Project : Construction of Doha 380/230/115/13.

8kV BSP
Contract No: 31131131/00

ACB/MCCB SETTING CALCULATION FOR ACDB BOARD - DHAHRAN HOME OWNERSHIP 380/115/13.8kV BSP 30.05.17
FULL LOAD BREAKER TRIP THERMAL OVERLOAD INSTANTANEOUS
PANEL DETAILS SHORT TIME SETTINGS (S) GROUND PROTECTION (G)
BREAKER CURRENT RATING SETTING (L) PROTECTION (I)
Sl.No MODEL BREAKER TYPE
BREAKER TYPE Ts in Sec Tg in Sec
TAG NO. FEEDER DESCRIPTION If In Ir in A Tr in Sec Is in A Ii in A Ig in A
NO.
MAIN ACDB-1

INCOMING FEEDERS

1 T301 Q101 INCOMER ACB 2165.06 2500 3WL ETU 27 0.825XIn 12 8XIn I2t OFF- 0.3 12XIn 0.3XIn I2t OFF- 0.4

2 T302 Q102 INCOMER ACB 2165.06 2500 3WL ETU 27 0.825XIn 12 8XIn I2t OFF- 0.3 12XIn 0.3XIn I2t OFF- 0.4

3 T302 Q103 ATS ACB 2165.06 2500 3WL ETU 27 1.0XIn 8 8XIn I t OFF- 0.2
2
10XIn 0.3XIn I2t OFF- 0.3

OUTGOING FEEDERS BUS-1

1 MACDB-1 Q1.01 125V Battery Charger-1 MCCB 287.87 400 3VA ETU 330 0.725XIn 10 6XIn 0.2XIn 0.3

2 MACDB-1 Q1.02 125V Battery Charger-3 MCCB 287.87 400 3VA ETU 330 0.725XIn 10 6XIn 0.2XIn 0.3

3 MACDB-1 Q1.03 SDB-01 MCCB 87.54 100 3VA ETU 330 0.9XIn 8 5XIn 0.2XIn 0.3

4 MACDB-1 Q1.04 SDB-04 MCCB 80.75 100 3VA ETU 330 0.9XIn 8 5XIn 0.2XIn 0.3

5 MACDB-1 Q1.05 SDB-05 MCCB 79.96 160 3VA ETU 330 1.0XIn 8 8XIn 0.2XIn 0.3

6 MACDB-1 Q1.06 SDB-07 MCCB 22.52 32 3VA ETU 330 1.0XIn 8 6XIn 0.2XIn 0.3

7 MACDB-1 Q1.07 400V,300A Recep. For T801 MCCB 299.93 400 3VA ETU 330 0.75XIn 8 6XIn 0.2XIn 0.3

8 MACDB-1 Q1.08 T801 Cooler Fan MCCB 158.93 250 3VA ETU 330 1.0XIn 8 4XIn 0.2XIn 0.2

9 MACDB-1 Q1.09 T802 Cooler Fan MCCB 158.93 250 3VA ETU 330 1.0XIn 8 4XIn 0.2XIn 0.2

10 MACDB-1 Q1.1 PACU-1A MCCB 411.24 630 3VA ETU 330 0.675XIn 8 6XIn 0.2XIn 0.3

11 MACDB-1 Q1.11 PACU-2A MCCB 377.64 400 3VA ETU 330 0.95XIn 8 6XIn 0.2XIn 0.3

12 MACDB-1 Q1.12 PACU-7A MCCB 172.08 200 3VA ETU 330 0.9XIn 8 6XIn 0.2XIn 0.3

13 MACDB-1 Q1.13 HVAC CP for PACU- 1A & 1B MCCB 223.72 250 3VA ETU 330 0.9XIn 8 6XIn 0.2XIn 0.2

14 MACDB-1 Q1.14 400V,300A Recep. For T802 MCCB 299.93 400 3VA ETU 330 0.9XIn 8 6XIn 0.2XIn 0.3

OUTGOING FEEDERS BUS-2

1 MACDB-1 Q2.01 125V Battery Charger-2 MCCB 287.87 400 3VA ETU 330 0.725XIn 10 6XIn 0.2XIn 0.3

2 MACDB-1 Q2.02 SDB-01 MCCB 87.54 100 3VA ETU 330 0.9XIn 8 5XIn 0.2XIn 0.3

3 MACDB-1 Q2.03 SDB-04 MCCB 80.75 100 3VA ETU 330 0.9XIn 8 5XIn 0.2XIn 0.3

4 MACDB-1 Q2.04 SDB-06 MCCB 24.07 100 3VA ETU 330 1.0XIn 8 5XIn 0.2XIn 0.4

5 MACDB-1 Q2.05 400V,300A Recep. For T803 MCCB 299.93 400 3VA ETU 330 0.9XIn 8 6XIn 0.2XIn 0.3

6 MACDB-1 Q2.06 400V,300A Recep. For T601 MCCB 299.93 400 3VA ETU 330 0.9XIn 8 6XIn 0.2XIn 0.3

7 MACDB-1 Q2.07 T803 Cooler Fan MCCB 158.93 250 3VA ETU 330 1.0XIn 8 6XIn 0.2XIn 0.2

Page 1 of 6
Project : Construction of Doha 380/230/115/13.8kV BSP
Contract No: 31131131/00

ACB/MCCB SETTING CALCULATION FOR ACDB BOARD - DHAHRAN HOME OWNERSHIP 380/115/13.8kV BSP 30.05.17
FULL LOAD BREAKER TRIP THERMAL OVERLOAD INSTANTANEOUS
PANEL DETAILS SHORT TIME SETTINGS (S) GROUND PROTECTION (G)
BREAKER CURRENT RATING SETTING (L) PROTECTION (I)
Sl.No MODEL BREAKER TYPE
BREAKER TYPE Ts in Sec Tg in Sec
TAG NO. FEEDER DESCRIPTION If In Ir in A Tr in Sec Is in A Ii in A Ig in A
NO.

8 MACDB-1 Q2.08 PACU-1B MCCB 411.24 630 3VA ETU 330 0.675XIn 8 6XIn 0.2XIn 0.3

9 MACDB-1 Q2.1 PACU-2B MCCB 314.7 400 3VA ETU 330 0.95XIn 8 6XIn 0.2XIn 0.3

10 MACDB-1 Q2.11 PACU-7B MCCB 143.4 200 3VA ETU 330 0.9XIn 8 6XIn 0.2XIn 0.3

11 MACDB-1 Q2.12 HVAC CP for PACU- 2A & 2B MCCB 223.72 250 3VA ETU 330 0.9XIn 8 6XIn 0.2XIn 0.2

12 MACDB-1 Q2.13 HVAC CP for PACU- 7A & 7B MCCB 223.72 250 3VA ETU 330 0.9XIn 8 6XIn 0.2XIn 0.2

13 MACDB-1 Q2.14 Electric Motor Driven Fire Pump MCCB 158.77 160 3VA ETU 330 1.0XIn 8 8XIn 0.2XIn 0.3

14 MACDB-1 Q2.15 400V,300A Recep. For T603 MCCB 299.93 400 3VA ETU 330 0.9XIn 8 6XIn 0.2XIn 0.3

SDB-1 (SDB1 - 400/230V)

INCOMING FEEDERS

1 MACDB-1 1.0 Incomer-1 MCCB 67.02 100 3VA ETU 330 0.9XIn 7 12XIn 0.2XIn 0.1

2 MACDB-1 2.0 Incomer-2 MCCB 67.02 100 3VA ETU 330 0.9XIn 7 12XIn 0.2XIn 0.1

3 3.0 Bus coupler MCCB 67.02 80 3VA ETU 330 0.9XIn 6 12XIn 0.2XIn 0.1

OUTGOING FEEDERS BUS-1

400V,63A Recp Near


1 SDB-1 1.01 MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.3XIn 0.3
PACU -1A & 1B

OUTGOING FEEDERS BUS-2

400V,63A Recp Near


1 SDB-1 2.01 MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.3XIn 0.3
PACU -2A & 2B

SDB-4 - 400/230V

INCOMING FEEDERS

1 1.0 Incomer-1 MCCB 64.69 80 3VA ETU 330 1.0XIn 7 12XIn 0.2XIn 0.1

2 2.0 Incomer-2 MCCB 64.69 80 3VA ETU 330 1.0XIn 7 12XIn 0.2XIn 0.1

3 3.0 Bus coupler MCCB 64.69 80 3VA ETU 330 0.9XIn 6 12XIn 0.2XIn 0.1

OUTGOING FEEDERS BUS-1

400V,63A Recp Near


1 SDB-4 1.01 MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.3XIn 0.3
PACU -7A & 7B

OUTGOING FEEDERS BUS-2

400V,63A Recp Near


1 SDB-4 2.01 MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.3XIn 0.3
Capacitor bank

SDB-5 - 400/230V

1 1.00 Incomer-1 MCCB 79.96 125 3VA ETU 330 0.9XIn 7 8XIn 0.4XIn 0.3

Page 2 of 6
Project : Construction of Doha 380/230/115/13.8kV BSP
Contract No: 31131131/00

ACB/MCCB SETTING CALCULATION FOR ACDB BOARD - DHAHRAN HOME OWNERSHIP 380/115/13.8kV BSP 30.05.17
FULL LOAD BREAKER TRIP THERMAL OVERLOAD INSTANTANEOUS
PANEL DETAILS SHORT TIME SETTINGS (S) GROUND PROTECTION (G)
BREAKER CURRENT RATING SETTING (L) PROTECTION (I)
Sl.No MODEL BREAKER TYPE
BREAKER TYPE Ts in Sec Tg in Sec
TAG NO. FEEDER DESCRIPTION If In Ir in A Tr in Sec Is in A Ii in A Ig in A
NO.
SDB-6 - 400/230V

1 1.00 Incomer-1 MCCB 68.96 100 3VA ETU 330 0.85XIn 7 12XIn 0.2XIn 0.1

OUTGOING FEEDERS

1 SDB-6 1.01 400V,63A Recp. Feeder MCCB 62.96 63 3VA ETU 330 1.0XIn 5 12XIn 0.2XIn 0.3

2 SDB-6 1.05 Supply to Jockey Pump MCCB 36.08 40 3VA ETU 330 1.0XIn 5 12XIn 0.3XIn 0.3

SDB-7 - 400/230V

1 1.00 Incomer-1 MCCB 22.16 32 3VA ETU 330 0.9XIn 7 12XIn 0.3XIn 0.3

MAIN ACDB-2 -380/220V

INCOMING FEEDERS

1 T303 1.0 Incomer-1 ACB 2165.06 2500 3WL ETU 27 0.95XIn 12 8XIn I2t OFF- 0.3 12XIn 0.3XIn I2t OFF- 0.4

2 T304 2.0 Incomer-2 ACB 2165.06 2500 3WL ETU 27 0.95XIn 12 8XIn I t OFF- 0.3
2
12XIn 0.3XIn I2t OFF- 0.4

3 3.0 Bus coupler ACB 2165.06 2500 3WL ETU 27 0.925XIn 8 8XIn I2t OFF- 0.2 10XIn 0.3XIn I2t OFF- 0.3

OUTGOING FEEDERS BUS-1

1 MACDB-2 1.01 SDB-02 MCCB 150 160 3VA ETU 330 1.0XIn 10 8XIn 0.4XIn 0.3

2 MACDB-2 1.02 SDB-03 MCCB 172.86 200 3VA ETU 330 1.0XIn 10 6XIn 0.2XIn 0.2

3 MACDB-2 1.03 ILP-01 MCCB 120.03 160 3VA ETU 330 0.825XIn 8 8XIn 0.4XIn 0.3

4 MACDB-2 1.04 ILP-02 MCCB 108.08 125 3VA ETU 330 0.9XIn 8

5 MACDB-2 1.05 ILP-03 MCCB 68.07 80 3VA ETU 330 1.0XIn 8

6 MACDB-2 1.06 ILP-04 MCCB 32.42 40 3VA ETU 330 0.9XIn 8

7 MACDB-2 1.07 OLP-01 MCCB 249.54 400 3VA ETU 330 0.7XIn 8

8 MACDB-2 1.08 48V BC-1 MCCB 43.3 160 3VA ETU 330 0.9XIn 8 8XIn 0.4XIn 0.3

9 MACDB-2 1.09 PACU-3A MCCB 331.34 400 3VA ETU 330 0.85XIn 8

10 MACDB-2 1.10 PACU-4A MCCB 331.34 400 3VA ETU 330 0.85XIn 8

11 MACDB-2 1.11 PACU-5A MCCB 215.29 250 3VA ETU 330 0.9XIn 8 6XIn 0.2XIn 0.2

12 MACDB-2 1.12 PACU-6A MCCB 215.29 250 3VA ETU 330 0.9XIn 8 6XIn 0.2XIn 0.2

13 MACDB-2 1.13 HVAC CP for PACU 3A & 3B MCCB 223.72 250 3VA ETU 330 0.9XIn 8 6XIn 0.2XIn 0.2

14 MACDB-2 1.14 HVAC CP for PACU 5A & 5B MCCB 223.72 250 3VA ETU 330 0.9XIn 8 6XIn 0.2XIn 0.2

15 MACDB-2 1.15 External Telecom Room MCCB 27.3 125 3VA ETU 330 0.9XIn 8

16 MACDB-2 1.16 T601 Cooler Fan MCCB 48.91 100 3VA ETU 330 1.0XIn 8
400V, 300A Recep for 150Mvar
17 MACDB-2 1.17 MCCB 299.99 400 3VA ETU 330 1.0XIn 8
Reactor

Page 3 of 6
Project : Construction of Doha 380/230/115/13.8kV BSP
Contract No: 31131131/00

ACB/MCCB SETTING CALCULATION FOR ACDB BOARD - DHAHRAN HOME OWNERSHIP 380/115/13.8kV BSP 30.05.17
FULL LOAD BREAKER TRIP THERMAL OVERLOAD INSTANTANEOUS
PANEL DETAILS SHORT TIME SETTINGS (S) GROUND PROTECTION (G)
BREAKER CURRENT RATING SETTING (L) PROTECTION (I)
Sl.No MODEL BREAKER TYPE
BREAKER TYPE Ts in Sec Tg in Sec
TAG NO. FEEDER DESCRIPTION If In Ir in A Tr in Sec Is in A Ii in A Ig in A
NO.
OUTGOING FEEDERS BUS-2

1 MACDB-2 2.01 SDB-02 MCCB 150 160 3VA ETU 330 1.0XIn 10 8XIn 0.4XIn 0.3

2 MACDB-2 2.02 SDB-03 MCCB 172.86 200 3VA ETU 330 1.0XIn 10 6XIn 0.2XIn 0.2

3 MACDB-2 2.03 ILP-01 MCCB 120.03 160 3VA ETU 330 0.825XIn 8 8XIn 0.4XIn 0.3

4 MACDB-2 2.04 ILP-02 MCCB 108.08 125 3VA ETU 330 0.9XIn 8 5XIn 0.2XIn 0.3

5 MACDB-2 2.05 ILP-03 MCCB 68.07 80 3VA ETU 330 1.0XIn 8 5XIn 0.2XIn 0.3

6 MACDB-2 2.06 ILP-04 MCCB 32.42 40 3VA ETU 330 0.9XIn 8 5XIn 0.2XIn 0.3

7 MACDB-2 2.07 OLP-01 MCCB 249.54 400 3VA ETU 330 0.7XIn 8 6XIn 0.2XIn 0.2

8 MACDB-2 2.08 48V BC-2 MCCB 43.3 160 3VA ETU 330 0.9XIn 8 8XIn 0.4XIn 0.3

9 MACDB-2 2.09 PACU-3B MCCB 331.34 400 3VA ETU 330 0.85XIn 8 6XIn 0.2XIn 0.2

10 MACDB-2 2.10 PACU-4B MCCB 331.34 400 3VA ETU 330 0.85XIn 8 6XIn 0.2XIn 0.2

11 MACDB-2 2.11 PACU-5B MCCB 215.29 250 3VA ETU 330 0.9XIn 8 6XIn 0.2XIn 0.2

12 MACDB-2 2.12 PACU-6B MCCB 215.29 250 3VA ETU 330 0.9XIn 8 6XIn 0.2XIn 0.2

13 MACDB-3 2.13 HVAC CP for PACU 4A & 4B MCCB 223.72 250 3VA ETU 330 0.9XIn 8 6XIn 0.2XIn 0.2

14 MACDB-4 2.14 HVAC CP for PACU 6A & 6B MCCB 223.72 250 3VA ETU 330 0.9XIn 8 6XIn 0.2XIn 0.2

15 MACDB-5 2.15 T602 Cooler Fan MCCB 48.91 100 3VA ETU 330 1.0XIn 8 5XIn 0.2XIn 0.3

16 MACDB-6 2.16 T603 Cooler Fan MCCB 48.91 100 3VA ETU 330 1.0XIn 8 5XIn 0.2XIn 0.3

SDB-2 - 400/230V

1 1.0 Incomer-1 MCCB 104.67 160 3VA ETU 330 0.9XIn 7 8XIn 0.4XIn 0.3

2 2.0 Incomer-2 MCCB 104.67 160 3VA ETU 330 0.9XIn 7 8XIn 0.4XIn 0.3

3 3.0 Bus coupler MCCB 104.67 125 3VA ETU 330 1.0XIn 6 8XIn 0.4XIn 0.3

OUTGOING FEEDERS BUS-1


400V, 63A Recp. in 380kV GIS
1 SDB-2 1.16 MCCB 39.98 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3
Room
400V, 63A Recp. in 380kV GIS
2 SDB-2 1.17 MCCB 39.98 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3
Room
3 SDB-2 1.18 Control BLDG PACU-2A MCCB 39.98 40 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3

4 SDB-2 1.26 400V,63A Recp. Near T-801 MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3

5 SDB-2 1.27 400V,63A Recp. Near T-802 MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3

6 SDB-2 1.28 400V,63A Recp. Near GIB MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3

7 SDB-2 1.29 400V,63A Recp. Near GIB MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3
400V,63A Recp. Near
8 SDB-2 1.30 MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3
PACU-3A & 3B

Page 4 of 6
Project : Construction of Doha 380/230/115/13.8kV BSP
Contract No: 31131131/00

ACB/MCCB SETTING CALCULATION FOR ACDB BOARD - DHAHRAN HOME OWNERSHIP 380/115/13.8kV BSP 30.05.17
FULL LOAD BREAKER TRIP THERMAL OVERLOAD INSTANTANEOUS
PANEL DETAILS SHORT TIME SETTINGS (S) GROUND PROTECTION (G)
BREAKER CURRENT RATING SETTING (L) PROTECTION (I)
Sl.No MODEL BREAKER TYPE
BREAKER TYPE Ts in Sec Tg in Sec
TAG NO. FEEDER DESCRIPTION If In Ir in A Tr in Sec Is in A Ii in A Ig in A
NO.
OUTGOING FEEDERS BUS-2
400V, 63A Recp. in 380kV GIS
1 SDB-2 2.16 MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3
Room
2 SDB-2 2.21 400V,63A Recp. Near T-803 MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3
400V,63A Recp. Near Shunt
3 SDB-2 2.28 MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3
Ractor
4 SDB-2 2.29 400V,63A Recp. Near GIB MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3
400V,63A Recp. Near
5 SDB-2 2.30 MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3
PACU-4A & 4B
SDB-3 - 400/230V

1 1.0 Incomer-1 MCCB 127.883 200 3VA ETU 330 0.9XIn 7 6XIn 0.2XIn 0.2

2 2.0 Incomer-2 MCCB 127.883 200 3VA ETU 330 0.9XIn 7 6XIn 0.2XIn 0.2

3 3.0 Bus coupler MCCB 127.883 160 3VA ETU 330 0.9XIn 6 6XIn 0.2XIn 0.2

OUTGOING FEEDERS BUS-1

1 SDB-3 1.01 400V,63A recep T601 MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3
400V, 63A Recp. in 115kV GIS
2 SDB-3 1.02 MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3
Room
400V, 63A Recp. in 115kV GIS
3 SDB-3 1.03 MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3
Room
4 SDB-3 1.04 400V,63A recep PACU-5A & 5B MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3

OUTGOING FEEDERS BUS-2

1 SDB-3 2.01 400V,63A recep T602 & T603 MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3
400V, 63A Recp. in 115kV GIS
2 SDB-3 2.02 MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3
Room
3 SDB-3 2.03 400V,63A recep PACU-6A & 6B MCCB 62.93 63 3VA ETU 330 1.0XIn 6 12XIn 0.2XIn 0.3

ILP-1 400/230V

1 1.0 Incomer-1 MCCB 108.47 160 3VA ETU 330 0.825XIn 7 8XIn 0.4XIn 0.3

2 2.0 Incomer-2 MCCB 108.47 160 3VA ETU 330 0.825XIn 7 8XIn 0.4XIn 0.3

3 3.0 Bus coupler MCCB 108.47 125 3VA ETU 330 0.875XIn 6 8XIn 0.4XIn 0.3

ILP-2 400/230V

1 1.0 Incomer-1 MCCB 87.22 125 3VA ETU 330 1.0XIn 7 5XIn 0.2XIn 0.3

2 2.0 Incomer-2 MCCB 87.22 125 3VA ETU 330 1.0XIn 7 5XIn 0.2XIn 0.3

3 3.0 Bus coupler MCCB 87.22 125 3VA ETU 330 0.9XIn 6 5XIn 0.2XIn 0.3

ILP-3 400/230V

1 1.0 Incomer-1 MCCB 61.66 80 3VA ETU 330 0.9XIn 7 5XIn 0.2XIn 0.3

2 2.0 Incomer-2 MCCB 61.66 80 3VA ETU 330 0.9XIn 7 5XIn 0.2XIn 0.3

3 3.0 Bus coupler MCCB 61.66 63 3VA ETU 330 0.9XIn 6 12XIn 0.2XIn 0.3

Page 5 of 6
Project : Construction of Doha 380/230/115/13.8kV BSP
Contract No: 31131131/00

ACB/MCCB SETTING CALCULATION FOR ACDB BOARD - DHAHRAN HOME OWNERSHIP 380/115/13.8kV BSP 30.05.17
FULL LOAD BREAKER TRIP THERMAL OVERLOAD INSTANTANEOUS
PANEL DETAILS SHORT TIME SETTINGS (S) GROUND PROTECTION (G)
BREAKER CURRENT RATING SETTING (L) PROTECTION (I)
Sl.No MODEL BREAKER TYPE
BREAKER TYPE Ts in Sec Tg in Sec
TAG NO. FEEDER DESCRIPTION If In Ir in A Tr in Sec Is in A Ii in A Ig in A
NO.
ILP-4 400/230V

1 1.0 Incomer-1 MCCB 28.72 40 3VA ETU 330 0.9XIn 7 12XIn 0.2XIn 0.3

2 2.0 Incomer-2 MCCB 28.72 40 3VA ETU 330 0.9XIn 7 12XIn 0.2XIn 0.3

3 3.0 Bus coupler MCCB 28.72 40 3VA ETU 330 0.9XIn 6 12XIn 0.2XIn 0.3

OLP-1 400/230V

1 1.0 Incomer-1 MCCB 207.95 250 3VA ETU 330 1.0XIn 7 6XIn 0.2XIn 0.2

2 2.0 Incomer-2 MCCB 207.95 250 3VA ETU 330 1.0XIn 7 6XIn 0.2XIn 0.2

3 3.0 Bus coupler MCCB 207.95 250 3VA ETU 330 0.9XIn 6 6XIn 0.2XIn 0.2

Page 6 of 6