Escolar Documentos
Profissional Documentos
Cultura Documentos
Rack-mount Meter
Prometer 100 conform to all the essential requirements of EU R&TTE Directive (1999/5/EC) and WEEE
Directive 2002/96/EC.
Page 2 of 32 Installation and Basic Commissioning Manual for Prometer 100 BGX501-947-R03
Table of Contents
BGX501-947-R03 Installation and Basic Commissioning Manual for Prometer 100 Page 3 of 32
1 Important Safety Information 3 Installing the Prometer 100
Care must be exercised during the installation of
the Prometer 100 meter and associated equipment
due to the presence of mains voltages. Various
points under the terminal cover and on the main
printed circuit board (PCB) under the main cover
operate at hazardous voltages.
Danger of Electrocution
Page 4 of 32 Installation and Basic Commissioning Manual for Prometer 100 BGX501-947-R03
connector as used in CT connection can also be Note: A switch or circuit breaker should be used at
used. The internal earthing cable should be about a suitable location before meter connections. It is
5-10 cm in length to allow for ease of fitting and recommended to mark it as a disconnecting device.
access and not fouling with the sharp edges of the
rack etc. For 19 rack installations with two meters,
each meter must have its own earthing strap fitted 3.1 Overview
as above. Finally a proper earthing cable from rack
to earth should be put up by installer. Other The Prometer 100 is a 3-phase 4-wire or 3-phase 3-
accessories or shipway kit is supplied based on the wire CT-VT operated meter suitable for mounting in
requirement and mutual agreement like cable a panel. Prometer 100 has self-powered, auxiliary-
harnessing, seals, communication cords etc. powered; and a combination of self-powered and
auxiliary-powered variants (see section 3.1.1). The
VT secondary supply of 63.5 V AC (phase to
Earth symbol neutral voltage) or 110 V AC (phase to phase
voltage) needs to be given as input to product.
Similarly, three CTs (namely R/L1, Y/L2 and B/L3 if
Earth pin Preferred torque for applicable) need to be given as input to product of
loosening and tightening 1A/ 5A from secondary side. We recommend that
the nut is 1.0 NM to 1.2 NM
the VT and CT primary be configured in the factory
If you are dealing with an existing installation and at time of manufacture. The VT and CT can also be
need to remove the meter from its rack please read configured on site using M-Cubed 100. When the
section 3.1.1 regarding cables and earth leads. Prometer 100 is energised, the LCD with backlight
turned on indicates that the power supply is
working. The meter backlight turns off when meter
is in idle mode or auto display cycle is not running.
Details for the power supply and measurement options are shown below:
BGX501-947-R03 Installation and Basic Commissioning Manual for Prometer 100 Page 5 of 32
No. of Aux
Backup power supply
Variants Main supply Range of Aux supply
supply inputs
supported
Aux. supply Measurement 60-240 V AC/DC 20%, 50/60 Hz
voltage One
Self+Aux power supply input or
terminals (VT (Aux 2)
(Aux 2) supply) 24-48 V DC 20%
Measurement
voltage
Self power supply Not available Not available Not applicable
terminals (VT
supply)
Both as 60-240 V AC/DC 20%,
Aux. supply Two (dual)
Aux 1 50/60 Hz
Auxiliary power supply input (Aux. 1 & Aux.
(optional) or
(Aux 2) 2)
one as 24-48 V DC 20%
Table 1 Different Power Supply and other Variants available in Prometer 100
In case of auxiliary powered and self+auxiliary powered variants, meter will draw power from Aux 2
supply input. In its absence it will shift to Aux 1 supply (in case of auxiliary powered variant) and VT
supply (in case of self+auxiliary powered variant).
Note: Refer to alarm information for details on indication for auxiliary power supply failure.
Do not connect voltage transformer (VT) to any of the Aux supply input terminal as a general practice. If
it is necessary to connect VT secondary to Aux input then make sure to connect it to the Aux1 supply
only in presence of Aux 2 so that burden on measurement VT secondary can be minimal.
Connect your reliable auxiliary supply source like DC bank/AC lighting load/ Aux power transformer etc
to Aux 2 terminal only so that meter burden will be handled by it; or take your best judgment to connect
auxiliary supply source considering the rating and suitable operation of meter and best installation
practices followed.
The field replaceable battery is used as RTC backup. It is also used for meter reading and viewing
display in absence of mains power supply. It only supplies sufficient power to the meter reading and
display circuitry and will not fully power-up the meter. The battery can be replaced in the field. Take care
while inserting the battery; make sure that the polarity and fitment are correct.
Note: Useful life of field replaceable battery can be viewed on the meter display.
Ensure that the correct auxiliary voltage rating is used with the meter. The wrong voltage rating could
cause damage to the meter. Therefore it is recommended to verify and crosscheck the rating-plate on
the actual product in use at the site.
Page 6 of 32 Installation and Basic Commissioning Manual for Prometer 100 BGX501-947-R03
3.2 Calibration LEDs entire block. The outputs are of solid-state type and
when the meter is turned off, they are open.
It is recommended to use conditioned power supply
(isolated from Mains) for driving loads through pulse
output of product so that any malfunction in the load
or related circuit will not affect the metering. A
tentative scenario for reference is shown in below
diagram.
BGX501-947-R03 Installation and Basic Commissioning Manual for Prometer 100 Page 7 of 32
for the communication ports can be viewed on the to be daisy chained, then simply connect the
meter display under default display sequence. RS485 Out on the first meter to the RS485 In on
the next meter and so on. The pinning for both ports
3.5.1 Optical Communication Port is identical, so the same type of cable can be used
through-out and is not polarity conscious.
Page 8 of 32 Installation and Basic Commissioning Manual for Prometer 100 BGX501-947-R03
4 Connection Diagrams
The internal earthing cable between the meter and the rack should also be connected and for this an M4 size
screw should be used in the meter as well as in the rack. Please refer to section Installing the Prometer 100 for
further details.
For self-powered variants, B8 and B9 will not be fitted.
The central block is an Essailec type connector and the RS232, RS485 and Ethernet connectors are all RJ-45
type connectors.
The connection diagram shown on the meter top cover and shown in Figure 7 is for a fully loaded product.
Please refer to your actual order details as to the supplied meter type, number of pulse input/output fitted,
communication channels and power supply options. The meter capabilities will be according to your order.
BGX501-947-R03 Installation and Basic Commissioning Manual for Prometer 100 Page 9 of 32
5 Rack Installation Details
The Prometer 100 can be supplied with an 11 or 19 rack. The depth dimensions are the same for both
installations.
279.60
261.80
243
132.50
57.10
CL
CL 50.30
293.30
376.25
7.50
R5
Page 10 of 32 Installation and Basic Commissioning Manual for Prometer 100 BGX501-947-R03
The following diagram shows the front and rear sealing points. The sealing points are the same for 11 and 19
racks.
Note: IEC 1107 sealing cover slides upwards till 35 mm and hence take care where stacked up installations are
done for rack products. This sealing cover if not sealed, can be detached from the window if needed.
The following diagrams shows the Prometer 100 Rack mounted with panel cut-out details.
BGX501-947-R03 Installation and Basic Commissioning Manual for Prometer 100 Page 11 of 32
Figure 11: Fitting the Prometer 100 Rear Cover
Figure 12: Fitting Prometer 100 Meter into the 19" Rack
Page 12 of 32 Installation and Basic Commissioning Manual for Prometer 100 BGX501-947-R03
Figure 13: Two Prometer 100 Meters Fitted into a 19 inch rack
BGX501-947-R03 Installation and Basic Commissioning Manual for Prometer 100 Page 13 of 32
Figure 15: Panel Cut out Details for 19" Rack Installation
Page 14 of 32 Installation and Basic Commissioning Manual for Prometer 100 BGX501-947-R03
6 Verification and Commissioning
The meter is normally pre-configured so that the 1 - Default display sequence This can be used
basic functions can be used without further settings for checking the successful installation done by
like display, tariff etc. The meter can be configured user in field. It has different display screens to show
with M-Cubed 100 software to suit the customers parameters like commissioning value, meter date
specific requirements like primary CT-VT and time; primary voltages and currents; energy
commissioning etc. Also a number of extra and power values which need to be checked and
functions can be set in addition to those set at the noted by installer before leaving the site after an
factory based on the customers requirement and installation.
mutual agreement.
Slight differences may be observed between net
Verification and commissioning of the meter can be derived energy and the equivalent displayed
viewed through the display. The menu pages can values. This is not an error but due to the truncating
be used to set-up and enable features such as the effect of the display value. There is no energy loss
calibration LEDs, display delays, acknowledge and the difference will not increase or decrease
battery change, calibration LED constant, MODBUS with time.
(ID and baud rate), display language and manage
your favourite selections. For dial test (zero power factor situations for
reactive energy registers logging) refer to the high
The display is arranged into groups for easier resolution energy register display for Reactive
navigation. import (Q1+Q2) and Reactive export (Q3+Q4).
Similarly one needs to first ensure about tariff being
1. Default display sequence configured for Apparent energy logging either in lag
only or lag + lead mode before performing dial test
2. User configurable display sequences (1 to 7)
on display.
3. Favourite sequence
Select the Default Display Sequence from the top
4. Configuration menu
line menu. The following screen will be displayed
5. Abbreviations
BGX501-947-R03 Installation and Basic Commissioning Manual for Prometer 100 Page 15 of 32
(In case of 3-phase 4-wire) (In case of 3-phase 3-wire)
Page 16 of 32 Installation and Basic Commissioning Manual for Prometer 100 BGX501-947-R03
This display shows the energy This display indicates that out of
pulse weight of pulse outputs 5, 6 four configurable pulse I/Os, two
and 7. (pulse I/Os 3 and 4) are
configured as pulse outputs and
two (pulse I/Os 1 and 2) are
configured as pulse inputs.
Note:
NA means Not applicable.
- - - means that energy
parameter is not configured for
pulse output.
Note:
Refer to Abbreviations sequence
for the full form of the abbreviations
used in the displays.
2 - User configurable display sequences These are the display sequences (maximum seven sequences)
set through configuration file for the sequence name (for example, Page 1: Instant Data as shown in below
figure) and the parameters to be displayed in each sequence as per requirement. There is no limitation of
setting different parameters to be displayed in an individual sequence, but in general, the meter can have a
maximum of 242 display parameters including both manual and auto-cycle displays. The maximum number of
display parameters for a meter depends on the requirement.
BGX501-947-R03 Installation and Basic Commissioning Manual for Prometer 100 Page 17 of 32
3 - Favourite sequence These are selected from all the available sequences (default and user configurable
display sequences) and are your personal selection of commonly visited pages. The list is field configurable and
a maximum of 20 alphanumeric parameters can be selected in favourite display sequence.
When the favourite sequence is full, you will need to delete complete list in this sequence to make space for the
new one, so be sure before selecting parameters.
The configuration menu is used to set-up and enable features such as the calibration LEDs, display delays,
calibration LED constant, acknowledge battery change, MODBUS configuration and display language on
display. They are also used to manage your favourite selections.
The configuration menu is password protected which can be accessed only by users authorized to change the
above configurations.
Page 18 of 32 Installation and Basic Commissioning Manual for Prometer 100 BGX501-947-R03
At the password prompt enter the 6-digit password (default password is 000000) using Up and Down buttons
Use the Down key to enter a digit at the cursor position and use the Up key to move the cursor to the right while
entering a digit. After completing the entry, press the Enter button to confirm. Correct password gives access to
the first screen of configuration menu. An incorrect password will display Incorrect Password message.
The features which can be configured through the menu buttons are shown below. Use the Up and Down
buttons to scroll to the required option and press the Enter button to select.
BGX501-947-R03 Installation and Basic Commissioning Manual for Prometer 100 Page 19 of 32
Display Off Duration - After completing one full automatic display cycling sequence, there will be a delay of
0 to 240 seconds (as configured in the meter) before the display resumes from the beginning.
Use the Up key for increment and the Down key for decrement.
Press the Up key for 5 seconds to go to the previous page.
c) Delete favourite sequence (deletion of all parameters) refer to 3 - Favourite sequence above
Use the Up key for increment and the Down key for decrement.
Press the Up key for 5 seconds to go to the previous page.
Page 20 of 32 Installation and Basic Commissioning Manual for Prometer 100 BGX501-947-R03
f) Modbus configuration (ID and Baud rate)
Use the Up key for increment and the Down key for decrement.
Press the Up key for 5 seconds to go to the previous page.
g) IP configuration
Use the Down key to enter the value at the cursor position and use the Up key to move the cursor to the
right.
Press the Up key for 5 seconds to go to the previous page.
BGX501-947-R03 Installation and Basic Commissioning Manual for Prometer 100 Page 21 of 32
h) Display language configuration
i) Exit This option switches to a blank (idle) screen with backlight on. This is applicable where ever this
option is available in complete display.
5 - Abbreviations
This sequence is used to display the full form of the abbreviations used in the displays.
Click on Connect.
Connect to the meter using either Serial or TCP/IP communication. Select the Com Port and the Baud Rate for
serial communication; and enter the Meter IP Address and Port Number for TCP/IP communication.
Note: In case of TCP/IP communication, enter the port number as 4059 for DLMS.
Select the Use Access Level and then select the password level.
Page 22 of 32 Installation and Basic Commissioning Manual for Prometer 100 BGX501-947-R03
The following message will be displayed on successful connection.
BGX501-947-R03 Installation and Basic Commissioning Manual for Prometer 100 Page 23 of 32
Now click Prepare Configuration.
Click on Read configuration to get the present measuring information from meter. This process takes a few
seconds, with on-screen messages indicating progress.
Ensure that only CT/VT Ratio option is checked under commissioning options (uncheck the CT/VT Error
Compensation and Power Transformer Loss Compensation commissioning options). Enter the desired primary
CT-VT values as Input Parameters. Click on Apply button and then wait for click to apply in meter or you can
save it as off-line mode and apply it later.
Click Read configuration to check the meter CT/VT ratio. You can also check the CT/VT ratio on the meter
display (under Default Display Sequence).
Page 24 of 32 Installation and Basic Commissioning Manual for Prometer 100 BGX501-947-R03
7 Fitting the Battery
The field replaceable battery option is designed to support meter reading in absence of mains power supply
depending on the requirement. The procedure to fit the battery is as follows:
a) Swing-up the front cover and take out the battery holder.
b) Place the battery holder (fitted with new battery) in the space provided and cover it with the front cover using
a retaining screw.
Note: Ensure that the polarity is correct and the battery is snap fitted to the holder provided for it.
Figure 17: Battery Status Displays showing LOW and CRITICAL conditions
Note: Whenever the battery is replaced with the new battery, you need to acknowledge the battery change
using menu buttons. To acknowledge the battery change, go to the configuration menu and select Ack. Battery
Change.
BGX501-947-R03 Installation and Basic Commissioning Manual for Prometer 100 Page 25 of 32
Appendix A: Measurement Conventions
The convention for energy directions is as shown in figure below:
Page 26 of 32 Installation and Basic Commissioning Manual for Prometer 100 BGX501-947-R03
Appendix B: Connection and General Details
Electrical
Connection type HV3/HV4
Wiring configuration 3-phase 3-wire, 3-phase 4-wire
Voltage range (L-N/L-L) 57.7/100 V to 69.3/120 V (configurable) for HV3 and HV4
I basic : 1 to 5 A (configurable)
Current range
I max : maximum 10 A (configurable)
Accuracy Class 0.2S
Frequency 50/60 Hz 5%
If power drawn from Aux supply
<0.1 VA /phase (for voltage and current circuit)
<10 VA (burden on Aux supply)
Burden
If power drawn from VT (i.e. self powered)
<0.1 VA /phase (for voltage and current circuit)
<6 VA /phase (burden on VT supply)
STOC 10 times I max for 1 second
Measurement category CAT III 150 V AC (versus earth)
Compliance
IEC62052-11, IEC62053-22, IEC62053-23, IEC62056-52, IEC61010-1,
Standards IEC61010-2-030, CE
Mechanical
428 x 133 x 260 mm approx. (meter with 19 rack)
Dimensions (L X W X D)
299 x 133 x 260 mm approx. (meter with 11 rack)
Translucent polycarbonate cover (with clear transparent window for display)
Enclosure
and overall mild steel body
Sealable screws on the front and back fascia of meter, sealing provision for
Sealing
optical port and MD reset button
Meter 3.8 kg approx. ( 0.1 kg)
Weight 11 rack 2.1 kg ( 0.1 kg)
19 rack 3.3 kg ( 0.1 kg)
Ingress Protection (IP) IP53 on front fascia and IP20 on back side
Environmental
0 0
-25 C to + 55 C (EN)
Operating range
-10 0C to + 65 0C (IEC)
Temperature 0 0
-25 C to +70 C (EN)
Limit range of operation -25 0C to + 70 0C (IEC)
BGX501-947-R03 Installation and Basic Commissioning Manual for Prometer 100 Page 27 of 32
-25 0C to +70 0C (EN)
Limit range for storage
-25 0C to +70 0C (IEC)
-25 0C to +70 0C (EN)
Limit range for transportation
-25 0C to + 70 0C (IEC)
Display operating range -20 0C to + 70 0C
Environment Indoor only
Humidity 95% non-condensing
Altitude level Up to 2000 m
Pollution degree Type 2
Over voltage category CAT III (refer to measuring and auxiliary inputs 150 V AC versus earth)
Protection class Basic insulation
Battery type (field replaceable) AA, lithium thionyl chloride, 3.6 V, 2 Ah
Page 28 of 32 Installation and Basic Commissioning Manual for Prometer 100 BGX501-947-R03
Appendix C: Frequently asked questions/ Troubleshooting information
1. Meter is not powering up.
Refer to the rating plate for the power supply option supported by the meter. Also refer to the
connection diagram available on the top of the meter. Make sure that the polarity of wires and
terminals always match and connections are tight.
5. How to change the calibration LED configuration from reactive to apparent energy?
Refer to the rating plate and default display sequence for the calibration LEDs configured in the meter.
The calibration LED configuration can be changed using the push buttons (configuration menu on the
meter display). The configuration menu is password protected which can be accessed only by users
authorized to change the configurations.
6. How to verify the status of the real time clock (RTC) battery?
The status of the real-time clock battery is provided on the meter display (Meter Health Status under
default display sequence).
BGX501-947-R03 Installation and Basic Commissioning Manual for Prometer 100 Page 29 of 32
7. How to increase the calibration LED constant?
The calibration LED constant is configured as per the commissioning set in the meter. However, you
can change the same using push buttons (Calib LED Constant under configuration menu on the meter
display).
Page 30 of 32 Installation and Basic Commissioning Manual for Prometer 100 BGX501-947-R03
Notes:
BGX501-947-R03 Installation and Basic Commissioning Manual for Prometer 100 Page 31 of 32
Cewe Instrument AB
Box 1006
(Repslagaregatan 43)
SE 611 29 Nykping
Sweden
t: +46 155 775 00
f: +46 155 775 97
UK contact details
t: +44 (0) 1962 840048
f: +44 (0) 1962 841046
BGX5 0 1 - 9 4 7