Você está na página 1de 8

Fusing Equipment

Electrical Apparatus

Automatic Sectionalizing Link 240-93


GENERAL
The Cooper Bussmann Automatic
Sectionalizing Link (ASL) is a self-
contained circuit-opening device that,
when used with either an upstream
auto-recloser or multi-shot circuit
breaker, sectionalizes and isolates the
network thereby reducing the number
of customers disconnected due to
permanent faults.
The ASL differentiates between
transient and permanent faults, greatly
reducing the number of outages caused
by transient no-damage faults such as
lightning.
Using the Bussmann ASL, an econom-
ical system can be installed utilizing
most existing expulsion dropout fuse
mounts in conjunction with multishot
circuit breakers or auto-reclosers.
DESIGN FEATURES
Increased network
reliability with an overall
reduction in cost
The ASL differentiates between
transient and permanent faults,
providing automatic disconnection of
permanent faults. By virtually eliminating
nuisance outages, significant reduction
in system operating costs are
achieved.
Comprehensive range of Figure 1.
Cooper Bussmann Automatic Sectionalizing Link (ASL).
ratings
ASL is available with voltage ratings up
to 38 kV, pick-up currents from 16 to
320 A and 1, 2 or 3 count options. Fits into existing Silent, reliable drop-out
Color bands are located on the body expulsion fuse mounts action
of the ASL for easy identification of The ASL C-type version fits all the High output force of the replacement
count and pick-up rating. common NEMA interchangeable actuator provides rapid, reliable drop
mounts such as Coopers Type L out action, even under icing, to provide
cutout. They swing down upon opera- visual indication of a faulty line. Dead
tion, providing visual indication of a time operation ensures no sparks,
fault downstream. This allows for fast ionized gas or contact erosion,
system restoration. ASLs are installed minimizing fire risks.
and removed using existing pole head
equipment. Detailed installation Immunity to magnetizing
instructions are available with every inrush current
ASL and also upon request. The logic circuit ignores the first half-
cycle current and reacts only if both
the negative and positive half cycles
exceed the pick-up current. As magne-
tizing inrush currents are largely
unidirectional, they are ignored by
the logic circuit.

July 2005 New Issue 1


Printed in U.S.A.
Automatic Sectionalizing Link

Surge and EMI protection COLOR BAND


INDICATES
Electronics are shielded from magnetic NUMBER OF COUNTS UPPER
field influences by being enclosed 1 COUNT BROWN CONTACT
within the conducting tube. The ASL is 2 COUNT NO BAND
tested to withstand lightning impulse 3 COUNT GREEN PULL
currents and to be immune to radio RING
frequency interference.
Self powered, no
maintenance
The logic circuit and actuator are
powered by two current transformers
during the passage of fault current.
No additional power source is
required, and no maintenance is
needed.
Low threshold for hold off ACTUATOR
current (250 milliamps)
COLOR BAND
A return to load current following a INDICATES PICK-UP
temporary fault will not result in a CURRENT
mistaken count by the ASL. 16 A YELLOW
24 A RED
CONSTRUCTION 40 A BLUE
The ASL houses a fully encapsulated 56 A GREEN DIMENSIONS
logic circuit within its main conductive 80 A BLACK
Voltage Length
tube powered by encapsulated small 112 A WHITE Rating In (mm)
current transformers mounted on the LOWER
160 A BROWN CONTACT 15 kV 11.50 (292)
outside of the tube. This ensures that 224 A ORANGE 27 kV 14.96 (380)
the electronic circuitry is free from 320 A NO BAND 38 kV 18.43 (468)
electrical interference as the tube acts
as an effective Faraday cage. The Figure 2.
logic circuit is also environmentally ASL Construction Detail.
protected to prevent moisture ingress.
Energy derived from the current
transformers under fault conditions OPERATION The logic circuit is inhibited from
allows the ASL to be self powered to operating the latch mechanism until
ensure operation even when there is Under normal load conditions the the upstream recloser has tripped for
no initial load current. electronics remain inert. However, the second time and the line current
should the line current increase above has fallen to a value less than
In appearance the upper and lower a pre-set value (the pick-up current)
contacts of the ASL resemble that of 250 mA (the hold-off current) for a
the logic circuit activates. period of at least 0.1 seconds.
the fuse holder it replaces. Instead of a
fuse element melting to release the The upstream auto-recloser then The ASL thus operates during the
holder from the mount, operation is opens, temporarily removing the fault dead time of the upstream protective
accomplished by discharging a capac- from the line. The ASLs logic circuit, device and does so quickly, without
itor into a small actuator (or striker) powered by an internal capacitor, stores sparks or ionized gas emission and
which unlatches the holder tube and the incident for approximately 25 sec- without contact erosion.
causes it to swing down in the manner onds (the reclaim time).
of an expulsion fuse holder (See The logic circuit is designed to inhibit
When the upstream device recloses, response to transformer magnetizing
Figure 3). typically 3 to 10 seconds later, if the inrush current surges. Thus ASLs on
The actuator is an extremely reliable fault current is no longer present, the non-faulted lateral lines are not spuri-
device with high mechanical advan- ASL will ignore the incident after the ously operated by such currents, fol-
tage, providing rapid, reliable drop-out reclaim time and eventually reverts to lowing repeated operations of the
action even under icing conditions. an inert state again. However, if the upstream recloser.
The actuator is completely safe to fault current (i.e. current above the
handle and there are no special stor- pick-up current) is still present, the In practice, any lateral line fault
age or transporting requirements. logic circuit will decide that this repre- condition that persists for a time long
sents a permanent fault on the lateral enough to operate the upstream
The ASL is reset by installing a line and for a two-count unit will pre- recloser will operate the ASL, isolating
replacement actuator and re-inserting pare to de-latch. the lateral. Any transient or no-damage
the holder into its mount. The resetting current will be ignored (See Figure 4).
operation takes less time than that
needed to change a blown expulsion
fuse link.

2
240-93

LATCHED POSITION DE-LATCHED POSITION

Figure 3.
ASL in NEMA style fuse mount.

FAULT CURRENT

LEVEL OF CURRENT MAGNETIC


IN THE MAIN LINE INRUSH
CURRENT
NOMINAL LOAD
CURRENT

LINE
RESTORED
AUTO-RECLOSER
CONTACTS

CLOSED OPEN OPEN CLOSED


TRIP TRIP
RECLOSE
RECLOSE

SECTIONALIZER OPENS
LATERAL LINE
SECTIONALIZER LATERAL ISOLATED
OPERATION
SECOND
FIRST PULSE PULSE DEAD
NOTED AND STORED NOTED PERIOD
IN SECTIONALIZER NOTED
MEMORY

Figure 4.
Operational sequence of a sectionalizer isolating a lateral line fault (sequence shows a 2 count device).

3
Automatic Sectionalizing Link

APPLICATION The fuse link at the head of the lateral The main advantage of the ASL is
or branch coordinates with the recloser that transient fault interruption can
The Automatic Sectionalizing Link can with some limitations. There is a max- be effectively achieved with the pole-
be installed in existing cutouts at the imum current beyond which the fuse mounted auto-recloser or multishot
head of the laterals or branches on a link will operate before the recloser has circuit breaker down to the minimum
distribution system, downstream from a chance to clear a temporary fault. operating current of the ASL, without
an auto-recloser or multi-shot circuit Under high transient fault conditions, the necessity for delayed trips. Auto-
breaker. Figure 5 illustrates a typical such as a lightning strike, nuisance fuse reclosers can therefore be set for
protection scheme used on a distribu- link blowing can result. instantaneous trip, minimizing system
tion system, utilizing ASLs instead of damage. Fault withstand is not an
the typically used fuse links. Most distribution circuits have multiple issue as the short time-current with-
expulsion fuse links in series. Due to
The most common type of overhead stand rating of the ASL will be greater
the non-current limiting nature of
primary distribution circuit is the four- than the available fault current except
expulsion fuse links, there is a maxi-
wire multi-grounded neutral system. A for a few possible applications next to
mum current at which coordination can
main line (feeder) with a recloser near a substation.
be achieved. Above this current it is
its head originates from a substation likely that both the upstream and In the case of low ground fault currents,
with several laterals tapped off this downstream expulsion fuse links will by selecting an ASL with minimum
feeder. Often further branch lines are operate at the same time. pick-up current at or below the minimum
tapped off the lateral which in turn trip current of the auto-recloser,
supply power to end users. Transform- By replacing a fuse with an ASL at where possible, these ground faults
ers are individually fused and fuses at the head of a lateral or branch, as will result in operation of the ASL on the
the head of branches and laterals illustrated in Figure 5, the coordination faulty lateral, thus preventing lockout
provide further sectionalizing of the range is extended to the maximum of the recloser and wide loss of supply
system. short time withstand rating of the ASL. to customers. To achieve the optimum
ASLs have no time-current character-
In general, the individual transformer level of coordination and to take
istics and are easily applied between
fuse links are sized to operate on all account of tolerances, the lowest rat-
two fault-interrupting protective
selected overcurrents without causing ing of ASL should be 80% of the
devices. Accordingly, they are easily
the recloser to operate. Operation of ground fault or sensitive ground fault
added to an existing system or to an
this fuse link affects a small number settings, dependent on the scheme
existing coordination plan when addi-
of customers making such operations employed.
tional circuit sectionalizing is needed.
easily justifiable.

POLE MOUNTED AUTO RECLOSER


TRANSFORMER

RECLOSER

CUTOUT

4 COUNT

3 COUNT ASL ASL 2 COUNT ASL ASL 2 COUNT ASL


LATERAL
ASL
ASL 2 COUNT ASL

MAIN OVERHEAD LINE OR FEEDER

Figure 5.
Typical distribution system using ASLs.

4
240-93

SELECTION Number of Counts Load Breaking


When selecting an ASL for a specific The number of counts to operate is The ASL is designed for deadbreak
installation, a number of factors factory preset. The ASL should be operation only. If the unit is manually
should be considered. chosen with at least one less count opened under live line conditions, an
than the up-stream recloser. For exam- arc will be drawn across the contacts
System Voltage ple, a 4 shot recloser should be exactly as in the case of an expulsion
The ASL is insensitive to system matched with a maximum of a 3 count fuse. If the current is low enough and
voltage, and being in effect a solid ASL downstream. To reduce the if conditions are favorable, the arc may
conductor, has no insulation require- number of recloser operations, a 2 extinguish as the unit drops down to
ments. Hence the sole criterion count ASL unit would be the most the isolating position. Therefore, the
concerning voltage is that the ASL fits common. Where ASLs are used in same operating procedures will apply
into a mount of the appropriate voltage series, the downstream ASL should for the ASL as for expulsion fuses with
rating, meeting the dielectric values be one less count than the upstream regard to breaking load.
required (BIL and power frequency). ASL. 1 count ASLs are also available NEMA interchangeable mounts are
for applications such as underground
Pick-Up Current fitted with hooks, for use with a load-
cables where transient faults are break tool. To open the ASL under
(Actuating Current) unlikely. Choice of an ASL over a load, use an appropriate load break
fuse eliminates the coordination
For optimum coordination the lowest tool designed for use with interchange-
issues discussed previously.
rating of the ASL should be 80% of able cutouts and follow instructions
the minimum ground fault or sensitive Maximum Fault Current provided with the tool.
ground fault settings allowing auto-
recloser operations. Be sure the ASL has a short time-
current withstand equal to or greater
However, depending on the position of than the available fault current (See
the ASL, it must be chosen to withstand Table 1 Performance Characteristics).
the possible transformer magnetizing
inrush currents. Continuous Current
When a recloser switches in and out The ASLs continuous current rating
attempting to clear a fault on one must be equal to or greater than the
branch circuit, all the non-faulted system load current. This is normally
circuits experience surge currents not an issue, as all ASLs are rated at
due to magnetizing inrush determined 200 A continuous.
by the transformer KVA. Reclaim Time
The anti-magnetizing inrush circuit in The reclaim time is the time that the
the ASL ensures against spurious memory of the ASL retains prior counts
operation, provided both positive and and is nominally 25 seconds. However
negative going half cycles are below in practice this time will vary with the
the pick-up value. If the ratio of trans- value and duration of fault current
former capacity/pick-up settings is pulses. For high values of fault current,
made too small, then even the smaller particularly where the upstream
loops of the highly asymmetrical recloser is operating in delayed
magnetizing inrush current may be mode, the ASL reclaim time may
of sufficient value to override the extend by up to 15% while for instan-
inhibiting circuit and allow operation taneous tripping operation at lower
to occur. values of current near the pick-up
IEEE Standard C37.63 for mainline value, reclaim times will be reduced.
sectionalizers allows a ratio of 1.6:1 For details see Performance
for pick-up current to total available Characteristics. For these reasons it
transformer current. is recommended that the maximum
reclose time (dead time between
Present experience suggests that this shots) of the recloser be 15 seconds,
is satisfactory for most applications of as this must be shorter than the ASL
2 and 3 count ASLs. For 1 count ASLs reset time for correct coordination. If
and applications where the transformer the auto-recloser is operating in the
KVA is dominated by one large trans- instantaneous region of the trip char-
former, (i.e. more than 60% of the acteristic near the pick-up current of
total), a ratio of 2.5:1 is recommended. the ASL, the auto-recloser dead time
For example: for 2 and 3 count ASLs should not exceed 10 seconds.
a 40 A pick-up setting allows for maxi-
mum installed transformer capacity of Overvoltage Withstand
up to 25 A. Even though the maximum Cooper Bussmann ASLs have been
loading on the line might be 5 A, a small tested to withstand 65 kA lightning
percentage of the maximum available, surge current as defined in IEEE
magnetizing inrush dependent on the Standard C37.63, IEEE Standard
installed KVA is the determining factor. C62.11 and IEC 60099 for surge
arresters.

5
Automatic Sectionalizing Link

Dead Time PERFORMANCE TESTS are inappropriate, only those applica-


ble have been carried out.
The time for an ASL to drop open to a The only fully applicable standard for
safe isolating distance (from the ASLs is the Electricity Supply Industry In addition to those listed in the
instant when the line goes dead after (ESI) standard 41-27 Part 5. There Performance Characteristics, a number
the correct number of counts) is also exists an ANSI Standard of other tests have been performed to
approximately 250 milliseconds. To C37.63, which covers traditional demonstrate the suitability of the ASL.
prevent any possibility of the unit enclosed tank-type sectionalizers. In These include load make, mechanical
attempting to open under live condi- verifying the performance of the ASL, operation, icing, salt fog (corrosion)
tions the upstream recloser should as listed in the Performance and other environmental tests including
have a dead line time of not less than Characteristics, these two standards thermal cycling, rain-UV, and ozone.
0.5 seconds. have provided the basis for evaluation. Details of all these tests are available
As many of the test clauses of C37.63 on request.
Every ASL is functionally tested at
TABLE 1 least twice during manufacture.
Performance Characteristics Current pulses of 10% below nominal
pick-up value and 10% above nominal
Rated maximum voltage: 15 kV (110 kV BIL), 27 kV (150 kV BIL), 38 kV (170 kV BIL) pick-up value are applied. ASLs are
Maximum thermal rating: 200 A checked to ensure that they do not
react to the lower value but operate at
Rated frequency: 60 Hz the higher value.
Pick-up current: 60 Hz operation (+/-10%) 16, 24, 40, 56, 80, 112, 160, 224, 320 A
ORDERING INFORMATION
Number of counts: 1, 2 or 3
To order a Cooper Bussmann
Hold off current: 250 milliamperes Automatic Sectionalizing Link, first
choose the voltage rating and pick-up
Current withstand: Continuous 200 A
current from available options in
Momentary 1st peak 16,000 A Table 1. Then build part number as
shown in the example in Table 2.
1 sec 8,000 A Symmetrical
The part number for a replacement
10 sec 2,600 A Symmetrical
actuator is E2906.
Reclaim times: 25 seconds (+/- 15%)
Contact your Cooper Power Systems
Response time: representative for further information.
Minimum duration of current pulse 30 msec @ 1.5 X pick up setting
for overcurrent memory response: (reclaim time 10 seconds)
60 msec @ 1.3 X pick up setting
(reclaim time 15 seconds)
Circuit breaker dead time range: 0.5 sec to 15 sec
Minimum time of dead line after fault pulse for count: 80 msec to 120 msec
Ambient temperature limits: -22F to 176F
Surge current withstand: 65 kA per ANSI C37.63, IEEE Standard 62.11 and
IEC EN 60099-1

TABLE 2
Ordering Codes: First Select the Part Code from the Table Below
Symbol
Voltage Product Pick-up Mounting Number System
Rating Type Current (A) Type of Counts Frequency Definition
15 Sectionalizer to
be used in 15 kV Cutouts
ASL Automatic
Sectionalizing Links
112 Pick-up current set
at 112 Amperes
C Type C is for NEMA
interchangeable cutout
mount
2 Number of current
shots unit will accept
before operating
(1, 2, or 3)
US US for 60 Hz
(no mark for 50 Hz)
15 ASL 112 C 2 US Total Part No.*
* In the Example above the Part Number would be 15ASL112C2US

6
2005 Cooper Power Systems or its affiliates.
Bussmann is a registered trademark of the Cooper Industries, Inc.
IEEE Standard C37.63, IEEE Standard C62.11 and IEEE C57.109 are 1045 Hickory Street
trademarks of the Institute of Electrical and Electronics Engineer, Inc. Pewaukee, WI 53072 USA
ANSI is a registered trademark of the American National Standards Institute. www.cooperpower.com
MI
7/05

Você também pode gostar