AVC63-4 and AVC63-4D Voltage Regulators

AVC63-4 and AVC63-4D


Automatic
Voltage Regulators

AVC63-4D AVC63-4

Using enhanced technology, the AVC63-4 and AVC63-4D voltage


regulators are designed for use on 50/60Hz brushless generators.
These potted regulators are economical, small in size, ruggedly
constructed, and incorporate solid state technology with frequency
compensation, automatic voltage build-up, overexcitation shutdown and
EMI filtering as standard.

FEATURES:
Integrated circuitry for compact size, simplicity, high reliability.
Extremely rugged. FEATURES and
Exciter field current 4A continuous, 7A forcing. APPLICATIONS
this page
Regulation accuracy better than 1.0% no load to full load.
Fast response.
DESCRIPTION and
Frequency compensation. SPECIFICATIONS
Overexcitation shutdown. Pages 2 and 3
EMI suppression. INTERCONNECT
CSA certified. Page 3
UL recognized.
DIMENSIONS
GOST-R certified #POCC US.ME05.B03392. Page 4

ADDITIONAL INFORMATION
INSTRUCTION MANUAL
Request Publication 9166800890

SVC-4
4-07
P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A. 62249 PHONE 618-654-2341 FAX 618-654-2351
AVC63-4 and AVC63-4D Voltage Regulators

DESCRIPTION:
The AVC63-4 and AVC63-4D voltage regulators main- model, the adjustment potentiometers are accessible
tain generator line voltage no load to full load on from the bottom side (label side) of the controller.
brushless generators from 5kW to over 100kW in size. Holes drilled through the terminal box (per Fig. 6) will
These voltage regulators sense generator average allow the user to adjust the potentiometers as needed.
voltage to sustain a precise regulation band within For applications where it is necessary to limit access
1% throughout the operating temperature range. to the adjustment potentiometers, the AVC63-4 would
This is accomplished by converting a 240Vac single be a suitable selection. This is because the AVC63-4
phase power input to a controlled DC output signal. voltage regulator provides adjustments from the
The solid-state voltage build-up circuit allows auto- component side of the controller (per Fig. 4). When
matic generator line voltage build-up with as low as mounted in a generator's terminal box, the controller's
6Vac residual voltage applied to the regulator's input potentiometers are accessible.
power circuit.
The overexcitation feature assists in protecting the
Customer accessible adjustments for stability, under- voltage regulator during a prolonged overexcitation
frequency and the voltage regulation set point are pro- condition. During this mode, a shutdown signal is sent
vided to allow the controller to be tuned to the desired to the power stage, turning off the regulator. This
performance. The location of these adjustments is feature will reset automatically when the generator
different depending on which model is selected. Both voltage drops below 6Vac for a minimum of 2 seconds.
the AVC63-4 and the AVC63-4D are intended to be
mounted inside the generator's terminal box. For appli- Figure 1 demonstrates the underfrequency characteris-
cations that require the voltage regulator adjustments tics of the voltage regulator during prime mover low
to be made from outside of the terminal box, the speed conditions. Customer curve selection matches
AVC63-4D should be considered. On this particular the voltage regulator to 50 or 60 Hz systems.

Figure 1a - Frequency Compensation Characteristic, Figure 1b - Frequency Compensation Characteristic,


60Hz 50Hz

SPECIFICATIONS:
EXCITER
SENSING/POWER
DC OUTPUT FIELD
INPUT
RESISTANCE
MAX FORCING
MAX. 1 MIN MIN. SINGLE
MAX. PHASE
CONT. (240 Vac INPUT) OHMS @
VOLTAGE
BURDEN
OHMS
25C RANGE
AMP VOLT AMP VOLT
4 63 7 100 15 100 171-264Vac 500VA

2
AVC63-4 and AVC63-4D Voltage Regulators

SPECIFICATIONS (continued):
DC OUTPUT POWER: 4 Adc at 63 Vdc maximum VOLTAGE BUILDUP: Internal provisions for automatic
continuous, 7 Adc at 100 Vdc one minute forcing. voltage buildup from generator residual voltages as low
(Forcing with 240 Vac nominal input). as 6 Vac.

EXCITER FIELD DC RESISTANCE: 15 ohms mini- TERMINATIONS: 1/4 Fast-On Terminals.


mum; 100 ohms maximum.
POWER DISSIPATION: 8 Watts maximum.
AC SENSING/POWER INPUT: Operating range:
190-240 Vac single phase 10%, 50/60 Hz 10%. OPERATING TEMPERATURE: -40C (-40F) to
Burden 500VA. +60C (+140F).

VOLTAGE ADJUST RANGE: 171-264 Vac. STORAGE TEMPERATURE: -65C (-85F) to +85C
(+185F).
REGULATION ACCURACY: Better than 1.0%
no load to full load. VIBRATION: Withstands 1.3 Gs at 5 to 26 Hz; 0.036
double amplitude at 27 to 52 Hz; and 5 Gs at 52 to
RESPONSE TIME: Less than 1.5 cycles for 5% 1000 Hz.
change in sensing voltage.
SHOCK: Withstands up to 20 Gs in each of three
EMI SUPPRESSION: Internal electromagnetic mutually perpendicular axes.
interference filtering.
WEIGHT: 8 oz. (0.22 kg) Net.
OVEREXCITATION SHUTDOWN: Field voltage shuts
down after time delay if exciter field voltage exceeds
100 Vdc 5%. The time delay is inversely proportional
to the magnitude of the detected overvoltage condition ACCESSORY
up to the 135 Vdc point, thus allowing nominal forcing
for approximately 1 minute. Beyond 135 Vdc, the field Remote Adjustment Rheostat: 1000 ohm, 2W rheostat
voltage is removed within 2.0 seconds. with locking slotted shaft, Basler Electric P/N 17727.

Figure 2 - Typical Interconnection Diagram, Figure 3 - Jumper Locations


208/240Vac Nominal

3
AVC63-4 and AVC63-4D Voltage Regulators

Figure 4 - AVC63-4 Potentiometer Control Locations Figure 5 - AVC63-4D Potentiometer Control


Locations

Figure 6 - Outline and Drilling Drawing

P.A.E. Les Pins, 67319 Wasselonne Cedex FRANCE Route 143, Box 269, Highland, Illinois U.S.A. 62249 1300 North Zhongshan Road, Wujiang Economic Development Zone
Tel +33 3.88.87.1010 Fax +33 3.88.87.0808 Tel +1 618.654.2341 Fax +1 618.654.2351 Suzhou, Jiangsu Province, P.R. China 215200
e-mail: beifrance@basler.com e-mail: info@basler.com Tel +86(0)512 6346 1730 Fax +86(0)512 6346 1760
e-mail: beichina@basler.com
www.basler.com Printed in U.S.A.

Você também pode gostar