CALCULO DE LA CARGA INSTALADA:

Ambientes Area en m2
rea techada del 1 Piso 92
rea techada del 2 Piso 92
rea techada del 3 Piso 92
rea techada de azotea 50
Total: 326

CARGA INSTALADA

Carga Unitaria Carga


AMBIENTES rea techada (m2) (W/m2) Instalada (KW)

1er Piso 92 20 1.84


2do Piso 92 20 1.84
3er Piso 92 20 1.84
Azotea 50 20 1.00

Total: 326 6.52

MXIMA DEMANDA

Factor de Mxima demanda


TOTAL CARGA Factor de Mxima demanda
AMBIENTES INSTALADA (KW) demanda
simultaneidad para solicitar
(KW)
(KW) (KW)

1er Piso 1.84 0.80 1.47


2do Piso 1.84 0.80 1.47
3er Piso 1.84 0.80 1.47
Azotea 1.00 0.80 0.80

SUBTOTAL 5.22 0.70 3.65


CONDUCTOR ALIMENTADOR DE TODA LA INSTALACION 2_1x120mm2 N2XH CON LLAVE TERMICA 3x250 A

MXIMA DEMANDA DIVERSIFICADA: 3.65 KW


Corriente de diseo

M .D M .D.
I I
V Cos V cos 3

INSTALACION

C1: ALUMBRADO
1 piso TD-1 C2: TOMACORRIENTE
TOTAL
C1: ALUMBRADO
2 PISO TD-3 C2: TOMACORRIENTES
TOTAL
C1: ALUMBRADO
3 PISO TD-4 C2: TOMACORRIENTES
TOTAL
C1 ALUMBRADO
AZOTEA TD-6 C2: TOMACORRIENTES
TOTAL

TABLERO GENERAL
TOTAL
M .D.
cos 3

Demanda unitaria Factor de Mxima demanda


Numero Voltaje (KV) Cos
(W) simultaneidad (KW)

13.00 72.00 1.00 0.94 0.22 0.9


17.00 250.00 0.50 2.13 0.22 0.9
. 3.06 0.22 0.9
17.00 72.00 1.00 1.22 0.22 0.9
18.00 250.00 0.50 2.25 0.22 0.9
3.47 0.22 0.9
16.00 72.00 1.00 1.15 0.22 0.9
15.00 250.00 0.50 1.88 0.22 0.9
3.03 0.22 0.9
6.00 72.00 1.00 0.43 0.22 0.9
10.00 250.00 1.00 2.50 0.22 0.9
2.93 0.22 0.9

5.22 0.22 0.90


I (A) 25% I (A) Id (A)

4.73 4.73
10.73 10.73
15.46 3.86 19.32
6.18 6.18
11.36 11.36
17.55 4.39 21.93
5.82 5.82
9.47 9.47
15.29 3.82 19.11
2.18 2.18
12.63 12.63
14.81 3.70 18.51

15.23 3.81 19.03


Caida de tension

L R20 (W/ 0.0175


V k Id R
S 40 k 2

INSTALACION

C1: ALUMBRADO
1 piso TD-1 C2: TOMACORRIENTE
TOTAL
C1: ALUMBRADO
2 PISO TD-3 C2: TOMACORRIENTES
TOTAL
C1: ALUMBRADO
3 PISO TD-4 C2: TOMACORRIENTES
TOTAL
C1 ALUMBRADO
AZOTEA TD-6 C2: TOMACORRIENTES
TOTAL

TABLERO GENERAL
TOTAL
Llave
Tipo de S (mm2) linea
Id (A) L (m) S (mm2) V (V) termomag
conductor tierra
netica
4.73 25.00 2.50 1.65 1% TW 2x15 A
10.73 25.00 4.00 2.35 1% TW 2x20 A
19.32 10.00 4.00 1.69 1% TW 2x25 A 6.00
6.18 25.00 4.00 1.35 1% TW 2x15 A
11.36 25.00 4.00 2.49 1% TW 2x20 A
21.93 3.50 4.00 0.67 0% TW 2x25 A 6.00
5.82 25.00 4.00 1.27 1% TW 2x15 A
9.47 25.00 4.00 2.07 1% TW 2x20 A
19.11 7.00 4.00 1.17 1% TW 2x32 A 10.00
2.18 5.00 2.50 0.15 0% TW 2x15 A
12.63 10.00 4.00 1.10 1% TW 2x20 A
18.51 14.00 4.00 2.27 1% TW 2x25 A 6.00

19.03 10.50 4.00 1.75 1% THW 2x50 A 10.00