If the above conditions are satisfied, then drive will operate according to set
point given on SCADA.( -10 to +10 V Analog Input from PLC 21)
If BFRV is closed then KA10 will energize and if opened KA11 will energize.
If Chute is closed then KA12 will energize and if opened KA13 will energize.
III. Manual operation for BFRV from 3DAC panel
Manual operation conditions for both BFRV and Chute from 3DAC panel and field local box
The following relays or KA14 (LSV open feedback) should not active in 3DAC
panel for BFRV drive manual operation from 3DAC panel or from field local box.
KA19 - BFRV auto allowed from PLC
KA25 - Servo Open for BFRV from 3DAC Panel
KA26 - Servo Close for BFRV from 3DAC Panel
KA29 - Servo Open for BFRV from field local box
KA30 - Servo Close for BFRV from field Local box
The following relays should not active in 3DAC panel for Chute drive manual
operation from 3DAC panel or from field local box.
KA20 - Chute auto allowed from PLC
KA27 - Servo Open for Chute from 3DAC Panel
KA28 - Servo Close for Chute from 3DAC Panel
KA31 - Servo Open for Chute from field local box
KA32 - Servo Close for Chute from field local box
V. Manual operation for BFRV from field local box
If any of the running drives gets failed, the following procedure can be applied
for taking the standby drive in operation.
Change selection in SCADA.
Press QS2 pushbutton on 3DAC panel. KM2 contactor will energize and standby
drive gets powered up.
Select SA4 selector switch to either BFRV or Chute position according to the
requirement.
If SA4 towards BFRV, KA21 relay will energize & BFRV standby ready lamp will
glow on 3DAC panel. If SA4 towards Chute, KA22 relay will energize & Chute
standby ready lamp will glow on 3DAC panel.
The following relays should be active for BFRV operation in standby drive.
KA19
KA24
KA14
KA21
The following relays should be active for Chute operation in standby drive.
KA20
KA24
KA22
3DAC PANEL SERVO SYSTEM RELAYS/CONTACTORS DESCRIPTION