Você está na página 1de 2

Technical Data Bulletin

M1002- 30198

Micro 1002/1002E
Special Hazard Control Panel
The Micro 1002/1002E Control Panel is supplied
with the following standard features:

C Two Class A or Class B supervised detection zones


programmable for single zone or cross zone detection
C One Class A or Class B manual station input
C One Class A or Class B abort station input programmable
to four different options
C Two Class B supervised solenoid outputs
C Supervisory input option
C Two Class A or Class B alarm outputs
C Pre-discharge timer
C Auxiliary relay card option
C Battery volt / ammeter option

Description

The Chemetron Fire Systems Micro 1002/1002E Two Class A or B indicating Alarm Circuits and two Class
Control Panel has been designed as a compact control B Releasing Solenoid outputs are also provided.
center for Special Hazard Fire Protection System For single solenoid systems, the second release
applications. The microprocessor based unit is suitable circuit is programmable to provide a dedicated Supervi-
to perform detection and control functions associated sory Input for Trouble Only indications.
with the following: The Micro 1002/1002E is supplied premounted in a
C NFPA 12 High Pressure CO2 Systems Nema 1 enclosure with a hinged door. It includes an
C NFPA 12A Halon 1301 Systems integral 24 VDC standby battery system capable of pro-
C NFPA 72 Local Signaling Systems viding in excess of 90 hours of battery back-up service.
C NFPA 2001 Clean Agent Systems Optional modules available for the Micro 1002/ 1002E
The Micro 1002/1002E features four power limited include:
inputs that are Class A or Class B supervised: Two C Volt / Ammeter Module to monitor the battery volt-
detection zones, suitable for smoke detectors, thermal age and the battery charging current.
detectors and normally open alarm initiating devices. C Zone Relay Board to provide an additional Alarm and
The detection zones are programmable for single zone Trouble contact as well as independent contacts that
or cross zone detection. Inputs are also provided for transfer in conjunction with each of the Indicating
Manual Station actuation and Programmable Abort Alarm outputs and Releasing outputs.
Switch operation.

Ordering Information

Shipping Weight
Stock Number Description Size (Inches) lbs (kgs)
70100702 Micro 1002 Control Panel, 120 VAC 16 x 14.5 x 5 16 (7.3)
70100744 Micro 1002E Control Panel, 230 VAC, 50 Hz 16 x 14.5 x 5 16 (7.3)
70100700 Volt / Ammeter Module 1 (.45)
70100699 Zone Relay Board 1 (.45)
70100320 Battery 12V, 7AH 5.94 x 3.7 x 2.56 6 (2.7)

1998 Chemetron Fire Systems. All rights reserved (3/98). Chemetron Fire Systems is a registered trademark.
Technical Data Bulletin
M1002- 30198

Distributed by
The seller makes no warranties, express or implied,
including, but not limited to, the implied warranties of
merchantability and fitness for a particular purpose, except
as expressly stated in seller's sales contract or sales
acknowledgment form.

4801 Southwick Drive, 3rd Floor


Matteson, IL 60443
708/748-1503
Fax 708/748-2847

1998 Chemetron Fire Systems. All rights reserved (3/98). Chemetron Fire Systems is a registered trademark.