MULTIPLE OF TRIP RATING PLUG

10000
1000

2000

3000

4000

5000
6000
7000
8000
9000
100

200

300

400

500
600
700
800
900
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90
1000 1000
900 900
800 Reduced Energy Let-through Pickup (RELT), Pickup range 1.5X to 800
700 15X Trip Rating Plug maximum instantaneous pickup, and additional clearing time may 700
600 be required for very low instantaneous pickup under self power. 600
500 .1 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7 500

400 400
2X Trip Rating Plug
300 300

10X Trip Rating Plug


200 200

10mS additional at
minimum possible Time band additional time may be
100 RELT pick up calculated via the following formula; 100
90 (Minimum Pickup Additional t = 21.25 18x%Sensor 90
80 80
70
X trip rating plug. 1000
70
60
(56% sensor) Up to 119% sensor 60
TIME IN SECONDS

TIME IN SECONDS
50 .1 50
.09
40 Adjustable in 0.5X steps .08 40
.07
30 .06 30
.05

20 .04 20

.03 0mS additional at 119% sensor

10 .02 10
9 9
8 8
7 7
6 6
5 .01 5
.1 .2 .3 .4 .5 .6 .7 .8 .9 1 2 3 4 5 6 7
4 4

3 3

2 2

Maximum Adjustable Instantaneous Pickup,


Based on Nominal Frame for AKR and WavePro
1 1
.9 .9
.8
Frame = 800 1600 2000 3200 4000 5000 .8
.7 AKR/WavePro with Short Time ON 15 15 15 13 9 7 .7
DES-101B

DES-101B
.6 .6
AKR/WavePro with Short Time OFF 10 10 10 10 9 7
.5 .5
.4 .4

.3 .3

.2 .2

.1 .1
.09 58ms Maximum .09
.08 Clear Time .08
.07
Application .07
.06 .06
Determines
.05 End of Curve .05

.04 .04

.03 .03

.02 .02

12ms
Commit Time
.01 .01
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090
100

200

300

400

500
600
700
800
900
1000

2000

3000

4000

5000
6000
7000
8000
9000
10000

MULTIPLE OF TRIP RATING PLUG

Low-Voltage Circuit Breakers DES-101B


Frames 800-5000A AKR & WavePro
EntelliGuard TU trip unit for Adjustable Instantaneous Minimum
ANSI Trip Conversion Kits Pickup 2X Rating Plug
800-5000A Low Voltage Power Circuit Breaker
Adjustable Instantaneous RELT Minimum
All Voltages: 600 Vac and below UL 1066 Stored Energy Mechanism Pickup 1.5X Rating Plug
This curve also applies to GE EntelliGuard TU Trip Circuit Breakers Note: When the trip is provided with
Retrofit kits used in various brands and models of Instantaneous Zone-Selective-Interlocking (I-ZSI)
UL 1066 or ANSI rated Low Voltage Power Circuit Adjustable Selective Instantaneous Trip the Instantaneous may be shifted to a commit
Breakers. However the clearing time may be different.
The RELT clearing time will be the same as the circuit
Reduced Energy Let Through time (bottom of band) of 67mS and a clear time
breaker's original instantaneous clearing time. The Instantaneous Trip (RELT) of 127mS.
adjustable Selective Instantaneous clearing time will
be 1/2 cycle slower than the original circuit breaker's
Curves apply at 60 Hertz
instantaneous clearing time.
and from -20C to 55C circuit breaker ambient temperature.