Up-gradation of Konaban GGS and Pipeline Grid

Project of Tripura Asset

JOBPROCEDURE FOR
INSTALLATION ANDTESTING OF
ELECTRICAL WORKS

Doc.No.UKon-PGP/E&I-001 Rev.0

Project :Up-gradation of Konaban GGS and Pipeline Grid


Client :Oil and Natural Gas Corporation Ltd.
Contractor :KazStroy Services Infrastructure India Pvt. Ltd.
TPIA :ABS Industrial Verification (India) Pvt. Ltd.

o 20.04.2011 IssueforComments

Rev. Date PurposeofIssue Prep'd By Review'dBy App'dBy


INSTALLATION & TESTING OF
ELECTRICAL WORKS
Doc.No.:UKon-PGPIEI-001, Rev-O

TABLEOFCONTENTS

1.0 PURPOSE 3

2.0 SCOPE 3

3.0 REFERENCES 3

4.0 TERMS&DEFINITIONS 3

5.0 RESPONSIBILITIES 4

6.0 METHODOLOGY 5

7.0 HEALTH,SAFETYANDENVIRONMENT 12

8.0 QUALITYASSURANCEIQUALITYCONTROL 12

9.0 APPENDICESIFORMATS 12
INSTALLATION & TESTING OF
NN ELECTRICAL WORKS
Doc.No.:UKon-PGP/EI-001, Rev-O

1.0 PURPOSE

Thepurposeofthisdocumentistolaydownspecificguidelinesandrequirements
forElectricalworksinaccordancewithdrawingsandstandardstobeusedin the Up-
gradationofKonabanGGSandPipeline GridProjectofTripuraAsset
ConstructionWorkby KSS.

2.0 SCOPE

ThisProcedurecovers theworkmethodforelectricalworksinaccordancewith
drawingsandstandardstobeusedintheUp-gradationof KonabanGGSand
PipelineGridProjectof TripuraAssetConstructionWorkbyKSS.

Thescope ofworkincludesfacilitiesforpipelinenetworkfor.

A. 20" dia.pipelinefrom

I. ADBGGStoPalatanaterminal(53km)

B. 16"dia.Pipelinefrom

I. KonabanGGStoNimbutaliJunction(12km)
II. SonamuraGGStoPalatanaTerminal(22km),

C. 8"dia.Pipelinefrom

I. KunjabanManifoldtoADBGGS(18km)
II. SundalbariManifoldtoSonamuraGGS(12km),

D. 6"dia.Pipelinefrom

I. KunjabanManifoldto ADBGGS(18km)
II. SundalbariManifoldtoSonamuraGGS(12kM).

3.0 REFERENCES

Followingdocumentsintotalityorinpartshallformthereferencedocuments:

-, cificationforScopeof WorkandSupply(Electrical)
I,\ ;~ signandConstructionRequirementsForCrossCountryHydrocarbonPipelines
01SDB141.
GasTransmissionanddistributionPipingSystemASMEB31.8.

4.0 TERMS &DEFINITIONS


INSTALLATION &TE.STINGOF
'ELECTRICALWORKS
Doc.No.:UKonPGPIEl..o01, Rav..o

For the Purpose of this document, the term "shall" indicates a mandatory
requirementand"should"indtcatesarecommendedpractice.

,. AI.Itermsused inthedevelopmentofthis procedurearedefinedin a)

QualityAssuranceManual

b) ONGe'sSpecification

-.0 RE PO lBLUT

ProjectManagerShaHberesponsibleforqualityoJthejobandshall provide adequate


resources, tools and
infrastructuretoImplementthisprocedure. , I
I

ResidentConstructionManager - ShallreporttotheProjectManager.
Shall beresponsibleforoverallimplementation,
monitoring andcontrolofconstructionand
commissioningactivIties

QNQC ManagerIin-charge -ShallreporttoProjectMana.gerandHeadQA/QC


atH.O.
Shallbe responsibleforthecomplianceofthis
procedure.

OA/OCEngineer ShallreporttoQAlQC ManagerIln-charge.


Shallensureproperimplementationof this procedure.
Shallchecksandverifiestheactivities.
Shan beresponsibleforcustody,maintenance
calibrationandissuanceofaUmeasuringandtest
equipment.

SiteEngIneer ShallreporttotheResidentConstructionManager.
PreparationorElectrlcalwokschedulesaddressing
specificissuesandcharacteristicsofeach spread.
- Overallcontrolandsafetymanagementandforthe
[m~l~mentationof procedure a.ndsupe~. iSIS.e
activity.
Generationofreportsduringtheactivity. .
UoI"'~...._
Explainingiallother persons involvedin.,q::r1~!iMi"~:J:
worktobedonepriortostarttheactivity.

.,.H.SEOfficers Shall report to Resident Canst


Manager/Project Manageradministrativelyan
HOfortechnicalmatters.
Implementation of all safety requirementsduring
Electricalworkoperations
INSTALLATION&TESTINGOF
ELECTRICALWORKS
Doc.No.:UKon-PGP/EI"()01, Rev..()

Ensuringthatthecommunicationsystemisworking
properlyandthatemergencyequipmentisinplace.

6.0 METHODOLOGY

LAYINGOFCABLE

1. InspectionofcabledrumshallbecarriedoutforitsconformitywithONGCSpecs.
Beforepullingthecables.Cablesshallbelaidintrenches,cabletraysorconduits
asrequired.
2. Beforecablelaying,cableroutinggivenonthelayoutdrawingsshallbecheckedin
thefieldtoavoidinterferencewithstructures,heatresources,drains,piping,air
conditioningductetc.andminoradjustmentsifrequired,shallbedonetosuitthe
fieldconditionswithinformationtoONGC.
3. Cabledrumshallberolledinthedirectionindicationonthesideof thedrum.Care
should be taken to avoid sharp turns, tension, twists etc. in order to avoid
mechanicalinjuries to thecables.
4. Highvoltage,mediumvoltageandothercontrolcablesshallbeseparated from
eachotherbyadequatespacingorrunningthroughindependentpipes,trenches
orcablestrays,asapplicable.
5. Cablingforfirewatersystemshallbeasfaraspossibletakeninexclusiveroute
throughundergroundtrench.
6. Allcableroutes shallbecarefullymeasuredandcablescuttotherequiredlengths,
leavingsufficientlengthforthefinalconnectionofthecabletotheterminalofthe
equipment.Thequantityindicatedinthecablescheduleisonlyapproximate.
7. Allcableroutesshallbecarefullymeasuredandcablecuttotherequiredlength,
leavingsufficientlengthforterminationtoequipment.
8. Cablesshallbeneatly arrangedinthetrenches/traysinsuchamannerthatcriss
crossingisavoidedandfinaltakeofftothemotor/switchgearisfacilitated.Cable
routingbetweenlinedcabletrenchandequipment/motorsshallbetakenthrough
GIpipesleevesofadequatesize.
9. Allcableswillbeidentifiedclosetotheirterminationpointbycablenumbersas
perthecableschedule.
10.Directlyburiedcableshall belaidundergroundinexcavatedcabletrenches.
11.Beforethestartofcablelayingdrumscheduleshallbepreparedanditshallbe
followed&recorded.
12.Trenchesshallbeofsufficientdepthandwidthforaccommodationofallcables
correctlyspacedandarrangedwithaviewofheatdissipationandeconomyof design.
13. Minimumdepthofburiedcablestrenchshallbe900mmfor lowvoltage.The
'I. dthewidthofthetrenchshallvarydependinguponthenumberoflayers
'~bijIS..~.~ its" voltagegrade.
re lesrisefromtrenchestomotor,controlstation,lighting panelsetc.they
'4
be eninGIpipesformechanicalprotectionuptoaminimumof300mm
above Fe
&~ ~ lingstresslimitshall beobservedtopreventanydamagetocableduring
~~rQ .Thecablemanufacturer'sminimumbendingradiussh "be maintained, .JII

16. Segregation ofcabledrumandtracabilityshallbedoneint beor layi~~tl!~


thehel ofcableschedule,laoutdrawin s&ackin list 0
INSTALLATION&TESTINGOF
ELECTRICALWORKS
Doc.No.:UKonPGPIEI-001, Rev-O

I . Cable trenches, to be dug, should be according to specified length, width, and depth
asper theapproved construction drawings. Cable laying, dressinq, testing, qualified
workmen shalldocrimping &termination.
18. Cables shall beneatly arranged inthetrench/trays insuch amanner so that the
criss-crossing is avoided and final take off to equipment and local panels is facilitated.
19. To protect cable against dirt&moisture their ends shall besealed with aPVCor
Rubber hood (ifrequired).
20.AII Ihe specified tests for the cables shall be performed asper ONGC standards
andshould berecorded onapproved formats anddocumented properly.
21.Cable markers shall beusedaspertheONGC standards and Specification.

R HI. .I. LL IO~ /WORK

Earthing Materials

1. The earthing materials shall be checked for any damage caused during
transportation quantity withpacking list.
2. Allhardware used forearthing installation shall behotdip galvanized. Thickness
ofhotdipgalvanizing shallnotbelessthan75microns.
3. Theearthelectrode andearth plateshallbeasperONGC standard.

Earthing System and Lightning Protection

Installation, testing andcommissioning ofcomplete earthing system and lightning


protection including supply of all earthing materials and earthing accessories for
earthing system ofallequipments suppliedlinstalled bythecontractor, earthing of above
ground cathodically unprotected pipe linesatthepipeline terminal area.

Connections

1. Allelectrical equipment shall bedoubly earthed byconnecting twopoints oneach equipment


tothemainearthing ring.The earthing ringshall beconnected vialinks toseveral
earthelectrodes.
2. The earthing grid shall form closed loop with earth electrodes connected to the
gridWithdouble stripconnections.
3. In hazardous areas all major process equipment shall be connected to the earthing
ring by means of anti-looseninq connections and all pipelines will be bonded and
earthed on entering and exi11ngthebattery limits of process area as perONGC spec.
. 'htning down conductors shall bebrought toearth electrode inshortest path
asl'Sf", asible to minimize" Surge impedance". All hardware used for eart . ins~aJ~lion
shall behotdip galvanizedorzinc passivated. Spring she shall
eu edforearthing connections ofallequipments.

AUthecontacl surfaces ofelectrical equipment Iearthing wires should '~~ ~


foranytypeofgrease, paint,coating beforemaking earthing connections. ;;

6. Theearth loopImpedance toanypomtIntheelectrical system shallhave which


Willensure saustacto 0eration of rotecuve devices
I;NSTALLATION &T;ESTIN,G QIF
- - ---- - ----

ELECTR,ICALWORKS
~Doc.No.:UKon.PGPJEI-001. Rev..()

7. Resistance ofindividual earth electrodes shanbemeasured after disconnecting it


fromtheearthing gridasperspecifications andtheearthing resistance ofthegrid shan be
measured by connecting all electrodes to the grid' as per standard formats and itshould
beless thanone OHM.The earthing installations shallbe carried outinaccordance
withearthing 'layoutdrawings andspecifications.
8. Theearthing gridshaUformclosed loopwithearth electrodes connected tothe
gridwahdouble stripconnections.

9. Thefollowing shallbeearthed:
a)System neutral.
b)Current andPotential Transformer Secondary Neutral.
0)Lightning!arrestors.
d)Alltransformers, switchgear andtheirearth buses, busduct. e)Motor
frames. Etc
10.Lightning protection- shall be provided for the equipment, structures and
buildings which arehigher than20meters oraspertheriskindexanalysis worked out.
11. The shield wire shall be connected with main grid solidly andnot through
supporting steelstructures.
1i2. Lightjng fixtures shall be earthed through the extra core provided inthe lighting cable
forthispurpose.

Fir'eiOet.ectionand Alarm System

Installation, testing andcommissioning ofcomplete firedetection andalarm system.

1. Allmaterials willbestored inadryplaceafter receipt atsite.


2. Allmaterials willbechecked foridenUfication andquantity asperpacking list.
3. All smoke and heat detectors will be installed asper AFC drawings and vendor's
recommendations.
4. Wiring ofalldetectors wlllbedone asperdrawing (loopwise).
5. Installation of a'llMCPs/BGUs will be done as per AFC drawing at a height of
1200mm(toplevelofMCP) above f100rfFGL
6. Installation ofexitsigns, sirenslhoaters etcwHlbedone asperAFCdrawings.
7. FireAlarm panel/repeater panels will beinstalled asper AFC drawing andvendor
recommendations. Baseframe willbeprepared forfloormounted panelandforwall
mounted panels angle frame fastened towallwrthanchor fasteners orgrouted will beused.
8. Testing and commissioning will be done as per vendor's ITPand
recommendations.
9. Alln~?e~sary jnte~ocks as per,specificaUonwith othersystems(M~tep
co ltiamngetc)WIllbechecked andensured. ..\ A
,!t~,IZS u ,'\.. ~.~ .......
~,~--
,

~ ctrical' works (Applicable forintennediate SVCP'stations)


J)0
l'@ scope of supply installation, testing and cornrnissioninq of all at
~pmenVitems including those forcabling. fig.htning,earthing and lightning protClU\~!o.......J_
fdrv.arioUs types of Intermediate SVcum CPstations will include thefollowing but
limitedtothesame.
INSTAiLLATION &TESTING OF
ELECTR'liCAtWQ:RKS

UNINTERRUPTED POWER ,SUPPLY(UPS)

1. The equipment willbeshipped tositeandstored inadryplace.


2. Theswitchboard willbehandled withcare, avoiding impact totheequipment.
3. Ca.ble entries and floorsupporting,steelwork, l'evelingandcleanliness willbe checked
before transporting oftheUPSPanels.
4. Necessary mounting, base frame will be prepared and will be placed as per approved
layout drawings.
S. UPSPanelswillbeerected atthedesignated position asperapproved drawings.
6. Proper leveling ofbase frame wlUbeensured.
7. Proper alignment ofUPS Panels and fixing ofbase frame w.iththe mounting base frame
woul'dbedone.
B. All lose accessories and inter panel wiring will be completed as per the
manufacturer drawings.
9. Incoming power supply, battery bank connection and outgoing feeder cables will
beconnected aspertherelevant connection details.
10.Installation checks winbecarried outasperField Inspection Repo.rts.
11. Load Test and Battery Bank chatg,ing/disCharging will be carried out as per vendor's
ITP andrecommendations.

BatteryCharger

12. Cable entries andfloorsupporting steelwork leveling.andcleanness shallbe checked


before transporting ofthebatterycha.rger.
13. Necessary' rnountinq base frame will be prepared and will be placed as per Ii
approved layout drawings.
14. Batte.ry charger will be erected at the designated position as per approved
drawings.
15.Proper leveling ofbase frame wUlbeensured.
16.Proper alignment ofbattery charger and fixing of base frame with the mounting baseframe
would bedone.
17.All IOS9 accessories and inter panel wiring will' be completed as per the
manufacturer recommendation.
18.Incomingpower supply, battery bank connection andoutgoing feeder cables will
beconnected aspertherelevant connection details. ~
19.Installatio~ c~ec_ks,Will becar:nedou..tasperinspection testplan.
_ Precommlsslomng, checks wdlbedone asfollows: ., \
V
C
Il h " Check thecharger output voltage andbattery bankvoltage.
'I e After both these voltages reach the same level, allow the battery bank to trickle
lr
p charging across thefloat charger.
offall
o
breake
0,- w ,
e er
' of
I
f
tbe th
batte
ery b
charo
ger o
switst
ch c
for h
he ar
g
an
er
al fir
opest
rat a
n. n
.~ dt
Swith
ch e
on nt
the h
ef
inc
lo
mI at
g c
powh
er ar
su g
ply er
and.
che Ch
cke ec
d k
th
volt
ep
age ol
at ari
the ty
in att
ter he
min ba
als tte
onb ryt
atte er
mi
ry
na
char ls.
ger

S
W
i
t
c
h
o
n
t
IN.STALLAT,I,ON &TESTING'OF
ELECTRICALWORKS
Doc.No.:UKon,..pGPIEI001,Rev..o
K5

Switch overtotheautooperation ofthebatte,rycharger.


Check,fortheproper functioning ofallindication lampandalarms.
Check the functIoning of all modes of operations such as normal-autolmanual,
noaUboostcharging andfaultdiagnostics etc.asperinspection and:testplan.
a Alltestswillbecarried outatthesiteasperONGC spec.

'Battery Bank

1. FlOOring, cable entries and floor supporting steelwork will be checked, before transport
ofbatteries andother accessories.
2. Battery rackswillbeassembled asperapproved relevant.drawings.
3. Battery rackwillbepositioned aspertheapproved layoutdrawings.
4. Battery cells wHIbe placed onthe rack suitably soastopermit connection ofthe positive
andnegative terminals according tothewiring diagram.
5. Electrolyte willbeprepared aspervendor speeitlcation,
6,.. Electrolyte willbeadded intothebattery cells byusing aclean plastic funnel and
jug,fromthetopofvent.
7. Check the batterycells for electrolyte levels after 30 minutes and add the electrolyte,
if the level has dropped. Check specific gravity &cell'veltage before charging.
8. Ba.tterybankterminals willbeconnected tothecharging UPSorBatterycharger.
9. Polarity bechecked atthebattery terminals.
10. Itwinbeensured thatcell vent caps are inclosed position before charging,(Itwin:
beopenduring charging).
11. Battery bank charging/dischargingwill be conducted as per vendor
recommendations.

MVSWITCH GEARS

This specificationis intended to cover the receipt at site, installation, testing and
commissioning of medium voltage switchgear comprising of Power Control Centres (PCC).
Motor Control Centres (MCC), Power-cum-Motor Control Centres (PMCC) etc..
and c?mplete with all materials and accessories for efflcient and tfci't\bl~- e "
operatron. \.,_,....J.~. .
~~
a rnentwillbeshipped tositeandstored inadryplace. ,.;.
a wmmD.Qar~willbehandled withcare, avoiding,impact ~otheequipment. .~ -- ......-.
a es,''>~oor supporting steelwork &.Ievellng will be checked b
-6f WI Iflgear.
of ......tiqfidquipment(cranes/hydra)will be decided atsiteaspersize/weight'
-a tronprJhe equipment
P , ...eveuRg' ofbase framewillbeensured.
All loose wiring &accessories will be completed as per manufacturer
recommendation.
9
INSTALLATION&TESTINGOF
ELECTRICALWORKS
CocoNo.:UKon-PGPIEI-001, R.ov-O

All cubicles, switches, starters, CT &PT chambers, bus bar chamber will be cleaned
andchecked fortightness ofallthecomponents.
Inter-panel wiring/bus coupling will bedone at site as per interconnection details
andvendor recommendations.
Allloosely supplied itemswillbeinstalled aspervendor's recommendations.
Incoming cables willbeterminated inadressed manner andproper supporting for heavy
cables willbeensured.
Erection ofequipment willbeasper"Equlpment Layout" drawings.
Before equipment isfinally grouted, itwould beshown toCHentRepresentative for approval.
Electrical connections wiJIbemade asperconnections details.
Mechanical &Electrical operation ofbreaker, modules andinterlock shall be checked.
After termination, spare entrywillbeplugged withmetallic/PVC plugs.
Proper sizelugsandferrules would beprovided.
" Earthing ofaltequipment willbedone asperearthingdetails anddrawing.
Equipment shallbecleaned internally andexternally. "
Proper tightness ofboltsofbusbars willbeensured.
Testing andcommissioning would bedone asperField Inspection ReportsNendor
recommendations.
Allinterlocks asperschematic drawings/logic would bechecked.
Allindicating lampsandinstruments wlllbechecked forcorrect operation.
Earthing ofSwitchboard willbedone asperInstallation StandardsNendor
recommendations.

HIGH MIST LIGHTING SYSTEM

Thefoundation forthemastwillbeaspervendor recommendation.


Hydra/crane withboom length reaching 213rdofthetotal heightofmastwillbe
usedforerection.
Headframe, winch system andcabling willbeinstalled aspervendor drawings
andrecommendations.
Proper wiringandconnections willbeensured.
Feeder pillerwillbeinstalled withaground clearance of300mm.
Testing andcommissioning willbecarried outandobservations willbe recorded
andsigned bycontractor andTPl/Client asperFieldInSp.~tion
Report. ~
Luxlevelwillbechecked andrecorded aspervendor specification. ~~
\z'},~~-
(}~ ...~.

~
9 "~,
specification isintended tocover theInstallation andcornmlssienlnq atsiteof
medium voltage motors withallmaterials andaccessories forefflcrent andtrouble
freeoperation.
INSTALLATIO &TESTING OF
N ELECTRICA WORKS
L Doc.No.:UKonPGPlEl"()O1,Rev..()
Motorswillbeshipped tositesafely andstored inadryplace.
Useoferection equipment(cranes, hydraetc)willbedoneaspersizeand location
ofthemotors.

Motors willbeinstalled atsitewithproper alignment todriven equipment asper


layoutdrawings andTagNos.

Cable termination willbedonewithproper sizedglands andlugswithdue


consideration toareaclassification andinstallation standards.
Noload runwillbeconducted andobservations willberecorded andsigned by
Contractor andTPl/Client asperField Inspection Reports.
Ifrequired lubrication ofbearings andgearswillbecarried outbyVendor
recommended lubricants.
load runofmotors willbedone andobservations willberecorded &signed during
malcommissioning.
Interlocks andindications willbeprovided asperrequirement.
Earthing ofmotors/frame would bedone asperinstallation standards.

DC- ACConverter

Cable entries, floor supporting steelwork &leveling will be checked before transport
ofDC-to-DC converter system cabinet.
Proper leveling ofbaseframe willbeensured.
All loose wiring &accessories will be completed as per manufacturer
recommendanon.
Check outvoltage oftheconverter.
Incoming power supply, battery bank oonnection &outgoing feeder cables willbe checked.
Verification ofmaterial willbedoneasperpacking list.Anypartmissing/damaged would
bereported immediately
Erection ofequipment willbeasper "Equipment Layout" drawings.
Before equipment isfinally grouted, itwould beshown toClient Representative for approval.
Electrical connections willbemadeasperconnections details.
After terrninanon, spare entrywillbeplugged WithmetalliclPVC plugs.
Proper sizelugsandferrules would beprovided.
Earthing ofallequipment willbedone asperearthing details anddrawing.
Equipment shallbecleaned internally andexternally.
Testing andcornmissioninq would bedone aspervendor recommendations.

STATUTORY APPROVAL OFELECTRICAL INSTALLATION

Therequired statutory approval fromconcerned Electncal Authority shall be


obtained forallelectrical Installations andsubmitted toABS IONGC.
~-

INSTALLATION&TESTINGOF
ELECTRICALWORKS
Doc.No.:UKon-PGPIEI..()01,Rev..()

Note: Incase ofanyconflict between thisprocedure andcontract specification, the


latershallprevail.

.0 HEALTH SAFETY AND ENVIRONMENT

AllPPEisamustinthisactivity.
Onlytrained personnel tobedeployed forthisactivity.
Personnel around mustbeinformed evacuated toasafedistance.
AllMeasurin9 &TestEquipments used mustbewellmaintained.
Regular awareness program shallbearranged.
KSSshallarrange firstaidbox.

8.0 QUALITY ASSURANCE J QUALITY CONTROL

Quality Assurance willbe maintained by systematic implementation of this


procedure andgenerating necessary quality records.

9.0 APPENDICESAND FORMATS

Appendix: 01 ITP-Battery
(UKON-PGPJE&IIITP-01 Rev0)

Appendix: 02 ITP-Installation ofEarthin g


(UKON-PGPfE&I/ITP-02 Rev0)

Appendix: 03 ITP- Battery Charger


(UKON-PGP/E&IIITP-03 Rev0)

Appendix: 04 ITP- Installation Emergency Switch Board


ofAC&(UKON- Rev0)
PGP/E&IJITP-04
Appendix: 05 ITP- Lighting System
(UKON-PGP/E&I/ITP-05 Rev0)

Appendix: 06 ITP- UninterruptedPow er Supply


(UKON-PGPfE&I/ITP-06 Rev0)

Appendix: 07 ITP- Cable Laying


(UKON-PGP/E&IIITP-07 Rev0)

Appendix: 08 ITP-Miscellaneous Electr ical Equipment


(UKON-PGP/E&I/ITP-08 Rev0)

Format: 01 Commissioning Test Report Cable


(UKON-PGP/E&IIFM-01 Rev0)

Format: 02 Commissioning Test ReportBattery Discharge


(UKON-PGP/E&IIFM-02 Rev0)

Format 03 Cornrnisslon'nq Test ReportUPS


INSTALLATION &TESTING OF
ELECTRICAL WORKS
Doc.No.:UKonPGPIEI-001, Rev-O

(UKON-PGP/E&I/FM-03Rev0)

Format: 04 InspectionReportLighting
(UKON-PGP/E&IIFM-04Rev0)

Format: 05 InspectionTestReportEarthing
(UKON-PGP/E&I/FM-05Rev0)

Format: 06 InspectionTestReportSwitchBoards
(UKON-PGP/E&I/FM-06Rev0)

Format: 07 IRValueofLighting
(UKON-PGP/E&IIFM-07Rev0)

Format: 08 IlluminationLevel
(UKON-PGP/E&IIFM-08Rev0)

Format: 09 InspectionReportMisc.Elect.EquipmentInstallation
(UKON-PGP/E&I/FM-09Rev0)

Format: 10 InspectionTestReportEarthingWorkS
(UKON-PGP/E&IIFM-10Rev0)

Format: 11 InspectionReportCable
(UKON-PGP/E&I/FM-11Rev0)

Format: 12 Commissioning TestReportBattery Charger,


Rectifier,DCtoDC Converter
(UKON-PGP/E&IIFM-12Rev0)

Format: 13 CommissioningTestReportPotentialTransformer
(UKON-PGP/E&I/FM-13Rev0)

Format: 14 InspectionreportACDC EmergencySwitchBoards


(UKON-PGP/E&IIFM-14Rev0)

Format: 15

Format: 16

IRValueofCable
(UKON-PGP/E&IIFM-17Rev0)