Você está na página 1de 4

<<Contents>> <<Index>>

General Model LFS2753


Specications YFGW Communication
Package (for ALE111)
GS 33M15D60-40E

GENERAL SUBSYSTEM COMMUNICATION


YFGW Communication Package (for ALE111) is SPECIFICATIONS
designed for monitoring ISA100.11a eld wireless
devices from CENTUM systems. The CENTUM Data Flow
VP Field Control Station (FCS) communicates with
the eld wireless devices via the Field Wireless Data from the YFGW is stored in the PI/O image area
Integrated Gateway (YFGW) from the ALE111 in the ALE111 module and transmitted to the FCS.
Ethernet Communication Module installed in local or Data from the YFGW are stored in the communication
remote nodes. Furthermore, the FCS executes control I/O data area in the FCS and those are utilized by
calculations using the acquired data. connecting to the I/O terminals of the communication
blocks in the same way as with the general analog/
digital I/O signals. Abnormal and recovery status of the
eld wireless devices are notied to the communication
I/O data status as a system alarm.
Note: The FCS cannot write (output) the data to YFGW.
FCS
Regulatory Control Sequence Control
Function Block Function Block

Data Data Reference/


Setting
Communication I/O Data Area

ALE111

ALE111 PI/O Image

Communication
Program

Ethernet
YFGW

Field Wireless Data

F01E.ai

Figure Data Flow

Yokogawa Electric Corporation GS 33M15D60-40E


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Copyright Jun. 1, 2010(YK)
Tel.: 81-422-52-5634 Fax.: 81-422-52-8902 1st Edition Jun. 1, 2010(YK)
<<Contents>> <<Index>> 2
Subsystem Connection Specications
The FCS communicates with subsystems via ALE111 Ethernet Communication Module.
Total Number of ALR111, ALR121, ALE111, ALP111, AGS813 and AGP813 for Connection:
For LFS1300 Control Function for Standard Field Control Station:
Max. 6/FCS (3 pairs for dual-redundant operation)
For LFS1330 Control Function for Enhanced Field Control Station:
Max. 16/FCS (8 pairs for dual-redundant operation)
For LFS1350 Control Function for Compact Field Control Unit (for FIO):
Max. 8/FCS (4 pairs for dual-redundant operation)
For LFS1500 Control Function for Basic Field Control Unit (for FIO, for Vnet/IP):
Max. 16/FCS (8 pairs for dual-redundant operation) (*1)

*1: When LFS1530 Application Capacity Expansion Package is not used, the maximum number is 8/FCS. For details, refer to
GS 33L15C20-40E Control Function for Basic Field Control Unit (for FIO, for Vnet/IP).

Total 8 modules of ALE111, ALR111, ALR121 and ALF111 can be installed per ER bus (remote node) segment (4
pairs for dual-redundant operation per FCS).
Number of Communicable I/O Data
Max. 4,000 words per FCS (1 word = 16 bits)

Note: The amount includes the data from other communication packages.

ALE111 COMMUNICATION MODULE SPECIFICATIONS


Number of Communicable Data:
Max. 1,000 words per ALE111
Connection Method:
One to one connection using a crossing cable or star connection via HUB
LAN Specications:
IEE802.3 compliant
Physical layer: 10BASE-T
Transmission speed: 10 Mbps
Number of physical port: 1 port
Maximum distance: 100 m (radius of 100 m from the HUB)
Access control: CSMA/CD
Communication protocol: ARP, ICMP, UDP/IP, and TCP/IP

Note: An ALE111 module cannot run multiple communication packages.


FCS

YFGW
ALE111 module
ESB bus
HUB

Ethernet Ethernet
F02E.ai

Figure Example of Connection with Field Wireless Integrated Gateway

All Rights Reserved. Copyright 2010, Yokogawa Electric Corporation GS 33M15D60-40E Jun. 1, 2010-00
<<Contents>> <<Index>> 3
YFGW COMMUNICATION PACKAGE (FOR ALE111) SPECIFICATIONS
Basic Specications
Connected device: YFGW710 Field Wireless Integrated Gateway
Number of YFGW to be connected: Max. 4 gateways/ALE111
Number of eld wireless device to be connected: Max. 128 devices/ALE111 and 1000 devices/FCS (*1)
Transmission Protocol: Modbus/TCP
Internal data to be transmitted: Input register
Communication Capacity: Max. 125 words/communication
Number of subsystem stations: Max. 30 stations/ALE111(*2)
Data sampling period: 1 sec or less per 1,000 eld wireless devices (*3)
CPU loading by YFGW communication package: within 10% per 1,000 eld wireless devices (*1)

*1: When one communication denition (4 words) per eld wireless device is applied.
*2: When 30 or less eld wireless devices are dened for ALE111, a station number per each device can be set. In case the
total number of eld wireless devices for ALE111 exceeds 30, a station number is set per YFGW.
*3: Data sampling period from the YFGW. The data from the eld wireless devices are updated as per the data transfer period
of each device.

Acquired Data Specications


Object Attribute Data Type
AI (Analog Input) PV (Process data) 32-bit oating point
UAPMO (User Application Management Object) DIAG_STATUS (Device diagnosis information) 32-bit unsigned integer

REDUNDANCY FUNCTION
The YFGW Communication Package (for ALE111) enables to congure Ethernet Communication Module to dual-
redundant by inserting two ALE111 modules into the adjacent slots (odd number and even number slot).
SB401
SB401
ALE111
ALE111

Ethernet HUB
Same subnet

YFGW710

F03.ai

Figure Ethernet Communication Module Redundancy)

All Rights Reserved. Copyright 2010, Yokogawa Electric Corporation GS 33M15D60-40E Jun. 1, 2010-00
<<Contents>> <<Index>> 4
OPERATING ENVIRONMENT
Hardware requirements
AFF50S, AFF50D, AFS30S, AFS30D, AFS40S, AFS40D, AFG30S, AFG30D, AFG40S, AFG40D, AFG81S, AFG81D,
AFG82S, AFG82D, AFG83S, AFG83D, AFG84S, AFG84D, AFV10S, AFV10D

Software requirements
LFS1300 Control Function for Standard Field Control Station (for FIO) (*1)
LFS1330 Control Function for Enhanced Field Control Station (for FIO) (*1)
LFS1350 Control Function for Compact Field Control Unit (for FIO) (*1)
LFS1500 Control Function for Basic Field Control Unit (for FIO, for Vnet/IP) (*1)

Engineering requirements
LHS5100 or LHM5100 Standard Builder Function is required. (*1)

*1: Supported by R4.02.30 or later.

MODEL AND SUFFIX CODES


FA-M3 Communication Package (for ALE111)
(Basic software licence)
Description
Model LFS2753 YFGW Communication Package (for ALE111) [Media model LHSKM30-V11]
-V Software License
1V For single (license)
Sufx Codes
2V For dual-redundant (license)
1 English version

ORDERING INFORMATION
Specify model and sufx codes.

TRADEMARKS
CENTUM is a registered trademark of Yokogawa Electric Corporation.
Modbus is a registered trademark of Schneider Electric.
Other product and company names appearing in this document are trademarks or registered trademarks of their
respective holders.

All Rights Reserved. Copyright 2010, Yokogawa Electric Corporation GS 33M15D60-40E Jun. 1, 2010-00
Subject to change without notice.

Você também pode gostar