Escolar Documentos
Profissional Documentos
Cultura Documentos
ALE111
Communication
Program
Ethernet
YFGW
F01E.ai
*1: When LFS1530 Application Capacity Expansion Package is not used, the maximum number is 8/FCS. For details, refer to
GS 33L15C20-40E Control Function for Basic Field Control Unit (for FIO, for Vnet/IP).
Total 8 modules of ALE111, ALR111, ALR121 and ALF111 can be installed per ER bus (remote node) segment (4
pairs for dual-redundant operation per FCS).
Number of Communicable I/O Data
Max. 4,000 words per FCS (1 word = 16 bits)
Note: The amount includes the data from other communication packages.
YFGW
ALE111 module
ESB bus
HUB
Ethernet Ethernet
F02E.ai
All Rights Reserved. Copyright 2010, Yokogawa Electric Corporation GS 33M15D60-40E Jun. 1, 2010-00
<<Contents>> <<Index>> 3
YFGW COMMUNICATION PACKAGE (FOR ALE111) SPECIFICATIONS
Basic Specications
Connected device: YFGW710 Field Wireless Integrated Gateway
Number of YFGW to be connected: Max. 4 gateways/ALE111
Number of eld wireless device to be connected: Max. 128 devices/ALE111 and 1000 devices/FCS (*1)
Transmission Protocol: Modbus/TCP
Internal data to be transmitted: Input register
Communication Capacity: Max. 125 words/communication
Number of subsystem stations: Max. 30 stations/ALE111(*2)
Data sampling period: 1 sec or less per 1,000 eld wireless devices (*3)
CPU loading by YFGW communication package: within 10% per 1,000 eld wireless devices (*1)
*1: When one communication denition (4 words) per eld wireless device is applied.
*2: When 30 or less eld wireless devices are dened for ALE111, a station number per each device can be set. In case the
total number of eld wireless devices for ALE111 exceeds 30, a station number is set per YFGW.
*3: Data sampling period from the YFGW. The data from the eld wireless devices are updated as per the data transfer period
of each device.
REDUNDANCY FUNCTION
The YFGW Communication Package (for ALE111) enables to congure Ethernet Communication Module to dual-
redundant by inserting two ALE111 modules into the adjacent slots (odd number and even number slot).
SB401
SB401
ALE111
ALE111
Ethernet HUB
Same subnet
YFGW710
F03.ai
All Rights Reserved. Copyright 2010, Yokogawa Electric Corporation GS 33M15D60-40E Jun. 1, 2010-00
<<Contents>> <<Index>> 4
OPERATING ENVIRONMENT
Hardware requirements
AFF50S, AFF50D, AFS30S, AFS30D, AFS40S, AFS40D, AFG30S, AFG30D, AFG40S, AFG40D, AFG81S, AFG81D,
AFG82S, AFG82D, AFG83S, AFG83D, AFG84S, AFG84D, AFV10S, AFV10D
Software requirements
LFS1300 Control Function for Standard Field Control Station (for FIO) (*1)
LFS1330 Control Function for Enhanced Field Control Station (for FIO) (*1)
LFS1350 Control Function for Compact Field Control Unit (for FIO) (*1)
LFS1500 Control Function for Basic Field Control Unit (for FIO, for Vnet/IP) (*1)
Engineering requirements
LHS5100 or LHM5100 Standard Builder Function is required. (*1)
ORDERING INFORMATION
Specify model and sufx codes.
TRADEMARKS
CENTUM is a registered trademark of Yokogawa Electric Corporation.
Modbus is a registered trademark of Schneider Electric.
Other product and company names appearing in this document are trademarks or registered trademarks of their
respective holders.
All Rights Reserved. Copyright 2010, Yokogawa Electric Corporation GS 33M15D60-40E Jun. 1, 2010-00
Subject to change without notice.