Document Name: ASTM E119: Standard Test Methods for Fire Tests of
Building Construction and Materials

CFR Section(s): 49 CFR 238 Appendix B(a)(1)(v)

Standards Body: American Society for Testing and Materials

Official Incorporator:
THE EXECUTIVE DIRECTOR
OFFICE OF THE FEDERAL REGISTER
WASHINGTON, D.C.
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.aslm.org) for the latest information

cd.ID.tf Designation: E 119 - OOa


An American National Standard

.ull
INTERNAnONAL

Standard Test Methods for


Fire Tests of Building Construction and Materials1
This standard is issued under the fixed designation E 119; the number immediately following the designation indicates the year of
Original adoption or, in the case of revision. the year of last revisioll. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapprovaJ.

This standard lias been approved for use by agellcies of the Departmellt of Defellse.

INTRODUCTION

The performance of walls, columns, floors, and other building members under fire exposure
conditions is an item of major importance in securing constructions that are safe, and that are not a
menace to neighboring structures nor to the public. Recognition of this is registered in the codes of
many authorities, municipal and other. It is important to secure balance of the many units in a single
building, and of buildings of like character and use in a community; and also to promote uniformity
in requirements of various authorities throughout the country. To do this it is necessary that the
fire-resistive properties of materials and assemblies be measured and specified according to a conunon
standard expressed in terms that are applicable alike to a wide variety of materials, situations, and
conditions of exposure.
Such a standard is found in the methods that follow. They prescribe a standard exposing fire of
controlled extent and severity. Performance is defined as the period of resistance to standard exposure
elapsing before the first critical point in behavior is observed. Results are reported in units in which
field exposures can be judged and expressed.
The methods may be cited as the "Standard Fire Tests," and the performance or exposure shall be
expressed as "2-h," "6-h," "~-h," etc.
When a factor of safety exceeding that inherent in the test conditions is desired, a proportional
increase should be made in the specified time-classification period.

1. Scope period of exposure and shall not be construed as having


1.1 The test methods described in this fire-test-response determined suitability for use under other conditions or after
standard are applicable to assemblies of masonry units and to fire exposure.
composite assemblies of structural materials for buildings, 1.3 This standard is llsed to measure and describe the
including bearing and other walls and partitions, columns, response of materials, products, or assemblies to heat and
girders, beams, slabs, and composite slab and beam assemblies flame under controlled conditions, but does not by itself
for floors and roofs. They are also applicable to other assem- incorporate all factors requ.ired for fire hazard or fire risk
blies and structural units that constitute permanent integral assessment of the materials, products or assemblies under
parts of a finished building. actual fire conditions..
1.2 It is the intent that classifications shall register compara- 1.4 These test methods prescribe a standard fire exposure
ti ve performance to specific fire-test conditions during the for comparing the test results of building construction assem-
blies. The results of these tests are one factor in assessing
predicted fire performance of building construction and assem-
I These test methods are under the jurisdiction of ASTM Committee E05 on Fire blies. Application of these test results to predict the perfor-
Standards and are the dllect responsibility of Subcommittee E05.11 on Construction mance of actual building construction requires the evaluation
Assemblies.
Current edition approved July 10, 2000. Published October 2000. Originally of test conditions.
published as C 19-19171'. Last previous edition E 119 - 00. 1.5 The values stated in inch-pound units are to be regarded
These test methods, of which the present standard represents a revision, were as the standard. The values given in parentheses are for
prepared by Sectional Committee on Fire Tests of Materials and Construction, under
the joint sponsorsbip of the National Bureau of Standards, the ANSI Fire Protection
information only.
Group, and ASTM, functioning under the procedure of the American National 1.6 This standard does not purport to address all of the
Standards Institute. safety concems, if any, associated with its use. It is the

Copyright ASTM Intemational. 100 Barr Harbor Drive, PO Box 0700, West Conshohockan, PA 194213-2959, United Stales.

1
E119-00a
responsibility of the user of this standard to establish appIV- 4.4.1 Full information as to performance of assemblies
priate safety and health practices and determine the applica- constructed with components or lengths other than those tested.
bility of regulatory limitations prior to use. 4.4.2 Evaluation of the degree by which the assembly
1.7 The text: of this standard references notes and footnotes contributes to the fire hazard by generation of smoke, toxic
which provide explanatory material. These notes and footnotes gases, or other products of combustion.
(excluding those in tables and figures) shall not be considered 4.4.3 Measurement of the degree of control or limitation of
as requirements of the standard. the passage of smoke or products of combustion through the
assembly.
2. Referenced Documents 4.4.4 Simulation of the fire behavior of joints between
2.1 ASTM Standards: building elements such as 'fioor-wall or wall-wall, etc., connec-
C 569 Test Method for Indentation Hardness of Preformed tions.
Thermal Insulations2 4.4.5 Measurement of flame spread over surface of tested
E 176 Terminology of Fire Standards' element.
4.4.6 The effect of fire endurance of conventional openings
3. Terminology in the assembly, that is, electrical receptacle outlets, plumbing
3.1 Definitions-For definitions of terms found in this test pipe, etc., unless specifically provided for in the construction
method, refer to Terminology E 176. tested.
4. Significance and Use CONTROL OF FIRE TESTS
4.1 This test method is intended to evaluate the duration for
5. Time~ Temperature Curve
which the types of assemblies noted in 1.1 contain a fire, retain
their structural integrity, or exhibit both properties dependent 5.1 The conduct of fire tests of materials and construction
upon the type of assembly involved during a predetermined test shall be controlled by the standard time-temperature curve
exposure. shown in Fig. 1. The points on the curve that determine its
4.2 The test exposes a specimen to a standard fire controlled character are:
to achieve specified temperatures throughout a specified time 1000F (538C) at5 min
1300F (704C) at 10 min
period. When required, the fire exposure is followed by the 1550F (843C) at 30 min
application of a specified standard fire hose stream. The test 1700F (927C) at 1 h
provides a relative measure of the fire-test-response of compa- 1850F (1010C) at 2 h
2000F (1093C) at 4 h
rable assemblies under these fire exposure conditions. The 2300F (1260C) at 8 h or over
exposure is not representative of all fire conditions because
conditions vary with changes in the amount. nature and 5.2 For a closer definition of the time-tempemture curve, see
distribution of fire loading, ventilation, compartment size and Appendix Xl.
configuration, and heat sink characteristics of the compartment. NOTE i-Recommendations for Recording Fuel FLow to Furnace
Variation from the test conditions or specimen construction, Burners-The following provides guidance on the desired characteristics
such as size, materials, method of assembly, also affects the
fire-test-response. For these reasons, evaluation of the variation 240 J
is required for application to construction in the field. V- 1200
4.3 The test standard provides for the following:
100 0
V
4.3.1 For walls, partitions, and fioor or roof assemblies: V- 1000
4.3.1.1 Measurement of the transmission of heat. u
4.3.1.2 Measurement of the transmission of hot gases 1L.1601
through the assembly, sufficient to ignite cotton waste. ~
of - 800 ~
~ "0
4.3.1.3 For load bearing elements, measurement of the load
e~I~O
e-
carrying ability of the test specimen during the test exposure. - 600 1::
B ~
4.3.2 For individual load bearing assemblies such as beams
and columns: = 60
E , 400
"
!
4.3.2.1 Measurement of the load carrying ability under tlle
test exposure with consideration for the end support conditions
(that is, restrained or not restrained).
'" 40 ) 200

4.4 The test standard does not provide the following:


)0 o
2 6 B

2 Discontilllled---See 1987 Annual Book of ASTM Standards, Vol 04.06. Time, h


~ Amilia! Book Of ASTM Standards, Vol 04.07. FIG. 1 Time-Temperature Curve

2
E 119-00a
of instrumentation for recording the flow of fuel to the furnace burners. 6.2 The temperatures shall be read at intervals not exceed-
Fuel flow data may be useful for a furnace heat balance analysis, for ing 5 min during the first 2 h, and thereafter the intervals shall
measuring the effect of furnace or control changes, and for comparing the
not exceed 10 min.
performance of assemblies of different properties in the fire endurance
test 4
6.3 The accuracy of the furnace control shall be such that
the area under the time-temperature curve, obtained by aver-
Record the integrated (cumulative) flow of gas (or other fuel) to the
furnace burners at 10 min. 20 min, 30 min. and every 30 min thereafter or aging the results from the pyrometer readings, is within 10 %
more frequently. Total gas consumed during the total test period is also to of the corresponding area under the standard time-temperature
be determined. A recording flow meter has advantages over periodic curve shown in Fig. 1 for fire tests of 1 h or less duration,
readings on an instantaneous or totalizing flow meter. Select a measuring within 7.5 % for those over 1 h and not more than 2 h, and
and recording system to provide flow rate readings accurate to within within 5 % for tests exceeding 2 h in duration.
5%.
Report the type of fuel, its higher (gross) heating value. and the fuel 7. Temperatures of Unexposed Surfaces of Floors, Roofs,
flow (corrected to standard conditions of 60 0 P (l6C) and 30.0 in. Hg) as
Walls, and Partitions
a function of time.
7.1 Temperatures of unexposed surfaces shall be measured
6. Furnace Temperatures with thermocouples or thermometers (Note 4) placed under
dry, felted pads meeting the requirements listed in Annex AI.
6.1 The temperature fixed by the curve shall be the average
The wire leads of the thermocouple or the stem of the
temperatme from not fewer than nine thermocouples for a
thermometer shall have an immersion under the pad and be in
fioor, roof, wall, or partition and not fewer than eight thermo-
contact with the unexposed surface for not less than 3th in. (89
couples for a structural column. Furnace thermocouples shall
mm). The hot junction of the thermocouple or the bulb of the
be symmetrically disposed and distributed to show the tem-
thermometer shall be placed approximately under the center of
perature near all parts of the sample, the thermocouples being
the pad. The outside diameter of protecting or insulating tubes,
enclosed in protection tubes of such materials and dimensions
and of thermometer stems, shall be not more than 5116 in. (8
that the time constant of the protected thermocouple assembly
mm). The pad shall be held firmly against the surface, and shall
lies within the range from 5.0 to 7.2 min (Note 2). The exposed
fit closely about the thermocouples or thermometer stems.
length of the pyrometer tube and thermocouple in the furnace Thermometers shall be of the partial-immersion type, with a
chamber shall be not less than 12 in. (305 mm). It is not length of stem, between the end of the bulb aod the inunersion
prohibited to use other types of protecting tubes or pyrometers mark, of 3 in. (76 mm). The wires for the thermocouple in the
that, under test conditions, give the same indications as the length covered by the pad shall be not heavier thao No. 18 B
above standard within the limit of accuracy that applies for & S gage (0.04 in.) (1.02 mm) and shall be electrically
furnace-temperature measurements. insulated with heat-resistant and moisture-resistant coatings.
6.1.1 For floors and columns, the junction of the thermo-
couples shall be placed 12 in. (305 mm) away from the NOTE 3-For the purpose of testing roof assemblies, the unexposed
surface shall be defined as the surface exposed to ambient air.
exposed face of the sample at the beginning of the test and,
NOTE 4-Under certain conditions it may be unsafe or impracticable to
during the test, shall not touch the sample as a result of its use thermometers.
deflection.
6.1.2 For walls and partitions, the thermocouples shall be 7.2 Temperatures shall be recorded at not fewer than nine
placed 6 in. (152 mm) away from the exposed face of the points on the surface. Five of these shall be symmetrically
sample at the beginning of the test, and shall not touch the disposed, one to be approximately at the center of the speci-
men, and four at approximately the center of its quarter
sample dming the test, in the event of deflecton.
sections. The other fom shall be located to obtain representa-
NOTE 2-A typical thermocouple assembly meeting these time constant tive information on the performance of the construction under
requirements may be fabricated by fusion-welding the twisted ends of No. test. The thermocouples shall not be located closer to the edges
18 gage Chro.mel-Alumel wires, mounting the leads in porcelain insulators of the test specimen than one and one-half times the thickness
and inserting the assembly so the thermocouple bead is Ylln. (13 mm)
of the construction, or 12 in. (305 mm). Exception: those cases
from the sealed end of a standard weight nominal lh.-in. iron, steel, or
InconeP pipe. The time constant is either measured or calculated from
in which there is an element of the construction that is not
knowledge of its physical and thermal properties. The time constant for otherwise represented in the remainder of the test specimen.
this and for several other thermocouple assemblies was measured in The thermocouples shall not be located opposite or on top of
1976.6 beams, girders, pilasters, or other structural members if tem-
peratures at such points will be lower than at more represen-
tative locations. The thermocouples shall not be located over
fasteners such as screws, nails, or staples that will be higher or
.j Hannathy, T. Z., "Desigu of Fire Test Furnaces," Fire Tecluwlog)" Vol. 5, No.
lower in temperature than at a more representative location if
2, May 1969, pp. 146--150; Seigel, L. G.," Effects of Furnace Design on Fire
Endurance Test Results," Fire Test Peifonnance, ASTM STP 464, ASTM, 1970, pp. the aggregate area of any part of such fasteners on the
57-67; and Williamson, R B., and Buchanan, A. H., "A Heat Balance Analysis of unexposed surface is less than 1 % of the area within any 6-in.
the Standard Fire Endurance Test" (152-mm) diameter circle, unless the fasteners extend through
5 Inconel is a registered tradenome of INCO Alloys, Inc., 3800 IDverside Dr.,
P. O. Box 1958, Huntingdon, WV 25720.
the assembly.
,; Supporting data are available from ASTM Headquarters. Request 7.3 Temperature readings shall be taken at intervals not
RR: E05--1001. exceeding IS min until a reading exceeding 212F (100C) has

3
E119-00a
been obtained at anyone point. Thereafter the readings may be C correction in the same units as I,
taken more frequently at the discretion of the testing body, hut I indicated fire-resistllI1ce period,
the intervals need not be less than 5 min. A area under the curve of indicated average furnace temperature
for the first three fourths of the indicated period.
7.4 Where the conditions of acceptance place a limitation on
A, area under the standm'd furnace curve for the same part of the
the rise of temperature of the unexposed sUlface, the tempera- indicated period, and
ture end point of the fire endurance period shall be determined L lag correction in the same units as A and A s(54 C1Ph or 30"Ch
by the average of the measurements taken at individual points; (3240"Fmin or I800Cmin).
except that if a temperature rise 30 % in excess of the specified
8.5 Unsymmetrical wall assemblies are tested with either
limit occurs at anyone of these points, the remainder sha11 be
side exposed to the fire, and the report shall indicate the side so
ignored and the fire endurance period judged as ended.
exposed. When both sides are tested, the report then shall so
indicate the fire endurance classification applicable to each
CLASSIFICATION AS DETERMINED BY TEST
side.
8. Report of Results TEST SPECIMEN
8.1 Results shall be reported in accordance with the perfor- 9. Test Specimen
mance in the tests prescribed in these test methods. They shall
9.1 The test specimen shall be truly representative of the
be expressed in time periods of resistance, to the nearest
constlUction for which classification is desired, as to matelials,
integral minute. Reports shall include observations of details of
workmanship. and details sllch as dimensions of parts, and
the behavior of the material or construction during the test and
shall be built under conditions representative of those obtaining
after the furnace fire is extinguished, including information on
as practically applied in building construction and operation.
deformation, spalling, cracking, burning of the specimen or its
The physical properties of the materials and ingredients used in
component parts, continuance of fiaming, and production of
the test specimen shall be determined and recorded.
smoke.
8.2 Reports of tests involving wall, fioor, beam, or ceiling
9.2 The size and dimensions of the test specimen specified
herein shall apply for rating constructions of dimensions within
constructions in which restraint is provided against expansion,
the range employed in buildings. When the conditions of use
contraction, or rotation of the construction shall describe the
limit the construction to smaller dimensions, the dimensions of
method used to provide this restraint.
the specimen shall be reduced proportionately for a test
8.2.1 Describe the physical details of the restraint system
qualifying them for such restricted use.
and provide information to define the longitudinal and rota-
9.3 Specimens designed with a builtup roof shall be tested
tional resistance of the test specimen by the restraint system.
with a roof covering of 3ply. l5lb (6.Skg) type felt, with not
8.2.2 Describe the restraint conditions with regard to the
more than 120 Ib (54 kg) per square (100 ft2(9 m 2)) of hot
free movement of the test specimen prior to encountering
mopping asphalt without gravel surfacing. Tests of assemblies
resistance to expansion, contraction or rotation.
with this covering do not preclude the field use of other
8.3 Reports of tests in which other than maximum load
coverings with a larger number of plys of felt, with a greater
conditions are imposed shall fully define the conditions of
amount of asphalt or with gravel surfacing.
loading used in the test and shall be designated in the title of
9.4 Roofing systems designed for other than the use of
the report of the test as a restricted load condition.
built-up roof coverings shall be tested using materials and
8.4 When the indicated resistance period is 1;2 h or over,
details of construction representative of field application.
determined by the average or maximum temperature rise on the
unexposed surface or within the test sample, or by failure under CONDUCT OF FIRE TESTS
load, a correction shall be applied for variation of the furnace
exposure from that prescribed, where it will affect the classi- 10. Fire Endurance Test
fication, by multiplying the indicated pedod by two thirds of 10.1 Continue the fire endurance test on the specimen with
the difference in area between the curve of average furnace its applied load, if any, until failure occurs, or until the
temperature and the standard curve for the first three fourths of specimen has withstood the test conditions for a period equal to
the period and dividing the product by the area between the that herein specified in the conditions of acceptance for the
standard curve and a base line of 6soF (20C) for the same part given type of construction.
of the indicated period, the latter area increased by 54Ph or 10.2 Continue the test beyond the time the fire endurance
30Ch (3240Fmin or lS00Cmin) to compensate for the classification is determined when the purpose in doing so is to
thermal lag of the furnace thermocouples during the first part of obtain additional data.
the test. For fire exposure in the test higher than standard, the
11. Hose Stream Test
indicated resistance period shall be increased by the amount of
the correction and be similarly decreased for fire exposure 11.1 Where required by the conditions of acceptance, the
below standard. hose stream test shall be conducted to SUbject the specimen
described in 11.2 or 11.3 to the impact, erosion, and cooling
NOTE 5-The correction can be expressed by the following equation: effects of a hose stream.
C ~ 2l(A - AJf3(A, + L) 11.1.1 Exemption-The hose stream test shall not be re-
quired in the case of constructions having a resistance period,
where:
indicated in the fire endurance test, of less than 1 h.

4
<0 E 119-00a
11.2 The hose stream test shall be conducted on a duplicate played during the test, an air stream shall not be directed across
test specimen. the surface of the specimen.
11.2.1 The duplicate specimen shall be exposed to the 12.1.1 Prior to fire test, condition constructions with the
effects of the hose stream immediately after being subjected to objective of providing a moisture condition within the speci-
a fire endurance test for a time period of one-half the fire men representative of that in similar construction in buildings.
endurance classification period determined from the fire endur- For purposes of standardization, this condition is established at
ance test on the initial specimen. equilibrium resulting from drying in an ambient atmosphere of
11.2.2 The length of time that the duplicate specimen is 50 % relative humidity at 73"F (Note 6). However, with some
subjected to the fire endurance test shall not exceed I h. constructions, it is difficult or impossible to achieve such
11.3 Optional Program-As an alternative procedure, con- uniformity. Accordiugly, where this is the case, specimeus are
duct the hose stream test on the initially tested specimen tested when the dampest portion of the structure, the portion at
immediately following its fire endurance test. 6-in. (152-mm) depth below the surface of massive construc-
11.4 In conducting the hose stream test, direct the hose tions, has achieved a moisture content corresponding to drying
stream first at the middle and then at ali parts of the exposed to equilibrium with air in the range of 50 to 75 % relative
face of the specimen. Aay changes in direction shall be made humidity at 73 5"F (23 3 "C). In the event that specimens
slowly. dried in a heated building fail to meet these requirements after
11.5 Stream Equipment and Details-The stream shall be a 12-month conditioning period, or in the event that the nature
delivered through a 2\6-in. (64-mm) hose discharging through of the construction is such that it is evident that drying of the
a National Standard Playpipe of corresponding size equipped specimen interior is prevented by hermetic sealing, these
with a Ills-in. (28.5-mm) discharge tip of the standard-laper moisture condition requirements are waived, and the specimen
smooth-bore pattern without shoulder at the orifice. The water tested when its strength is at least equal to its design strength.
pressure and duration of application shall be as prescribed in 12.1.2 Avoid drying procedures that will alter the structural
Table 1. or fire endurance characteristics of the specimen from those
11.6 Nozzle Distance-The distance between the tip of the produced as the result of drying in accordance with procedures
nozzle and the center of the exposed surface shali be deter- given in 12.1.1.
mined by the deviation from normal between the center of the 12.1.3 Within 72 h prior to the fire test information on the
nozzle axis and the center of the exposed surface of the actual moisture content and distribution within the specimen
specimen. The distance shall be 20 ft (6 m) when the axis shall be obtained. Include this information in the test report
through the center of the nozzle is normal to the center of the (Note 7).
exposed surface. This distance shall be decreased by an amount
NOTE 6-A recommended method for determining the relative humid-
equal to 1 ft (305 = ) for each 10" of deviation from the ity within a hardened concrete specimen with electric sensing elements is
normal. described in Appendix I of the paper by Menzel, C. A" "A Method for
Determining the Moisture Condition of Hardened Concrete in Terms of
12. Protection and Conditioning of Test Specimen Relative Humidity," Proceedings, ASTM, Vol 55, 1955, p. 1085. A similar
procedure with electric sensing elements is permitted to be used to
12.1 Protect the test specimen during and after fabrication to
determine the relative humidity within fire test specimens made with other
assure its quality and condition at the time of test. It shall not materials.
be tested until its final strength has been attained, and, until an With wood constrllctions. the moisture meter based on the electrical
air-dry condition has been achieved in accordance with the resistance method can be used. when appropriate, as an alternative to the
requirements given in 12.1.1 through 12.1.3. Protect the testing relative humidity method to indicate when wood has attained the proper
equipment and sample undergoing the fire test from any moisture content. Electrical methods are described on pages 320 and 321
condition of wind or weather, that is capable of affecting of the 1955 edition of the Wood Handbook of the Forest Products
Laboratory, U.S. Department of Agriculture. The relationships between
results. The ambient air temperature at the begianing of the test
relative humidity and moisture content are given by the graphs in Fig. 23
shali be within the range of 50 to 90"F (10 to 32"C). The on p. 327. They indicate that wood has a moisture content of 13 % at a
velocity of air across the unexposed surface of the sample, relative hwnidity of 70 % for a temperature of 70 to 80F (21 to 27C).
measured just before the test begins, shali not exceed 4.4 ft (1.3 NOTE 7-If the moisture condition of the fire test assembly is likely to
m)/s, as determined by an anemometer placed at right angles to change drastically from the 72-h sampling time prior to test, the sampling
the unexposed surface. When mechanical ventilation is em- should be made not later than 24 h prior to the test.

13. Precision and Bias 7

TABLE 1 Conditions For Hose Stream Test 13.1 No comprehensive test program has been conducted to
Duration of develop data on which to derive statistical measures of
Water Pressure at. Application, mini repeatability (within-laboratory vatiability) and reproducibility
Resistance Period Base of k~~ZZle, pSI 100 ft2(9 m2)
() exposed area (among-laboratory variability). The limited data indicate that
there is a degree of repeatability and reproducibility for some
8 h and over 45 (310) 6
4 h and over if less than 8 h 45 (310) 5 types of assemblies. Results depend on factors such as the type
2 h and over if less than 4 h 30 (207) 2'h
11/2 h and over if less than 2 h 30 (207) 1'h
1 h and over if less than 1 'h h 30 (207) 1
Less than 1 h, if desired 30 (207) 1 1 Supporting data are available from ASTM Headquarters. Request RR: E05-
1003.

5
.E119-00a
of assembly and materials being tested. the characteristics of TESTS OF NONBEARING WALLS AND PARTITIONS
the furnace, the type and level of applied load, the nature of the
17. Size of Specimen
boundary conditions (restraint and end fixity), and details of
workmanship during assembly. 17.1 The area exposed to fire shall be not less than 100 fe(9
m 2 ), with neither dimension less than 9 ft (2.7 m). Restrain the
TESTS OF BEARING WALLS AND PARTITIONS test specimen on all four edges.
18. Conditions of Acceptance
14. Size of Specimen 18.1 Regard the test as successful when the following
14.1 The area exposed to fire shall be not less than 100 fr(9 conditions are met:
m 2), with neither dimension less than 9 ft (2.7 m). The test 18.1.1 The wall or partition has withstood the fire endurance
specimen shall not be restrained on its vertical edges. test without passage of flame or gases hot enough to ignite
cotton waste, for a period equal to that for which classification
15. Loading is desired.
18.1.2 The wall or partition has withstood the fire and hose
15.1 Throughout the fire endurance and hose stream tests, stream test as specified in 10, without passage of flame, of
apply a superimposed load to the specimen to simulate a gases hot enough to ignite cotton waste, or of passage of water
maximum load condition. This load shall be the maximum load from the hose stream. The assembly shall be considered to have
condition allowed under nationally recognized structural de- failed the hose stream test if an opening develops that permits
sign criteria unless limited design criteria are specified and a a projection of water from the stream beyond the unexposed
corresponding reduced load is applied. A double wall assembly surface during the time of the hose stream test.
shall be loaded during the test to simulate field use conditions, 18.1.3 Transmission of heat through the wall or partition
with either side loaded separately or both sidcs together (Note during the fire endurance test shall not have been such as to
8). The method used shall be reported. raise the temperature on its unexposed surface more than
250F (139C) above its initial temperature.
Nal'E 8-The choice depends on the intended use, and whether the load
on the exposed side, after it has failed, will be transferred to the unexposed TESTS OF COLUMNS
side. If, in the intended use, the load from the structure above is supponed
19. Size of Specimen
by both walls as a unit and would be or is transferred to the unexposed side
in case of collapse of the exposed side, both walls should be loaded in the 19.1 The length of the column exposed to fire shall be not
test by a single unit. If, in the intended use the load from the structure less than 9 ft (2.7 m). Apply the contemplated details of
above each wall is supported by each wall separately, the walls should be connections and their protection, if any, according to the
loaded separately in the test by separate load sources. If the intended use methods of field practice. The column shall be vertical during
of the construction system being tested involved situations of both loading the fire exposure.
conditions described above, the walls should be loaded separately in the
test by separate load sources. In tests conducted with the walls loaded 20. Loading
separately the condition of acceptance requiring the walls to maintain the 20.1 Throughout the fire endurance test, expose the column
applied load shall be based on the time at which the first of either of the
to fire on all sides and load it with a superimposed load to
walls fail to sustain the load.
simulate a maximum load condition. This load shall be the
16. Conditions of Acceptance maximum load condition allowed under nationally recognized
structural design criteria unless limited design criteria are
16.1 Regard the test as successful if the following condi- specified and a conesponding reduced load is applied. Make
tions are met: provision for transmitting the load to the exposed portion of the
16.1.1 The wall or partition shall have sustained the applied column without increasing the effective column length.
load during the fire endurance test without passage of flame or 20.2 As an optional procedure, subject the column to 1314
gases hot enough to ignite cotton waste, for a period equal to times its designed working load before the fire endurance test
that for which classification is desired. is undertaken. The fact that such a test has been made shall not
be construed as having had a deleterious effect on the fire
16.1.2 The wall or partition shall have sustained the applied
endurance test performance.
load during the fire and hose stream test as specified in Section
11, without passage of flame, of gases hot enough to ignite 21. Condition of Acceptance
cotton waste, or of the hose stream. The assembly shall be 21.1 Regard the test as successful if the column sustains the
considered to have failed the hose stream test if an opening applied load during the fire endurance test for a period equal to
develops that permits a projection of water from the stream that for which classification is desired.
beyond the unexposed surface during the time of the hose
stream test. ALTERNATIVE TEST OF PROTECTION FOR
STRUCTURAL STEEL COLUMNS
16.1.3 Transmission of heat through the wall or partition
during the fire endurance test shall not have been such as to 22. Application
raise the temperature on its unexposed surface more than 22.1 This alternative test procedure is used to evaluate the
250 0 P (139C) above its initial temperature. protection of steel columns without application of design load,

6
cO E119-00a
provided that the protection material is not required by design restraint applicable to floor and roof constructions and individual beams in
to function structurally in resisting loads. actual building construction.
27.3 One fire endurance classification shall be developed
23. Size and Characteristics of Specimen from tests of assemblies not restrained against thermal expan-
23.1 The length of the protected column shall be at least 8 sion based upon the conditions of acceptance specified in
ft (2.4 m). The column shall be vertical during the fire 32.1.1 and 32.1.2.
exposure. 27.4 Individual unrestrained beam classifications are devel-
23.2 Restrain the applied protection material againstlongi- oped for beams from restrained assembly tests and from
tudinal temperature expansion greater than that of the steel unrestrained assembly tests, using the conditions of acceptance
column with rigid steel plates or reinforced concrete attached specified in 40.1.1 and 40.1.2, or 40.1.3.
to the ends of the steel column before the protection is applied.
The size of the plates or amount of concrete shall provide direct 28. Size and Characteristics of Spechnen
bearing for the entire transverse area of the protection material. 28.1 The area exposed to fire shall be not less than 180
23.3 Provide the ends of the specimen, including the means ff(16 m2 ) with neither dimension less than 12 ft (3.7 m).
for restraint, with thermal insulation to limit direct heat transfer Structural members, if a part of the construction under test,
from the furnace. shall lie within the combustion chamber and have a side
clearance of not less than 8 in. (203 mm) from its walls.
24. Temperature Measurement 28.2 Specimens representing forms of construction in which
24.1 Measure the temperature of the steel with not fewer restraint to thermal expansion occurs shall be so restrained in
than three thermocouples at each offour levels. The upper and the furnace.
lower levels shall be 2 ft (0.6 m) from the ends of the steel
column, and the two intermediate levels shall be equally 29. Loading
spaced. For situations in which the protection material thick- 29.1 Throughout the fire endurance test, apply a superhn-
ness is not uniform along the specimen length, at least one of posed load to the specimen to simulate a maximum load
the levels at which temperatures are measured shall include the condition. This load shall he the maximum load condition
point of minimum cover. Place the thermocouples at each level allowed under nationally recognized structural design criteria
to measure temperatures of the component elements of the steel unless limited design criteria are specified and a corresponding
section.
reduced load is applied.
25. Exposure to Fire
30. Temperature Measurement
25.1 Throughout the fire endurance test expose the speci-
30.1 For specimens employing structural members (beams,
men to fire on all sides for its full length.
open-web steel joists, etc.) spaced at more than 4 ft (1.2 m) on
26. Conditions of Acceptance centers, measure the temperature of the steel in these structural
members with four thermocouples at each of three or more
26.1 Regard the test as successful if the transmission of heat sections equally spaced along the length of the members. For
through the protection during the period of fire exposure for situations in which the protection material thickness is not
which classification is desired does not raise the average uniform along the specimen length, at least one of the sections
(arithmetical) temperature of the steel at anyone of the four at which temperatures are measured shall include the point of
levels above lOOQoF (538C), or does not raise the temperature minimum cover.
above 1200"F (649"C) at anyone of the measured points. 30.2 For specimens employing structural members (beams,
open-web steel joists, etc.) spaced at 4 ft (1.2 m) on center or
TESTS OF FLOORS AND ROOFS
less, measure the temperature of the steel in these structural
27. Application members with four thermocouples placed on each member. No
more than four members shall be so instrumented. Place the
27.1 This procedure is applicable to floor and roof assem- thermocouples at locations, such as at midspan, over joints in
blies with or without attached, furred, or suspended ceilings the ceiling, and over light fixtures. It shall not be required that
and requhes application of fire exposure to the underside of the all four thermocouples be located at the same section.
specimen under test. 30.3 Locate thermocouples as shown in Fig. 2: two on the
27.2 Two fire endurance classifications shall be developed bottom of the bottom flange or chord, one on the web at the
from tests of assemblies restrained against thermal expansion; center, and one on the top flange or chord.
a restrained assembly classification based upon the conditions 30.4 For reinforced or prestressed concrete structural mem-
of acceptance specified in 31.1.1 and 31.1.2 and where bers. locate thermocouples on each of the tension reinforcing
applicable, to the conditions in 31.1.3 through3I.1.5; and an elements, unless there are more than eight such elements, in
unrestrained assembly classification based upon the conditions which case place thermocouples on eight elements selected in
of acceptance specified in 32.1.1 and 32.1.2 and where such a manner as to obtain representative temperatures of all
applicable, to the conditions in 32.1.3 through 32.1.6. the elements.
NOTE 9-See Appendix X3, which is intended as a guide for assisting 30.5 For steel floor or roof units locate four thermocouples
the user of this test method in detennining the conditions of thermal on each section (a section to comprise the width of one unit),

7
E 119-00a
31.1.2 Transmission of heat through the specimen during
the classification period shall not have been such as to raise the
average temperature on its unexposed surface more than 250F
(l39'C) above its initial temperature.
31.1.3 For specimens employing steel structural members
(beams, open-web steel joists, etc.) spaced more than 4 ft (1.2
Section A m) on centers, the assembly shall achieve a fire endurance
classification on the basis of the temperature criteria specified
in 32.1.3 for assembly classifications up to and includulg 1 h.
For classifications greater than 1 h, the above temperature
criteria shall apply for a period of one half the classification of
the assembly or 1 h, whichever is the greater.
31.1.4 For specimens employing steel structural members
(beam, open-web steel joists, etc.) spaced 4 ft (1.2 m) orless on
centers, the assembly shall achieve a fire endurance classifica-
tion on the basis of the temperature criteria specified in 32.1.4
Sect ion B for assembly classifications up to and including 1 h. For
FIG. 2 Typical Thermocouple Distributions classifications greater than 1 h, the above temperature criteria
shall apply for a period of one half the classification of the
assembly or 1 h, whichever is the greater.
one on the bottom plane of the unit at an edge joint, one on the 31.1.5 For specimens employing conventionally designed
bottom plane of the unit remote from the edge, one on a side concrete beams, spaced more than 4 ft (1.2 m) on centers, the
wall of the unit, and one on the top plane of the unit. The assembly shall achieve a fire endurance classification on the
thermocouples shall be applied, where practicable, to the basis of the temperature criteria specified in 32.1.5 for assem-
surface of the units remote from fire and spaced across the bly classifications up to and including 1 h. For classifications
width of the unit. No more than four nor less than two sections greater than 1 h, the above temperature criteria shall apply for
need he so instrumented in each representative span. Locate the a period of one half the classification of the assembly or I h,
groups of four thennocouples in representative locations. whichever is the greater.
Typical thermocouple locations for a unit section are shown in
Fig. 3. 32. Conditions of Acceptance-Unrestrained Assembly
32.1 In obtaining an unrestrained assembly classification,
31. Conditions of Acceptance-Restrained Assembly the following conditions shall be met:
31.1 In obtaining a restrained assembly classification, the 32.1.1 The specimen shall have sustained the applied load
following conditions shall be met: during the classification period without developing unexposed
31.1.1 The specimen shall have sustained the applied load surface conditions which will ignite cotton waste.
during the classification period without developing unexposed 32.1.2 The transmission of heat through the specimen dur-
surface conditions which will ignite cotton waste. ing the classification period shall not have been such as to raise
the average temperature on its unexposed surface more than
250'F (1 39'C) above its initial temperature.
32.1.3 For specimens employing steel structural members
(beams, open-web steel joists, etc.), spaced more than 4 ft (1.2
m) on centers, the temperature of the steel shall not have
Fl",ted Urlil exceeded 1300F (704C) at any location during the classifi-
cation period nor shall the average temperature recorded by
four themlOcouples at any section have exceeded l100F
(593'C) during the classification period.
32.1.4 For specimens employing steel structural members
(beams, open-web steel joists, etc.), spaced 4 ft (1.2 m) or less
on center, the average temperature recorded by all joist or beam
thermocouples shall not have exceeded 1100F (593C) during
Cellular Unil
the classification period.
32.1.5 For specimens employing conventionally designed
concrete structural members (excluding cast-in-place concrete

9 cr6
roof or floor slabs having spans equal to or less than those
c=Jlr tested), the average temperature of the tension steel at any
section shall not have exceeded SOoop (427C) for cold-drawn
Cellwcr Unil prestressing steel or llOOF (593'C) for reinforcing steel
FIG. 3 Typical Location of Thermocouples during the classification period.

8
~Dn., E 119 - OOa
C1ijffl1
32.1.6 For spechnens employing steel floor or roof units in 32.1.3 of one half the classification of the assembly or I h,
intended for use in spans greater than those tested, the average whichever is the greater.
temperature recorded by all thermocouples located on anyone
span of the floor or roof units shall not have exceeded noaop ALTERNATIVE CLASSIFICATION PROCEDURE
(593C) during the classification period. FOR LOADED BEAMS

33. Report of Results 38. Application


33.1 The fire endurance classification of a restrained assem- 38.1 An individual unrestrained beam classification is de-
bly shall be reported as that developed by applying the veloped for beams from tests as part of a floor or roof assembly
conditions of acceptance specified in 31.1.1 and 31.1.2, and as described in Sections 27-30 (except 27.3) and from tests for
where applicable, to the conditions in 31.1.3 through 31.1.5. loaded restrained beams as described in Sections 34-36. The
33.2 The fire endurance classification of an unrestrained fire endurance classification so derived shall be applicable to
assembly shall be reported as that developed by applying the beams when used with a floor or roof construction which has
conditions of acceptance specified in 32.1.1 and 32.1.2 and, a comparable or greater capacity for heat dissipation from the
where applicable, to the conditions in 32.1.3 through 32.1.6. beam than the floor or roof with which it was tested. The fire
endurance classification developed by this test method shall not
TESTS OF LOADED RESTRAINED BEAMS be applicable to sizes of beams smaller than those tested.
34. Application 39. Temperature Measurement
34.1 An individual restrained beam classification is ob- 39.1 Measure the temperature of the steel in structural
tained by this procedure for loaded restrained beams based members with four thermocouples at three or more sections
upon the conditions of acceptance specified in 37. The fire equally spaced along the length of the members. For situations
endurance classification so derived shall be applicable to the in which the protection material thickness is not uniform along
beam when used with a floor or roof construction which has a the specimen length, at least one of the sections at which
comparable or greater capacity for heat dissipation from the temperatures are measured shall include the point of minimum
beam than the floor or roof with which it was tested. The fire cover.
endurance classification developed by this method shall not be 39.2 Locate the thermocouples as shown in Fig. 2: two on
applicable to sizes of beams smaller than those tested. the bottom of the bottom flange or chord, one on the web at the
center, and one on the bottom of the top flange or chord.
35. Size and Characteristics of Specimen
39.3 For reinforced or prestressed concrete structural mem-
35.1 The length of beam exposed to the fire shall be not less bers, locate thermocouples on each of the tension reinforcing
than 12 ft (3.7 m) and the member shall be tested in a elements unless there are more than eight such elements, in
horizontal position. which case place thermocouples on eight elements selected in
35.2 For specimens tested with a representative section of a such a manner as to obtain representative temperatures of all
floor or roof construction, such sections shall be not more than the elements.
7 ft (2.1 m) wide and sy=etrically located with reference to
the beam. 40. Conditions of Acceptance
35.3 Restrain the beam including that part of the floor or 40.1 In obtaining an unrestrained beam classification the
roof element forming the complete beam as designed (such as following conditions shall be met:
composite steel or concrete construction) against longitudinal 40.1.1 The specimen shall have sustained the applied load
thermal expansion in a manner simulating the restraint in the during the classification period.
construction represented. Do not support or restrain the perim- 40.1.2 For steel beams the temperature of the steel shall not
eter of the floor or roof element of the specimen, except that have exceeded 1300F (704C) at any location during the
part which forms part of a beam as designed. classification period nor shall the average temperature recorded
by four thermocouples at any section have exceeded 1l00F
36. Loading
(593"C) during this period.
36.1 Throughout the fire endurance test, apply a superim- 40.1.3 For conventionally designed concrete beams, the
posed load to the specimen to simulate a maximum load average temperature of the tension steel at any section shall not
condition. This load shall be the maximum load condition have exceeded 800F (427C) for cold-drawn prestressing steel
allowed under nationally recognized structural design criteria or 1100F for reinforcing steel during the classification period.
unless limited design criteria are specified and a corresponding
reduced load is applied. ALTERNATIVE TEST OF PROTECTION FOR SOLID
STRUCTURAL STEEL BEAMS AND GIRDERS
37. Conditions of Acceptance
37.1 The following conditions shall be met: 41. Application
37.1.1 The spechnen shall have sustained the applied load 41.1 This alternative test procedure is used to evaluate the
during the classification period. protection of steel beams and girders without application of
37.1.2 The specimen shall have achieved a fire endurance design load, provided that the protection is not required by
classification on the basis of the temperature criteria specified design to function structurally in resisting applied loads. The

9
AI1T~ E 119 - OOa
dlillf1
fire endurance classification so derived shall be applicable to 47. Temperature Performance of Protective Membranes
beams when used with a floor or roof construction which has
47.1 The temperature performance of protective membranes
a comparable or greater capacity for heat dissipation from the
shall be measured with thermocouples. the measuring junctions
beam than the floor or roof with which it is tested. The fire
of which are in intimate contact with the exposed surface of the
endurance classification developed by this test method shall not
elements being protected. The diameter of the wires used to
be applicable to sizes of beams smaller than those tested.
form the thermo-junction shall not be greater than the thickness
42. Size and Characteristics of Specimen of sheet metal framing or panel members to which they are
42.1 The length of beam or girder exposed to the fire shall attached and in no case greater than No. 18 B&S gage (0.040
be not less than 12 ft (3.7 m) and the member shall be tested in in.) (1.02 mm). The lead shall be electrically insulated with
a horizontal position. A section of a representative floor or roof heat-resistant and moisture-resistant coatings.
construction not less than 5 ft (1.5 m) wide, symmetrically 47.2 For each class of elements being protected, tempera-
located with reference to the beam or girder and extending its ture readings shall be taken at not fewer than five representa-
full length, shall be included in the test specimen. tive points. None of the thermocouples shall be located nearer
42.2 Restrain the applied protection material against longi- to the edges of the test assembly than 12 in. (305 mm). An
tudinal temperature expansion greater than that of the steel exception is made in those cases in which there is an element
beam or girder with rigid steel plates or reinforced concrete or feature of the construction that is not otherwise represented
attached to the ends of the steel beams before the protection in the test assembly. None of the thermocouples shall be
material is applied. Provide the ends of the specimen, including located opposite, on top of, or adjacent to fasteners such as
the means for restraint, with thermal insulation to limit direct screws, nails, or staples when such locations are excluded for
heat transfer from the furnace. thermocouple placement on the unexposed surface of the test
assembly in 7.2.
43. Temperature Measurement
47.3 Thermocouples shall be located to obtain information
43.1 Measure the temperature of the steel with not fewer
on the temperature at the interface between the exposed
than four thermocouples at each of four sections equally spaced
membrane and the substrate or element being protected.
along the length of the beam no nearer than 2 ft (0.6 m) from
the inside face of the furnace. For situations in which the 47.4 Temperature readings shall be taken at intervals not
protection material thickness is not uniform along the specimen exceeding 5 minutes.
length, at least one of the sections at which temperatures are
measured shall include the point of minimum cover. Place the 48. Conditions of Performance
thermocouples at each section to measure temperatures of the 48.1 Unless otherwise specified, the performance of protec-
component elements of the steel section. tive membranes shall be detennined as the time at which the
44. Conditions of Acceptance following conditions occur:
48.1.1 The average temperature rise of any set of thermo-
44.1 Regard the test as successful if the transmission of heat
through the protection during the period of fire exposure for couples for each class of element being protected is more than
which classification is desired does not raise the average 250'F (139"C) above the initial temperature, or
(arithmetical) temperature of the steel at anyone of the four 48.1.2 The temperature rise of anyone thermocouple of the
sections above lOOOF (538C), or does not raise the tempera- set for each class of element being protected is more than
ture above 1200'F (649'C) at anyone of the measured points. 325'F (181 'C) above the initial temperature.

PERFORMANCE OF 49. Report of Results


PROTECTIVE MEMBRANES IN WALL,
PARTITION, FLOOR, OR ROOF ASSEMBLIES 49.1 The protective membrane performance, for each class
of element being protected, shall be reported to the nearest
45. Application integral minute.
45.1 To detennine the thermal protection afforded by mem- 49.2 The test report shall identify each class of elements
brane elements in wall, partition, floor, or roof assemblies, the being protected and shall show the location of each thermo-
nonstructural performance of protecti ve membranes shall be couple.
obtained by this procedure. The performance of protective 49.3 The test report shall show the time-temperature data
membranes is supplementary information only and is not a recorded for each thermocouple and the average temperature
substitute for the fire endurance classification determined for the set of thermocouples on each element being protected.
elsewhere in this fire-test-response standard.
46. Size of Specimen 50. Keywords
46.1 The size of the specimen shall conform to 14.1 for 50.1 beams; building construction; building materials; col-
bearing walls and partitions, 17.1 for nonbearing wans and unms; fire; fire endurance; fire-rated assembly; fire-resistance;
partitions, or 28.1 for floors and roofs. fire-test-response standard; floors; walls

10
E 119-00a

ANNEX
(Mandatory Information)

AI. REQUIREMENTS FOR THERMOCOUPLE PADS

AI.l Asbestos Pads~Asbestos pads used in measurements demonstrated that a refractory fiber material designated
of temperature of unexposed surfaces of specimens shall be of Ceraform 126,8 placed with the softer surfaces in contact with
felted amosite asbestos free of organic additives and shall the thermocouple, may be substituted for the asbestos pad
exhibit the following properties: when distortion of the unexposed face of the sample is
ALl.! Length and width, 6 V, in. (152 3 mm). minimal. The pads are relatively rigid and shall not be used on
A1.1.2 Thickness, 0.40 0.05 in. (10.2 1.3 mm). The surfaces subject to sharp distortions or discontinuities during
thickness measurement shall be made under the llght load of a the test? Properties of Ceraform 126 material shall be as
1f2-in. (13-mm) diameter pad of a dial micrometer gage. follows:
A1.1.3 Dry weight, 0.260 0.0261b (0.12 0.01 kg). Al.2.1 Length and width, 6 V, in. (152 3 mm).
Al.!.4 Thermal conductivity (at 150F (66C), 0.38 A1.2.2 Thickness, 0.375 0.063 in. (9.5 1.6 mm) (see
0.027 Btuin.lhft2 .oF (0.055 0.003 W/mK). A1.1.2).
A1.1.5 Harduess indentation shall be 0.157 0.07 in. (4.0 A1.2.3 Dry weight, 0.147 0.053 Ib (67 24 g)
1.8 mm) or 10-25 (modified Brinell). Indentation shall be A1.2.4 Thermal conductivity (at 150F (66C)), 0.37
determined in accordance with Test Method C 569. Modified 0.03 Btuin.Ihft'oF (0.053 0.004 W/mK).
Brinell values of harduess are obtained by the relationship A1.2.5 Harduess (see Al.1.5) indentation on soft face shall
224
be 0.075 0.025 in. (1.9 0.6 mm).
Hardness = -
y
A1.2.6 The pads may be shaped by wetting, forming, and
then drying to constant weight to provide complete contact on
where y ;;;; the measured indentation in inches. sharply contoured surfaces.
A1.1.6 The pads shall be sufficiently soft so that, without
breaking, they may be shaped to contact over the whole surface
g Ceraform 126 is a registered tradename of Manville Specialty Products Group,
against which they are placed. P. O. Box 5108, Deliver, CO 80217.
9 Supporting data are available from ASTM Headquarters. Request RR: E05-

A1.2 Refractory Fiber Pads-Comparative fhe tests have 1004.

11
APTI., E 119 - OOa
dliHfI

APPENDIXES

(Nonmandatory Information)

Xl. STANDARD TIMETEMPERATURE CURVE FOR CONTROL OF FlRE TESTS

TABLE X1.1 STANDARD TIMETEMPERATURE CURVE FOR CONTROL OF FIRE TESTS

TIme Area Above 68F Base Area Above 20"C Base


Temperature, F Temperature, C
h:min OF-min F-h "C-min G-h

0:00 68 00 a 20 00 a
0:05 1 000 2 330 39 538 1 290 22
0:10 1 300 7 740 129 704 4 300 72
0:15 1 399 14 150 236 760 7860 131
0:20 462 20970 350 795 11 650 194
0:25 510 28050 468 821 15590 260
0:80 550 35360 589 843 19650 328
0:35 584 42 860 714 862 23810 397
0:40 613 50 510 842 878 28060 46B
0:45 63B 58 300 971 892 32390 540
0:50 661 66 200 103 905 36780 613
0:55 681 74 220 237 916 41 230 6B7
1:00 700 82330 372 927 45740 762

1:05 718 90540 509 937 50300 B3B


1:10 735 98830 647 946 54910 915
1:15 750 107 200 787 955 59560 993
1:20 765 115 650 928 963 64250 071
1:25 779 124 180 2 070 971 68990 150
1:30 1 792 132 760 2 213 978 73760 229
1:35 1 804 141 420 2 357 985 78560 309
1:40 1 815 150 120 2502 991 83400 390
1:45 826 1S8 890 2 648 996 88280 471
1:50 835 167 700 2795 1 001 93 170 553
1:55 843 176 550 2942 1 006 98080 635
2:00 850 185 440 3 091 1 010 103 020 717

2:10 862 203 330 3389 017 112 960 882


2:20 875 221 330 3689 024 122 960 2049
2:30 888 239 470 3991 031 133 040 2217
2:40 1 900 257 720 4295 03B 143 180 2386
2:50 1 912 276 110 4602 045 153 390 2556
3:00 1 925 294 610 4 910 052 163 670 2728

3:10 1 938 313 250 5 221 059 174 030 2 900


3:20 1 950 332 000 5 533 066 184 450 3074
3:30 1 962 350 890 5 B4B 072 194 940 3 249
3:40 1 975 369 890 6 165 1 079 205 500 3425
3:50 1 988 389 030 6484 1 086 216 130 3602
4:00 2000 408 280 6805 1 093 226 820 3780

4:10 2 012 427 670 7 128 100 237 590 3960


4:20 2025 447 160 7453 107 248 430 4 140
4:30 2038 466 810 7780 114 259 340 4322
4:40 2050 486 560 8 110 121 270 310 4505
4:50 2062 506 450 8441 128 281 360 4689
5:00 2075 526 450 8774 135 292 470 4874

5:10 2088 546 580 9 110 142 303 660 5 061


5:20 2 100 566 840 9447 149 314 910 5248
5:30 2 112 587 220 79787 156 326 240 5437
5:40 2 125 607 730 10 129 163 337 630 5 627
5:50 2 138 628 360 10473 170 349 909 5818
6:00 2 150 649 120 10 819 177 360 620 6010

6:10 2 162 670 000 11 167 184 372 230 6204

12
~ E 119-00a

TABLE X1.1 Continued


Time Area Above 68"F Base Area Above 20"C Base
Temperature," F Temperature, "C
h:min "F~min "F-h "G-min "C-h

6:20 2 175 691 010 11 517 1 191 383 900 6398


6:30 2 188 712 140 11 869 1 198 395 640 6594
6:40 2 200 733 400 12 223 1 204 407 450 6 791
6:50 2 212 754 780 12 580 1 211 419 330 6989
7:00 2225 776 290 12 938 1 218 431 270 7 188

7:10 2 238 797 920 13 299 1 225 443 290 7388


7:20 2250 819 680 13 661 1 232 455 380 7590
7:30 2 262 841 560 14 026 1 239 467 540 7 792
7:40 2275 863 570 14393 1 246 479 760 7996
7:50 2288 885 700 14762 1 253 492 060 8 201
8:00 2300 907 960 15 133 1 260 504 420 8407

X2. SUGGESTED REPORT FORM


ASTM E119

TITLE PAGE

(Preferably Cover)

Laboratory
Project Number

ASTM E1l9 (year)

STANDARD FIRE ENDURANCE TEST

Fire Endurance Time


Construction
Date Tested
Sponsor
Material
Maximum Load Conditions, or Restricted Load Conditions (as the conditions of the test dictate)

(Identify if test is part of a research program)

(Add--Table of Contents)

X2.1 Description of Laboratory Test Facility-Furnace, X2.3 Description of Test Assembly:


restraining frame, details of end conditions, including wedges, X2.3.l Give size of test specimen.
bearing, etc. X2.3.2 Give details of structural design, including safety
X2.1.1 If construction is to be tested under load indicate factors of all structural members in test assembly.
how lbe load is applied and controlled. (Give loading diagram.) X2.3.3 Include plan, elevation, principal cross section, plus
Indicate whether the load is a maximum load condition or a other sections as needed for clarity.
restricted load condition and for either condition, report the X2.3.4 Give details of attachment of test panel in frame.
specific loads and the basis for limitation, such as bending X2.3.5 Location of thermocouples, deflection points, and
stress, shear, etc. A restricted load condition shall be reported other items for test.
as a percentage of the maximum load condition. X2.3.6 Describe general ambient conditions at:
X2.1.2 If construction is to be tested as nonload bearing X2.3.6.l Time of construction,
indicate whether frame is rigid or moves in test, or whether test X2.3.6.2 During curing (time from construction to test), and
is of temperature rise only. X2.3.6.3 Time of test.

X2.2 Description of all Materials-Type, size, class, X2.4 Description of Test:


strength, densities, trade name, and any additional data neces- X2.4.1 Report temperature at beginning and every 5 min. If
sary to define materials. The testing laboratory should indicate charts are included in report, clearly indicate time and tem-
whelber materials meet ASTM Standards by markings, or by perature:
statement of sponsor, or by physical or chemical test by the X2.4.1.1 In furnace space,
testing laboratory. X2.4.1.2 On unexposed surface, and

13
OE119-00a
X2.4.1.3 On protected framing members as stipulated in X2.S.2 If construction is unsymmetrical (has different de-
Standard. tails on each face) be sure to indicate the face exposed to fire
with comments on fire resistance from the opposite side.
NOTE X2.i-It is recommended that temperature observations not
required by the standard. but useful, be reported in the Appendix to the X2.5.3 Fire test.
report. These include temperatures on tbe face of framing members in X2.6 Summarize Results, include:
back of protection and others that may be required by various Building
Codes. X2.6.l Endurance time,
X2.6.2 Nature of failure, and
X2,4.2 Report deflections every 5 min for the first 15 min of X2.6.3 Hose stream test results.
test and the last hour. In between, evelY 10 min.
X2,4.3 Report appearance of exposed face: X2.7 List Official Observers-Signatures of responsible
X2,4.3.1 Every 15 min, persons.
X2.4.3.2 At any noticeable development, give details and X2.S Appendix-Include all data not specifically required
time, that is, cracks, buckling, flal11ing, smoke, loss of material, by test standard, but useful to better understanding of test
etc" and results. Special observations for Building Code approvals
X2,4.3.3 At end of the test include the amount of drop out, should be in appendix.
condition of fasteners. sag, etc.
X2.4.4 Report appearance of unexposed face: X2.9 Pictures-All taken to show what cannot be covered
X2,4,4.1 Every 15 min, in the report or to clarify.
X2.4.4.2 At any noticeable development including crack- X2.9.1 Assembly in construction.
ing, smoking, buckling, give details and time, and X2.9.2 Exposed face prior to fire test.
X2,4.4.3 At the end of test. X2.9.3 Unexposed face at start of endurance test; include
X2,4.5 Report time of failure by: recording equipment when possible.
X2.4.5.1 Temperature rise, X2.9.4 Unexposed face at end of fire endurance test.
X2,4.5.2 Failure to carry load. and X2.9.5 Exposed face at end of fire endurance test.
X2,4.5.3 Passage of flame-heat-smoke. X2.9.6 Unexposed face at end of fire exposure before hose
X2.4.6 If a hose stream test is required repeat necessary test.
parts of X2.1 and X2.3. If failure occurs in hose stream X2.9.7 Exposed face at end of fire exposure before hose
test-describe! test.
X2.9.S Exposed face after hose stream test.
X2.5 Official Comments on: X2.9.9 Unexposed face after hose stream test.
X2.5.1 Included shall be a statement to the effect that the X2.1O It is essential to have the following:
construction truly represents field construction. If the construc- X2.10.1 Detailed drawing of test assembly.
tion does not represent typical field constlUction, then the X2.IO.2 Pictures (X2.9.!' X2.9,4X2.9,4, X2.9.S, and
deviations shall be noted. X2.9.9) for every test report.

X3. GUIDE FOR DETERMINING CONDITIONS OF RESTRAINT FOR FLOOR AND ROOF ASSElVffiLillS AND FOR
INDIVIDUAL BEAMS

X3.1 The revisions adopted in 1970 introduced the concept shown that certain conditions of restraint will improve fire
of fire endurance classifications based on two conditions of endurance, methodologies for establishing the presence of
support: restrained and unrestrained. As a result, specimens can sufficient restraint in actual constructions have not been stan-
be fire tested in such a manner as to derive these two dardized.
classifications.
X3.4 For the purpose of this guide, restraint in buildings is
X3.2 A restrained condition in fire tests, as used in this test defined as follows: "Floor and roof assemblies and individual
method, is one in which expansion at the supports of a load beams in buildings shall be considered restrained when the
carrying element resulting from the effects of the fire is resisted surrounding or supporting structure is capable of resisting
by forces external to the element. An unrestrained condition is substantial thermal expansion throughout the range of antici-
one in which the load carrying element is free to expand and pated elevated temperatures. Construction not complying with
rotate at its supports. tins definition are assumed to be free to rotate and expand and
shall therefore be considered as unrestrained."
X3.3 This guide is based on knowledge currently available
and recommends that all constructions be classified as either X3.S This definition requires the exercise of engineering
restrained or unrestrained. This classification will enable the judgment to determine what constitutes restraint to "substantial
architect, engineer, or building official to correlate the fire thermal expansion." Restraint may be provided by the lateral
endurance classification, based on conditions of restraint, with stiffness of supports for floor and roof assemblies and interme-
the construction type under consideration. While it has been diate beams forming part of the assembly. In order to develop

14
o E 119-00a
restraint, connections must adequately transfer thennal thrusts are listed. Having these examples in mind as well as the
to such supports. The rigidity of adjoining panels or structures philosophy expressed in the preamble, the user should be able
should be considered in assessing the capability of a structure to rationalize the less common types of construction.
to resist thennal expansion. Continuity, such as that occurring
in beams acting continuously over more than two supports, will
induce rotational restraint which will usually add to the fire
resistance of structural members.

X3.6 In Table X3.1 only the co=on types of constructions

TABLE X3.1 Construction Classification, Restrained and Unrestrained


I.Wall bearing:
Single span and simply supported end spans of multiple bays:A
(1) Open-web steel joists or steel beams, supporting concrete slab, precast units, or metal decklng unrestrained
(2) Concrete slabs, precast units, or metal decking unrestrained
Interior spans of multiple bays:
(1) Open-web steel joists, steel beams or metal decking. supporting continuous concrete slab restrained
(2) Open-web steel joists or steel beams, supporting precast units or metal decking unrestrained
(3) Cast-in-place concrete slab systems restrained
(4) Precast concrete where the potential thermal expansion is resisted by adjacent constructionS restrained
II.Steel framing:
(1) Steel beams welded, riveted, or bolted to the framing members restrained
(2) All types of cast-in-place floor and roof systems (such as beam-and-slabs, flat slabs, pan joists, and waffle slabs) where the floor or restrained
roof system is secured to the framing members
(3) All types of prefabricated floor or roof systems where the structural members are secured to the framing members and the potential restrained
thermal expansion of the floor or roof system is resisted by the framing system or the adjoining floor or roof constructionS
II1.Concrete framing:
(1) Beams securely fastened to the framing members restrained
(2) All types of cast-in-place floor or roof systems (such as beam-and-slabs, flat slabs, pan joists, and waffle slabs) where the floor restrained
system is cast with the framing members
(3) Interior and exterior spans of precast systems with cast-in-place joints resulting in restraint equivalent to that which would exist in restrained
condition III (1)
(4) All types of prefabricated floor or roof systems where the structural members are secured to such systems and the potential thermal restrained
expansion of the floor or roof systems is resisted by the framing system or the adjoining floor or roof constructionB
IV.Wood construction:
All types unrestrained
A Floor and roof systems can be considered restrained when they are tied into walls with or without tie beams, the walls being designed and detailed to resist thermal
thrust from the floor or roof system.
S For example, resistance to potential thermal expansion is considered to be achieved when:
(1) Continuous structural concrete topping is used,
(2) The space between the ends of precast units or between the ends of units and the vertical face of supports is filled with concrete or mortar, or
(3) The space between the ends of precast units and the vertical faces of supports, or between the ends of solid or hollow core slab units does not exceed 0.25 %
of the length for normal weight concrete members or 0.1 % of the length for structural lightweight concrete members.

X4. METHOD OF CORRECTING FIDE ENDURANCE FOR CONCRETE SLABS DETERMINED BY


UNEXPOSED SURFACE TEMPERATURE RISE FOR NONSTANDARD MOISTURE CONTENT

X4.1 Scope X4.2 Symbols


X4.1.1 The standard fire endurance is the time determined X4.2.1 The symbols used in this Appendix are defined as ~
by unexposed surface temperature rise of a test specimen at a follows:
standard moisture level
X4.1.2 This appendix gives a procedure to correct the fire A = factor characterizing the drying conditions (see
endurance of unprotected vertical or horizontal slabs (solid or Table X4.1),
hollow), made from essentially inorganic building materials; b = factor characterizing the permeability of the speci-
and conditioned on both sides, when moisture content at the men (see Table X4.2),
time of test is other than at a standard moisture level. FE = fire endurance of specimen, h,
X4.1.3 From among the common inorganic building mate- RH = relative humidity,
rials, only the hydrated portland cement products can hold m = moisture content. volume fraction ft'/ft' or cm
(after due conditioning in accordance with 11) sufficient 3/cm3,
amount of moisture to affect noticeably the result of the fire rna = average moisture content of test specimen,
test. Consequently, correcting the experimental fire endurance me = average moisture content of cement paste,
of constructions containing less than 5 volume % of portland
rn, = nominal eqUilibrium moisture content of cement
paste for a given RH (see Table X4.3).
cement paste is not necessary.

15
OE119-00a
~ equilibrium moisture content of cement paste at the TABLE X4.2 Factor Characterizing Permeability of Test Specimen
m"
standard RH level (see Table X4.3). Material b
m, = average moishl.l'e content of a standard conditioned Normal weight and gun-applied concrete (dry unit weight greater
than 135 Iblfi3(2162 kg/rna
5.5
concrete specimen of same concrete and cement
lightweight concrete (dry unit weight between 65 and 115 Iblft3 6.0
paste volume as the test specimen, and (1361 and 1641 kg/rna
v ~ volume fraction of cement paste, ft3fft3 or em 3/cm3, Lightweight insulating concrete (dry unit weight less than 50 Iblfts 10.0
(601 kg/mS

X4.3 Calculation of Moisture Content


TABLE X4.3 Factor CharacterizIng Drying Conditions
X4.3.1 The average moisture content, mao is the volume
fraction of moisture (ft3/ft 3(or cm3/cm3)) in the material Factor A for Portland
Cement
relative to its dry condition; where dry condition is defined as Middepth RH of
Conditioning Environment Normal
that resulting when the material is heated in an oven at 221 Test Specimen, %
Weight
Light-Weight
I'F (lOS:: 0.5'C) until no further weight loss occurs. Concrete
Concrete
X4.3.2 The average moisture content of the cement paste 80 to 80 F (15.6 to 26.rC)
Q
any 1.0 1.0
can be estimated from the known value of RH at middepth atmospheric conditions
Q

(assuming the material has never been subject to rewetting) by 120 to 160 F (48.9 to 70 to 75 0.7 0.7
71.1C)20t035%RH
calculating first the moisture content in the cement paste as 190 to 200F (67.8 to 70 to 75 0.45 0
follows: 93.3 C) 0 to 5 % RH
Q

120 to 200F (48.9 to less than 70 0 0


lIle =Ame 93SC) 5 10 35 % RH
X4.3.3 The average moisture content of the test specimen is
then calculated as follows:
rna = vm c
5 % RH until the RH at its middepth was reduced to 70 %. It
X4.3.4 Calculate the average moisture content of a standard had a 2.90-h fire endurance. Determine the adjusted fire
conditioned specimen as follows: endurance.
m~ = vm es X4.5.1.1 Step l-Calculate m. as follows:
where mes is the value of me in Table X4.1 pertaining to the For 70 % RH,
standard RH level. m" = 0.225

X4.4 Correction Procedure (see Table X4.l)


X4.4.1 The correction procedure starts with the selection of For 200'F (93'C) and 5 % RH conditioniug, for normal
an empirical factor to reflect the permeability of the material as weight concrete
suggested in Table X4.2. With known values of m a and ms A ~ 0.45
calculate the products bma and bm s. On the nomogram (Fig. (see Table X4.3)
X4.1) draw lines from point R to values of bma and bms on the
..lIIe = 0.45 X 0.225 = 0.101
right-hand scale. From the point representing the actual fire
endurance time (FE) on the left-hand scale draw a line parallel (see X4.3.1)
to R -bm a to intersect the curve. From this point on the curve For v ~ 0.232
draw a line parallel to R-bm s and find the corrected fire rna = 0.232 X O.lDl = 0.0234
endurance on the FE scale.
(see X4.3.3)
X4.S Illustrative Example that is, the concrete contains 2.34 volume % moisture at time
X4.5.1 A wall made from normal weight concrete having of test.
23.2 volume % of paste, was conditioned at 200'F (93'C) and X4.5.1.2 Step 2-Calculate m, as follows:
As an example, if the standard moisture level is assumed to
TABLE X4.1 Equilibrium Moisture Content (Desorption) of correspond to a middepth RH of 75 %, then me = 0.24
Cement Paste at Given Relative Humidity
ms = 0.232 X 0.24 = 0.0557
RH at middepth, % m.
(see X4.3.4)
90 0.30
85 0.275 that is. the standard moisture level is 5.57 volume %.
80 0.255 X4.S.1.3 Step 3-Ca1culate bm as follows:
75 0.24
70 0.225
65 0.21
60 0.195 b = 5.5 see Table X4.3
55 0.185 bm. 5.5 X 0.0234 ~ 0.129
50 0.175 bin, = 5.5 X 0.0557 ~ 0.306
45 0.16
40 0.15 X4.5.1.4 Step 4--Draw lines on the nomogram from pointR
to bm, and bm,(see Fig. X4.1).

16
E 119-00a

R~~~--------------------------~---,
'::::'=:::::--- b-rna
a
-_ ---
--
-- -------
------- ---+- 0.1

----- 0.2

0.3

4 0.4 '

0.5 E
;:
zw
0.6 f--
z
0
---- -- -- 0.7 ()

--
w
""W 3
()
z

a::
::>
-----
------- -----~~~
0.8

0.9
o
z 1.0 .0
w
w Z
a:: 0
IT: ;::
()
w
2 a::
a::
0

:;:
a::
w
CL

o~ ________________________________ ~

FIG. X4.1 Nomogram for Correcting Fire Endurance for Nonstandard Moisture Content

X4.5.1.5 Step 5-Draw a line from the FE ordinate, 2.90, FE = 3.19 is the adjusted fire endurance; that is, the fire
parallel to line R-bma to intersect the curve. endurance that would have resulted if the specimen had been
X4.5.1.6 Step 6--Draw a line parallel to R-bm, from a point tested at the standard moisture level, here assumed to corre-
on the curve, to intersect the FE ordinate scale. The value of spond to 75 % RH at roiddepth.

XS. COMMENTARY

XS.l Introduction planning and performance of fire tests and in the reporting of
X5.1.1 This co=entary has been prepared to provide the results. No attempt has been made to incorporate all the
user of Test Methods E 119 with background information on available information on fire testing in this commentary. The
the development of the sbmdard and its application in fire serious student of fire testing is strongly urged to peruse the
protection of buildings. It also provides guidance in the referenced documents for a better appreciation of the history of

17
cO E l19-00a
fire-resistant design (1, 2)10 and the intricate problems associ- 4. Ventilation, as detennined by the size and shape of
ated with testing and with interpretation of test results. openings (17, 18, 19, 21, 27, 28, 29).
X5.1.2 Floors and walls designed as fire separations have 5. Geometry of the fire compartment-Size and shape.
been recognized for many years as efficient tools in restricting 6. Thermal characteristics of the enclosure boundaries.
fires to the area of origin, or limiting their spread (3, 4, 5, 6, 7, 7. Relative humidity of the atmosphere.
8,9,10,11). Prior to 1900, relative fire safety was achieved by For the purposes of this commentary, fire severity is defined
mandating specific materials. By the year 1900, the appearance as a measure of the fire intensity (temperature) and fire
of a multitude of new materials and innovative designs and duration. It is expressed in terms of minutes or hours of fire
constructions accelerated the demand for performance stan- exposure and in Test Methods E 119 is assumed to be equiva-
dards. The British Fire Prevention Committee, established in lent to that defined by the standard temperature-time (T-t)
1894, was the first to produce tables listing fire resisting floors, Curve, that is, the area under the T-t curve (27).
ceilings, doors and partitions (5). Test furnaces in the United
States were constructed shortly after 1900 at the Underwriters X5.4 Scope and Significance
Laboratories Inc., Columbia University, and the National X5.4.1 Test Methods E 119 is intended to evaluate in terms
Bureau of Standards (NBS) (1, 12). These early furnaces of endurance time, the ability of an assembly to contain a fire,
eventually led to the development of Test Methods E 119. or to retain its structural integrity, or both during the test
conditions imposed by the standard. It also contains standard
X5.2 Historical Aspects conditions for measuring heat transfer through membrane
XS.2.1 Test Methods E 119 was first published by ASTM as elements protecting combustible framing or surfaces.
CI9 in 1918. A number of refinements have been made in the X5.4.2 The end-point criteria by which the test result is
standard since that time, such as the classification of beams and assessed are related to:
of floor and roof assemblies based on condi tions of support. 1. Transmission of heat through the test assembly.
Several provisions, including the temperature-time curve and 2. Ability of the test assembly to withstand the transmission
the major apparatus, remain essentially unchanged. The roots of flames or gases hot enough to ignite combustible material.
of fire testing as we define it today can be traced back to about 3. Ability of the assembly to carry the load and withstand
1800. A comprehensive review of early fire testing has been restraining forces during the fire test period.
published (1). 4. Temperatures of the steel under some conditions.
X5.4.3 It is the intent that classifications shall register
X5.3 Fire-Load Concept performance during the period of exposure and shall not be
X5.3.1 Specifications for fire resistance in regulatory docu- construed as having determined suitability for use after the
ments continue to be based largely on the fire-load concept exposure.
developed by NBS in the 1920s and reported in the 1928 NFPA X5.4.4 The standard, although being specific about the
Quarterly by Ingberg. The concept incorporates the premise assembly to be tested, enables the testing laboratory to deter-
that the duration of a fire is proportional to the fire loading, that mine whether the specimen is "truly representative" of the
is, the mass of combustible materials per unit floor area. The assembly intended for evaluation. This is necessmy because of
relationship between the mass of combustible materials and fire the wide variation in assemblies. For instance, wall test
duration was established on the basis of burnout tests in specimens generally do not contain electric switches and
structures incorporating materials having calorific or potential outlets, that in some designs may affect test results. Floor test
heat values equivalent to wood and paper. that is, 7000 to 8000 specimens may or may not contain electrical raceways and
BtU/lb (16.3 to 18.6 MJ/kg). The fire-load of noncellulosic outlets or pull boxes for power and communication wiring.
materials such as oils, waxes. and flammable liquids were Cover plates over trench headers are also present in some
interpreted on the basis of their equivalent calorific content (5, designs. The testing laboratory is in the best position to judge
13,14,15). In the simplest terms, the above premise states that the effects of such items.
10 Ib of combustible materials per square foot (50 kg/m2 ) of
floor area will produce a fire of 1 h duration. XS.5 Test Furnaces
X5.3.2 Increasing sophistication in the knowledge of mate- X5.5.1 Test Methods E 119 does not provide specific con-
rials and the fire process has resulted from numerous research struction details of the furnace. Readers are urged to consult
E~~~11,~~~~~~~.n,~.~ reference documents for a more comprehensive review of
25, 26, 27). It is now generally conceded that fire severity as fumace design and performance (25).
well as the temperature-time relationship of a fire depends on
several factors, including; XS.6 Temperature-Time Curve
1. Fire load-Amount and type. XS.6.1 A specific temperature-time relationship for the test
2. Distribution of this fire load. fire is defined in the standard and in Appendix Xl. The actual
3. Specific surface characteristics of the fire load (5, 27). recorded temperatures in the fumace is required to be within
specified percentages of those of the standard curve. Accuracy
in measuring temperature is generally easier to achieve after 1
10 The boldface numbers in parentheses refer to the list of references at the end
h due to stabilizing of the furnace and the slope of the T-t curve.
of this test method. The number and type of temperature-measuring devices are

18
eE119-00a
outlined in the standard. Specific standard practices for loca- allows for more confidence in extrapolating testing results. For
tion and use of these temperature-measuring devices are also instance, the maximum length of a floor specimen in most test
outlined in the standard. However, no uniformity of the facilities is 16 ft (4.9 m). It is, therefore, necessary to
temperatures within the fire chamber is specified. extrapolate developed fire-endurance ratings to much longer
XS.6.2 The standard T-t curve used in Test Methods E 119 is spans.
considered to represent a severe building fire (5). The curve XS.8.2 When a floor or roof assembly is designed for a
was adopted in 1918 as a result of several conferences by specific use, such as used in prefabricated housing units, the
eleven technical organizations, including testing laboratories, assembly may be tested with a restricted load condition. The
insurance underwriters, fire protection associations, and tech- loading condition used for such tests shall be defined in the test
nical societies (1, 16, 30). The T-t relationship of these test report. The standard does not require specific loading devices.
methods represents only one fire situation. Data are available to Some laboratories use large containers of water; others use a
evaluate the performance of assemblies under fire exposure system of hydraulic rams for floor and roof assemblies. When
conditions that may be more representative of particular fire uniformly distributed load is simulated by point-loading (sev-
situations, that is, using different T-t relationships to simulate eral, small-area loads), it is recommended that the load at any
specific fire conditions (9, 11, 16, 19, 22, 23, 27, 29, 31, 32). such area not exceed 25 % of the total load and that the
XS.6.3 Furnace pressure is not specified and is generally individual point-loading have a width at least equal to the depth
slightly negative. The pressure may have an effect on the test of the fioor. Wall furnaces are generally equipped with hydrau-
results, and the test conditions should always be carefully lic rams.
controlled. XS.8.3 The standard requires that load-bearing walls and
partitions sustain the applied test load during the fire endurance
XS.7 Test Specimen and hose stream tests. A former requirement that load-bearing
XS.7.1 The test specimen is required to represent as c10sely walls and partitions also sustain twice the specified superim-
as possible the actual construction in the field, subject to the posed test load after cooliag but within 72 h of the test period
limits imposed by the test facilities. has been deleted from the test method as being unreallstic.
XS.7.2 All specimens are required to be conditioned so as to Non-bearing walls and partitions are not loaded during the test
attain a moisture content comparable to that in the field prior to but are restrained on all sides. This restraint may impose more
testing. For uniformity, the standard moisture content is defined stress than a load on top. Committee E-S has several times
as that in equilibrium with an atmosphere of SO % relative reviewed the loading procedures for framed walls and parti-
humidity at 73'F (23'C). Massive concrete units which may tions. It was the committee's unanimous decision that such a
require unusually long drying periods may be fire tested after wall be tested either with calculated maximum design load or
a 12-month conditioning period. Appendix X4 describes how with a load expected to occur in practice. The method used to
the test result should be corrected to account for any variation compute the design loads must be reported.
from the standard moisture condition (33). XS.8.4 Some important stresses, such as those caused by
XS.7.3 With few exceptions, only the interior face of creep and shrinkage in the wan itself and its supporting frame
exterior wall assemblies and the ceiling portion or underside of must be present, and the designer should recognize these
floor or roof assemblies are exposed to the standard fire (24, stresses in his analysis. Committee E-S has investigated the
2S). This practice is rationalized on the assumption that the possibility of openings occurring at a joint at comers of
outside face of exterior walls is not usually subjected to the non-load-bearing enclosures due to differential movement.
same fire as the interior face and that the fire exposure of the While the possibility exists that this wili occur, the committee
upper side of a fioor or roof assembly is seldom as intense as has not found it feasible to amend the test based on data
that of the underside. available.
XS.7.4 Although the standard does not contajn specific XS.8.S Double walls pose a unique problem as to load
criteria for judging the impact of through joints nor "poke- application. Which wall should be loaded? Or should both
through" devices, such as electrical or telephone outlets, it walls be loaded simultaneously? Committee E-S has devoted
should be recognized that these components should be evalu- considerable time to debating this problem, and recommends
ated with respect to structural-performance and temperature- the decision be made by the user after an analysis of the
rise criteria if they constitute a significant part of the tested loading conditions anticipated in service both before and after
assembly. a fire. Such loading conditions are to be reported.
XS.7.5 For obvious reasons, symmetrical walls and parti-
tions are tested only on one side. Assymmetrical walls and XS.9 Integrity
partitions may be required to be tested with either or both sides XS.9.! All walls and partitions that qualify for a fire
individually exposed to the fire. If both sides are exposed, the endurance classification of 1 h or more are required to be
report should indicate the fire endurance classification for each subjected to the cooling impact and erosion effects of a stream
case. of water from a 2'h-in. (63.5-mm) hose discharging through a
standard play pipe equipped with a 1VB-in. (28.5-mm) tip under
XS.S Loading specified pressures. In this hose stream test, the ability of the
XS.S.l Floors and roofs are required to be loaded during test .construction to resist disintegration under adverse conditions is
to provide a maximum load condition determined by the examined. The requirement for a hose stream test was earlier
applicable nationally recognized design criteria. This practice removed from the test procedure for coluI1ll1s and floor or roof

19
OE119-00a
assemblies because of impracticality and the possibility of tively (Sections 38 through 40). It is also possible to evaluate
excessive damage to the furnace. the protective cover of steel beams by measuring the tempera-
ture of the steel that is protected (Sections 41 through 44). The
XS.I0 Conditions of Tests fire endurance classification is only applicable to beams used
XS.lO.l Columns are generally tested with all four sides with a floor or roof construction that has a comparable or
exposed to the test fire. However, it is possible to test a column greater capacity for heat dissipation from the beam than the
with three sides exposed (fourth side against a wall). The floor or roof with which it is tested.
standard requires that specimens be tested under conditions XS.ll Other Observations
contemplated in the design. The former general practice of
XS.l1.1 No limitation is imposed on the deformation of the
testing colunms with pin connection at top and bottom to
specimen during or after the test period. It is assumed that the
simulate the most critical condition is no longer a criterion.
deflection or deformation of an assembly is limited only by its
XS.10.2 Columns are required to sustain successfully the
ability to stay in place (under load where specified) during the
design load during the test period. The standard also permits
test period.
columns to be loaded up to 1-% times the design load prior to
XS.II.2 A complete record of deformation during the en-
the fire test if desired by the submitter. Such loading, however,
durance test may be helpful in the application of test results,
shall not be construed as having had a deleterious effect on the
and shall be reported.
fire endurance test performance. Instead of loading, steel
X5.11.3 Other observations, such as the evolution of un-
columns, whose protective covering does not cany load, may
usual quantities of visible smoke, vapors, or gases that may
be assigned a fire-resistance classification on the basis of
affect the proper decision regarding use of the test results,
temperature of the steel only. With such coluI1Uls, the protec-
should be reported.
tive cover shall be restrained against longitudinal expansion.
Wood colunms are tested for load-carrying ability only. XS.12 Protective Membranes
XS.lO.3 From test results, it has been established that XS.12.1 The standard provides criteria for evaluating the
variations of restraint conditions can considerably influence the protection that membrane elements can offer to combustible
time of fire resistance for a structure or a structural element. framing and paneling, for example, joists, wall studs, and
Restraints are generally beneficial to fire resistance; however, paneling or boards on the unexposed side of an assembly, and
there are conditions where restraint can have a detrimental other combustible materials. The results of these tests are
effect on the performance of a specimen during a fire-resistance reported as protective membrane ratings.
test (34, 3S). The users of test results are advised to study the
reference documents as well as Appendix X3 and Table X3.1. XS.13 Future
X5.1DA An unrestrained classification for a steel beam or a XS.13.1 ASTM Committee E-S on Fire Standards through
reinforced concrete beam used as part of an assembly tested in Subcommittee EDS.11 is continually striving to update Test
restrained condition can be assessed from the temperature Methods E 119. Users of the test method are encouraged to
records obtained for the steel or the reinforcing steel respec- contact the committee for further information.

REFERENCES

(1) Babrauskas, Vytenis; Williamson, Robert Brady, Historical Basis of (10) Harmathy, T. Z., Peifonnance of Building Elements in Spreadillg
Fire Resistance Testing, Part I and Part II, Fire Technology, Vol 14, No. Fire, DBR Paper No. 752, National Research Council of Canada,
3 and No.4, 1978, pp. 184-194, 304-316. NRCC 16437, Fire Research Vol I, 1977n8, pp. 119-132.
(2) Shaub, Harry, "Early History of Fire Endurance Testing in the United (11) Harmathy. T. Z., "Design Approach to Fire Safety ill Bui/dings"
States," Symposium on Fire Test Methods, ASTM STP 301, ASTM, Progressive Architecture, NRCC 14076, April 1974, pp. 82-87.
1961, pp. 1-9.
(12) Rule 508 Industrial Code, New York State Labor Law. See p. 513,
w

(3) Dilam, C. H., Modem Building Inspection, et aI, R. C. Colling and New York City Building Code, 1934 Edition.
Associates, Los Angeles, CA, 1942.
(13) Robertson, A F., and Gross, D., ''Fire Load, Fire Severity, and Fire
(4) Facts About Fires, National Fire Protection Assn., 1971.
Endurance," Fire Test Pelfonnance. ASTM STP 464, ASTM, 1970,
(5) Bird and Docking, Fire in Buildings, D. VanNostrand Co., Inc., New
pp.3-29.
York, NY, 1949.
(14) Building Materials and Standards, BMS 92, National Bureau of
(6) Fergusion, R. S., Principles of Fire Protection - National Bldg. Code
Standards, Washington, DC. October 1942.
of Canada, Technical Paper No. 272, Div. of Bldg. Research, National
Research Council of Canada, Ottawa, March 1970. (15) Ingberg, S. H., et aI, "Combustible Contents in Buildings," BMS 149,
(7) Konicek L., and Lie, T. T., "Temperature Tables for Ventilation National Bureau of Standards, Washington. DC. July 1957.
Controlled Fires," Bldg. Research Note No. 94, National Research (16) Seigel, L. G., The Severity of Fires in Steel-Framed Buildings Her
Council of Canada, September 1974. Majesty's Stationary Office, 1968, London, Proceedings of the
(8) Gordon, C. C., Considerations of Life Safety {Illd Bldg. Use, DBR Symposium held at the Fire Research Station, Boreham Woods, Herts
Paper No. 699, Bldg. Research Div., National Research Council of (England) on Jan. 24, 1967, pp. 59-63.
Canada, Ottawa, January 1977. (17) Gross, D., Field Burnout Tests of Apartment Dwelling Units, Bldg.
(9) Shorter, G. W., Fire Protection Engineer alld Modem Building Design, Science Series 10, U. S. Dept. of Commerce, National Bureau of
Fire Technology, Vol 4, No.3, August 1968, pp. 206---213. Standards, Sept. 29, 1967.

20
~ E 119-00a
(18) Law, Margaret, Radiation from Fires in a Compartment. Fire Re- (31) ISOfI'E-WG5 Report, March 9--10, 1967. at Copenhagen. Denmark
search Technical Paper No. 20, Her Majesty's Stationary Office, (Sweden-B)-Exhiblt 14. Preliminary report on some theoretical
London, 1968. studies for structural elements of the effect on their fire resistance of
(19) Heselden, A. J. M., Parameters Determining the Severity of Fire, variations of T-t curve for cooling down period, Magusson, Sven-Erik
Symposium No. 2 Her Majesty's Stationary Office, 1965, London, and Pettersson, Ove.
Proceedings of the Symposium held at the Fire Research Station, (32) Ryan, J. v., and Robertson, A. E, ''Proposed Criteria for Defining
Bareham Woods, Herts (England) on Jan. 24, 1967, pp. 19-27. Load Failure of Beams, Floors, and Roof Construction During Fire
(20) Sfintesco, D., FlImace Tests and Fire Resistance, ibid 17. Tests," JOllmal of Research of the National Bureau of Standards,
(21) Gross, D., and Robertson, A. F., Experimental Fires in Enclosures, Washington, DC, Vol 63C, No.2, 1959.
Tenth Symposium (International) on Combustion, The Combustion (33) Harmathy, T. Z., "Experimental Study on Moisture and Fire-
Institute, 1965, pp. 931-942. Endurance," Fire Technology, Vol 2, No.1, February 1966.
(22) Odeen, }(ai, Theoretical Study Of Fire Characteristics in Enclosed (34) Carlson, C. C., Selvaggio. S. L., Gustaferro, A. H., A Review of
Spaces, Div. of Bldg. Construction, Royal Institute of Technology, Studies of the Effects of Restraint on the Fire-Resistance of Pre-
Stockholm, Sweden, 1965. stressed Concrete. Feuerwider-stansfahigkeit von Spannbeton,
(23) Ryan, J. E., "Perspective on Methods of Msessing Fire Hazards in Ergebnisse einer Tagung der EI.P. in Braunschweig, Juni 1965.
Buildings," Ignition, Heat Release. and NOllcombustibility of Mate- Wiesbaden-Berlin, 1966, p. 32.
rials, ASTM STP 502, ASTM, 1972, pp. 11-23. (35) Issen, L. A, Gustafen-o, A H., Carlson, C. C.," Fire Tests of Concrete
(24) Harmathy, T. Z., Performance of Building Elements in Spreading
Members: An Improved Method for Estimating Thermal Restraint
Fire, DBR Paper No. 752, National Research Conncil of Canada,
Forces," Fire Test Performance, ASTM STP 464. ASTM, 1970, pp.
NRCC 16437, Fire Research Vol 1, 1977nS, pp. 119-132.
153-185.
(25) Harmathy, T. Z., "Design of Fire Test Furnaces," Fire Technology,
(36) Stone, Richard, "Danger-Flammable," Wall Street Journal, New
Vol 5, No.2, May 1969, pp. 146--150.
York, NY, Dec. 8. 1970.
(26) Harmathy, T. Z.," Fire Resistance versus Flame Spread Resistance,"
Fire Technology, Vol 12. No.4, November 1976. pp. 290-302 and (37) Warren, J. H . Corona, A A., ''This Method Tests Fire Protective
330. Coatings," Hydrocarbon Processing, January 1975.
(27) Harmathy, T. Z., "A New Look at Compartment Fires, Part I and Part (38) Castle. G. K., ''The Nature of Various Fire Environments and the
II," Fire Technology, VoIS. NO.3 and No.4, August and November Application of Modern Material Approaches for Fire Protection of
1972, pp. 196-217; 326-351. Exterior Structural Steel," presented at American Institute of Chemi-
(28) Satsberg, E, lllinois Institute of Technology Research Institute cal Engineers Loss Prevention Symposium, November 1973, Phila-
Limited release on research data conducted for U. S. Dept. of Civil delphia, PA.
Defense. (39) Crowley. D., et al, ''Test Facilities for Measuring the Thermal
(29) Hannathy, T. Z., Designers Option: Fire Resistance or Velltitalion, Response of Materials to the Fire Environment" JOllmal of Testing
Technical Paper No. 436, Division of Building Research, National and Evaluation, Vall. NO.5.
Research Council of Canada, Ottawa, NRCC 14746. (40) Ingberg. S. H., ''The Hose-Stream Test as a Part of Fire-Testing
(30) Fire Protection Handbook, Revised Thirteenth Edition, National Fire Procedure." Symposium on Fire Test Methods (1962), ASTM STP
Protection Assn., Boston, MA. 1969. 344, ASTM. 1963, pp. 57-68.

ASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentioned
in this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the risk
of infringement of such rights, are entirely their own responsibility.

This standard is subject to revision at any time by the responsible technical committee and must be reviewed evel}' five years and
if not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standards
and should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of the
responsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you should
make your views known to the ASTM Committee on Standards, at the address shown below.

This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box ClOD, West Conshohocken, PA 19428-2959,
United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the above
address or at 610-832-9585 (phone), 610-832-9555 (fax), or service@astm.org (e-mail); or through the ASTM website
(www.astm.org).

21