Escolar Documentos
Profissional Documentos
Cultura Documentos
Electrical Apparatus
2
240-93
Figure 3.
ASL in NEMA style fuse mount.
FAULT CURRENT
LINE
RESTORED
AUTO-RECLOSER
CONTACTS
SECTIONALIZER OPENS
LATERAL LINE
SECTIONALIZER LATERAL ISOLATED
OPERATION
SECOND
FIRST PULSE PULSE DEAD
NOTED AND STORED NOTED PERIOD
IN SECTIONALIZER NOTED
MEMORY
Figure 4.
Operational sequence of a sectionalizer isolating a lateral line fault (sequence shows a 2 count device).
3
Automatic Sectionalizing Link
APPLICATION The fuse link at the head of the lateral The main advantage of the ASL is
or branch coordinates with the recloser that transient fault interruption can
The Automatic Sectionalizing Link can with some limitations. There is a max- be effectively achieved with the pole-
be installed in existing cutouts at the imum current beyond which the fuse mounted auto-recloser or multishot
head of the laterals or branches on a link will operate before the recloser has circuit breaker down to the minimum
distribution system, downstream from a chance to clear a temporary fault. operating current of the ASL, without
an auto-recloser or multi-shot circuit Under high transient fault conditions, the necessity for delayed trips. Auto-
breaker. Figure 5 illustrates a typical such as a lightning strike, nuisance fuse reclosers can therefore be set for
protection scheme used on a distribu- link blowing can result. instantaneous trip, minimizing system
tion system, utilizing ASLs instead of damage. Fault withstand is not an
the typically used fuse links. Most distribution circuits have multiple issue as the short time-current with-
expulsion fuse links in series. Due to
The most common type of overhead stand rating of the ASL will be greater
the non-current limiting nature of
primary distribution circuit is the four- than the available fault current except
expulsion fuse links, there is a maxi-
wire multi-grounded neutral system. A for a few possible applications next to
mum current at which coordination can
main line (feeder) with a recloser near a substation.
be achieved. Above this current it is
its head originates from a substation likely that both the upstream and In the case of low ground fault currents,
with several laterals tapped off this downstream expulsion fuse links will by selecting an ASL with minimum
feeder. Often further branch lines are operate at the same time. pick-up current at or below the minimum
tapped off the lateral which in turn trip current of the auto-recloser,
supply power to end users. Transform- By replacing a fuse with an ASL at where possible, these ground faults
ers are individually fused and fuses at the head of a lateral or branch, as will result in operation of the ASL on the
the head of branches and laterals illustrated in Figure 5, the coordination faulty lateral, thus preventing lockout
provide further sectionalizing of the range is extended to the maximum of the recloser and wide loss of supply
system. short time withstand rating of the ASL. to customers. To achieve the optimum
ASLs have no time-current character-
In general, the individual transformer level of coordination and to take
istics and are easily applied between
fuse links are sized to operate on all account of tolerances, the lowest rat-
two fault-interrupting protective
selected overcurrents without causing ing of ASL should be 80% of the
devices. Accordingly, they are easily
the recloser to operate. Operation of ground fault or sensitive ground fault
added to an existing system or to an
this fuse link affects a small number settings, dependent on the scheme
existing coordination plan when addi-
of customers making such operations employed.
tional circuit sectionalizing is needed.
easily justifiable.
RECLOSER
CUTOUT
4 COUNT
Figure 5.
Typical distribution system using ASLs.
4
240-93
5
Automatic Sectionalizing Link
TABLE 2
Ordering Codes: First Select the Part Code from the Table Below
Symbol
Voltage Product Pick-up Mounting Number System
Rating Type Current (A) Type of Counts Frequency Definition
15 Sectionalizer to
be used in 15 kV Cutouts
ASL Automatic
Sectionalizing Links
112 Pick-up current set
at 112 Amperes
C Type C is for NEMA
interchangeable cutout
mount
2 Number of current
shots unit will accept
before operating
(1, 2, or 3)
US US for 60 Hz
(no mark for 50 Hz)
15 ASL 112 C 2 US Total Part No.*
* In the Example above the Part Number would be 15ASL112C2US
6
2005 Cooper Power Systems or its affiliates.
Bussmann is a registered trademark of the Cooper Industries, Inc.
IEEE Standard C37.63, IEEE Standard C62.11 and IEEE C57.109 are 1045 Hickory Street
trademarks of the Institute of Electrical and Electronics Engineer, Inc. Pewaukee, WI 53072 USA
ANSI is a registered trademark of the American National Standards Institute. www.cooperpower.com
MI
7/05