Relion 630 series

Feeder protection and control


REF630
Flexibility for demanding utility and
industrial power distribution systems
Extensive earth-fault protection for
distribution networks

REF630 is a comprehensive feeder management relay The 630 series relays are equipped with a large graphical
for protection, control, measurement and supervision in display which can show customizable single-line diagrams
utility and industrial power distribution systems, including (SLD) with position indication for the circuit breaker,
radial, looped and meshed distribution networks, with disconnectors and the earthing switch. Also measured values
or without distributed power generation. REF630 is also can be displayed. The SLDs can be flexibly adjusted to meet
ideal for feeder bay control. user requirements using PCM600.

Application The 630 series HMI is distinguished by fifteen three-color


REF630 has been designed to be the main protection LEDs and five configurable push buttons, which can be
for overhead lines and cable feeders, in either isolated used as control buttons for various tasks such as blocking,
neutral, resistance-earthed, compensated or effectively adjusting setting groups or triggering the disturbance
earthed distribution networks. There are four pre-defined recorder. The five push buttons can also be conveniently
configurations, designed to match the most typical feeder used as menu shortcuts. Another distinguishing feature is the
protection and control requirements and intended for open/ detached HMI, as an option to the integrated HMI, which is
closed ring feeder applications, radial overhead/mixed line highly beneficial from a wiring perspective due to the large
feeder applications, ring/meshed feeder applications and bus number of IOs the 630 series relays are equipped with.
sectionalizers. The pre-defined configurations can be used
as such or easily tailored to application-specific requirements Standardized communication
with freely selectable functions. REF630 fully supports the IEC 61850 standard for communi-
cation in substations. The feeder management relay also
REF630 can be used in either single or double-busbar supports the DNP3 (TCP/IP) and 60870-5-103 communication
applications with one or two breakers and numerous protocols, and is able to use two communication protocols
switching devices. It also supports a substantial number simultaneously. The supported communication protocols,
of both manually and motor-operated disconnectors and including IEC 61850, offer seamless connectivity to various
earthing switches. Consequently, REF630 can be used to station automation and SCADA systems.
control various types of switchgears.
The implementation of the IEC 61850 standard in REF630
The earth-fault protection has been significantly extended, covers both vertical and horizontal communication, including
now including not only directional and non-directional, GOOSE messaging according to IEC 61850-8-1 with both
transient/intermittent, wattmetric and admittance-based but binary and analog signals. Analog GOOSE messaging
also both harmonics-based and multifrequency admittance- enables fast transfer of analog measured values over the
based earth-fault protection. The new additions take the station bus. This facilitates, for example, sharing of RTD input
earth-fault protection to new heights, creating an extensive values such as surrounding temperature with other relays.
earth-fault protection portfolio. In addition, the sensitivity of GOOSE messaging is an alternative to traditional hardwiring
the intermittent earth-fault protection has been significantly signaling for exchanging interlocking information between
improved and reactive power undervoltage protection added. the relays. For time-critical applications, REF630 supports
synchronization over Ethernet using SNTP or over a separate
REF630 also includes a fault locator which locates short bus using IRIG-B.
circuits in radial distribution networks and earth faults in
effectively and low-resistance earthed ones. If the fault current 630 series
is as high as or higher than the load current, earth faults in REF630 is a member of ABBs Relion product family and
isolated neutral distribution networks will also be located. part of its 630 protection and control series. The 630 series
relays are characterized by functional scalability and flexibile
The pre-configurations can be tailored to meet the application configurability, and have been designed to unleash the full
requirements using the IEC 61850-compliant protection and potential of the IEC 61850 standard for communication and
control IED manager PCM600. interoperability of substation automation devices. In addition
to REF630, the 630 series includes the following relays:
Human-machine Interface (HMI)
As a member of the Relion product family, REF630 shares RET630 Transformer protection and control
the same Human Machine Interface (HMI) look and feel as the REM630 Motor protection and control
other Relion protection and control relays and IEDs. The same REG630 Generator protection and control
look and feel includes the location of a push button with a
certain function and the menu structure.

2 Feeder protection and control | REF630


UL1UL2UL3
Uo

REF630 FEEDER PROTECTION AND CONTROL IED


Preconfiguration B for radial overhead/mixed line feeder
PRE-
CONFIGURATION
B

PROTECTION LOCAL HMI *) ALSO AVAILABLE

- 5 prog. push buttons on LHMI


1 1 - Disturbance and fault recorders
IO - IED self-supervision
94 - Local/Remote push button on LHMI
- Sequence event recorder
- User management
- WebHMI

2 AND
3I OR
I2> I2/I1> 3Ith>F 3I>>>
46 46PD 49F 50P/51P *) Fixed or detached LHMI is available.

1 1 2
3I>/Io>BF 3I> 3I>>
CONDITION MONITORING COMMUNICATION
51BF/51NBF 51P-1 51P-2
AND SUPERVISION
Protocols: 1 0 1 0 0 0 1 1
1 1 1 1 IEC 61850-8-1 1 0 1 1 0 0 1 0
3I2f> FUSEF CBCM E IEC 60870-5-103 1 1 0 0 1 1 1 0
68 60 CBCM E DNP3 1 0 1 1 0 1 1 0
1 0 1 0 0 0 1 1
1 0 1 1 0 0 1 0
Interfaces:
UL1UL2UL3 1 1 3
Ethernet: TX (RJ45), FX (LC)
MCS 3I OPTS TCS
Serial: Serial glass fiber (ST),
MCS 3I OPTM TCM
Serial plastic fiber
(snap-in connector)
Io 1 2
Io>>> Io> Io>> Io> U<>
50N/51N 51N-1 51N-2 67N-1 U<>

Uo
CONTROL AND INDICATION 1) MEASUREMENT
3
Z< FLOC Yo> Object Ctrl 2) - I, U, Io, Uo, P, Q, E, pf, f
21, 21P, 21N 21FL 21YN - Symmetrical components
CB 2 - Limit value supervision
3 3 DC
8
3U< Po> Q>, 3U< ES Analog interface types B
27 32N 32Q, 27 1)
Check availability of binary inputs/outputs Current transformer 51)
from technical documentation
3 2 2 2 2)
Control and indication function for Voltage transformer 4
P> U2> U1> U1< primary object
1)
One of available current transformer
32R/32O 47O- 47O+ 47U+ inputs is sensitive (0.1 / 0.5 A)

3 3 2 1 1
Io>HA 3U> Uo> 3I> OI SYNC PQM3I PQM3Upe
51NHA 59 59G 67-1 79 25 PQM3I PQM3Vpg

3I>> Io> Io>IEF Io>Y PQM3Upp


67-2 67N-2 67NIEF 67YN PQM3Vpp

6 5 5 5
UFLS/R f> df/dt> f< PQMUBU PQMU
81LSH 81O 81R 81U PQMUBV PQMV

16 2
MAP SOTF
MAP SOTF
REMARKS
Optional 2 No. of instances enabled
function by default

Function(s) not enabled by 1 No. of instances not enabled


default in preconfiguration, by default in preconfiguration,
can be enabled afterwards can be enabled afterwards

REF630 functional overview of the pre-configuration B.

REF630 | Feeder protection and control 3


REF630 feeder protection and
control pre-configurations
Pre-configurations
Description Pre-configuration
Pre-configuration A for open/closed ring feeder A
Pre-configuration B for radial overhead/mixed line feeder B
Pre-configuration C for ring/meshed feeder C
Pre-configuration D for bus sectionalizer D
Maximum number of instances available n

Supported functions with codes and symbols


Functionality IEC 61850 IEC 60617 ANSI A B C D n
Protection
Three-phase non-directional overcurrent, low stage PHLPTOC 3I> 51P-1 1 1 1 1 1
Three-phase non-directional overcurrent, high stage PHHPTOC 3I>> 51P-2 2 2 2 2 2
Three-phase non-directional overcurrent, instantaneous stage PHIPTOC 3I>>> 50P/51P 1 1 1 1 1
Three-phase directional overcurrent, low stage DPHLPDOC 3I> 67-1 2 - - - 2
Three-phase directional overcurrent, high stage DPHHPDOC 3I>> 67-2 1 - - - 1
Non-directional earth-fault, low stage EFLPTOC I0> 51N-1 - 1 - 1 1
Non-directional earth-fault, high stage EFHPTOC I0>> 51N-2 1 1 1 1 1
Non-directional earth-fault, instantaneous stage EFIPTOC I0>>> 50N/51N - 1 - 1 1
Directional earth-fault, low stage DEFLPDEF I0> 67N-1 2 1 3 - 3
Directional earth-fault, high stage DEFHPDEF I0>> 67N-2 1 - 1 - 1
Transient/intermittent earth-fault INTRPTEF I0> IEF 67NIEF 1 - - - 1
Admittance-based earth-fault EFPADM Yo> 21YN - - - - 3
Multifrequency admittance-based earth-fault MFADPSDE Yo> Y 67YN - - - - 1
Wattmetric earth-fault WPWDE Po> 32N - - - - 3
Harmonics-based earth-fault HAEPTOC Io>HA 51NHA - - - - 1
Negative-sequence overcurrent NSPTOC I2> 46 2 2 2 2 2
Three-phase thermal overload for feeder T1PTTR 3Ith>F 49F 1 1 1 - 1
Phase discontinuity PDNSPTOC I2/I1> 46PD 1 1 1 - 1
Three-phase current inrush detection INRPHAR 3I2f> 68 1 1 1 1 1
Three-phase overvoltage PHPTOV 3U> 59 - - 3 - 3
Three-phase undervoltage PHPTUV 3U< 27 - - 3 - 3
Positive-sequence overvoltage PSPTOV U1> 47O+ - - - - 2
Positive-sequence undervoltage PSPTUV U1< 47U+ - - - - 2
Negative-sequence overvoltage NSPTOV U2> 47O- - - - - 2
Residual overvoltage ROVPTOV U0> 59G - - 3 - 3
Directional reactive power undervoltage DQPTUV Q>-->,3U< 32Q, 27 - - - - 2
Reverse power / Directional overpower DOPPDPR P> 32R/32O - - - - 3
Frequency gradient DAPFRC df/dt> 81R - - - - 5
Overfrequency DAPTOF f> 81O - - - - 5
Underfrequency DAPTUF f< 81U - - - - 5
Load-shedding LSHDPFRQ UFLS/R 81LSH - - - - 6
Fault locator SCEFRFLO FLOC 21FL - - - - 1
Circuit breaker failure CCBRBRF 3I>/I0>BF 51BF/51NBF 1 1 1 1 2
Autoreclosing DARREC OI 79 1 1 1 - 2
Tripping logic TRPPTRC IO 94 1 1 1 1 2
Distance protection DSTPDIS Z< 21, 21P, 21N - - 1 - 1
Automatic switch onto fault logic CVRSOF SOTF SOTF - - 1 - 2
Multipurpose analog protection MAPGAPC MAP MAP - - - - 16
Protection-related functions
Local accelerat. logic DSTPLAL LAL LAL - - 1 - 1
Communication logic for residual overcurrent RESCPSCH CLN 85N - - 1 - 1
Scheme communic. logic DSOCPSCH CL 85 - - 1 - 1
Current reversal and WEI logic CRWPSCH CLCRW 85CRW - - 1 - 1
Current reversal and WEI logic for residual overcurrent RCRWPSCH CLCRWN 85NCRW - - 1 - 1

4 Feeder protection and control | REF630


Supported functions with codes and symbols
Functionality IEC 61850 IEC 60617 ANSI A B C D n
Control
Bay control QCCBAY CBAY CBAY 1 1 1 1 1
Interlocking interface SCILO 3 3 4 4 4 1 10
Circuit breaker/disconnector control GNRLCSWI I O CB/DC I O CB/DC 4 4 4 1 10
Circuit breaker DAXCBR I O CB I O CB 1 1 1 1 2
Disconnector DAXSWI I O DC I O DC 3 3 3 - 8
Local remote switch interface LOCREM R/L R/L - - - - 1
Synchrocheck SYNCRSYN SYNC 25 - - - - 1
Generic process I/O
Single point control (8 signals) SPC8GGIO - - - - - - 5
Double point indication DPGGIO - - - - - - 15
Single point indication SPGGIO - - - - - - 64
Generic measured value MVGGIO - - - - - - 15
Logic Rotating Switch for function selection and
SLGGIO - - - - - - 10
LHMI presentation
Selector mini switch VSGGIO - - - - - - 10
Pulse counter for energy metering PCGGIO - - - - - - 4
Event counter CNTGGIO - - - - - - 1
Supervision and monitoring
Runtime counter for machines and devices MDSOPT OPTS OPTM - - - - 1
Circuit breaker condition monitoring SSCBR CBCM CBCM 1 1 1 1 2
Fuse failure supervision SEQRFUF FUSEF 60 1 1 1 - 2
Current circuit supervision CCRDIF MCS 3I MCS 3I 1 1 1 - 2
Trip-circuit supervision TCSSCBR TCS TCM 3 3 3 3 3
Station battery supervision SPVNZBAT U<> U<> - - - - 1
Energy monitoring EPDMMTR E E - - - - 1
Measured value limit supervision MVEXP - - - - - - 40
Power quality
Voltage variation PHQVVR PQMU PQMV - - - - 1
Voltage unbalance VSQVUB PQMUBU PQMUBV - - - - 1
Current harmonics CMHAI PQM3I PQM3I - - - - 1
Voltage harmonics phase-to-phase VPPMHAI PQM3Upp PQM3Vpp - - - - 1
Voltage harmonics phase-to-earth VPHMHAI PQM3Upe PQM3Vpg - - - - 1
Measurement
Three-phase current CMMXU 3I 3I 1 1 1 1 1
Three-phase voltage (phase-to-earth) VPHMMXU 3Upe 3Upe 1 1 1 1 2
Three-phase voltage (phase-to-phase) VPPMMXU 3Upp 3Upp - - - - 2
Residual current RESCMMXU I0 I0 1 1 1 1 1
Residual voltage RESVMMXU U0 Vn 1 1 1 - 1
Power monitoring with P, Q, S, power factor, frequency PWRMMXU PQf PQf 1 1 1 1 1
Sequence current CSMSQI I1, I2 I1, I2 1 1 1 1 1
Sequence voltage VSMSQI U1, U2 V1, V2 1 1 1 1 1
Disturbance recorder function
Analog channels 1-10 (samples) A1RADR ACH1 ACH1 1 1 1 1 1
Analog channel 11-20 (samples) A2RADR ACH2 ACH2 - - - - 1
Analog channel 21-30 (samples) A3RADR ACH3 ACH3 - - - - 1
Analog channel 31-40 (calc val) A4RADR ACH4 ACH4 - - - - 1
Binary channels 1-16 B1RBDR BCH1 BCH1 1 1 1 1 1
Binary channels 17-32 B2RBDR BCH2 BCH2 1 1 1 1 1
Binary channels 33-48 B3RBDR BCH3 BCH3 1 1 1 1 1
Binary channels 49-64 B4RBDR BCH4 BCH4 1 - 1 - 1
Station communication (GOOSE)
Binary receive GOOSEBINRCV - - - - - - 10
Double point receive GOOSEDPRCV - - - - - - 32
Interlock receive GOOSEINTLKRCV - - - - - - 59
Integer receive GOOSEINTRCV - - - - - - 32
Measured value receive GOOSEMVRCV - - - - - - 60
Single point receive GOOSESPRCV - - - - - - 64

REF630 | Feeder protection and control 5


Contact us

For more information see REF630 Product Guide

Copyright 2014 ABB. All rights reserved.


or contact us:

ABB Oy Medium Voltage Products,


Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone: +358 10 22 11
Fax: +358 10 22 41094

www.abb.com/substationautomation