JOB NAME: DATE:07.03.

2017
Floor Name:
SPACE FOR: 10.00 height
SIZE: 220 Sq ft 2200 Cu ft Estimate for: SUMMER
SOLAR GAIN GLASS HEAT GAIN CONDITION DB (F) WB (F)
ITEM Area Sun Gain Factor Btu/hour OUTSIDE 100 83
(Sq ft) (Btu/h.sq ft) ROOM 71
N - Glass 90 23 0.56 1159 DIFFERENCE 29 XXXX
NE - Glass 0 12 0.56 0
E - Glass 0 12 0.56 0 OUTSIDE AIR (VENTILATION)
SE - Glass 0 12 0.56 0 3 People X 5.0
S - Glass 20 12 0.56 134 2200 Cu ft X 1.0
SW - Glass 0 85 0.56 0
W - Glass 0 163 0.56 0
NW - Glass 0 138 0.56 0 EFF. SENSIBLE HEAT FACTOR (ESHF) =
Sky light 0 118 0.56 0 Indicated ADP = 58
SOLAR & TRANS. GAIN WALLS & ROOF Selected ADP = 52
ITEM Area Eq. temp. diff. U Dehum. temp rise = 16.72
(Sq ft) (F) (Btu/h.sq ft) DEHUMIDIFIED CFM = 966
N - Wall 0 30 0.36 0
NE - Wall 0 12 0.36 0
E - Wall 0 12 0.36 0
SE - Wall 0 18 0.36 0
S - Wall 70 46 0.36 1159
SW - Wall 0 52 0.36 0
W - Wall 0 46 0.36 0
NW - Wall 0 32 0.36 0
Roof Sun 220 55 0.4 4840
Roof Shaded 0 28 0.15 0 NOTES
TRANS. GAIN EXCEPT WALLS & ROOF Occupancy = 3 Nos
ITEM Area Temp. diff. U Lighting = 1.25 W/Sq ft
(Sq ft) (F) (Btu/h.sq ft) Eq. Load = 0.00 KW
All Glass 110 29 0.5 1595 Height = 10.00 FT
Partition 225 24 0.37 1998 Fresh Air= 5.0 Cfm per person
Ceiling 0 24 0.41 0 = 1.0 Air changes per hour
Floor 220 29 0.41 2616 Internal Heat - People
INTERNAL HEAT GAIN Sensible Heat = 245
People 3 Nos X 245 735 Latent Heat = 205
Light 275 W X 2 3.41 938
Eq. Load 0.0 W X 3.41 0
ROOM SENSIBLE HEAT (RSH) 15174
Supply duct heat Supply duct Heat gain from 4 607
gain + leak. loss + fan HP(%)
Safety factor (%) 10.0 1517
OUTSIDE AIR TR As per REF Load >
CFM F BF FACTOR TR As per DH CFM >
37 29 0.12 1.08 138
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 17437 TR Recommanded >
LATENT HEAT
People 3 Nos X 205
ROOM LATENT HEAT (RLH) 615
Supply duct leakage loss + Safety factor % 5.0 31
OUTSIDE AIR
CFM GR/LB BF FACTOR
37 66 0.12 0.68 197
EFFECTIVE ROOM LATENT HEAT (ERLH) 843
EFFECTIVE ROOM TOTAL HEAT (ERTH) 18280
OUTSIDE AIR HEAT (SENSIBLE) CHECK FIGURES
CFM F 1 - BF FACTOR Btu/h/ Sq ft = 108.4
37 29 0.88 1.08 1011 CFM / Sq ft = 4.39
OUTSIDE AIR HEAT (LATENT) Sq ft / TR = 111
CFM GR/LB 1 - BF FACTOR CFM/ TR = 486
37 66 0.88 0.68 1448
HEAT SUB TOTAL 20739
Return duct heat HP Pump + Dehum. & Pipe 15.0 3111
gain & leak. loss loss (%)
+

TR 1.99 GRAND TOTAL HEAT 23849


DATE:07.03.2017 Rev:R0

% RH DP (F) GR/LB
68 130
55 64
XXXX XXXX 66

CFM/Person 28
Air change per hour 37
CFM VENTILATION 37

0.95
F
F
F
TR > 2.76

Cfm per person ASHRAE


Air changes per hour

1.99
2.76