STRA-07 Room Controller. Installation and maintenance manual.

Content STRA-07 for Fancoils


Installation preparations................................2
Controller/Display handling.........................5
Technical data..................................................5
Installation.......................................................6
Configuration..................................................6
Operating modes............................................7
Activation operating modes.........................7
Control states..................................................8
Actuators.........................................................9
Fan control.......................................................9
Forced ventilation/Condensation detector/
Frost protection..............................................10
Parameter settings.........................................10

Flkt Woods 8713 GB 2014.04 1 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.

STRA-07 for Fancoils


Installation instruction
Ensure that the installation complies with local safety regulations. Information about commissioning of the product can
be found in the manual STRA Manual, which is available for download from www.flaktwoods.com.
1. 2.



3. 4.












alt.



5. Dimensions
Dimensions in mm

Flkt Woods 8713 GB 2014.04 2 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.

STRA-07 for Fancoils


Wiring STRA-07 has been constructed to be as compact as
possible. Therefore, the controllers communication input
is not galvanically separated from the supply voltage.
This means that it is important to keep G and G0 in order,
as well as the communication inputs A and B.
All units that share the same transformer and
communication loop must use the same transformer-
pole for G (terminal 10) and G0 (terminal 11). On the
communication loop the A-terminal (terminal 42) should
only be connected to another A-terminal and the B-
terminal (terminal 43) to another B-terminal. Otherwise,
there is great danger of short-circuit with damaged
components as a result.
Inputs
AI PT1000-sensor, 0...50C, accuracy +/- 0.1C
UI AI: PT1000-sensor, 0...100C, accuracy +/- 0.2C or
DI: see DI below
CI Flkt Woodss condensation detector, STRZ-16
DI Closing potential-free contact connected to +C in
one end
Outputs
DO 24 V AC, max 0,5 A
UO DO:24 V AC, max 2.0 A or AO:0.5...10 V DC, max
5 mA +C, power output for DI only...24 V DC,
max 10mA, short circuit protected

Flkt Woods 8713 GB 2014.04 3 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.

Terminal Designation Operation


10 G Supply voltage 24 V AC
11 G0 Supply voltage 0 V
12 D01 For forced ventilation, low speed. 24 V AC output, max 0,5 A. 24 V AC actuator is connected between terminal 12
and terminal 20, GDO.
13 DO2 For forced ventilation, average speed. 24 V AC output, max 0,5 A. 24 V AC actuator is connected between terminal
13 and terminal 20, GDO.
14 D03 For forced ventilation, high speed. 24 V AC output, max 0,5 A. 24 V AC actuator is connected between terminal 13
and terminal 20, GDO
20 GDO 24 V AC out common for DO. Internally connected to terminal 10, G.
21 G0 0 V common for UO. Internally connected to terminal 11, G0.
22 D04 For forced ventilation, 24 V AC output, max 0,5 A. 24 V AC actuator is connected between terminal 22 and terminal
20, GDO
23 UO1 Control of heating (FS) or cooling via change-over.
For 0...10 V DC valve actuator, max 5 mA (FS). The valve actuators 010 V control signal terminal is connected to
terminal 23 and its supply terminals to terminals 10 and 11. Make sure that the reference pole G0 is connected to
the correct terminal on the actuator.
alternative
For 24 V AC thermal actuator, max 2,0 A. The thermal actuator is connected between terminals 23 and 20, GDO.
On the display, go into the parameter menu and change parameter 20 to thermal actuator.
24 UO2 Control output heating or cooling (FS).
For 0...10 V DC valve actuator, max 5 mA (FS). The valve actuators 010 V control signal terminal is connected to
terminal 24 and its supply terminals to terminals 10 and 11. Make sure that the reference pole G0 is connected to
the correct terminal on the actuator.
alternative
For 24 V AC thermal actuator, max 2,0 A. The thermal actuator is connected between terminals 24 and 20, GDO.
On the display, go into the parameter menu and change parameter 20 to thermal actuator.
30 AI1 For external room sensor, PT1000. Measuring range 0...50C. Sensor is connected between terminals 30 and 41,
AGnd.
31 UI1 For switching between heating and cooling on a two-pipe system (Change-over). PT1000-sensor is connected
between terminals 31 and 41, AGnd. Measuring range: 0...100C. alternatively For potential-free contact. A potential-
free contact is connected between terminals 31 and 40, +C.
32 DI1 Occupancy detector. A potential-free contact is connected between terminals 32 and 40, +C. Closed contact
corresponds to occupancy.
See also section Occupancy detector in the section Operating modes.
33 DI2/CI Flkt Woodss condensation detector, STRZ-16 (FS). The sensor is connected between terminals 33 and 41, AGnd.
alternative
Window contact (DI). A potential-free contact is connected between terminals 33 and 40, +C. Closed contact
indicates closed window.
40 +C 24 V DC out common for DI and UI (with digital function)
41 AGnd Analogue ground, reference for AI and UI (with analogue function)
42 A RS-485-Communication
43 B RS-485-Communication

Flkt Woods 8713 GB 2014.04 4 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.

STRA-07 for Fancoils


Plug-in of relay-box STRZ-14 to fan coil unit Plug-in of condensation detector

Plug-in of relay-box STRZ-14 to STRA-07


QFDK, mounted in ceiling

Flkt Woods 8713 GB 2014.04 5 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.

STRA-07 for Fancoils


Display handling Set point
The display has the following indications: In Occupied mode, the controller operates from a heating
setpoint (FS = 22C), or a cooling setpoint (FS = 24C) that
can be changed using the INCREASE and DECREASE
buttons.
Pressing on INCREASE increases the current setpoint by
0.5C with each press up to the max. limit (FS = +3C).
Pressing on DECREASE decreases the current setpoint by
0.5C with each press down to the min. limit (FS = -3C).
Switching between heating and cooling setpoints is done
automatically in the controller depending on the heating
and cooling requirement.

Fan control
Fan control STRA-07 has a fan button. When you press
the button, a symbol is shown in the display for 10
seconds. During this time, it is possible to change the fan
speed using the INCREASE/DECREASE buttons. The
controller has the following positions:
It is possible to set different parameter values in a
Auto Automatic control of the fan
parameter menu in the display, using the buttons on
speed to maintain desired
the controller. You change parameter values with the
room temperature.
INCREASE and DECREASE buttons and confirm changes
0 Fan Off.
with the Occupancy button.
I Manual position with low
speed.
II Manual position with
medium speed.
III Manual position with high
speed.


In operating modes Off and Unoccupied, the fan is
stopped, regardless of the setting in the display.

Flkt Woods 8713 GB 2014.04 6 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.

Technical data

Supply voltage 18...30 V AC, 50...60 Hz


Internal consumption 2.5 VA
Ambient temperature 0...50C
Storage temperature -20...+70C
Ambient humidity Max 90% RH
Protection class IP20
Communication RS485 (EXOline or Modbus) with automatic detection/change-over
Modbus 8 bits, 1 or 2 stop bits. Odd, even (FS) or no parity.
Communication speed 9600 bps (not changeable)
Built-in temperature sensor NTC type, measuring range 0...50C, accuracy +/-0.5C at 15...30C
Material, casing Polycarbonate, PC
Weight 110 g
This product conforms with the requirements of European EMC standards CENELEC EN 61000-6-1 and
EN 61000-6-3, and the requirements of European LVD standard IEC 60 730-1. It carries the CE mark.

Inputs
External room sensor PT1000-sensor, 050C. Suitable sensor is Flkt Woods STRZ-05
Occupancy detector Closing potential-free contact. Suitable occupancy detector is Flkt Woods STRZ-09.
Condensation detector alt. window contact Flkt Woods condensation detector STRZ-16 alt. window contact STRZ-38 resp. potential-free contact
CO2 sensor STRZ-18, CO2 sensor with built-in relay. Active sensor is also possible to use.

Outputs
Fan control 3 outputs for speed I, II and III respectively, 24 V AC, max 0.5 A
Forced ventilation 24 V AC actuator, max 0.5 A
Valve actuator alt. thermal actuator 2 outputs
Valve actuator 010 V DC, max 5 mA
Thermal actuator 24 V AC, max 2.0 A
Control Heating or cooling

Actuator exercise FS = 23 hours interval
Terminal blocks So-called lift type for cable cross-section 2.1 mm2

Flkt Woods 8713 GB 2014.04 7 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.

STRA-07 for Fancoils


Configuration Display: the background lighting is lit (dimmed), and the
occupancy indication is shown (see the chapter Display
The controllers are configured via the display through handling). The current room temperature (or setpoint
setting the required parameters. See section Display depending on the configuration) is also shown in the
handling/Parameter menu. Different applications require display.
different parameters to be set.
Bypass
Operating modes
Operating mode Bypass means that the controller controls
STRA-07 has five different operating modes. Through the the room temperature in the same way as in operating
occupancy button you are able to switch between three of mode Occupied. The output for forced ventilation is
them. Occupied is the preset mode. also active. After a configurable time (FS=2 hours) in
Bypass, the controller automatically returns to the preset
Off operating mode.
Operating mode Off means that the controller is not Bypass is normally activated when the Occupancy
heating or cooling, and the fans are stopped. However, button is pressed, via an occupancy detector or a central
the temperature must not drop below the set minimum command. The operating mode is useful for example in
temperature (FS=8C). If it does, the controller will start conference rooms, where many people are present at the
heating, and (if a fan is used) start the fan whether it has same time for a certain period of time.
been manually stopped or not.
Display: the background lighting is lit (dimmed).
Display: The background lighting is not lit, and only OFF The occupancy indication and the symbol for forced
is shown in the display. ventilation are shown (see the chapter Display handling).
The current room temperature (or setpoint depending on
Unoccupied the configuration) is shown in the display.
Operating mode Unoccupied means that the room where
the controller is placed is not used for an extended Activation of the different operating modes
period of time, for example during holidays or long Preset operating mode
weekends. Both heating and cooling are disconnected
and the fans are stopped within a temperature interval Occupied is the preset operating mode. On models
with configurable min/max temperatures (FS min=15C, without display the preset mode can be changed to Stand-
max=30C). by using dipswitch SW3. OFF (FS): Occupied, ON: Stand-
by. This is configured in the parameter menu in the
Display: The background lighting is not lit, but the display, parameter 45. The operating mode is changed at
current room temperature (or setpoint depending on the the following events:
configuration) is shown in the display. OFF is also shown
in the display. When the Occupancy button is pressed (if the controller
has an Occupancy button).
Stand-by Activation/deactivation of an occupancy detector on the
Operating mode Stand-by means that the room is in digital input.
an energy save mode and is not used at the moment. CO2 value exceeded.
This can be during nights, weekends, evenings etc.
Via central control, for example central time control,
The controller is prepared to change operating mode
central booking system etc.
to Occupied (comfort) if someone enters the room
(presence). The room temperature is controlled around
the applicable heating and cooling setpoints, with Occupancy button
an extended temperature interval (FS=+/-3C). For
example, if the heating setpoint=22C and the cooling
setpoint=24C, the controller will allow the temperature in
the room to be between 19C and 27C. The setpoints can
also be adjusted +/- 3C via the display.
Display: the background lighting is lit (dimmed).
STANDBY and the current room temperature (or setpoint
depending on the configuration) are shown in the display.

Occupied
Operating mode Occupied means that the room is in
use and is therefore in a comfort mode. The controller
regulates the room temperature around a heating setpoint
and a cooling setpoint (FS heating setpoint=22C, cooling
setpoint=24C). The setpoints can also be adjusted +/- 3C
locally via the display, or via a central command.

Flkt Woods 8713 GB 2014.04 8 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.

STRA-07 for Fancoils


Shutdown Cooling/Cooling
When the Occupancy button is held depressed for more For the control states, UO1 is used for the left control
than 5 seconds, the controller changes operating mode to function and UO2 is used for the right control function.
Shutdown (Off/Unoccupied), regardless of the current For control states where only one control function is
operating mode. Via the display , you can configure active (Heating, Heating or cooling via the change-over
which operating mode, Off or Unoccupied, should be function, and Cooling), only UO1 is used.
activated on Shutdown. The factory setting is that
Unoccupied is activated. Heating
If you press the Occupancy button for less than 5 seconds In control state Heating, the unit is always a heating
when the controller is in operating mode Shutdown controller and controls according to the heating setpoint
or the preset operating mode, the controller changes plus/minus the setpoint displacement. The setpoint can be
to operating mode Bypass. If you press the button for adjusted in the display.
less than 5 seconds when the controller is in Bypass, it
changes operating mode to the Preset operating mode. Heating or cooling via the change-over function
After a configurable time in Bypass (FS=2 hours), the Like control state Heating but with change-over function,
controller returns to the preset operating mode. i. e. when the change-over input is active, the controller
For handling of the Occupancy button in combination becomes a cooling controller and regulates according
with central control, see the section Central control below. to the basic cooling setpoint plus/minus the setpoint
displacement. See more in the section Change-over.
Occupancy detector
Heating/Heating

Split output signal


In control state Heating/Heating, the controller is always
a heating controller and controls according to the basic
heating setpoint plus the setpoint displacement. When
the controller output signal reaches 50%, it is divided
between two actuators. 048% of the signal is sent to
actuator 1 and 52100% of the signal is sent to actuator 2.
See the figure below.
For local control of the operating mode between the
preset operating mode and Bypass, an occupancy detector

is connected.
When occupancy is indicated, the controller changes
operating mode to Bypass. If you want to be able to
enter the room temporarily without activating Bypass,
for example to pick something up, you can configure a
powerup delay. This means that Bypass is not activated
until the power-up delay has expired. The Bypass delay
can be set to a value between 0 and 60 minutes (FS=0
min).
In Bypass on presence, there is a switch-off timer, which
means that if there is no occupancy indication during this
time (FS=10 min), the controller will return to the preset
operating mode.
Heating/Cooling
Control states In control state Heating/Cooling, the controller functions
The controllers can be configured for different control as a heating controller when the room temperature
states/control sequences: is lower than the basic heating setpoint plus half the
neutral zone. The neutral zone is the difference in
Heating temperature between the heating setpoint and the cooling
Heating or cooling via the change-over function setpoint. When the room temperature exceeds this limit,
Heating/Heating the controller becomes a cooling controller. There is a
hysteresis of 0.1C when the controller changes from
Heating/Cooling heating to cooling controller and vice versa. When the
Heating/Cooling with VAV-control and forced supply controller is heating, it regulates according to the basic
air function heating setpoint plus the setpoint displacement, and
when it is cooling according to the basic cooling setpoint
Heating/Cooling with VAV-control
plus the setpoint adjustment.
Cooling

Flkt Woods 8713 GB 2014.04 9 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.

STRA-07 for Fancoils


Thermal actuators
When thermal actuator control has been selected, this
is controlled digitally with time proportional pulses
via output UO. By pulsing, the opening degree of the
actuator (and its valve) is varied. The period time (in
seconds) is the sum of the on and off output times on the
output. The period time is FS=60s. The controller varies
the on and off output times proportionally depending on
the output signal demand to the actuator.

Actuator exercise
All actuators are exercised. The exercise takes place at
set intervals in hours (FS=23 hours interval). An opening
Cooling signal is sent to the actuator for as long time as the run
time has been configured. Then a closing signal is sent for
In control state Cooling, the unit is always a cooling as long time and the exercise is finished.
controller and controls according to the basic cooling
setpoint plus the setpoint displacement.

Cooling/Cooling
Split output signal
In control mode Cooling/Cooling, the controller always
functions as a cooling controller and controls according to
the basic cooling setpoint plus the setpoint displacement.
When the controller output signal reaches 50%, it is
divided between two actuators. 048% of the signal is
sent to actuator 1 and 52100% of the signal is sent to
actuator 2. See the figure below.

Actuators
STRA-07 can be used with two types of actuators:
Analogue 010 V actuators
Thermal actuators
The actuator type is set via the parameter menu in the
display.

Analogue actuators
The following output signals can be set for analogue
actuators:
010 V (FS)
210 V
102 V
100 V

Flkt Woods 8713 GB 2014.04 10 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.

STRA-07 for Fancoils


Fan control Manual setting of speed I-III means that the speed of the
fan in operating modes Stand-by, Occupied and Bypass
In STRA-07 it is possible to control a fan at the following
is always the set speed. In the other operating modes, the
speeds: Off, Low speed, Medium speed, High speed,
fan is demand controlled.
Auto. The fan speed in the Auto position depends on the
controller output signal and the settings for each speed.
Auto control
Manual control In auto mode, you can configure if the fan should be
controlled by the heating output, the cooling output, or
The fan can be manually controlled to work at any speed.
both the heating and cooling outputs. When the selected
On models with display, you press the fan button once
output exceeds the start value that has been set for each
and a fan symbol is lit for 10 seconds in the display. As
speed (FS speed 1=20%, speed 2=60%, speed 3=100%),
long as the symbol is lit, you can change the fan speed
the fan is activated. It stops when the controller output
with the INCREASE/DECREASE buttons. Models without
signal drops below the set value minus the set hysteresis
display have a fan switch.
(FS=5%).

When the fan speed changes, there is always a minimum


delay (2-3 s) between the inactivation of the output for the
current speed and the activation of the output for the new
speed. Only one fan speed output is defined at a time.

Off/Unoccupied
In operating modes Off and Unoccupied, the fan is
stopped, regardless of the position of the fan switch or the
setting in the display, on condition that the temperature
is within the set temperature limits. If the temperature
is not within the set temperature limits, the fan will be
started in the corresponding Auto position, regardless of
the settings.

Figure 9. Fan button on models with display

Figure 10. Alter fan speed


The controller has the following positions:
Auto Automatic control of the fan
speed to maintain desired
room temperature.
0 Fan Off.
I Manual position with low
speed.
II Manual position with
medium speed.
III Manual position with high
speed.

Flkt Woods 8713 GB 2014.04 11 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.

STRA-07 for Fancoils


Functions description Parameter Settings
STRA-07 is delivered with a number of factory settings.
Change-over To acquire the desired function, the controller must
Change-over is a function for installations with 2-pipe be adapted to its specific application. This is done
systems. It makes it possible to use the same pipe for both through the parameter menu in the display. Applications
heating and cooling, depending on requirements during may vary and incorrectly set parameters can effect the
for example the summer (cooling output) and the winter controller and application negatively. Be sure to set the
(heating output). necessary parameters relevant for your application. If you
experience problems, contact Flkt Woods TSS controls.
Control states
Parameter menu
To activate the change-over function, control mode
Heating or cooling via the change-over function should be It is possible to set different parameter values in a
configured. parameter menu. The parameter menu is accessed by
simultaneously holding the INCREASE and DECREASE
STRA-07 has an input for change-over. The input can be
buttons depressed for about 5 seconds and then pressing
either of the type analogue Pt1000-sensor or a closing
the INCREASE button twice. The Service indication will
contact connected to a digital input (FS=Pt1000-input).
be displayed.
The Pt1000-sensor is mounted so that it senses the
First the display will show the parameter-number 1.
temperature on the feed wire to the battery. If the
Scroll between parameters by using the INCREASE and
temperature drops below 18C (FS), change-over is
DECREASE buttons.
activated and the heating output, UO1 alt. DO2/DO3 (-T-
models), is set to cooling. When the temperature exceeds Press the Occupancy button to select the desired
22C (FS) the change-over function is deactivated and the parameter. The parameter number will be replaced by
heating output is set to heating. the parameter value. The value can be changed using
the INCREASE and DECREASE buttons. If a button is
When using a digital signal input (potential-free contact),
held depressed the value will start scrolling, first slowly
closing the contact switches the change-over function and
and then with increasing speed in 3 4 steps with 2 3
sets the heating output, UO1 alt. DO2/DO3 (-T-models),
seconds between steps.
to cooling. On open contact, the change-over function sets
the heating output to heating. Acknowledge/Regret
It is also possible to control change-over via a central To acknowledge and store a set parameter value, press
command. See the variable list in Part IV of this manual. the Occupancy button again, the display then returns to
showing the parameter number. To retrieve the original
Condensation detector value, i.e. the value before change, press the INCREASE
and DECREASE buttons at the same time. The original
Special input CI value is shown on the display.
There is a special input (CI) on STRA-07 controllers. This Return
input is intended for Flkt Woodss condensation detector, After a certain time, about 1 minute, or when the
STRZ-16, and functions internally as a digital input, i. e. INCREASE and DECREASE buttons are pressed at the
condensation or no condensation. same time while in the menu, the display returns to the
When the condensation detector is activated, the cooling normal view. Exit is shown on the display after the last
control is blocked and the controller is set in neutral parameter. The parameter menu is exited by pressing the
position. When condensation ceases, the controller will Occupancy button while in Exit. Pressing on INCREASE
start controlling from the neutral position. goes to the first parameter and pressing on DECREASE
goes to the last parameter..
Window Contact
When the window contact has been configurated the
regulator is set to normal operation when window is
closed. If the window is open, the regulator is set in mode
off, heating and cooling outputs are set to 0 V and the
frost protection function is activated.

Frost protection
STRA has built-in frost protection, which is activated
when the controller is not in use. The frost protection
prevents the temperature from dropping below
8C. Return to normal fan speed and control occurs
automatically when the room temperature exceeds 8C.

Flkt Woods 8713 GB 2014.04 12 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.

STRA-07 for Fancoils


Quick guide to Flkt Woods standard applications:
1. Desired basic heating setpoint: 01
2. Desired basic cooling setpoint: 02
3. Application control state: 11
4. Type of temperature sensor: 15
5. State of function UO1 (heating output): 20
6. State of function UO2 (cooling output): 21
7. State output signal range, heating actuator: 29
8. State output signal range, cooling actuator: 30
9. Preset operating mode: 45
10. State operating mode by depressing occupancy button for 46
5 sec:
11. Configuration of fan control 50
12. Start signal (%) for fan speed 1 51
13. Start signal (%) for fan speed 2 52
14. Start signal (%) for fan speed 3 53

Parameters
The following parameters can be changed in the parameter menu (FS = Factory setting):
Parameter number Description Values Unit FS STRA-07
1 Occupied Heating Setpoint C 22
2 Occupied Cooling Setpoint C 24
3 Standby Neutral Zone C 3
4 Unoccupied Heating Setpoint C 15
5 Unoccupied Cooling Setpoint C 30
6 Frost protection Setpoint C 8
7 P-Band C 10
8 I-Time sec 300
9 Cooling Changeover difference temperature (Room C 3
and media)
10 Heating Changeover difference temperature (Room C 4
and media)
11 Heating/Cooling Functions 0=Heat, 3
1=Heat/Heat,
2=Heat or Cool via changeover,
3=Heat/Cool,
4=Heat/Cool with VAV and forced v'entilation,
5=Heat/Cool with VAV,
6=Cool,
7=Cool/Cool,
8=Heat/Cool with UO3,
9=Heat/Cool with Change-Over
12 Boost Mode Timer min 120
13 P.I.R Delay Off min 10
14 P.I.R Delay On min 0
15 Connected sensor on AI1 0=internal, 0
1=external,
2=Change over sensor
16 UI1 Signal 0 = Disabled, 2
1 = Change over sensor digital,
2 = Change over sensor analogue
17 Connected sensor DI1 Input 0=Disabled, 3
1=Window contact,
3=P.I.R,
4=Change over sensor
18 Connected sensor DI2 input 0=Disabled, 2
1=Window Contact,
2=Condensation Sensor,
4=Change over sensor
20 Function of UO1 Signal 0=None, 3
1=Thermal actuator heat,
2= None,
3=Heating actuator 0...10V,
4= None,
5=On/off actuator heat,
6= None
21 Function of UO2 Signal 0= None 4
1= None,
2=Thermal actuator Cool,
3= None,
4=Cooling actuator 010V,
5= None,
6=On/off actuator cool

Flkt Woods 8713 GB 2014.04 13 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.

Parameters
The following parameters can be changed in the parameter menu (FS = Factory setting):
Parameter number Description Values Unit FS STRA-07
22 Function of UO3 Signal 0=None, 0
1=Forced Vent Digital,
2=Forced Vent 3 Step Analog,
3=None,
4=Ordinary Analog output,
5=None,
6=Control of EC-fan
24 U03 output in manual mode 0
28 Actuator type for UO3 0=0-10v, 0
1=2-10v,
2=10-2v,
3=10-0v
29 Heating Modulating Actuator Control 0=0-10v, 0
1=2-10v,
2=10-2v,
3=10-0v
30 Cooling Modulating Actuator Control 0=0-10v, 0
1=2-10v,
2=10-2v,
3=10-0v
31 Heating Thermal Actuator Time sec 60
32 Cooling Thermal Actuator Time sec 60
33 Travelling Time for Increase/Decrease Heating Valve 0 sec 120
(Not in use)
34 Travelling Time for Increase/Decrease Cooling Valve 0 sec 120
(Not in use)
35 Increase/Decrease NZ (Not in use) 0 % 2
36 Heating Valve Periodic Exercise Interval 0=inactive hours 23
37 Cooling Valve Periodic Exercise Interval 0=inactive hours 23
38 Hysteresis for the heating thermostat function C 2
39 Hysteresis for the cooling thermostat function C 2
40 The minimum heat output in heating mode % 0
41 Fan runs on low speed (Not in use) 0 0
42 Display View 0=Actual Temp Value, 0
1=Heating Setpoint,
2=Cooling Setpoint,
3=Average of Heating/Cooling,
4=Only Setpoint Displacement,
5=CO2,
6=Heating Setpoint + Setpoint Displacement,
7=Cooling Setpoint + Setpoint Displacement,
8=Average of Heating/Cooling Setpoints + Setpoint
Displacement,
9=Calculated Flow in L/S
43 Highest Setpoint Offset Increase C 3
44 Lowest Setpoint Offset Decrease C 3
45 Normal Mode Function 0=Off, 3
1=Unoccupied,
2=Stand-by,
3=Occupied
46 Energy Saving Mode Function 0=Off, 1
1=Unoccupied
47 BMS Operating Mode 0=Off, 5
1=Unoccupied,
2=Standby,
3=Occupied,
4=Not Used,
5=No Remote control
48 Minimum airflow on cooling UO2 in % of 0-10V. 20
Parameter is in use when cooling/heating mode with
VAV is selected.
49 Maximum airflow on cooling UO2 in % of 0-10V. 0
Parameter is in use when heating/cooling mode with
VAV is selected.
50 Fan Control 0=No control, 3
1=Heating,

2=Cooling,
3=Both
51 Fan Speed 1 Limit 0 % 5
52 Fan Speed 2 Limit 0 % 60

Flkt Woods 8713 GB 2014.04 14 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.

Parameters
The following parameters can be changed in the parameter menu (FS = Factory setting):
Parameter number Description Values Unit FS STRA-07
53 Fan Speed 3 Limit 0 % 100
54 Fan Start/Stop Hyst 0 5
55 Fan Speeds 0 3
56 External Temperature Sensor Calibration Gain AI1 C 0
57 Sensor Calibration Gain UI1 C 0
58 Internal Temperature Sensor Calibration Gain C 0
59 Filter factor for AI temperature C 0.2
60 Normally open/Normally closed DI1 0 = For N/C-actuator, 0
1=For N/O-actuator
61 Normally open/Normally closed DI2 0=N/O, 1
1=N/C
62 Normally open/Normally closed UI1 0=N/O, 0
1=N/C
63 Heating Manual Override 0=, 2
1=Manual,
2=Auto
64 Cooling Manual Override 0=, 2
1=Manual,
2=Auto
65 Forced ventilation Manual Override 0=, 2
1=Manual,
2=Auto
66 Changeover Manual Override 0=Heating, 2
1=Cooling,
2=Auto
67 Manual Mode Heating Output % 0
68 Manual Mode Cooling Output % 0
69 Modbus Address
70 Modbus Parity 0=None, 2
1=Odd,
2=Even
71 Modbus Timeout millisecond 3
72 Modbus Response Delay Millisecond 5
73 Heating output 0 = For N/C-actuator, 0
1=For N/O-actuator
74 HMI Displacement View 0=The offset, 0 0
1=The active setpoint + offset,
2=The heating setpoint + offset,
3=The cooling setpoint + offset,
4=Occupied Heating Setpoint + Offset,
5=Occupied Cooling setpoint + Offset,
6=Occupied Average + Offset
75 Free Cooling 0=ON, 1=OFF N/A 0
76 Forced Ventilation control mode 0=No Action, 0
1=Forced on Heat/Cool output at 100%,
2=Forced on Cool output at 100%
77 P.I.R Activated Operation Mode 3=Occupied, 4
4=Bypass
78 The Controller PLA Address. Used in EXOline 0
79 The Controller ELA Address. Used in EXOline 0
80 Cool output 0=N/O, 1=N/C 0
81 AI2 Input 0=Disable, 0
5=CO2,
7=0-100% ,
8=Flow calculation,
9=0-10V
82 Flow at 0 volt on AI2 (Not in use) 0 l/s 0
83 Flow at 10 volt at AI2 (Not in use) 0 l/s 100
84 The minimum time the valve is open when the sec 60
calculation of change over is made
86 Alarm triggers when temperature falls below C 40
87 Alarm triggers when temperature raise above C 15
97 CO2 Level to Change to Boost Mode PPM 0
98 CO2 Level below "Boost Mode CO2 Start" value to PPM 0
start Boost Mode Timer countdown
100 AI CO2 Filter 0
104 CO2 Sensor PPM for 0v PPM 104
105 CO2 Sensor PPM for 10v PPM 0

Flkt Woods 8713 GB 2014.04 15 Specifications are subject of alteration without further notice.
STRA-07 Room Controller. Installation and maintenance manual.

Parameters
The following parameters can be changed in the parameter menu (FS = Factory setting):
Parameter number Description Values Unit FS STRA-07
112 VAV CO2 Minimum Limit PPM 0
113 VAV CO2 Maximum Limit PPM 0
114 Port Mode 0=EXOline/Modbus, 0
1=BACnet
115 BACnet address Above 127 = Slave
116 BACnet device ID low 4 figures
117 BACnet device ID high 3 figures
118 BACnet Max Master 127
119 Com Speed 0=9600, 0
1=19200,
2=38400,
3=76800 (BACnet)
120 Reset com to factory default (Modbus 9K6, 8, N, 1) 0
121 The lowest output the fan will need to start (Not in 0 V 10
use)
122 The highest speed of the fan (Not in use) 0 V 100
125 The Model in Regin Range 1939 = STRA-07, Read Only 1939
1943 = STRA-04,
1945 = STRA-14
126 Major Version
127 Minor Version
128 Branch Version
129 Revision

Flkt Woods 8713 GB 2014.04 16 Specifications are subject of alteration without further notice.