
2.000
1.000
1.000
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
0.000 0.000
Figure 62: Peak Heating - Case 800 Figure 63: Peak Heating - Case 810
5.000 5.000
4.138 4.188
4.115
3.909 3.939 3.915 3.963
4.000 3.902 4.000
3.793 3.786 3.812
3.709 3.648
3.566 3.606
ESP ESP
3.227
BLA ST BLAST
2.979
3.000 DOE2 3.000 DOE2
SRES SRES
MWH
MWH
SERIRES SERIRES
S3PA S S3PA S
TRNSYS TRNSYS
2.000 TA SE 2.000 TA SE
EnergyPlus EnergyPlus
A PACHE APACHE
1.000 1.000
0.000 0.000
Figure 64: Peak Heating - Case 900 Figure 65: Peak Heating - Case 910
5.000 5.000
4.081 4.083
4.000 3.797 4.000 3.801
3.760 3.764
3.557 3.608 3.564 3.618
3.517 3.547 3.536 3.548
3.453 3.456
3.294 ESP 3.292 ESP
BLAST BLA ST
3.000 2.850 DOE2 3.000 2.858 DOE2
SRES SRES
MWH
MWH
SERIRES SERIRES
S3PA S S3PAS
TRNSYS TRNSY S
2.000 TASE 2.000 TA SE
Energy Plus EnergyPlus
APA CHE A PACHE
1.000 1.000
0.000 0.000
24
Figure 66: Peak Heating - Case 920 Figure 67: Peak Heating - Case 930
5.000 5.000
MWH
MWH
SERIRES SERIRES
S3PA S S3PAS
TRNSYS TRNSY S
2.000 TA SE 2.000 TA SE
EnergyPlus EnergyPlus
A PACHE APA CHE
1.000 1.000
0.000 0.000
Figure 68: Peak Heating - Case 940 Figure 69: Peak Heating - Case 950
12.000 5.000
9.923
10.000
4.000
ESP BLAST
8.000
BLAST DOE2
DOE2 3.000 SRES
6.428 SRES SERIRES
6.116 6.117
MWH
MWH
5.810 5.855 SERIRES S3PA S
6.000 5.665
S3PA S TRNSYS
5.028 5.122
TRNSYS TASE
TA SE 2.000 APA CHE
3.980 EnergyPlus ESP
4.000
APACHE EnergyPlus
1.000
2.000
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
0.000 0.000
3.500
2.522
2.500 2.410
ESP
BLA ST
DOE2
2.000 SRES
MWH
SERIRES
S3PAS
1.500 TRNSY S
TA SE
EnergyPlus
A PACHE
1.000
0.500
0.000
25
Figures 71-105
Annual Cooling Load
26
Figure 71: Annual Cooling - Case 195 Figure 72: Annual Cooling - Case 200
1.000 1.000
0.900 0.900
0.800 0.800
0.716
0.699
ESP 0.677 0.683
0.700 0.700 ESP
BLA ST 0.633
0.613 BLA ST
DOE2 0.600 0.570 DOE2
0.600
SRES SRES
0.510
H
0.498 SERIRES
MWH
MW
0.488 0.4861 SERIRES 0.500
0.500 0.474 0.474
S3PA S
0.443
0.414 0.421 S3PA S TRNSYS
0.400 TA SE
0.400 TRNSYS
EnergyPlus
TA SE
0.300 A PACHE
0.300 0.264
0.200
0.200
0.100
0.100
0.000
0.000
Figure 73: Annual Cooling - Case 210 Figure 74: Annual Cooling - Case 215
1.000 1.000
0.900 0.900
0.853
SERIRES
MWH
SERIRES
0.500 0.500
S3PAS S3PA S
TRNSYS TRNSY S
0.400 TA SE 0.400 TA SE
EnergyPlus EnergyPlus
0.300 APACHE 0.300 APA CHE
0.100 0.100
0.000 0.000
Figure 75: Annual Cooling - Case 220 Figure 76: Annual Cooling - Case 230
1.000 4.000
0.900
0.835 3.500
0.827
0.800
0.734 0.737
3.000
0.701
0.683
0.700 0.669 ESP ESP
BLAST BLAST
2.500
0.600 DOE2 DOE2
SRES SRES
H
H
SERIRES SERIRES
MW
MW
0.500 2.000
S3PA S S3PA S
0.454
0.500
0.100
0.000 0.000
Figure 77: Annual Cooling - Case 240 Figure 78: Annual Cooling - Case 250
4.000 4.000
3.500 3.380
3.213
SERIRES
H
SERIRES
MW
MW
2.000 2.000
S3PA S S3PAS
TRNSY S TRNSY S
TASE TASE
1.500
1.239 1.246 EnergyPlus EnergyPlus
0.660
0.500 0.415
0.000 0.000
Figure 79: Annual Cooling - Case 270 Figure 80: Annual Cooling - Case 280
12.000 10.000
10.350 9.000
9.828
10.000
8.000
8.670 8.795 8.764 8.714
8.523 7.114
S3PAS S3PAS
TRNSY S TRNSY S
TA SE 4.000 TA SE
Energy Plus Energy Plus
4.000
APACHE 3.000 APACHE
2.000
2.000
1.000
0.000 0.000
27
Figure 81: Annual Cooling - Case 290 Figure 82: Annual Cooling - Case 300
10 10
9 9
8.089
8 7.721 8
7.431
7.011 7.1
6.903
7 6.699 ESP 7 6.665 ESP
6.521
BLA ST BLA ST
DOE2 5.836 5.849 5.781 DOE2
6 6 5.721
5.487
SRES SRES
5.204
MWH
MWH
SERIRES SERIRES
5 5
S3PA S S3PA S
4.302
TRNSYS TRNSYS
4 TA SE 4 TA SE
EnergyPlus EnergyPlus
3 A PACHE 3 A PACHE
2 2
1 1
0 0
Figure 83: Annual Cooling - Case 310 Figure 84: Annual Cooling - Case 320
10 10
9 9
8 8
7.304
7 ESP 7 ESP
6.576
BLAST BLAST
5.906 5.914 5.956
6 DOE2 6 5.663 5.715 DOE2
5.471
SRES SRES
5.136 5.061
MWH
SERIRES
MWH
SERIRES
5 5
4.57 S3PA S S3PA S
4.082 TRNSYS TRNSYS
3.875
4 3.727 TA SE 4 TASE
EnergyPlus EnergyPlus
3 2.732 APACHE 3 APA CHE
2.471
2 2
1 1
0 0
Figure 85: Annual Cooling - Case 395 Figure 86: Annual Cooling - Case 400
0.2 0.2
0.18 0.18
0.16 0.16
SERIRES SERIRES
0.1 0.1
S3PAS S3PA S
TRNSY S TRNSYS
0.08 TA SE 0.08 TA SE
EnergyPlus EnergyPlus
0.061
0.058
0.06 A PACHE 0.06 A PACHE
0.04468 0.044
0.04 0.042
0.04 0.04 0.035
Figure 87: Annual Cooling - Case 410 Figure 88: Annual Cooling - Case 420
0.2 0.2
0.189 0.188
0.18 0.18
0.1575
0.16 0.16 0.154
0.147
0.143
0.139
0.14 ESP 0.14 ESP
BLA ST BLAST
MWH
SERIRES SERIRES
0.1 0.1
S3PA S S3PA S
0.084 0.084
TRNSYS TRNSYS
0.08 TA SE 0.08 TA SE
0.06707 0.065
0.063 EnergyPlus EnergyPlus
0.059 0.058
0.06 A PACHE 0.06 APACHE
0.051
0.04 0.04
0.02 0.02
0.01 0.011
0
0 0
Figure 89: Annual Cooling - Case 430 Figure 90: Annual Cooling - Case 440
1 10
0.9 0.875 9
0.8 8
0.704
0.684
0.7 ESP 7 ESP
0.617 0.6174 BLAST BLA ST
0.6 DOE2 6 DOE2
0.563
0.542 0.534 SRES SRES
5.204
MWH
MWH
SERIRES SERIRES
0.5 5 4.674 4.684
S3PA S S3PAS
0.422 4.172
TRNSYS 3.967 3.992 3.975 4.05 TRNSY S
0.4 TASE 4 TA SE
EnergyPlus EnergyPlus
0.3 APA CHE 3 A PACHE
0.2 2
0.1 1
0 0
28
Figure 91: Annual Cooling - Case 600 Figure 92: Annual Cooling - Case 610
10 10
9 9
7.964
8 8
7.278
7.079
7 6.778 7
6.571 ESP ESP
6.433 6.492 6.492 6.395
6.137 BLA ST BLA ST
MWH
SERIRES 4.851 SERIRES
5 5 4.764 4.685
S3PA S 4.601 4.551 S3PA S
TRNSYS TRNSYS
3.915
4 TA SE 4 TA SE
EnergyPlus EnergyPlus
3 A PACHE 3 A PACHE
2 2
1 1
0 0
Figure 93: Annual Cooling - Case 620 Figure 94: Annual Cooling - Case 630
10 10
9 9
8 8
7 ESP 7 ESP
BLAST BLAST
6 DOE2 6 DOE2
SRES SRES
5.004
MWH
SERIRES
MWH
SERIRES
5 4.633 5
S3PA S S3PA S
4.334 4.351
4.092 4.144 TRNSYS TRNSYS
4.011 3.901 3.879
4 TA SE 4 3.701 TASE
3.417 3.493
EnergyPlus 3.108 EnergyPlus
3 APACHE 3 2.817 2.779 APA CHE
2.489 2.489 2.416
2.129
2 2 1.721
1 1
0 0
Figure 95: Annual Cooling - Case 640 Figure 96: Annual Cooling - Case 650
10 10
9 9
8 7.811 8
7.026
7 6.759 ESP 7
6.508 6.545 ESP
6.247 6.246 6.343
6.183 6.175 BLA ST BLA ST
5.952 5.894
6 DOE2 6 5.795 DOE2
SRES 5.456 SRES
5.14 5.088 5.119 5.006
4.959
MWH
MWH
3 A PACHE 3 A PACHE
2 2
1 1
0 0
Figure 97: Annual Cooling - Case 800 Figure 98: Annual Cooling - Case 810
1 4
0.9
3.5
0.8
MWH
SERIRES SERIRES
0.5 2
S3PA S S3PA S
1.711 1.708
TRNSYS 1.624 TRNSYS
0.4 TASE TA SE
1.5 1.405
0.325 Energy Plus 1.307 Energy Plus
1.191 1.159
0.3 0.272 A PA CHE APACHE
1.052
0.224 0.222 1
0.195 0.2073
0.2
0.143
0.113
0.5
0.1
0.055
0 0
Figure 99: Annual Cooling - Case 900 Figure 100: Annual Cooling - Case 910
4 4
3.165
3 3
ESP ESP
2.6 2.572 2.599
2.455 2.485 BLAST BLA ST
2.5 2.5
2.268 2.278 DOE2 DOE2
2.132 SRES SRES
MWH
MWH
SERIRES SERIRES
2 2 1.872 1.854
S3PAS 1.767 S3PAS
TRNSYS TRNSY S
1.533
TASE 1.428 TA SE
1.5 1.5
1.326
Energy Plus EnergyPlus
APACHE 1.123 1.136 A PACHE
0.976
1 1
0.821
0.5 0.5
0 0
29
Figure 101: Annual Cooling - Case 920 Figure 102: Annual Cooling - Case 930
4 4
3.5 3.5
3.092
2.943
3 3
MWH
SERIRES 1.934 SERIRES
2 1.84 2
S3PA S S3PA S
TRNSYS 1.599 1.62 TRNSYS
TA SE 1.439 1.416 TA SE
1.5 1.5
EnergyPlus 1.266 EnergyPlus
A PACHE A PACHE
1.039
1 1 0.894
0.5 0.5
0 0
Figure 103: Annual Cooling - Case 940 Figure 104: Annual Cooling - Case 950
4 1
0.921
0.9
3.5
3.241
SERIRES
MWH
SERIRES
2 0.5 0.461
S3PA S S3PA S
TRNSYS TRNSYS
0.387
TA SE 0.4 TASE
1.5
Energy Plus Energy Plus
APACHE 0.3 APA CHE
0.2
0.5
0.1
0 0
0.9
0.803
0.786
0.8
0.718
0.7 0.666 ESP
0.643
BLA ST
0.6 0.579 DOE2
0.562
SRES
MWH
0.488 SERIRES
0.5
S3PAS
0.428
0.4113 TRNSY S
0.4 TA SE
EnergyPlus
0.3 A PACHE
0.2
0.1
0
30
Figures 106-140
Peak Cooling Load
31
Figure 106: Peak Cooling - Case 195 Figure 107: Peak Cooling - Case 200
2 2
1.5 1.5
ESP ESP
BLAST BLA ST
DOE2 DOE2
1.111 1.1051.1005555561.126 1.09
SRES SRES
1.017
SERIRES SERIRES
kW
kW
1 1
S3PA S S3PA S
0.853 0.863
0.806 0.7990.791388889 0.79 0.7965 0.812 TRNSY S TRNSYS
0.728 TASE TA SE
0.651 Energy Plus EnergyPlus
0.616
APA CHE A PACHE
0.5 0.5
0 0
Figure 108: Peak Cooling - Case 210 Figure 109: Peak Cooling - Case 215
2 2
1.5 1.5
kW
kW
1 1
S3PAS S3PA S
TRNSYS TRNSY S
TA SE TA SE
Energy Plus EnergyPlus
APACHE APA CHE
0.476
0.5 0.5
0 0
Figure 110: Peak Cooling - Case 220 Figure 111: Peak Cooling - Case 230
2 2
1.875 1.878
1.6
1.5 1.455
1 0.937 1
S3PA S S3PA S
TRNSY S TRNSYS
TASE 0.8 TA SE
EnergyPlus EnergyPlus
0.56 A PA CHE 0.6 A PACHE
0.5
0.4
0.2
0 0
Figure 112: Peak Cooling - Case 240 Figure 113: Peak Cooling - Case 250
2 10
1.8 9
kW
1 5
S3PA S S3PAS
TRNSY S TRNSY S
0.8 0.739 TASE 4 TASE
3.36
EnergyPlus 3.227777778 3.172 EnergyPlus
3.036
0.6 A PA CHE 3 A PA CHE
2.605 2.59 2.582
2.258
0.4 2
0.2 1
0 0
Figure 114: Peak Cooling - Case 270 Figure 115: Peak Cooling - Case 280
10 10
9 9
7.967
8 8
7.234
kW
5 5 4.786111111 4.795
4.631 4.63
S3PAS 4.444 S3PAS
TRNSY S TRNSY S
4 TA SE 4 TA SE
EnergyPlus Energy Plus
3 APACHE 3 APACHE
2 2
1 1
0 0
32
Figure 116: Peak Cooling - Case 290 Figure 117: Peak Cooling - Case 300
10 10
9 9
8 7.793 8
6.91
7 6.7 6.621 ESP 7 ESP
6.555
6.428
6.269 6.202777778 BLA ST BLA ST
6 DOE2 6 DOE2
SRES SRES
5.072 4.929
SERIRES SERIRES
kW
kW
5 5 4.657
S3PA S S3PA S
4.3364.277777778
TRNSYS 4.093 4.162 TRNSYS
4 TA SE 4 TA SE
3.404
EnergyPlus EnergyPlus
3 A PACHE 3 A PACHE
2 2
1 1
0 0
Figure 118: Peak Cooling - Case 310 Figure 119: Peak Cooling - C ase 320
10 10
9 9
8 8
7.332
7 ESP 7 ESP
6.484
BLAST 6.183 6.177777778 6.141 BLAST
5.946 6.047
6 DOE2 6 5.701 DOE2
SRES SRES
SERIRES SERIRES
kW
kW
5 4.666 5
S3PA S S3PA S
4.186
TRNSYS TRNSYS
4 3.749 3.669 3.588888889 TA SE 4
3.604 TASE
3.425
Energy Plus Energy Plus
2.848 APACHE APA CHE
3 3
2 2
1 1
0 0
Figure 120: Peak Cooling - Case 395 Figure 121: Peak Cooling - Case 400
2 2
1.5 1.5
ESP ESP
BLA ST BLA ST
DOE2 DOE2
SRES SRES
SERIRES SERIRES
kW
kW
1 1
S3PAS S3PA S
TRNSY S TRNSYS
TA SE 0.712 TA SE
EnergyPlus 0.666
EnergyPlus
0.6120.613333333
A PACHE 0.581 0.572 0.56 A PACHE
0.5 0.421 0.5
0.394
0.362 0.356 0.3625 0.345
0.282
0.265
0 0 0
0 0
Figure 122: Peak Cooling - Case 410 Figure 123: Peak Cooling - Case 420
2 2
1.5 1.5
ESP ESP
BLA ST BLAST
DOE2 DOE2
SRES 1.078 SRES
1.047
SERIRES SERIRES
kW
kW
0.5 0.5
0.413
0.258
0.035
0 0
Figure 124: Peak Cooling - C ase 430 Figure 125: Peak Cooling - Case 440
10 10
9 9
8 8
7 ESP 7 ESP
BLAST BLA ST
6 DOE2 6 DOE2
5.615
SRES 5.278 SRES
5.053
SERIRES SERIRES
kW
kW
5 5 4.686111111 4.743
S3PA S 4.546 4.424 4.465 S3PAS
TRNSYS TRNSY S
4 TASE 4 TA SE
Energy Plus EnergyPlus
3 APA CHE 3 A PACHE
2.578
1 1
0 0
33
Figure 126: Peak Cooling - Case 600 Figure 127: Peak Cooling - Case 610
10 10
9 9
8 8
7.551
7.215
7 6.827 6.812 7
6.557 ESP ESP
6.486111111 6.452 6.371
6.194 6.286 BLA ST 6.17 6.257 BLA ST
6.064 6.146
5.965 5.848
DOE2 5.824 DOE2
6 6 5.669 5.675
SRES SRES
SERIRES SERIRES
kW
kW
5 5
S3PA S S3PA S
TRNSYS TRNSYS
4 TA SE 4 TA SE
EnergyPlus EnergyPlus
3 A PACHE 3 A PACHE
2 2
1 1
0 0
Figure 128: Peak Cooling - Case 620 Figure 129: Peak Cooling - Case 630
10
10
9
9
8
8
7 ESP ESP
7
BLAST BLA ST
6 DOE2 DOE2
6
SRES SRES
4.959 5.096
SERIRES SERIRES
kW
kW
4.593 S3PA S 5 S3PAS
4.43 4.316
4.297 4.275 4.206 4.4
4.075 TRNSYS 4.116 TRNSY S
4 3.634 TA SE 3.762 TA SE
4 3.704 3.588 3.6653.6083333333.546 3.672
Energy Plus EnergyPlus
3.072
3 APACHE APACHE
3
2 2
1 1
0 0
Figure 130: Peak Cooling - Case 640 Figure 131: Peak Cooling - Case 650
10 10
9 9
8 8
7.537 7.458
kW
5 5
S3PAS S3PA S
TRNSY S TRNSYS
4 TA SE 4 TA SE
EnergyPlus EnergyPlus
3 A PACHE 3 A PACHE
2 2
1 1
0 0
Figure 132: Peak Cooling - Case 800 Figure 133: Peak Cooling - Case 810
2 10
1.5
1.382
1.352 1.358 7
ESP ESP
BLA ST BLAST
DOE2 6 DOE2
SRES SRES
1.028
0.967 0.982777778 SERIRES SERIRES
kW
kW
1 0.949 5
S3PA S S3PA S
TRNSYS TRNSYS
0.743 TA SE 4 3.624 TA SE
EnergyPlus Energy Plus
0.585 2.991
A PACHE 2.862 APACHE
3
2.357 2.432 2.343611111 2.484
0.5
1.852
2
0 0
Figure 134: Peak Cooling - C ase 900 Figure 135: Peak Cooling - Case 910
10 10
9 9
8 8
7 ESP 7 ESP
BLAST BLA ST
6 DOE2 6 DOE2
SRES SRES
4.901 SERIRES SERIRES
kW
kW
5 5
S3PA S S3PAS
TRNSYS 3.973 TRNSY S
3.871
4 TASE 4 TA SE
3.458 3.566666667 3.457
3.334 3.389 3.277
3.155 3.261 Energy Plus 3.147 EnergyPlus
2.888 2.786 2.791666667 2.78
3 APA CHE 3 A PACHE
2.5 2.574
2.336
1.896
2 2
1 1
0 0
34
Figure 136: Peak Cooling - Case 920 Figure 137: Peak Cooling - Case 930
10 10
9 9
8 8
7 ESP 7 ESP
BLA ST BLA ST
6 DOE2 6 DOE2
SRES SRES
SERIRES SERIRES
kW
kW
5 5
S3PA S S3PA S
TRNSYS TRNSYS
4 3.777 4
3.505 TA SE TA SE
3.487
3.109 EnergyPlus 3.08 3.203 EnergyPlus
3.071 3.05 2.952 3.043
2.933
3 A PACHE 3 A PACHE
2.546 2.4862.498333333 2.58
2.385 2.388 2.442
2.304
1.873
2 2
1 1
0 0
Figure 138: Peak Cooling - Case 940 Figure 139: Peak Cooling - Case 950
10 10
9 9
8 8
7 ESP 7 ESP
BLAST BLAST
6 DOE2 6 DOE2
SRES SRES
4.901 SERIRES SERIRES
kW
kW
5 5
S3PA S S3PA S
TRNSYS TRNSYS
3.871 3.848
4 4 TASE
3.566666667 3.457 TA SE
3.458 3.389
3.334 3.261 3.17 Energy Plus
3.155 Energy Plus
2.888 2.867 APA CHE
3 APACHE 3 2.621 2.664 2.677 2.686111111 2.666
2.44
2.033
2 2
1 1
0 0
1.5
1.403
1.37 1.378
1.306 ESP
BLA ST
1.179 1.197
1.144 1.156 DOE2
1.057 SRES
SERIRES
kW
1 0.953
S3PAS
TRNSY S
TA SE
EnergyPlus
A PACHE
0.5
0
35
Free-Floating Temperatures
36
Figure 141: Max Annual Hourly Zone Temperature - Case 600FF Figure 142: Max Annual Hourly Zone Temperature - Case 900FF
71 50
70 69.81
69.5 49
69 68.6 48
68
ESP 47 ESP
BLAST BLA ST
67
DOE2 46 DOE2
SRES SRES
66
degC
degC
SERIRES 44.8 SERIRES
65.25 65.25 65.22 45
65.11
64.929 64.9 S3PA S S3PA S
65
64.4 TRNSY S TRNSYS
TA SE 44 TA SE
64 43.44 43.44
EnergyPlus 43.17 EnergyPlus
43
APA CHE 43 42.7 A PACHE
63 42.46 42.4
41.99
42 41.812
62
61 41
60 40
Figure 143: Max Annual Hourly Zone Temperature - Case 650FF Figure 144: Max Annual Hourly Zone Temperature - Case 950FF
71 39
38.5
70 38.5
69
68.49 38
68.2
37.58
68
ESP 37.5 ESP
67
BLA ST BLAST
67
DOE2 37 DOE2
SRES SRES
66 36.6
degC
SERIRES
degC
SERIRES
36.5
S3PAS 36.23 S3PA S
65 36.1
TRNSYS TRNSY S
36 35.9
TA SE 35.77 TA SE
63.74 63.82 63.69
64 35.65 35.67
63.45 Energy Plus EnergyPlus
63.236 63.3 35.54
APACHE 35.5 APA CHE
63 62.7
35
62
61 34.5
60 34
Figure 145: Max Annual Hourly Zone Temperature - Case 960 Figure 146: Min Annual Hourly Zone Temperature - Case 600FF
56 -8
55.34
55
-10
-9.96
54
-12
53 ESP ESP
BLAST BLAST
-14
52 DOE2 DOE2
51.5
SRES SRES
51.21
51
degC
degC
SERIRES SERIRES
51 -16 -15.565
S3PA S S3PA S
50.2
TRNSY S TRNSY S
50 -17.05
TASE TA SE
-18
49.34 -17.8 -17.81 -17.9
EnergyPlus -18 -18.07 EnergyPlus
48.943 49 48.92 -18.47
48.88 A PA CHE APA CHE
49 -18.8
-20
48
-22
47
46 -24
Figure 147: Min Annual Hourly Zone Temperature - Case 900FF Figure 148: Min Annual Hourly Zone Temperature - Case 650FF
0 -8
-10
-1 -9.97
-12
-1.647
-2
ESP ESP
BLA ST BLAST
-14
DOE2 DOE2
-3 SRES SRES
-3.1
degC
degC
-4 TRNSYS TRNSYS
-3.94 -4 TA SE TASE
-18
-4.3 EnergyPlus Energy Plus
-4.5
-4.67 A PACHE A PA CHE
-5
-20
-5.64
-6
-22 -21.6
-6.38 -22.564
-22.96 -23 -22.9 -22.83 -22.91 -22.86
-23.1
-7 -24
Figure 149: Min Annual Hourly Zone Temperature - Case 950FF Figure 150: Min Annual Hourly Zone Temperature - Case 960
-8 5
3.9
4
-10
-9.83
3.1
3 2.729
-12
2.22
ESP ESP
2
BLAST 1.63 BLAST
-14 1.4
DOE2 1.1 DOE2
SRES 1 0.75 SRES
degC
degC
SERIRES SERIRES
-16
S3PA S S3PA S
TRNSY S 0 TRNSY S
TA SE TASE
-18 -0.39
EnergyPlus EnergyPlus
-1
-18.6 APA CHE A PA CHE
-19.484 -19.34
-20 -19.7
-20.04 -19.96 -19.9 -2
-20.2
-20.4
-22
-3 -2.82
-24 -4
37
Figure 151: Average Annual Hourly Zone Temperature - Case 600FF Figure 152: Average Annual Hourly Zone Temperature - Case 900FF
27 27
25.93 25.93
26 26
25.72
degC
24.47
degC
23 23
22 22
Figure 153: Average Annual H ourly Zone Temperature - C ase 650FF Figure 154: Average Annual Hourly Zone Temperature - Case 950FF
21 17
20 16
19.62
ESP ESP
19.1 BLA ST BLAST
18.96 14.97
19 DOE2 15 DOE2
18.69 SRES 14.64 SRES
14.53
degC
degC
17 13
16 12
30
28.96
29
28.69
28.54
ESP
BLAST
28 28
28 DOE2
27.72 SRES
27.6
27.49
degC
SERIRES
S3PA S
TRNSY S
27 26.85 TASE
EnergyPlus
26.43 A PA CHE
26
25
38
Figure 156: Low Mass Basic Sensitivity Tests: Annual Heating - Figure 157: Low Mass Basic Sensitivity Tests: Annual Heating -
Cases 610-600 (overhang added to south window) Cases 620-600 (east/west windows replace south window)
0.12 0.8
0.7 0.682
0.098
0.1
0.089
0.6
ESP ESP
0.08 0.077
BLAST BLA ST
DOE2 0.5 DOE2
0.067
SRES SRES
H
SERIRES
MWH
0.059 SERIRES
MW
0.06 0.4 0.366
0.054 S3PA S S3PA S
TRNSY S 0.328 TRNSYS
0.317 0.312
TA SE 0.3 0.276 TA SE
0 0
Figure 158: Low Mass Basic Sensitivity Tests: Annual Heating - C ases Figure 159: Low Mass Basic Sensitivity Tests: Annual Heating -
630-620 (side-fins & overhangs added to east/west windows) Cases 640-600 (night set-back)
1.4 0
1.29
1.2
-0.5
1 ESP ESP
BLA ST BLAST
DOE2 -1 DOE2
0.8 SRES SRES
0.692 SERIRES
H
MWH
SERIRES
MW
S3PAS S3PA S
0.6 0.551 TRNSYS TRNSY S
0.525 0.531 -1.5
TA SE TA SE
-1.511
0.437 -1.545 EnergyPlus
0.436 Energy Plus
0 -2.5
Figure 160: Low Mass Basic Sensitivity Tests: Annual Cooling - Figure 161: Low Mass Basic Sensitivity Tests: Annual Cooling -
Cases 610-600 (overhang added to south window) Cases 620-600 (east/west windows replace south window)
0 0
-0.5
-0.5
ESP -1 ESP
BLAST BLA ST
DOE2 DOE2
-1
SRES -1.5 SRES
H
SERIRES
MWH
SERIRES
MW
S3PA S S3PA S
-1.272
TRNSY S -2 TRNSYS
-1.5 TA SE
TA SE
-1.582 EnergyPlus EnergyPlus
APA CHE -2.341 A PACHE
-1.728 -2.5 -2.427 -2.427
-2.481 -2.516
-1.83 -1.844 -2.591
-1.891 -1.886 -2.645
-2 -2.72 -2.745
-3
-2.96
-2.186
-2.222 -2.227
-2.5 -3.5
Figure 162: Low Mass B asic Sensitivity Tests: Annual C ooling - Cases Figure 163: Low Mass Basic Sensitivity Tests: Annual Cooling -
630-620 (side-fins & overhangs added to east/w est w indow s) Cases 640-600 (night set-back)
0 0
-0.05
-0.5
SERIRES
MW
-1.5
-1.485 S3PAS S3PA S
-1.522
TRNSYS -0.185 TRNSY S
-0.2
TA SE TA SE
-1.845 -0.22 EnergyPlus
-2 Energy Plus
-0.228
APACHE -0.25 APA CHE
-0.245 -0.246
-0.25 -0.252
-0.27
-2.5
-0.3
-2.63
-0.32
-3 -0.35
Figure 164: Low Mass Basic Sensitivity Tests: Annual Cooling - Figure 165: Low Mass Basic Sensitivity Tests: Peak Heating - Cases
Cases 650-600 (venting) 610-600 (overhang added to south window)
0 0.002
0.001
0 0 0 0
-0.2 0
-0.4 -0.001
-0.002
ESP ESP
-0.6 BLAST BLAST
-0.004
DOE2 DOE2
SERIRES
kW
MW
-0.006
S3PA S S3PA S
-1 TRNSY S TRNSY S
TASE TA SE
-0.008
-1.2 EnergyPlus -0.008 EnergyPlus
-0.008333333
A PA CHE APA CHE
-1.293 -1.284 -0.01
-1.321 -1.322
-1.4
-1.384 -1.373 -1.389
-1.419 -1.404
-0.011
-1.6 -0.012
-0.012
-1.612
-1.8 -0.014
40
Figure 166: Low Mass Basic Sensitivity Tests: Peak Heating - Cases Figure 167: Low Mass Basic Sensitivity Tests: Peak Heating - Cases
620-600 (east/west windows replace south window) 630-620 (side-fins & overhangs added to east/west windows)
0.300 0.005
0.003
0.001 0.001
0.000 0.000 0.000 0.000
0.250 0.240 0.000
kW
kW
S3PA S S3PAS
-0.008 -0.026
-0.017
-0.050 -0.030
Figure 168: Low Mass Basic Sensitivity Tests: Peak Heating - Cases Figure 169: Low Mass Basic Sensitivity Tests: Peak Cooling - Cases
640-600 (night set-back) 610-600 (overhang added to south window)
4.000 0.000
3.771
3.407 -0.100
3.500
-0.116
-0.141
-0.200
3.000
ESP ESP
2.600
BLAST -0.300 BLAST
2.445 -0.300
2.500 DOE2 DOE2
2.272 2.310 -0.336
SRES -0.400 SRES
SERIRES SERIRES
kW
kW
2.000 1.898
1.795 1.792 S3PA S S3PA S
-0.456
TRNSY S -0.500 TRNSY S
1.546
1.500 TA SE -0.525 TA SE
EnergyPlus -0.600 EnergyPlus
-0.592 -0.604
APA CHE APA CHE
1.000
-0.700 -0.666
0.500
-0.800
-0.811
0.000 -0.900
Figure 170: Low Mass Basic Sensitivity Tests: Peak Cooling - Cases Figure 171: Low Mass Basic Sensitivity Tests: Peak Cooling - Cases
620-600 (east/west windows replace south window) 630-620 (side-fins & overhangs added to east/west windows)
0.000 0.000
-0.200
-0.500
-0.400 -0.371
-1.500 -0.842
S3PA S S3PAS
-1.000 TRNSYS
TRNSYS
-1.716 TA SE TA SE
-2.500
-2.560 -2.592 -1.600 -1.550
-3.000 -1.800
Figure 172: Low Mass Basic Sensitivity Tests: Peak Cooling - Cases Figure 173: Low Mass Basic Sensitivity Tests: Peak Cooling - Cases
640-600 (night set-back) 650-600 (venting)
0.000 0.000
-0.010 -0.020
-0.014 -0.015
-0.020 -0.040
ESP ESP
-0.030 BLAST -0.060 BLAST
kW
-0.090 -0.180
41
Figure 174: High Mass Basic Sensitivity Tests: Annual Heating - Figure 175: High Mass Basic Sensitivity Tests: Annual Heating -
Cases 900-600 (mass effect with south window) Cases 910-900 (overhang added to south window)
0 0.5
0.442
0.45
-0.5
0.405
0.4 0.382 0.386
-1
H
SERIRES
H
SERIRES
MW
MW
0.25
S3PA S S3PA S
-2.5 TRNSY S TRNSYS
TA SE 0.2 0.179 TA SE
-3 EnergyPlus EnergyPlus
APA CHE 0.15 A PACHE
-3.126 -3.163 -3.152
-3.217
-3.329 -3.321 -3.311
-3.5 -3.406
0.1
-3.608
-4 -3.837
0.05
-4.5 0
Figure 176: High Mass Basic Sensitivity Tests: Annual Heating - Cases Figure 177: High Mass Basic Sensitivity Tests: Annual Heating -
920-900 (east/w est w indow s replace south w indow ) Cases 930-920 (side-fins & overhangs added to east/west windows)
3 2.5
2.505
2.5 2.383 2.37 2.006
2
2.259
2.196
2.143 2.142 2.121
2.07
2.011 ESP ESP
2 BLA ST BLAST
DOE2 1.5 DOE2
SRES SRES
SERIRES
H
MWH
SERIRES
MW
1.5
S3PAS S3PA S
1.08
TRNSYS TRNSY S
0.933 0.964
1 TA SE
TA SE
0.83
1 Energy Plus EnergyPlus
0.721
APACHE 0.662 0.67 0.682 APA CHE
0.595
0.5
0.5
0 0
Figure 178: High Mass Basic Sensitivity Tests: Annual Heating - Figure 179: High Mass Basic Sensitivity Tests: Annual Heating -
Cases 940-900 (night set-back) Cases 960-900 (mass effect with sunspace)
0 2
1.8 1.718
-0.1
1.6
-0.2
ESP 1.4 1.328 ESP
BLAST BLA ST
-0.3 1.213
DOE2 1.2 1.141 DOE2
SRES 1.054 1.056 1.061 SRES
0.987
H
SERIRES
MWH
SERIRES
MW
-0.4 -0.377 1
S3PA S S3PA S
0.863
TRNSY S TRNSYS
0.775
0.8 TA SE
-0.5 -0.469 TA SE
EnergyPlus EnergyPlus
APA CHE 0.6 A PACHE
-0.551
-0.6 -0.577 -0.575
-0.589
-0.625 0.4
-0.633
-0.666
-0.7
0.2
-0.718
-0.8 0
43
Figure 180: High Mass Basic Sensitivity Tests: Peak Heating - Cases Figure 181: High Mass Basic Sensitivity Tests: Peak Heating - Cases
900-600 (mass effect with south window) 910-900 (overhang added to south window)
0.000 0.025
-0.100 0.019
0.020
kW
kW
0.010
S3PA S S3PA S
0.008
-0.400 TRNSY S 0.007 TRNSYS
-0.414 TA SE TA SE
-0.429
-0.444 EnergyPlus 0.005 0.004 0.004 EnergyPlus
-0.002
-0.700 -0.005
Figure 182: High Mass Basic Sensitivity Tests: Peak Heating - Cases Figure 183: High Mass Basic Sensitivity Tests: Peak Heating - Cases
920-900 (east/west windows replace south window) 930-920 (side-fins & overhangs added to east/west windows)
0.500 0.140
0.458 0.127
0.450
0.421
0.120
0.400
kW
0.250
S3PAS S3PA S
0.216
TRNSYS 0.060 TRNSY S
0.192
0.200
TA SE TA SE
0.047
EnergyPlus EnergyPlus
0.150 APACHE APA CHE
0.040 0.035 0.036
0.029 0.029
0.027
0.100
0.075 0.022
0.019
0.020
0.050 0.009
0.000 0.000
Figure 184: High Mass Basic Sensitivity Tests: Peak Heating - Cases Figure 185: High Mass Basic Sensitivity Tests: Peak Heating - Cases
940-900 (night set-back) 960-900 (mass effect with sunspace)
7.000 0.000
kW
0.000 -1.400
44
Figure 186: High Mass Basic Sensitivity Tests: Annual Cooling - Figure 187: High Mass Basic Sensitivity Tests: Annual Cooling -
Cases 900-600 (mass effect with south window) Cases 910-900 (overhang added to south window)
0 0
-0.5 -0.2
-1
-0.4
H
SERIRES SERIRES
MW
MW
-2.5 -0.832
S3PA S S3PA S
TRNSY S -1 TRNSYS
-3
TA SE -1.067 TA SE
EnergyPlus -1.2 -1.144 -1.145 -1.142 EnergyPlus
-1.159
-3.5 APA CHE A PACHE
-1.311 -1.293
-1.4
-4 -3.833
-3.92
-4.005 -4.007
-4.113 -4.179 -4.117 -1.479
-4.5 -4.303 -1.6 -1.561
-4.549
-4.624
-5 -1.8
Figure 188: High Mass Basic Sensitivity Tests: Annual Cooling - Cases Figure 189: High Mass Basic Sensitivity Tests: Annual Cooling -
920-900 (east/west windows replace south window) Cases 930-920 (side-fins & overhangs added to east/west windows)
0.2 0
0.168
-0.2
0.1
0.056 -0.4
0.016 0.014
ESP -0.6 ESP
0 BLA ST BLAST
-0.682
-0.015 DOE2 -0.714 DOE2
-0.8
-0.77
SRES -0.801 SRES
-0.854 -0.837
-0.067
MWH
SERIRES
H
SERIRES
MW
-0.1 -1
S3PAS -1.002 S3PA S
-1.018
-0.115 TRNSY S
TRNSYS
-1.2 TA SE
TA SE -1.174
-0.2 EnergyPlus EnergyPlus
APACHE -1.4 APA CHE
-0.222
-1.6
-0.3
-0.292
-0.323 -1.8 -1.719
-0.4 -2
Figure 190: High Mass Basic Sensitivity Tests: Annual Cooling - Figure 191: High Mass Basic Sensitivity Tests: Annual Cooling -
Cases 940-900 (night set-back) Cases 950-900 (venting)
0 0
-0.02
-0.5
-0.04
SERIRES SERIRES
MW
-2.244
-0.16
-2.5
-0.18 -0.174
-2.826
-0.2 -3
Figure 192: High Mass Basic Sensitivity Tests: Annual Cooling - Cases
960-900 (mass effect with sunspace)
-0.5
ESP
-1 BLA ST
DOE2
SRES
MWH
SERIRES
-1.5
S3PAS
-1.644 TRNSYS
-1.689 -1.716 TA SE
-1.813
-2 -1.929 EnergyPlus
-1.934
-2.027 APACHE
-2.0737
-2.362
-2.5
-2.697
-3
46
Figure 193: High Mass Basic Sensitivity Tests: Peak Cooling - Cases Figure 194: High Mass Basic Sensitivity Tests: Peak Cooling - Cases
900-600 (mass effect with south window) 910-900 (overhang added to south window)
0.000 0.000
-0.500
-0.200
-1.000
ESP -0.310 ESP
BLAST -0.400 BLA ST
-1.500 DOE2 DOE2
SRES SRES
SERIRES SERIRES
kW
-0.548
kW
-2.000 -0.600
S3PA S -0.594 S3PA S
-0.609
TRNSY S -0.655 TRNSYS
TA SE -0.687 TA SE
-2.500
EnergyPlus -0.800 EnergyPlus
-0.775
-2.650 APA CHE A PACHE
-2.810
-3.000 -2.919
-2.956 -2.952
-3.063 -0.928
-3.198 -1.000
-3.306 -3.296 -0.992
-3.500 -3.355
-1.122
-4.000 -1.200
Figure 195: High Mass Basic Sensitivity Tests: Peak Cooling - Cases Figure 196: High Mass Basic Sensitivity Tests: Peak Cooling - Cases
920-900 (east/west windows replace south window) 930-920 (side-fins & overhangs added to east/west windows)
0.200 0.000
0.048
0.000 -0.200
kW
kW
-1.000 -1.200
-1.201
-1.124
-1.200 -1.400
Figure 197: High Mass Basic Sensitivity Tests: Peak Cooling - Cases Figure 198: High Mass Basic Sensitivity Tests: Peak Cooling - Cases
940-900 (night set-back) 950-900 (venting)
1.000 0.000
0.900
-0.200
0.800
0.500 -0.600
TRNSY S -0.590 S3PA S
TA SE -0.657 TRNSYS
0.400 -0.701 TA SE
APA CHE
-0.723
ESP -0.800 EnergyPlus
0.300 -0.794 A PACHE
EnergyPlus -0.821
-0.855
-0.881
0.200
-1.000
0.100 -1.053
0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
0.000 -1.200
Figure 199: High Mass Basic Sensitivity Tests: Peak Cooling - Cases
960-900 (mass effect with sunspace)
0.000
-0.500
-1.000
ESP
BLA ST
-1.500
DOE2
SRES
SERIRES
kW
-2.000 -1.935
-2.011 S3PAS
-2.054 -2.105
-2.155 -2.189 -2.192 TRNSYS
-2.500 TA SE
-2.401
-2.501 EnergyPlus
APACHE
-3.000
-3.500
-3.595
-4.000
47
Figure 200: Low Mass In-Depth Sensitivity Tests: Annual Heating - Figure 201: Low Mass In-Depth Sensitivity Tests: Annual Heating -
Cases 200-195 (opaque panel replaces wall) Cases 210-200 (external emissivity)
2.500 1.400
1.204
1.200
1.961
2.000
H
SERIRES
MWH
SERIRES
MW
S3PA S 0.614 S3PA S
1.085
TRNSY S 0.600 TRNSYS
1.000 TA SE
TA SE
EnergyPlus EnergyPlus
APA CHE 0.400 A PACHE
0.500
0.200 0.159
0.111 0.099 0.085
0.000
0.000 0.000
Figure 202: Low Mass In-Depth Sensitivity Tests: Annual Heating - Figure 203: Low Mass In-Depth Sensitivity Tests: Annual Heating -
Cases 220-215 (external emissivity) Cases 215-200 (internal emissivity)
1.600 1.400
1.260
1.397
1.400
1.200
1.200
ESP 1.000 ESP
BLA ST BLA ST
1.000 0.820
DOE2 DOE2
SRES 0.800 SRES
0.735
MWH
H
SERIRES SERIRES
MW
0.800 0.656 0.645
0.710 S3PAS S3PA S
TRNSYS 0.600 TRNSYS
TA SE TA SE
0.600
EnergyPlus 0.437 EnergyPlus
APACHE 0.400 A PACHE
0.400 0.295
0.000
0.000 0.000
Figure 204: Low Mass In-Depth Sensitivity Tests: Annual Heating - Figure 205: Low Mass In-Depth Sensitivity Tests: Annual Heating -
Cases 220-210 (internal emissivity) Cases 230-220 (infiltration)
1.400 4.000
1.333
3.615
3.525 3.531 3.522 3.543 3.527 3.540
3.432 3.456
3.500
1.200
3.000
1.000 ESP ESP
0.916
BLAST BLAST
2.500
DOE2 DOE2
0.800 0.743 SRES SRES
MWH
0.687 SERIRES
H
SERIRES
MW
0.656 2.000
S3PA S S3PA S
0.600 TRNSY S TRNSY S
0.488 TASE TA SE
0.470 1.500
EnergyPlus EnergyPlus
0.400 A PA CHE APA CHE
1.000
0.200
0.500
0.000 0.000
Figure 206: Low Mass In-Depth Sensitivity Tests: Annual Heating - Figure 207: Low Mass In-Depth Sensitivity Tests: Annual Heating -
Cases 240-220 (internal gains) Cases 250-220 (external solar absorptance)
0.000
0.000
-0.200
-0.500
-0.400 ESP
ESP
BLA ST
BLA ST
DOE2
-0.600 DOE2 -1.000
SRES
SRES
MWH
SERIRES
MWH
SERIRES
-0.800 S3PAS
S3PA S
TRNSYS
TRNSYS -1.500
-1.476 -1.474 -1.448 TA SE
TA SE -1.494 -1.523
-1.000 -1.533
EnergyPlus
EnergyPlus
-1.699 APACHE
A PACHE -1.763
-1.200
-1.206 -1.221 -1.203 -2.000
-1.228
-1.295 -1.279
-1.400 -1.339 -1.333 -1.341
-2.193
-1.600 -2.500
Figure 208: Low Mass In-Depth Sensitivity Tests: Annual Heating - Figure 209: Low Mass In-Depth Sensitivity Tests: Annual Heating -
Cases 270-220 (south window replaces opaque panel) Cases 280-270 (internal solar absorptance)
0.000 0.700
0.596
0.600
-0.500
H
MW
MW
-1.500
S3PA S 0.311 S3PA S
0.291
TRNSY S 0.300 TRNSY S
TA SE TASE
0.228 0.232
-2.000 EnergyPlus EnergyPlus
-1.948
APA CHE 0.195 A PA CHE
0.200
0.165
-2.207
-2.285 -2.250
-2.350
-2.500 -2.434
-2.493 0.100
-2.761
-3.000 0.000
49
Figure 210: Low Mass In-Depth Sensitivity Tests: Annual Heating - Figure 211: Low Mass In-Depth Sensitivity Tests: Annual Heating -
Cases 320-270 (cooling setpoint) Cases 290-270 (south window overhang)
0.000 0.250
-0.100
0.198
0.200
-0.200
ESP ESP
-0.300 BLAST BLA ST
DOE2 0.150 DOE2
H
SERIRES
MWH
SERIRES
MW
S3PA S S3PA S
-0.500 TRNSY S TRNSYS
0.100 TA SE
TA SE 0.088 0.085
-0.600 EnergyPlus EnergyPlus
-0.577
APA CHE 0.067 0.064 A PACHE
-0.651 -0.649
-0.700
-0.699 0.050
-0.721 -0.729
0.029
-0.757 0.022
-0.800 -0.779 0.020
-0.900 0.000
Figure 212: Low Mass In-Depth Sensitivity Tests: Annual Heating - Figure 213 Low Mass In-Depth Sensitivity Tests: Annual Heating -
Cases 300-270 (east/west windows) Cases 310-300 (east/west side-fins & overhangs)
0.700 1.600
1.200
0.500 ESP ESP
BLA ST BLA ST
DOE2 1.000 DOE2
0.400 SRES SRES
MWH
H
SERIRES SERIRES
MW
0.800
S3PAS S3PA S
0.297
0.300 TRNSYS TRNSYS
0.251 0.246 TA SE 0.600 TA SE
EnergyPlus 0.492 0.486 EnergyPlus
0.460
0.200 APACHE A PACHE
0.175
0.147 0.400 0.350
0.328
0.250
0.201
0.100 0.077
0.200
0.044
0.000 0.000
Figure 214: Low Mass In-Depth Sensitivity Tests: Peak Heating - Figure 215: Low Mass In-Depth Sensitivity Tests: Peak Heating -
Cases 200-195 (opaque panel replaces wall) Cases 210-200 (external emissivity)
1.200 0.060
1.119 0.050
0.040
1.000
0.030
0.024
0.021
0.812 ESP 0.020 ESP
0.787 0.778 0.784 0.779 0.011
0.800 BLAST BLA ST
DOE2 0.000 DOE2
0.647 SRES 0.000 SRES
MWH
SERIRES SERIRES
MW
0.600
S3PA S S3PA S
TRNSY S -0.020 TRNSYS
TA SE TA SE
0.200
-0.060 -0.057
0.000 -0.080
Figure 216: Low Mass In-Depth Sensitivity Tests: Peak Heating - Figure 217: Low Mass In-Depth Sensitivity Tests: Peak Heating -
Cases 220-215 (external emissivity) Cases 215-200 (internal emissivity)
0.090 0.700
0.080
0.080 0.603
0.600
0.070
0.062 0.500
ESP ESP
0.059
0.060 BLA ST BLAST
DOE2 DOE2
0.389
SRES 0.400 SRES
0.050
MWH
MWH
SERIRES SERIRES
0.041 0.042 0.325
S3PAS 0.307 0.308 S3PA S
0.040 0.037 TRNSYS TRNSY S
0.300
TA SE TA SE
0.020 0.136
0.100 0.076
0.010
0.000
0.000 0.000
Figure 218: Low Mass In-Depth Sensitivity Tests: Peak Heating - Figure 219: Low Mass In-Depth Sensitivity Tests: Peak Heating -
Cases 220-210 (internal emissivity) Cases 230-220 (infiltration)
0.700 2.000
0.632 1.811
1.800
1.704
0.600
1.584 1.584 1.587
1.600 1.556
1.519 1.529 1.506
SERIRES
H
SERIRES
MW
0.328 1.000
0.307 S3PA S S3PA S
0.300 TRNSY S TRNSYS
TASE 0.800
TA SE
EnergyPlus EnergyPlus
0.195 A PA CHE 0.600
0.200 A PACHE
0.166
0.400
0.100
0.200
0.000 0.000
50
Figure 220: Low Mass In-Depth Sensitivity Tests: Peak Heating - Figure 221: Low Mass In-Depth Sensitivity Tests: Peak Heating -
Cases 240-220 (internal gains) Cases 250-220 (external solar absorptance)
0.000 0.006
0.005
0.004
-0.050
H
H
SERIRES SERIRES
MW
MW
-0.007
-0.250 -0.008
Figure 222: Low Mass In-Depth Sensitivity Tests: Peak Heating - Figure 223: Low Mass In-Depth Sensitivity Tests: Peak Heating -
Cases 270-220 (south window replaces opaque panel) Cases 280-270 (internal solar absorptance)
0.250 0.030
0.218
0.021
ESP ESP
0.150 BLAST 0.020 BLAST
DOE2 DOE2
SRES SRES
SERIRES SERIRES
H
H
MW
MW
0.100 0.015
S3PA S S3PA S
TRNSY S TRNSY S
TA SE TA SE
Figure 224: Low Mass In-Depth Sensitivity Tests: Peak Heating - Figure 225: Low Mass In-Depth Sensitivity Tests: Peak Heating -
Cases 320-270 (cooling setpoint) Cases 290-270 (south window overhang)
0.000 0.000 0.000 0.000
0.000 0.010
0.009
0.008
-0.001
0.006
SERIRES
MWH
SERIRES
0.000
S3PA S S3PA S
-0.002 TRNSY S TRNSYS
-0.002 -0.002 -0.002
TA SE TA SE
EnergyPlus EnergyPlus
-0.003 APA CHE -0.004 A PACHE
-0.006
-0.003
-0.003 -0.003
-0.008
-0.008
-0.009
-0.004 -0.010
Figure 226: Low Mass In-Depth Sensitivity Tests: Peak Heating - Figure 227: Low Mass In-Depth Sensitivity Tests: Peak Heating -
Cases 300-270 (east/west windows) Cases 310-300 (east/west side-fins & overhangs)
0.300 0.002
0.001 0.001 0.001
0.259
SERIRES
MWH
SERIRES
-0.004
S3PAS S3PA S
0.100 TRNSYS TRNSY S
TA SE TA SE
EnergyPlus -0.006 EnergyPlus
0.050 APACHE APA CHE
0.032
0.020
-0.007
0.005
-0.001 0.000 -0.008
0.000
-0.008
-0.009
-0.050 -0.010
51
Figure 228: Low Mass In-Depth Sensitivity Tests: Annual Cooling - Figure 229: Low Mass In-Depth Sensitivity Tests: Annual Cooling -
Cases 200-195 (opaque panel replaces wall) Cases 210-200 (external emissivity)
0.300 0.050
0.008
0.000
0.000
H
SERIRES
MWH
SERIRES
MW
0.150 -0.200
S3PA S S3PA S
TRNSY S TRNSYS
-0.250 TA SE
TA SE
0.100 EnergyPlus EnergyPlus
APA CHE -0.300 A PACHE
-0.350
0.050
-0.400
-0.408
0.000 -0.450
Figure 230: Low Mass In-Depth Sensitivity Tests: Annual Cooling - Figure 231: Low Mass In-Depth Sensitivity Tests: Annual Cooling -
Cases 220-215 (external emissivity) Cases 215-200 (internal emissivity)
0.100 0.180
SERIRES
H
SERIRES 0.088
MW
-0.200
S3PAS S3PA S
0.080 TRNSY S
TRNSYS 0.072
0.069
TA SE TA SE
0.038
0.040
-0.400
0.020
-0.453
-0.500 0.000
Figure 232: Low Mass In-Depth Sensitivity Tests: Annual Cooling - Figure 233: Low Mass In-Depth Sensitivity Tests: Annual Cooling -
Cases 220-210 (internal emissivity) Cases 230-220 (infiltration)
0.100 0.350
0.088 0.311
0.090 0.086 0.304 0.304 0.303 0.302
0.300 0.293
0.286
0.275
0.080 0.268
0.073
0.069 0.250
0.070 ESP ESP
BLAST BLAST
DOE2 DOE2
0.060
SRES 0.200 SRES
H
SERIRES SERIRES
H
MW
MW
0.050
S3PA S S3PA S
0.042
TRNSY S 0.150 TRNSY S
0.040 TASE TA SE
EnergyPlus EnergyPlus
0.030 A PA CHE 0.100 APA CHE
0.024
0.020
0.050
0.010
0.000 0.000
Figure 234: Low Mass In-Depth Sensitivity Tests: Annual Cooling - Figure 235: Low Mass In-Depth Sensitivity Tests: Annual Cooling -
Cases 240-220 (internal gains) Cases 250-220 (external solar absorptance)
0.450 3.500
0.412 0.411
0.400 3.027
0.374 0.377 3.000
0.371
0.362
2.697
0.350 0.334
SERIRES SERIRES
MW
MW
1.644
S3PA S S3PAS
0.200 TRNSYS 1.500 TRNSYS
TA SE TA SE
0.100
0.500
0.050
0.000 0.000
Figure 236: Low Mass In-Depth Sensitivity Tests: Annual Cooling - Figure 237: Low Mass In-Depth Sensitivity Tests: Annual Cooling -
Cases 270-220 (south window replaces opaque panel) Cases 280-270 (internal solar absorptance)
10.000 0.000
9.515
9.001
9.000
-0.500
7.969 8.061 8.027 8.031
7.854
8.000
7.342
H
MW
MW
5.000
S3PA S S3PA S
TRNSY S -2.000 TRNSY S
4.000 TA SE TASE
EnergyPlus EnergyPlus
3.000 APA CHE A PA CHE
-2.500
-2.457
-2.655
2.000
-2.775 -2.801
-3.000
-2.990 -3.003
1.000
-3.236
-3.317
0.000 -3.500
53
Figure 238: Low Mass In-Depth Sensitivity Tests: Annual Cooling - Figure 239: Low Mass In-Depth Sensitivity Tests: Annual Cooling -
Cases 320-270 (cooling setpoint) Cases 290-270 (south window overhang)
0.000 0.000
-0.500
-0.500
H
SERIRES
MWH
SERIRES
MW
S3PA S S3PA S
-1.283
-2.000 TRNSY S TRNSYS
-1.500 TA SE
TA SE
EnergyPlus EnergyPlus
-1.659 A PACHE
-2.500 APA CHE
-2.467
-1.892
-2.000
-2.764 -2.808 -2.808 -2.002
-3.000 -2.881 -2.065
-2.107
-3.046 -3.051
-2.261
-3.252 -2.324
-3.500 -2.500
Figure 240: Low Mass In-Depth Sensitivity Tests: Annual Cooling - Figure 241: Low Mass In-Depth Sensitivity Tests: Annual Cooling -
Cases 300-270 (east/west windows) Cases 310-300 (east/west side-fins & overhangs)
0.000 0.000
-0.500 -0.500
H
SERIRES -1.570 SERIRES
MW
-1.629
S3PAS S3PA S
-2.000 TRNSYS -2.000 TRNSYS
-1.974 -1.994
TA SE TA SE
EnergyPlus EnergyPlus
-2.834
-3.000 -2.933 -3.000
-2.946
-3.043 -3.036
-3.163
-3.226 -3.250
-3.310
-3.500 -3.500
Figure 242: Low Mass In-Depth Sensitivity Tests: Peak Cooling - Figure 243: Low Mass In-Depth Sensitivity Tests: Peak Cooling -
Cases 200-195 (opaque panel replaces wall) Cases 210-200 (external emissivity)
0.400 0.050
0.016
0.000
0.000
0.350 0.336
-0.010 -0.008
SERIRES SERIRES
MW
0.200 -0.200
S3PA S S3PA S
TRNSY S TRNSYS
-0.250 TA SE
0.150 TA SE
EnergyPlus EnergyPlus
APA CHE -0.300 A PACHE
0.100
-0.350
0.050
-0.400 -0.387
0.000 -0.450
Figure 244: Low Mass In-Depth Sensitivity Tests: Peak Cooling - Figure 245: Low Mass In-Depth Sensitivity Tests: Peak Cooling -
Cases 220-215 (external emissivity) Cases 215-200 (internal emissivity)
0.100 0.250
0.236
0.021
0.000 -0.001
0.000
-0.005 -0.005 0.200
-0.033
ESP ESP
-0.100 BLA ST BLAST
0.149
DOE2 0.150 0.144 DOE2
0.140
SRES SRES
MWH
SERIRES
H
SERIRES
MW
-0.200
S3PAS 0.111 S3PAS
TRNSYS TRNSY S
0.100 TASE
TA SE
0.083
-0.300 EnergyPlus EnergyPLus
APACHE 0.066 A PA CHE
0.050
-0.400
-0.447
-0.500 0.000
Figure 246: Low Mass In-Depth Sensitivity Tests: Peak Cooling - Figure 247: Low Mass In-Depth Sensitivity Tests: Peak Cooling -
Cases 220-210 (internal emissivity) Cases 230-220 (infiltration)
0.300 0.600
ESP ESP
0.200 BLAST 0.400 BLA ST
DOE2 DOE2
SRES SRES
0.149 0.150
MWH
SERIRES
H
SERIRES
MW
0.150 0.300
S3PA S S3PA S
0.118 TRNSY S TRNSYS
0.111
TASE TA SE
0.100 EnergyPlus 0.200 EnergyPlus
0.084
A PA CHE A PACHE
0.071
0.050 0.100
0.000 0.000
54
Figure 248: Low Mass In-Depth Sensitivity Tests: Peak Cooling - Figure 249: Low Mass In-Depth Sensitivity Tests: Peak Cooling -
Cases 240-220 (internal gains) Cases 250-220 (external solar absorptance)
0.250 4.000
3.699
3.500
0.200 0.200
0.200
0.181 0.182 0.183 0.183 0.184 0.184
0.179 3.000
2.800
ESP ESP
BLA ST BLA ST
2.500
0.150 DOE2 DOE2
SRES SRES
2.049
1.975
H
MWH
SERIRES SERIRES
MW
2.000 1.870
S3PA S S3PAS
1.668
TRNSYS TRNSYS
0.100 TA SE
1.500 TA SE
EnergyPlus 1.250 1.240 EnergyPlus
A PACHE 1.043 APACHE
1.000
0.050
0.500
0.000 0.000
Figure 250: Low Mass Primitive Diagnostic Test: Peak Cooling - Figure 251: Low Mass Primitive Diagnostic Test: Peak Cooling -
Cases 270-220 (south window replaces opaque panel) Cases 280-270 (internal solar absorptance)
7.000 0.000
6.625
5.796 5.894
6.000
5.604 5.585 5.654
5.475 5.471 -0.500
H
MW
MW
S3PA S S3PA S
3.000 TRNSY S TRNSY S
TA SE -1.500 TASE
EnergyPlus EnergyPlus
-1.631
2.000 APA CHE A PA CHE
-1.873
-2.000 -1.912
-2.010 -1.978
-2.014
1.000
-2.208 -2.189
0.000 -2.500
Figure 252: Low Mass In-Depth Sensitivity Tests: Peak Cooling - Figure 253 Low Mass In-Depth Sensitivity Tests: Peak Cooling -
Cases 320-270 (cooling setpoint) Cases 290-270 (south window overhang)
0.000 0.000
-0.100
-0.100 -0.087 -0.086
-0.119
-0.200
ESP ESP
-0.174
BLAST -0.200 BLA ST
-0.300
DOE2 DOE2
SRES -0.246 -0.240 SRES
MWH
SERIRES SERIRES
MW
-0.400 -0.300
S3PA S S3PA S
TRNSY S -0.324 TRNSYS
TA SE TA SE
-0.500
EnergyPlus -0.400 EnergyPlus
APA CHE A PACHE
-0.600 -0.586
-0.621
-0.635 -0.636 -0.500
-0.655
-0.700
-0.695
-0.726
-0.750 -0.561
-0.800 -0.600
Figure 254: Low Mass In-Depth Sensitivity Tests: Peak Cooling - Figure 255: Low Mass Primitive Diagnostic Test: Peak Cooling -
Cases 300-270 (east/west windows) Cases 310-300 (east/west side-fins & overhangs)
0.000 0.000
-0.200
-0.500
-0.400 -0.344
-1.000 ESP -0.406
ESP
-0.471
BLA ST BLAST
DOE2 -0.600 -0.556 -0.558 DOE2
-1.500 SRES SRES
-0.667 -0.689
MWH
SERIRES
H
SERIRES
MW
-0.800
S3PAS S3PA S
-2.000 TRNSYS TRNSY S
-1.938
TA SE -1.000 TA SE
EnergyPlus EnergyPlus
-3.000 -2.895
-2.952 -1.400
-1.504
-3.500 -1.600
55
Figure 256: Low Mass In-Depth Sensitivity Tests: Annual Heating - Figure 257: Low Mass In-Depth Sensitivity Tests: Annual Heating -
Cases 400-395 (opaque panel replaces wall) Cases 410-400 (infiltration)
3.500 2.000
SERIRES
MWH
SERIRES
1.000
S3PAS S3PA S
1.500 TRNSYS TRNSY S
TA SE 0.800 TA SE
EnergyPlus EnergyPlus
1.000 APACHE 0.600 APA CHE
0.400
0.500
0.200
0.000 0.000
Figure 258: Low Mass In-Depth Sensitivity Tests: Annual Heating - Figure 259: Low Mass In-Depth Sensitivity Tests: Annual Heating -
Cases 420-410 (internal gains) Cases 430-420 (external solar absorptance)
0.000 0.000
-0.200
-0.200
-0.400
-0.400
ESP -0.600 ESP
BLAST BLA ST
-0.600 DOE2 DOE2
-0.800
SRES SRES
SERIRES
H
MWH
SERIRES
MW
-0.800 -1.000
S3PA S S3PAS
TRNSY S TRNSYS
-1.122 -1.112 -1.131
TASE -1.200
-1.000 -1.187 -1.187 TA SE
-1.197
EnergyPlus Energy Plus
A PA CHE -1.400 -1.324
-1.353 APACHE
-1.200
-1.869
-1.600 -2.000
Figure 260: Low Mass In-Depth Sensitivity Tests: Annual Heating - Figure 261: Low Mass In-Depth Sensitivity Tests: Annual Heating -
Cases 600-430 (south window replaces opaque panel) Cases 440-600 (internal solar absorptance)
0.000 0.450
0.426
0.400
-0.500
0.350
ESP ESP
BLAST 0.300 BLAST
0.280 0.277
0.270
-1.000 DOE2 DOE2
SRES 0.250 SRES
SERIRES 0.226 SERIRES
H
-1.133 -1.148
MW
MW
0.214 0.215
S3PA S S3PA S
TRNSY S 0.200 TRNSY S
-1.500 TA SE TASE
0.153
-1.590 EnergyPlus 0.150 EnergyPlus
-1.628
-1.715 APA CHE A PA CHE
-1.780
0.100
-2.000 -1.952 -1.940
-2.118 0.050
-2.500 0.000
57
Figure 262: Low Mass In-Depth Sensitivity Tests: Peak Heating - Figure 263: Low Mass In-Depth Sensitivity Tests: Peak Heating -
Cases 400-395 (opaque panel replaces wall) Cases 410-400 (infiltration)
1.400 1.000
1.310 1.318
1.250 0.885
0.900
0.844
1.200 1.148 1.138
1.115 0.792 0.792 0.794
1.079 0.800 0.778
1.071 0.758 0.757
0.734
kW
kW
0.500
S3PAS S3PA S
0.600 TRNSYS TRNSY S
0.400 TA SE
TA SE
Energy Plus EnergyPlus
APACHE 0.300 APA CHE
0.400
0.200
0.200
0.100
0.000 0.000
Figure 264: Low Mass In-Depth Sensitivity Tests: Peak Heating - Figure 265: Low Mass In-Depth Sensitivity Tests: Peak Heating -
Cases 420-410 (internal gains) Cases 430-420 (external solar absorptance)
0.000 0.012
0.011
0.010
-0.050
kW
S3PAS S3PAS
TRNSY S 0.004 TRNSYS
-0.150 TA SE TA SE
Series8 APACHE
A PACHE 0.002 Energy Plus
-0.182 -0.180 -0.183 -0.183 -0.182
-0.183
-0.188
-0.200
-0.200 -0.200 0.000 0.000 0.000 0.000 0.000 0.000 0.000
0.000
-0.001
-0.250 -0.002
Figure 266: Low Mass In-Depth Sensitivity Tests: Peak Heating - Figure 267: Low Mass In-Depth Sensitivity Tests: Peak Heating -
Cases 600-430 (south window replaces opaque panel) Cases 440-600 (internal solar absorptance)
0.250 0.025
0.217 0.022
ESP ESP
0.150 BLAST 0.015 BLAST
DOE2 DOE2
SRES SRES
SERIRES SERIRES
kW
kW
0.100 0.010
S3PA S S3PA S
TRNSY S TRNSY S
TA SE TASE
0.005
0.050 EnergyPlus 0.005 EnergyPlus
APA CHE A PA CHE
0.016 0.002 0.002
0.006
0.000 0.000
0.000 0.000
-0.005 -0.004 -0.005 -0.007 -0.001
-0.029
-0.050 -0.005
58
Figure 268: Low Mass In-Depth Sensitivity Tests: Annual Cooling - Figure 269: Low Mass In-Depth Sensitivity Tests: Annual Cooling -
Cases 400-395 (opaque panel replaces wall) Cases 410-400 (infiltration)
0.050 0.030
0.045
0.045 0.044 0.026
0.025
0.040 0.023 0.023
0.022
0.021 0.021
0.034 ESP
0.035 0.033 ESP
0.032 BLA ST 0.020 0.019 BLAST
0.030
0.029 DOE2 DOE2
0.030
SRES SRES
SERIRES
H
H
SERIRES
MW
MW
0.025 0.015
S3PAS S3PA S
TRNSYS TRNSY S
0.020 TA SE
TA SE
Energy Plus 0.010 EnergyPlus
0.015 APACHE 0.008 APA CHE
0.010
0.005
0.005
0.002
0.000 0.000
0.000 0.000
Figure 270: Low Mass In-Depth Sensitivity Tests: Annual Cooling - Figure 271: Low Mass In-Depth Sensitivity Tests: Annual Cooling -
Cases 420-410 (internal gains) Cases 430-420 (external solar absorptance)
0.120 0.800
0.732
0.105 0.104
0.700
0.100
0.090
0.088
0.600
0.081 ESP 0.531 ESP
0.078 0.515
0.080 BLAST BLA ST
0.496
0.500 0.470
DOE2 0.460 DOE2
SRES SRES
0.409
SERIRES 0.395
H
MWH
SERIRES
MW
0.020
0.011 0.100
0.000 0.000
Figure 272: Low Mass In-Depth Sensitivity Tests: Annual Cooling - Figure 273: Low Mass In-Depth Sensitivity Tests: Annual Cooling -
Cases 600-430 (south window replaces opaque panel) Cases 440-600 (internal solar absorptance)
8.000 0.000
7.280
H
MW
MW
4.000 -1.500
S3PA S S3PA S
TRNSY S TRNSY S
3.000 TA SE TASE
EnergyPlus -2.000 EnergyPlus
APA CHE A PA CHE
-2.094
2.000 -2.170
-2.261
-2.345
-2.500
1.000 -2.500 -2.517
-2.604
-2.760
0.000 -3.000
60
Figure 274: Low Mass In-Depth Sensitivity Tests: Peak Cooling - Figure 275: Low Mass In-Depth Sensitivity Tests: Peak Cooling -
Cases 400-395 (opaque panel replaces wall) Cases 410-400 (infiltration)
0.350 0.180
0.166
0.160
0.291 0.151
0.300 0.148 0.148
0.278
0.272 0.138
0.265 0.140
0.256 0.130
0.251
0.250 ESP ESP
0.227 0.118
BLA ST 0.120 BLAST
0.219 0.112
DOE2 DOE2
0.200 SRES 0.100 SRES
SERIRES SERIRES
kW
kW
S3PAS S3PA S
0.080 TRNSY S
0.150 TRNSYS
TA SE TA SE
Energy Plus 0.060 EnergyPlus
0.040 0.035
0.050
0.020
0.000
0.000 0.000
Figure 276: Low Mass In-Depth Sensitivity Tests: Peak Cooling - Figure 277: Low Mass In-Depth Sensitivity Tests: Peak Cooling -
Cases 420-410 (internal gains) Cases 430-420 (external solar absorptance)
0.250 1.800
0.233 1.657
0.223 0.224
0.218 0.215 0.215
0.214 1.600
0.211
0.200 0.195
1.400
1.235 ESP
ESP
BLAST 1.200 BLA ST
kW
0.849 0.861 0.851
S3PA S 0.796 S3PAS
TRNSY S 0.800 TRNSYS
0.715 0.701
0.100 TASE 0.637 TA SE
EnergyPlus 0.600 Energy Plus
A PA CHE APACHE
0.400
0.050
0.200
0.000 0.000
Figure 278: Low Mass In-Depth Sensitivity Tests: Peak Cooling - Figure 279: Low Mass In-Depth Sensitivity Tests: Peak Cooling -
Cases 600-430 (south window replaces opaque panel) Cases 440-600 (internal solar absorptance)
7.000 0.000
6.000 5.772
-0.500
5.229
5.065
5.000 4.701 4.711 ESP ESP
4.688 4.660
BLAST BLAST
4.193 4.234
DOE2 -1.000 DOE2
4.000 SRES SRES
SERIRES SERIRES
kW
kW
S3PA S S3PA S
3.000 TRNSY S TRNSY S
TA SE -1.500 TASE
-1.541 -1.534
EnergyPlus EnergyPlus
-1.648
2.000 APA CHE -1.709 A PA CHE
-1.774 -1.800
-1.821
-2.000 -1.936
1.000
0.000 -2.500
61
Figure 280: Basic and In-Depth Sensitivity Tests: Annual Heating - Figure 281: High Mass Basic and In-Depth Sensitivity Tests: Annual
Cases 800-430 (mass effect with opaque panel) Heating - Cases 900-800 (south window replaces opaque panel)
0.000 0.000
-0.100
-1.000
H
SERIRES
H
SERIRES
MW
MW
-3.000
S3PA S S3PA S
-0.400 TRNSY S TRNSYS
TA SE TA SE
-3.698
EnergyPlus -4.000 -3.820 EnergyPlus
Figure 282: High Mass Basic and In-Depth Sensitivity Tests: Annual Figure 283: High Mass Basic and In-Depth Sensitivity Tests: Annual
Heating - Cases 900-810 (internal solar absorptance) Heating - Cases 910-610 (mass effect with shaded south window)
0.000 0.000
-0.500
-0.200
-1.000
ESP ESP
-0.400 BLA ST BLAST
DOE2 -1.500 DOE2
SRES SRES
SERIRES
MWH
H
SERIRES
MW
-0.600 -2.000
S3PAS S3PA S
TRNSYS TRNSY S
-0.669
TA SE -2.500 TA SE
Figure 284: High Mass Basic and In-Depth Sensitivity Tests: Annual Figure 285: High Mass Basic and In-Depth Sensitivity Tests: Annual
Heating - Cases 920-620 (mass effect with east/west windows) Heating - Cases 930-630 (mass effect with shaded east/west
windows)
0.000
0.000
-0.200
-0.200
-0.400
ESP
-0.600 -0.400 ESP
BLAST
BLA ST
DOE2
DOE2
-0.800 SRES
-0.600 SRES
MWH
SERIRES
MWH
SERIRES
S3PA S
-1.000 -0.712 S3PA S
TRNSY S
-0.800 TRNSYS
TA SE
TA SE
-1.200 EnergyPlus
-0.884 EnergyPlus
APA CHE -0.907
-0.927
-1.000 A PACHE
-1.300 -1.297 -1.297 -1.007
-1.329 -1.012
-1.400 -1.348
-1.054
-1.428 -1.446
-1.461 -1.134 -1.128
-1.200
-1.600
-1.273
-1.689 -1.676
-1.800 -1.400
Figure 286: High Mass Basic and In-Depth Sensitivity Tests: Annual
Heating - Cases 940-640 (mass effect with south window & night set-
back)
0.000
-0.500
ESP
-1.000 BLA ST
DOE2
SRES
MWH
SERIRES
-1.500
S3PAS
TRNSYS
TA SE
-2.000 -1.867 -1.886 Energy Plus
-1.958 -1.963 -1.986
-2.024 APACHE
-2.179
-2.304 -2.269
-2.500 -2.392
-3.000
63
Figure 287: High Mass Basic and In-Depth Sensitivity Tests: Peak Figure 288: High Mass Basic and In-Depth Sensitivity Tests: Peak
Heating - Cases 800-430 (mass effect with opaque panel) Heating - Cases 900-800 (south window replaces opaque panel)
0.000 0.000
-0.050
-0.050
-0.100
ESP -0.107 ESP
BLAST BLA ST
DOE2 -0.150 -0.142 DOE2
-0.100
SRES SRES
-0.113 SERIRES SERIRES
kW
kW
-0.200
S3PA S S3PA S
TRNSY S TRNSYS
-0.150 -0.141 -0.142 -0.144 TA SE TA SE
-0.151 -0.149 -0.250
EnergyPlus EnergyPlus
-0.163 -0.265
APA CHE -0.269 A PACHE
-0.300 -0.294
-0.200
-0.198
-0.377 -0.378
-0.250 -0.400
Figure 289: High Mass Basic and In-Depth Sensitivity Tests: Peak Figure 290: High Mass Basic and In-Depth Sensitivity Tests: Peak
Heating - Cases 900-810 (internal solar absorptance) Heating - Cases 910-610
0.000 0.000
-0.020
-0.100
-0.040 -0.034
kW
kW
-0.166
-0.180 -0.700
Figure 291: High Mass Basic and In-Depth Sensitivity Tests: Peak Figure 292: High Mass Basic and In-Depth Sensitivity Tests: Peak
Heating - Cases 920-620 Heating - Cases 930-630 (mass effect with shaded east/west
windows)
0.000
0.000
-0.050
-0.050
-0.100 ESP
ESP
BLAST
BLA ST
DOE2
DOE2
-0.150 SRES -0.100
-0.150 SRES
SERIRES
kW
SERIRES
kW
S3PA S
S3PA S
-0.200 TRNSY S
TRNSYS
TA SE -0.150 -0.141
-0.214 TA SE
EnergyPlus
-0.235 EnergyPlus
-0.250 -0.238 APA CHE
-0.241 A PACHE
-0.248
-0.178
-0.264
-0.272 -0.200 -0.193 -0.191
-0.283
-0.300 -0.207
-0.209
-0.214
-0.318 -0.227
-0.237 -0.238
-0.350 -0.250
Figure 293: High Mass Basic and In-Depth Sensitivity Tests: Peak
Heating - Cases 940-640 (mass effect with south window & night set-
back)
2.500
2.000 1.845
1.500
ESP
1.000 BLA ST
DOE2
SRES
0.500
SERIRES
kW
S3PAS
0.000
TRNSYS
TA SE
-0.278 -0.230
-0.500 -0.414 Energy Plus
-0.458
-0.526 -0.581 APACHE
-0.600
-1.000
-1.252
-1.500
-1.480
-2.000
64
Figure 294: High Mass Basic and In-Depth Sensitivity Tests: Annual Figure 295: High Mass Basic and In-Depth Sensitivity Tests: Annual
Cooling - Cases 800-430 (mass effect with opaque panel) Cooling - Cases 900-800 (south window replaces opaque panel)
0.000 3.500
3.193
3.000 2.893
-0.100
MWH
MWH
SERIRES SERIRES
-0.300
S3PA S S3PA S
TRNSY S 1.500 TRNSYS
TA SE TA SE
-0.367 -0.368
-0.400 EnergyPlus EnergyPlus
-0.393 -0.391
-0.410 APA CHE 1.000 A PACHE
-0.429 -0.432
-0.462
-0.500
0.500
-0.550
-0.600 0.000
Figure 296: High Mass Basic and In-Depth Sensitivity Tests: Annual Figure 297: High Mass Basic and In-Depth Sensitivity Tests: Annual
Cooling - Cases 900-810 (internal solar absorptance) Cooling - Cases 910-610 (mass effect with shaded south window)
1.800 0.000
1.707
1.600 -0.500
1.454
1.400 -1.000
1.294
1.265
1.195 ESP ESP
1.200 BLA ST -1.500 BLAST
1.119
1.080
DOE2 DOE2
0.975 SRES SRES
1.000 -2.000
H
MWH
SERIRES SERIRES
MW S3PA S
S3PAS
0.800 -2.500 TRNSY S
TRNSYS
TA SE TA SE
-3.318 -3.275
0.400 -3.500 -3.336
-3.415
-3.576 -3.562
-3.739
0.200 -4.000 -3.876 -3.924
0.000 -4.500
Figure 298: High Mass Basic and In-Depth Sensitivity Tests: Annual Figure 299: High Mass Basic and In-Depth Sensitivity Tests: Annual
Cooling - Cases 920-620 (mass effect with east/west windows) Cooling - Cases 930-630 (mass effect with shaded east/west
windows)
0.000
0.000
-0.200
-0.500
ESP -0.400
ESP
BLAST
BLA ST
DOE2
-1.000 -0.600 DOE2
SRES
SRES
MWH
SERIRES
MWH
SERIRES
S3PA S -0.800
S3PA S
TRNSY S -0.827
-1.500 TRNSYS
-1.476 -1.483 TA SE
-1.554 -1.545 -1.000 TA SE
-1.577 EnergyPlus
-1.000 EnergyPlus
-1.690 -1.708 APA CHE -1.050
-1.738 -1.090 A PACHE
-1.200 -1.174 -1.159
-1.894 -1.912
-2.000 -1.223 -1.218
-1.320
-1.400
-1.463
-2.500 -1.600
Figure 300: High Mass Basic and In-Depth Sensitivity Tests: Annual Figure 301: High Mass Basic and In-Depth Sensitivity Tests: Annual
Cooling - Cases 940-640 (mass effect with south window & night set- Cooling - Cases 950-650 (mass effect with south window & venting)
back)
0.000
0.000
-0.500 -1.000
-1.000
-2.000 ESP
-1.500 ESP
BLA ST
BLA ST
DOE2
DOE2
-2.000 -3.000 SRES
SRES
MWH
SERIRES
MWH
SERIRES
-2.500 S3PAS
S3PAS
-4.000 TRNSYS
TRNSYS
-3.000 TA SE
TA SE
-4.429 -4.498 -4.493 Energy Plus
Energy Plus -4.614 -4.537 -4.558
-4.685 APACHE
-3.500 -5.000
APACHE -4.973
-3.647 -5.257
-3.758
-4.000 -3.873 -3.863
-3.990 -3.992 -3.990
-4.150 -6.000
-5.956
-4.500
-4.419
-4.570
-5.000 -7.000
66
Figure 302: High Mass Basic and In-Depth Sensitivity Tests: Peak Figure 303: High Mass Basic and In-Depth Sensitivity Tests: Peak
Cooling - Cases 800-430 (mass effect with opaque panel) Cooling - Cases 900-800 (south window replaces opaque panel)
0.000 4.000
3.519
3.500
-0.200
-0.294 3.000
-0.400 ESP 2.715 ESP
-0.410 -0.397 2.584
BLAST 2.519 BLA ST
2.440
DOE2 2.500 DOE2
2.303 2.306 2.303
-0.600 SRES 2.188 SRES
2.099
SERIRES SERIRES
kW
kW
2.000
-0.684 S3PAS S3PAS
-0.800 TRNSYS TRNSYS
- 0.805 -0.816 TASE TASE
-0.843 1.500
EnergyPlus Energy Plus
-0.908 -0.908
-1.000 APACHE APACHE
1.000
-1.200
0.500
-1.220
-1.400 0.000
Figure 304: High Mass Basic and In-Depth Sensitivity Tests: Peak Figure 305: High Mass Basic and In-Depth Sensitivity Tests: Peak
Cooling - Cases 900-810 (internal solar absorptance) Cooling - Cases 910-610 (mass effect with shaded south window)
4.000 0.000
3.458
3.500 -0.500
3.000 -1.000
ESP ESP
BLA ST BLAST
2.500 -1.500
DOE2 DOE2
SRES SRES
SERIRES SERIRES
kW
kW
2.000 -2.000
S3PA S S3PAS
TRNSY S TRNSYS
1.500 TA SE TASE
-2.500
1.277 EnergyPlus EnergyPlus
1.223
1.036 1.036 A PACHE A PACHE
1.000 0.880 0.902 0.905 -3.000 -2.883
0.798
-2.999
-3.094 -3.068
0.595
-3.242
0.500 -3.324
-3.500 -3.384
Figure 306: High Mass Basic and In-Depth Sensitivity Tests: Peak Figure 307: High Mass Basic and In-Depth Sensitivity Tests: Peak
Cooling - Cases 920-620 (mass effect with east/west windows) Cooling - Cases 930-630 (mass effect with shaded east/west
windows)
0.000
-0.900
-0.200
-0.950
-0.400
ESP -1.000
-0.600 ESP
BLAST
BLA ST
DOE2
-1.050 -1.036 DOE2
-0.800 SRES
SRES
SERIRES
kW
SERIRES
kW
-1.800 -1.300
Figure 308: High Mass Basic and In-Depth Sensitivity Tests: Peak Figure 309: High Mass Basic and In-Depth Sensitivity Tests: Peak
Cooling - Cases 940-640 (mass effect with south window & night set- Cooling - Cases 950-650 (mass effect with south window & venting)
back)
0.000
0.000
-0.500
-0.500
-1.000
ESP
-1.000 ESP
-1.500 BLAST
BLA ST
DOE2
DOE2
-2.000 SRES
-1.500 SRES
SERIRES
kW
SERIRES
kW
S3PAS
S3PA S -2.500
TRNSYS
-2.000 TRNSY S
TASE
TA SE
-3.000 EnergyPlus
EnergyPlus
APACHE
-2.500 A PACHE -3.210
-3.500
-2.636 -3.501 -3.466
-2.737 -3.610
-3.692 -3.642
-3.000 -2.905 -2.916 -2.875
-3.852 -3.812
-3.022 -4.000
-3.118 -3.998 -3.998
-3.273 -3.314 -3.273
-3.500 -4.500
67
80
70 ESP
60 BLAST
DOE2
50
Wh/m 2
SRES
40
SERIRES
30
S3PAS
20 TRNSYS
10 TASE
EnergyPlus
0
APACHE
80
70 ESP
60
BLAST
DOE2
50
Wh/m 2
SRES
40
SERIRES
30 S3PAS
20 TRNSYS
10 TASE
EnergyPlus
0
APACHE
900
800
ESP
700 BLAST
600 DOE2
Wh/m 2
500 SRES
400 SERIRES
300 S3PAS
200
TRNSYS
100
TASE
EnergyPlus
0
APACHE
900
800 ESP
700 BLAST
600 DOE2
Wh/m 2
500 SRES
400 SERIRES
300
S3PAS
200
TRNSYS
100
TASE
EnergyPlus
0
APACHE
69
Figure 314: Annual Incident Total Solar Figure 315: Annual Incident Total Solar
Radiation - Case 600 North Surface Radiation - Case 600 East Surface
2000 2000
1800 1800
1600 1600
ESP ESP
1400 BLAST 1400 BLAST
1217.3
DOE2 DOE2
1155 1152.75
1200 1200 1101
kWh/m 2
kWh/m 2
SRES 1083 1082 SRES
SERIRES 959 962 SERIRES
1000 1000
S3PAS S3PAS
TRNSYS TRNSYS
800 800
TASE TASE
Energy Plus Energy Plus
600 600
434 456 457 453 435.86 APACHE APACHE
427 407.3
367.4
400 400
200 200
0 0
Figure 316: Annual Incident Total Solar Figure 317: Annual Incident Total Solar
Radiation - Case 600 West Surface Radiation - Case 600 South Surface
2000 2000
1800 1800
1566 1548.2
1600 1600 1522
1456 1476 1467.7 1474 1468
ESP ESP
1400 BLAST 1400 BLAST
DOE2 DOE2
1200 1090 1200
kWh/m 2
kWh/m 2
400 400
200 200
0 0
2000
1831 1832 1831.8 1832 1832 1832 1807.64
1797
1800
1600
ESP
1400 BLAST
DOE2
1200
kWh/m 2
SRES
SERIRES
1000
S3PAS
TRNSYS
800
TASE
Energy Plus
600
APACHE
400
200
0
70
Figure 319: Annual Unshaded Transmitted Solar Figure 320: Annual Unshaded Transmitted
Radiation - Case 920 East/West Solar Radiation - Case 900 South
1200 1200
1051
984 992
1000 1000 946 962 954
926 914
ESP ESP
BLAST BLAST
800 735 800
732
706 705 DOE2 DOE2
689
662
kWh/m 2
kWh/m 2
642 SRES SRES
SERIRES SERIRES
600 563 600
S3PAS S3PAS
TRNSYS TRNSYS
TASE TASE
400 400
Ener gyPlus Ener gyPlus
APACHE APACHE
200 200
0 0
Figure 321: Annual Shaded Transmitted Solar Figure 322: Annual Shaded Transmitted Solar
Radiation - Case 930 East/West Radiation - Case 910 South
1200 1200
1000 1000
kWh/m 2
SRES SRES
599 SERIRES SERIRES
600 554 600
S3PAS S3PAS
481
441 TRNSYS TRNSYS
431 438 437
TASE TASE
400 400
Ener gyPlus Ener gyPlus
APACHE APACHE
200 200
0 0
Figure 323: Annual Transmissivity Coefficient of Figure 324: Annual Transmissivity Coefficient of
Windows - Case 920 East/West Windows - Case 900 South
0.800 0.800
0.681 0.687
0.700 0.674 0.700 0.671
0.657 0.654 0.648 0.652 0.650 0.652 0.650
0.641 0.647 0.641
0.628 0.623
kWh/m 2
SRES SRES
SERIRES SERIRES
0.400 0.400
S3PAS S3PAS
TRNSYS TRNSYS
0.300 TASE 0.300 TASE
Ener gyPlus Ener gyPlus
0.100 0.100
0.000 0.000
Figure 325: Annual Shading Coefficient of Figure 326: Annual Shading Coefficient of
Window Shading Devices: Overhangs & Fins - Window Shading Devices: Overhangs & Fins -
Case 930/920 East/West Case 910/900 South
0.346
0.339
0.350 0.329 0.350
kWh/m 2
0.050 0.050
0.000 0.000
71