CONTENT
1. Power System
OVERVIEW OF 2. Circuit Breaker
ELECTRICAL INSTALLATION 3. Cables
4. Earthing
SYSTEM
5. Short Circuit & Fault Level
Level 1 6. Case Study
1
11/12/2015
2
11/12/2015
3
11/12/2015
4
11/12/2015
5
11/12/2015
6
11/12/2015
7
11/12/2015
8
11/12/2015
9
11/12/2015
3. Cables 3. Cables
3.1 Cable Type 3.2 IEC 60446 Cable Colour
10
11/12/2015
3. Cables 3. Cables
3.3 Current Carrying of Cable
3.3 Current Carrying of Cable Ambient Temperature Correction Factor, Ca
11
11/12/2015
3. Cables 3. Cables
3.3 Current Carrying of Cable 3.3 Current Carrying of Cable
Ambient Temperature Correction Factor, Ca Grouping Correction Factor, Cg
Example : 25mm PVC cable laid at 40C
12
11/12/2015
3. Cables 3. Cables
3.3 Current Carrying of Cable 3.4 Cable Installation Cable Support
Grouping Correction Factor, Cg Cable Size Recommended Installation
Example : (a) 2 Circuits of 50mm XLPE cable laid on tray 16 In Conduit, In Trunking
(b) 1 Circuit of 50mm XLPE cable and 3 other circuit > 16 In Trunking, On Tray
13
11/12/2015
3. Cables 3. Cables
3.6 Voltage Drop
3.5 Earth Cable Sizing Relation to Phase 3.6.1 Voltage Drop R, X, Z
Conductor MS IEC 60364 -52 : Voltage drop from the supply to terminal should not
more than 4% of the declared nominal voltage. Not applicable for motor
(starting).
Phase Conductor Size, S Earth Cable Size 17th IEE : 4%. BS7671 : 3% for lighting, 5% for others.
Example : 400V source. Voltage drop of 4% = 16V
S 16 S
Cable 16mm : reactance is negligible, only resistance values are
16 < S 25 16 tabulated
S> 25 S/2 Cable > 16mm : resistance and reactance are both tabulated
Correction : Power Factor, Temperature, or both.
14
11/12/2015
3. Cables 3. Cables
3.6 Voltage Drop 3.6 Voltage Drop
3.6.2 Correction on Power Factor 3.6.2 Correction on the Power Factor
Example : Motor in full load = 102A, pf = 0.8, cable length = 75m, cable size = Example : Motor in full load = 102A, pf = 0.8, cable length = 75m, cable size =
35mm on tray. 35mm on tray.
Can I use Z only? BS7671 only given in one value of vdrop.
17th IEE Wiring Table 4D1A, Column 9, current rating 143A.
17th IEE Wiring Table 4D1A, Column 9, current rating 143A.
From Table 4D1B, Column 8,
From Table 4D1B, Column 8,
R = 1.1 , X = 0.24 , Z = 1.1
. . .
R = 1.1 , X = 0.24 , Z = 1.1
. . .
, =
, =
.
, = = 8.415 or 2.1% at 400V
. . . .
, = = 7.834V or 1.96% of 400V
15
11/12/2015
3. Cables 3. Cables
3.6 Voltage Drop 3.6 Voltage Drop
3.6.3 Correction for Operating Temperature 3.6.3 Correction for Operating Temperature
A. Resistance Temperature Coefficient (Conductor)
B. Vdrop due to the Changes of Resistance
16
11/12/2015
3. Cables 3. Cables
3.6 Voltage Drop 3.7 Ohms Law
3.6.4 Correction on Power Factor and Temperature Factor
Example : Given :- = , =
Motor in full load, = 102A,
pf = 0.8,
Cable length = 75m, Resistivity, =
Cable size = 35mm on tray, design temperature = 40C
17th IEE Wiring Table 4D1A, Column 9, tabulated current-carrying, =143A, Conductor operating
current, =70C Proportionality of the function
Table 4B1 = 0.87, Table 4C1 = 1.00
From Table 4D1B, Column 8,
R = 1.1 , X = 0.24 , Z = 1.1
. . .
Knowing,
, = ; =
17