CTA Remote Excel File Loader

Version 4.40

The CTA Remote Excel File Loader is used to:


- prepare and edit tests with Microsoft Excel on yo
- communicate with the CT Analyzer
- import CT Analyzer report files (*.xml) into Micro
- upload/download tests to and from the CT Analy
- prepare customer-specific test reports
- develop test automation under VBA.

The CTA Remote Excel File Loader performs re


can be extended further to a customer-specific rep
TEST button creates a new empty worksheet (XM
Help
As many test reports as required can be combined
worksheets, the button LOAD REPORT loads a re
button CHANGE SETTINGS to define or change t
automatically transfer the test settings to the CT A
CT Analyzer test is finished, the data are read fro
Excel worksheet.

Post-processing of the results is easy, since the re


numbers. In a separate blank worksheet or custom
of the OMICRON pre-made worksheets using Mic
OMICRON worksheets are updated, Microsoft Ex
this method, it is possible to create customer-spec
applications.

Sheet is password protected with "CTAnalyzer"


el File Loader is used to:
s with Microsoft Excel on your computer
e CT Analyzer
eport files (*.xml) into Microsoft Excel
s to and from the CT Analyzer
ecific test reports
on under VBA.

el File Loader performs remote-controlled tests with the CT Analyzer. The tool
r to a customer-specific report tool for the CT Analyzer. Clicking the NEW
new empty worksheet (XMLData(x)) for one test report.

s required can be combined to one customer-specific test report. In the


LOAD REPORT loads a report file created with the CT Analyzer. Use the
INGS to define or change the test settings. Use the button START TEST to
he test settings to the CT Analyzer, and to start the test. Once the
shed, the data are read from the CT Analyzer and loaded into the Microsoft

results is easy, since the results are converted into Microsoft Excel-compatible
e blank worksheet or customer-specific test report, you can reference to the data
made worksheets using Microsoft Excel formulas. When the data in the
are updated, Microsoft Excel also updates the customer-made worksheets. By
ble to create customer-specific Microsoft Excel templates for different

CTAnalyzer"
TEST SETTINGS:
Location: ULTRA TECH CEMENT\INDIA\MCC ROOM\DG INCOMER-1\R
Company: ULTRA TECH CEMENT
Country: INDIA
Station: MCC ROOM

Object: PRECISE ELECTRICALS\-\735082\1\1\-


Manufacturer: PRECISE ELECTRICALS
Type: -
CT Serial Number: 735082

Rated primary current I-pn: ?


Applied standard: IEC 61869-2
Class: 5P
FS:
ALF: 10.0
Kssc:
f: 50.0Hz
Tmeas: 25.0C
Rated burden: 15.0VA cosphi 0.8
Operating burden: 15.0VA cosphi 1.0
Ts:
Tp:
Duty:
t1:
t2:
tfr:
Comment:

General test information Assessments


Used test settings Burden test
Comment Residual Magnetism Test

TEST RESULTS:

General test information:


Test device: CT-Analyzer
Device Serial No.: MK509L
Date/Time: 2016-07-30, 11:06:53
Test language: English
Status info: Test successful
Error type: n/a
Error number: 0
Error location: 0
Error Info Text:

Overall Assessment: OK

Used test settings:

Location: ULTRA TECH CEMENT\INDIA\MCC ROOM\DG INCOMER-1\R


ULTRA TECH
Company: CEMENT
Country: INDIA
Station: MCC ROOM

Object: PRECISE ELECTRICALS\-\735082\1\1\-


Manufacturer: PRECISE ELECTRICALS
Type: -
Serial number: 735082

Rated primary current I-pn: 800.0A


Applied standard: IEC 61869-2
Class: 5P
FS:
ALF: 10.0
Kssc:
f: 50.0Hz
Tmeas: 25.0C
Rated burden: 15.0VA cosphi 0.8
Operating burden: 15.0VA cosphi 1.0
Ts:
Tp:
Duty:
t1:
t2:
tfr:

Comment:
Assessments: Auto. Manual
ALF: OK ?
ALFi: OK ?
FS: n/a ?
FSi n/a ?
Vb: n/a ?
Class: OK ?
Op. burden: n/a ?
max. Rct: n/a ?
Rprim: n/a ?
Ts: n/a ?
Kr: n/a ?
K*Kssc; Ktd*Kssc; Kx: n/a ?
I-al, Ie, Ik: n/a ?
V-al, Ek, Vk: n/a ?
Ie1, Ik1: n/a ?
RE @ 20*I-sn: n/a ?
RE @ Isn: n/a ?
Current ratio error (): OK ?
Phase error (): OK ?
Composite error(c): OK ?
Peak instantaneous error (^): n/a ?
Turns ratio error (t): n/a ?
Vk / Ik: n/a ?
Vk1 / Ik1: n/a ?
Vknee: n/a ?
RCF: n/a ?
^ ac:
Burden test:
Status info:
Error type:
Error number:
Error location:
Results:
Overload:
Test current:
Vmeas:
Z:

Residual Magnetism Test:


Status info:
Error type:
Error number:
Error location:
Results:
Residual Flux:
Residual Magnetism:

Primary Resistance Test:


Status info:
Error type:
Error number:
Error location:
Test current:
Results:
I-DC:
Tmeas:
Tref:

Resistance test:
Status info: Test successful
Error type: n/a
Error number: 0
Error location: 0
Test current: 1.0A
Results:
I-DC: 1.046A
Tmeas: 25.0C
Tref: 75.0C

Excitation test:
Status info: Test successful
Error type: n/a
Error number: 0
Error location: 0
Results:
Overload: No
Knee Points: 60044-1: V-kn: 163.56V
V-kn 2:
60044-6: V-kn: 152.83V
V-kn 2:
61869-2: V-kn: 163.4V
V-kn 2:
ANSI 30: V-kn: 142.66V
IEEE C57.13 V-kn: 122.56V

Ls: 0.0029826H
Kr: 82.35%
Eddy Resistance: 39213.383Ohm
Result with rated burden:
ALF: 11.5 11.480495
ALFi: 11.0 11.0214875
FS:
FSi:
Kssc:
Vb:
Kx:
Ktd:
Ts: 2.903s
peak:
E-max:
Error indirect (i) [%]: 0.5% 0.49615869
^ ac:

Excitation curve data:


Measured data Help for graph
EMF [Vs] UCrms [V] UCTrms [V] ICTrms [A]

1.0221321583 227.0606689453 227.3515930176 2.8260521889


1.0118578672 224.7783050537 224.7977294922 1.6806521416
1.0042481422 223.0878448486 223.0164489746 1.0641028881
0.9969987869 221.4774475098 221.3724212646 0.7198249698
0.9877280593 219.4180297852 219.2970275879 0.4884680212
0.9756560326 216.7362976074 216.607925415 0.3249001503
0.9608225822 213.4411315918 213.3088226318 0.2094495296
0.9448342323 209.8894042969 209.7546539307 0.1343723238
0.9274210334 206.0211639404 205.8843841553 0.0870934501
0.9076182246 201.6220855713 201.4840087891 0.0574108399
0.8835476041 196.2749328613 196.1362457275 0.0384320691
0.8443055153 187.5575256348 187.420135498 0.02409322
0.7978872061 177.2459716797 177.1122741699 0.0167609006
0.7487294078 166.3258514404 166.1978759766 0.0129024498
0.6966246367 154.751083374 154.6192016602 0.0106302304
0.6419549584 142.6065368652 142.4708557129 0.0090604704
0.5882492065 130.6761169434 130.5376281738 0.0079115704
0.5437148809 120.7830734253 120.6590499878 0.0073616598
0.5084098577 112.9402770996 112.8243026733 0.00686784
0.4350160062 96.6362609863 96.5365982056 0.0059693302
0.3561244607 79.1109619141 79.0306472778 0.0051305499
0.2778270841 61.717666626 61.6557617188 0.00433107
0.2078695595 46.1770057678 46.1310348511 0.0035947401
0.1702161133 37.8127555847 37.8221435547 0.00313188
0.094839178 21.0679931641 21.0735816956 0.0021319001
0.0528406389 11.7382936478 11.7415771484 0.00142009
0.0294467807 6.5415287018 6.5434703827 0.00093424
0.01640792 3.644982338 3.6461496353 0.00061204
0.0091388701 2.0301911831 2.0309035778 0.00040116
0.0045016101 1 1.0004003048 0.00024072
0.00283567 0.629899919 0.630179584 0.00017473
0.0015681901 0.3483536541 0.348534286 0.00011742
0.00087361 0.194073543 0.1941920221 0.00008226
0.00048666 0.1081179827 0.1081933379 0.00005987
0.00027118 0.0602402911 0.0602841415 0.00004928
Reference graph data
EMF [Vs] UCrms [V] UCTrms [V] ICTrms [A]

1 1 1
Ratio test:
Status info: Test successful
Error type: n/a
Error number: 0
Error location: 0

Results with operating burden:


Ratio: 800.0 0.99876656
N: 800.11 800.11495
Phase: 6.002min
I-p: 800.0A
Turns ratio error -t: 0.014%

Results with rated burden (VA):


POWER Current ratio error in % at % of rat
VA cosPhi Data type 1%
String value -0.586
15 0.8
Float value -0.586
String value -0.395
7.5 0.8
Float value -0.395
String value -0.139
3.75 1
Float value -0.139
String value -0.114
1.88 1
Float value -0.114
String value
Float value
String value
Float value
String value
Float value
String value
Float value

POWER Phase displacement in [min] at %


VA cosPhi Data type 1%
String value 19.57
15 0.8
Float value 19.57
String value 16.95
7.5 0.8
Float value 16.95
String value 18.55
3.75 1
Float value 18.55
String value 17.25
1.88 1
Float value 17.25
String value
Float value
String value
Float value
String value
Float value
String value
Float value

Core ratio measurement:


V0 V1 V2 I1

23.72443 23.730475 0.02965128 0.00224215

Measured points
EMF [Vs] UCrms [V] UCTrms [V] ICTrms [A]
0.17021611 37.812755 37.8221425 0.00313188
0.09483918 21.0679925 21.0735825 0.0021319
0.05284064 11.73829375 11.7415775 0.00142009
0.02944678 6.5415285 6.5434705 0.00093424
0.01640792 3.64498225 3.64614975 0.00061204
0.00913887 2.03019113 2.03090363 0.00040116
0.00450161 1 1.00040031 0.00024072
0.00283567 0.62989994 0.63017956 0.00017473
0.00156819 0.34835366 0.34853428 0.00011742
0.00087361 0.19407355 0.19419202 0.00008226
0.00048666 0.10811798 0.10819334 0.00005987
0.00027118 0.06024029 0.06028414 0.00004928

Class parallelogram for IEEE C57.13 metering CT:

Defined accuracy class:


Defined ratio factor:

Measurement points according to IEEE C57.13


% of primary current Measured RCF Phase displacement [min]
Table for borders in parallelogram
Limits for 10% I-pn
x y

AL Error Graph:
Defined accuracy limiting error: % Error Line

Max K-factor at rated burden:


Impedance at rated burden:

Max K-factor at operating burden:


Impedance at operating burden:

User-defined measurement point:


K-Value: 0.00
Burden: 0.00 Ohm
Accuracy limiting table:
Impedance [] K-Value [K]
Info for current ratio calculation below:
Calculation of current error at specified burden and primary current

I-pn [A] Burden [VA] cos


1% 8 0 0
5% 40 0 0
10% 80 0 0
20% 160 0 0
25% 200 0 0
50% 400 0 0
100% 800 0 0
120% 960 0 0
125% 1000 0 0
150% 1200 0 0
200% 1600 0 0
-
- -
1% 8 0 0.9
5% 40 0 0.9
10% 80 0 0.9
20% 160 0 0.9
25% 200 0 0.9
50% 400 0 0.9
100% 800 0 0.9
120% 960 0 0.9
125% 1000 0 0.9
150% 1200 0 0.9
200% 1600 0 0.9
Test cards:
NDIA\MCC ROOM\DG INCOMER-1\R\IS-2705 Burden test:
Feeder/Bay: DG INCOMER-1 Itest:
Phase: R Residual Magnetism test:
IEC-ID: IS-2705 Primary resistance test:
Resistance test:
S\-\735082\1\1\- Excitation test:
Core number: 1 Ratio test:
Tap: 1
Optional: -

Rated secondary current I-sn: 1.0A


Core type (P/M): P Assess @ Rated B.:
Class multiplier: 1 Delta compensation:
RF: ext (Icth):
Vb: RE(20*Isn):
Ktd: Ktd calculation:
max. Rct: ? max. Rprim:
Tref: 75.0C T Unit:
Ext. VA: Ktd Spec.:

V-al, Ek, Vk: E1, Vk1:


I-al, Ie, Ik: Ie1, Ik1:
Kx:
K:
t-al1:
t-al2:

Primary Resistance Test Ratio test


Resistance test Class parallelogram for IEEE C57.13 metering CT
Excitation test AL Error Graph
Device software version: 4.40 (14-06-24 09:36)
Hardware version: 01/01/08/05/00/11
Stylesheet version: 4
File name: B:\MSISettings.xml
Remote Excel File Loader Version4.4
Name of test file: \\OFFICE-SERVER\D on office server\MS Word Files\New MSWord files-2009\L&T K
Security key correct: Yes

NDIA\MCC ROOM\DG INCOMER-1\R\IS-2705

Feeder/Bay: DG INCOMER-1
Phase: R
IEC-ID IS-2705

S\-\735082\1\1\-
Core number: 1
Tap: 1
Optional: -

Rated secondary current I-sn: 1.0A


Core type (P/M): P Assess @ Rated B.:
Class multiplier: 1 Delta compensation:
RF: ext (Icth):
Vb: RE(20*Isn):
Ktd: Ktd calculation:
max. Rct: 5.823Ohm max. Rprim:
Tref: 75.0C T Unit:
min. VA at M-cores Isn 5A: 0.0VA Ext. VA:
Enable rated burdens < 1VA: disable Ktd Spec.:
V-al, Ek, Vk: E1, Vk1:
I-al, Ie, Ik: Ie1, Ik1:
Kx:
K:
t-al1:
t-al2:
Imeas:
Burden:
V-DC:
Rmeas:
Rref:

V-DC: 5.1067V
Rmeas: 4.882Ohm
Rref: 5.8226Ohm

CT model used by CT Analyzer

Rp Lp Ip
P1 IST

I-kn: 0.012361A (Vc) IL


I-kn 2:
Uc
I-kn: 0.017108A Lmain
I-kn 2: RH
I-kn: 0.012361A
I-kn 2:
I-kn: 0.009066A
P2
I-kn: 0.00746A
Np Ns
Lm: 51.7319H
V-al, Ek, Vk:
I-al, Ie, Ik:
E1, Vk1:
Ie1 Ik1:
Result with operating burden:
ALF: 10.8 10.75280375
ALFi: 10.6 10.5562675
FS:
FSi:
Kssc:
Vb:
Kx:
Ktd: IEC 60044-6
Ts: 2.484s
peak:
E-max:
Error indirect (i) [%]: 1.12% 1.11626413
^ ac:

Info for table below


ICTpeak [A] ICTrect [A] Phase Uct/Ict []

9.6040039063 1.2799607515 87.2991333008


5.8592729568 0.7728057504 87.6492462158
3.6078565121 0.5117401481 87.5128936768
2.322863102 0.362308383 87.0938873291
1.5082061291 0.2555745542 86.3624267578
0.9714005589 0.1760055572 85.1045074463
0.6217336059 0.1180155575 83.0885772705
0.3948948681 0.0799641684 80.2101135254
0.2521519065 0.0556368008 76.4584579468
0.1604079753 0.0399296507 71.8257369995
0.1014231667 0.0293784104 66.4448776245
0.057432279 0.0207004603 59.1522293091
0.0353034288 0.0156480502 53.0905189514
0.0240707994 0.0126506798 48.8306541443
0.0177826993 0.0106942803 46.1328010559
0.0138097098 0.0092439298 44.4517593384
0.0113838501 0.00812345 43.5453300476
0.0100328401 0.00755696 44.5067481995
0.0091349296 0.0070551601 44.630821228
0.0076679299 0.0061280401 45.3754806519
0.00661891 0.0052510998 47.2181396484
0.0056685498 0.0044169701 49.8709335327
0.0047770902 0.00365155 53.0972595215
0.0043273498 0.00316049 52.1190414429
0.0029672901 0.0021440899 57.4844284058
0.0019984499 0.0014238399 61.7017784119
0.00132529 0.00093432 64.7816619873
0.00087374 0.00061104 66.9810638428
0.00057734 0.00039988 68.6362686157
0.00035162 0.00023926 70.1187286377
0.00025797 0.00017324 70.8263473511
0.00017536 0.00011609 71.588470459
0.00011634 0.00008147 72.7856369019
0.00008466 0.00005955 74.9820175171
0.00006969 0.00004928 79.3859329224
ICTpeak [A] ICTrect [A] Phase Uct/Ict []

1
C urrent d eviation [%]
1.500 Ratio Error G

1 1.000

1
1 0.500

Deviation [%]: -0.1234% 0.000


Composite error [%]: 0.221% 0% 50% 100%

Polarity: OK
-0.500
RCF: 1.001235
TCF: 0.99892663
-1.000

-1.500 I-pn [%]


P h a s e d is p la c e m e n t [m in ]

80.00 Phase Displacem

60.00

40.00

20.00

0.00
0% 50% 100%

-20.00

-40.00

-60.00

-80.00 I-pn [%]

ent ratio error in % at % of rated current


5% 10% 20%
-0.358 -0.304 -0.261
-0.358 -0.304 -0.261
-0.233 -0.196 -0.169
-0.233 -0.196 -0.169
-0.1 -0.087 -0.078
-0.100 -0.087 -0.078
-0.086 -0.074 -0.066
-0.086 -0.074 -0.066

se displacement in [min] at % rated current


5% 10% 20%
10.69 8.59 6.81
10.69 8.59 6.81
8.52 6.81 5.49
8.52 6.81 5.49
8.74 6.99 5.71
8.74 6.99 5.71
7.44 5.91 4.8
7.44 5.91 4.80

Phase VI1 PhaseVI2

303.5172 0.01650788

Info for table below


ICTpeak [A] ICTrect [A] Phase Uct/Ict []
0.00432735 0.00316049 52.11904
0.00296729 0.00214409 57.48443
0.00199845 0.00142384 61.70178
0.00132529 0.00093432 64.78166
0.00087374 0.00061104 66.981065
0.00057734 0.00039988 68.63627
0.00035162 0.00023926 70.11873
0.00025797 0.00017324 70.826345
0.00017536 0.00011609 71.58847
0.00011634 0.00008147 72.785635
0.00008466 0.00005955 74.98202
0.00006969 0.00004928 79.385935

e displacement [min]
Limits for 100% I-pn
x y
Phase Composite error
Current deviation [%] displacement [min] [%]
-0.0870921016 13.4945958853 0.4787070453
-0.0707799792 6.1362491548 0.2130538821
-0.0612145253 4.7471782565 0.1694330722
-0.0542051643 3.8052338362 0.139143303
-0.0524722151 3.5684209317 0.1313387156
-0.0482334904 2.9181014746 0.1100541279
-0.0450047888 2.3736832291 0.0927471593
-0.044360932 2.2448976338 0.0887506306
-0.04423647 2.216624245 0.0878707692
-0.0436141938 2.0935414732 0.0840858296
-0.0427653976 1.9077627361 0.0785839111

-0.0870921016 13.4945958853 0.4787070453


-0.0707799792 6.1362491548 0.2130538821
-0.0612145253 4.7471782565 0.1694330722
-0.0542051643 3.8052338362 0.139143303
-0.0524722151 3.5684209317 0.1313387156
-0.0482334904 2.9181014746 0.1100541279
-0.0450047888 2.3736832291 0.0927471593
-0.044360932 2.2448976338 0.0887506306
-0.04423647 2.216624245 0.0878707692
-0.0436141938 2.0935414732 0.0840858296
-0.0427653976 1.9077627361 0.0785839111
disable

disable
disable
enable
enable
enable

IEC 60044-6

elogram for IEEE C57.13 metering CT


r\MS Word Files\New MSWord files-2009\L&T Karnataka\TECHNICAL\Reports-2016\CT-Test report\DG-1 PROTECTION (R).xml

disable
1

IEC 60044-6

C
sed by CT Analyzer

Lp Ip IST ICT Ls RCT


S1
(Vc) IL Iex
Uc IEddy
Lmain
RH Zb UCT
Reddy
(VB)

S2
Np Ns
Phase Uc/Ict [] Flux remanence [Vs] L [H] UCrect [V]

89.2739028931 0.824272275 0.1064277068 228.9024200439


88.8474731445 0.8241072893 0.1726934165 225.385345459
88.3064880371 0.823723197 0.2783503532 223.1636962891
87.6548614502 0.8210306168 0.4292111993 221.3395996094
86.7572631836 0.8205115795 0.6549025774 219.1846008301
85.3750915527 0.8202056289 1.0043808222 216.4618530273
83.2679672241 0.8169471025 1.5453928709 213.1461791992
80.3290634155 0.8111311793 2.3926222324 209.5831451416
76.5385742188 0.800342977 3.6780252457 205.7085723877
71.8808822632 0.7843964696 5.6581864357 201.3056793213
66.4835357666 0.759521544 8.7114982605 195.9565734863
59.1779251099 0.7126615047 14.7008895874 187.2423706055
53.1093101501 0.6499776244 22.6008434296 176.940826416
48.8458251953 0.5829096437 31.1053009033 166.0349731445
46.1460189819 0.5171853304 39.1742935181 154.4549560547
44.4638442993 0.4514378905 46.4857635498 142.3053741455
43.5567893982 0.390067637 51.674030304 130.3720245361
44.5185165405 0.3421790302 54.1935081482 120.5095596313
44.6426200867 0.3087361455 55.6556167603 112.6843643188
45.3876914978 0.244680658 56.7319107056 96.4159698486
47.2314033508 0.1837020516 53.8040733337 78.932800293
49.885925293 0.1304169148 49.0120315552 61.5796699524
53.1146736145 0.0891111866 43.5138893127 46.0741386414
52.1373291016 0.1104772985 39.3349304199 37.8221435547
57.5082931519 0.0547225289 31.9615879059 21.0735816956
61.7315750122 0.0274881609 26.4407482147 11.7415771484
64.8178024292 0.0136419302 22.2191848755 6.5434703827
67.0242919922 0.0069786501 18.7790317535 3.6461496353
68.6877441406 0.00361356 15.8291988373 2.0309035778
70.1831741333 0.00163918 12.646695137 1.0004003048
70.8996353149 0.00103132 10.992436409 0.630179584
71.6779327393 0.0006069 8.9429330826 0.348534286
72.8988876343 0.00031093 7.0646452904 0.1941920221
75.1316146851 0.00018012 5.4039058685 0.1081933379
79.6108322144 0.00031093 3.8898983002 0.0602841415
Phase Uc/Ict [] Flux remanence [Vs] L [H] UCrect [V]

1
Ratio Error Graph

-1 60 -60
-1 60 -60
-1 60 -60
15VA
7.5V
A

50% 100% 150% 200% 3.75


250%
VA
1.88
VA

I-pn [%]

Phase Displacement Graph

15VA
7.5V
A

50% 100% 150% 200% 3.75


250%
VA
1.88
VA

I-pn [%]

50% 100% 120% 200%


-0.216 -0.187 -0.18 !-0.160
-0.216 -0.187 -0.180 -0.160
-0.141 -0.125 -0.12 -0.11
-0.141 -0.125 -0.120 -0.110
-0.069 -0.065 -0.064 -0.062
-0.069 -0.065 -0.064 -0.062
-0.059 -0.055 -0.054 -0.053
-0.059 -0.055 -0.054 -0.053

50% 100% 120% 200%


4.83 3.48 3.13 !2.24
4.83 3.48 3.13 2.24
4.04 3.1 2.87 2.23
4.04 3.10 2.87 2.23
4.35 3.51 3.31 2.75
4.35 3.51 3.31 2.75
3.67 2.97 2.8 2.36
3.67 2.97 2.80 2.36

Phase Uc/Ict [] Flux remanence [Vs] L [H] UCrect [V]


52.13733 0.1104773 39.33493 37.8221425
57.508295 0.05472253 31.9615875 21.0735825
61.731575 0.02748816 26.4407475 11.7415775
64.8178 0.01364193 22.219185 6.5434705
67.02429 0.00697865 18.77903125 3.64614975
68.687745 0.00361356 15.82919875 2.03090363
70.183175 0.00163918 12.646695 1.00040031
70.899635 0.00103132 10.99243625 0.63017956
71.677935 0.0006069 8.942933 0.34853428
72.89889 0.00031093 7.0646455 0.19419202
75.131615 0.00018012 5.403906 0.10819334
79.61083 0.00031093 3.88989825 0.06028414
Calculated I-s [A]
0.012339307
0.049964603
0.0999387801
0.199891597
0.2498687655
0.4997592568
0.999550283
1.199467659
1.2494467497
1.4993454218
1.9991459846

0.012339307
0.049964603
0.0999387801
0.199891597
0.2498687655
0.4997592568
0.999550283
1.199467659
1.2494467497
1.4993454218
1.9991459846
-1 PROTECTION (R).xml
IEC 60044-1 Excitation Graph
1000
RMS Voltage

100

10

1
0.00001 0.0001 0.001 0.01 0.1 1

0.1

0.01
RMS current

IEC 60044-6 Excitation Graph


1000
RMS Voltage

100
IEC 60044-6 Excitation Graph
1000

RMS Voltage 100

10

1
0.00001 0.0001 0.001 0.01 0.1 1

0.1

0.01
Peak Current

IEEE C57.13 Excitation Graph


1000
RMS Voltage

100

10

1
0.00001 0.0001 0.001 0.01 0.1 1

0.1

0.01
RMS Current

IEC 61869-2 Excitation Graph


1000
Rect Voltage

100

10
1000

Rect Voltage
100

10

1
0.00001 0.0001 0.001 0.01 0.1 1

0.1

0.01
RMS current
ion Graph
1000

100

10 Meas
Data
Ref Data
Low V
1
Data
0.1 1 10

0.1

0.01

ion Graph
1000

100
ion Graph
1000

100

10 Meas
Data
Ref Data
Low V
1
Data
0.1 1 10

0.1

0.01

on Graph
1000

100

Meas Data
10
Ref Data
Low V Data
Knee ANSI 30
1 Knee IEEE
1 10 C57.13

0.1

0.01

ion Graph
1000

100

10 Meas
Data
Ref Data
1000

100

10 Meas
Data
Ref Data
Low V
1
Data
0.1 1 10

0.1

0.01
1
Company Name:

Company Address:

Order Number:

#NAME? #NAME? #NAME?


#NAME? #NAME? #NAME? #NAME?
#NAME? #NAME?
#NAME? #NAME?

#NAME?
I-pn: #NAME? #NAME? #NAME?
I-sn: #NAME? #NAME? #NAME? #NAME? #NAME?
#NAME? #NAME? #NAME#NAME? #NAME? #NAME? #NAME?
#NAME? #NAME? #NAME#NAME? #NAME? #NAME? #NAME?
#NAME? #NAME? #NAME? #NAME? #NAME? #NAME?
#NAME? #NAME? #NAME? #NAME? #NAME? #NAME?
#NAME? #NAME? #NAME? #NAME? #NAME? #NAME?
#NAME? #NAME? #NAME? #NAME?
#NAME? #NAME? #NAME? #NAME?

#NAME? #NAME?
#NAME? #NAME? #NAME? #NAME? cos : #NAME? #NAME #NAME?
#NAME? #NAME? #NAME? #NAME? #NAME? #NAME?

#NAME?
#NAME #NAME? #NAME #NAME? #NAME? #NAME?
#NAME #NAME? #NAME #NAME? #NAME #NAME? #NAME #NAME? #NAME #NAME? #NAME #NAME?
#NAME #NAME? #NAME #NAME? #NAME #NAME? #NAME #NAME?
#NAME #NAME?

#NAME?
#NAME? #NAME? : #NAME? : #NAME? : #NAME? #NAME? #NAME?#NAME #NAME?
c : #NAME?

#NAME? Excitation curve data

1000

100
Es / V

10

0.1

0.01
0.00001 0.0001 0.001 0.01 0.1 1 10
le / A

Column K Row 28 Row 29 Series 2


0.00001 0.0001 0.001 0.01 0.1 1 10
le / A

Column K Row 28 Row 29 Series 2

#NAME?
#NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?
#NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?
#NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?
#NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?
#NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?
#NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?

#NAME?
#NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?
#NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?
#NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?
#NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?
#NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?
#NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME? #NAME?

Error borders according IEC 60044-1 at % of rated current


Mult.Factor 1 5 10 20 50 100 120 200
Ratio
0.60 Error Graph 0.30
Current deviation [%]

-0.60 -0.30
12.000

10.000

8.000
100% Load

50% Load
6.000

25% Load

4.000

2.000

0.000
0 5 10 15 20 25 30 35
% I-pn
Help:

This template is an application-specific tool extension of the CTA Remote Excel File Loader in-
tended to get a comprehensive, printable test report for all classes according IEC 60044-1, IEC
60044-6, IEC 61869-2 and IEEE C57.13 (ANSI) standards.These results are distributed over eight
worksheets.

The first section of each of those worksheets holds fields to insert your company's name and
address as well as an order number. Those fields are not write-protected and to your disposal.
All fields of the "... Test" sections, which hold test results, the "General Test Information" section
and the "Used Test Settings" section are write-protected and therefore not available for customer-
entries.The same applies to the sections "Excitation Curve Data", "Current Ratio Error in % at...",
"Phase Displacement in [min] at..." and the two charts "Excitation Curve Data" and "Ratio Error
Graph".

The cells below that are available for customer-specific calculations or data entries.

The section "Excitation Curve Data" holds a subset of the "CT Excitation Measured Data" table
from the "Report" worksheet with a maximum number up to 30 (U,I)-pairs.

The applied standard, CT's core type and accuracy class definition of the input fields on the "Re-
port" worksheet determine the curve progressions displayed in charts, the excitation tables, the
kneepoint voltages and currents, etc.

To perform measurements, select the worksheet "Data" and open the settings form by clicking
either the "Settings" button or the colored "TEST SETTINGS" area. Enter the necessary para-
meters and text in the fields of the "TEST SETTINGS" block and start the test.

To insert a company logo, or change it, respectively, click the Page Setup command from the
File pull-down menu. Go to the Header/Footer tab and click the Custom Header... button.
Position your cursor into the "Right section:" and click the Insert Picture button. Browse the
folder structure to the picture of your choice, select it and click Insert. The company logo can
then be viewed by clicking the Print Preview command from the File pull-down menu.

If you need to change the contents of protected cells, click the Protection | Unprotect Sheet
command from the Tools pull-down menu. A password is not required to remove the worksheet
protection.

Please note that you remove the worksheet protection at your own risk. OMICRON electronics
does not assume responsibility for a correct operation if you edit initially protected parameters.
The same applies if you carry out modifications at the cell-specific VBA code.

Você também pode gostar