1. Haga el cuadro de cargas y calcule: La MD, POTENCIA CONTRATADA E ITM del sistema de
B.T.

CUADRO DE CARGAS
POT. INST. MD FP T Inon Idis RT RM KA
ITEM DESCRIPCIN GENERAL F.D
KW KW V A A A
5 MATJA 300 HP 08 POLOS 243 0.8 195 0.77 460 396.1 495.125 0.629 5.28 7.00
6 MATJA 500 HP 04 POLOS 401 0.8 321 0.87 460 578.5 723.125 0.723 6.42 7.40
7 MATJA 350 HP 02 POLOS 284 0.8 227 0.9 460 396.05 495.025 0.6286 5.28 7.00
8 SERV AUXILIARES FP=0,78 295 0.85 251 0.78 460 474.69 593.36 0.7535 4.51 5.0
9 CONDOMINIO MD=155 FP=0,83 182 0.85 155 0.83 460 275.21 344.013 0.688 4.33 5.24
10 CENTRO DE COMP FP=TECNICO 30 1 30 0.96 460 39.22 49.025 0.7844 4.7 5.0
TOTAL 1435 1178
FACTOR DE AMPLIACIN 1.15 CARACTERISTICAS DEL SUMINISTRO
FACTOR DE POTENCIA 0.85
POTENCIA DEL TRANSFORMADOR CALCULADO 1594
POTENCIA DEL TRANSFORMADOR KVA 1600
FACTOR DE SIMULTANEIDAD 0.65
933.07
POTENCIA CONTRATADA 933

2. Dimensione y seleccione el transformador - caractersticas electromecnicas ms


importantes

CARACTERISTICAS DEL FUNCIONAMIENTO DEL TRAFO


POTENCIA NOMINAL 1600 KVA
FRECUENCIA 60HZ
BAO DE
TIPO DE TRANSFORMADOR ACEITE
TENSION NOMINAL PRIMARIA 10KV
TENSION NOMINAL SECUNDARIA 0,46KV
3. Hacer el clculo de la corriente de corto circuito en los puntos A, B y C.

HALLAMOS LA CORRIENTE DE CORTOCIRCUITO EN EL PUNTO A

650
= = .
310

= 1.5 = .

0.65
= 562902 = .
20446

HALLAMOS LA CORRIENTE DE CORTOCIRCUITO EN EL PUNTO B

1.1 102 2
= = 0.1692 = (0.1 )2 + 1.005
650

0.1692
= = 0.1683 , = 0.01683
1.005

= 0.01683 + 0.1683

= 1.35(0.078 + 0.2091) = 0.301269.54

= + = 0.466974.84

10
= = .
3 0.4669

HALLAMOS LA CORRIENTE DE CORTOCIRCUITO EN EL PUNTO C


= 4.62 0.582 = 4.56

102
= (0.0058 + 0.0456) ( ) = 2.8782.75 10
1.6

= + = 0.466974.84 + 2.8782.75

= 3.3381.65 10

. 462
460 = 3.33 ( ) = 0.00756 460
102

. 46
= = .
3 0.00756

4. Hacer el clculo de la corriente de corto circuito en el punto D y E.

HALLAMOS LA CORRIENTE DE CORTOCIRCUITO EN EL PUNTO D.

35074625.84 3000016.26
= +
3 4600.90.92 3 4600.96

= 434.5

= 1.25 = 543.125

0.03091857435.50.9100
= = 8.53%
460400

Entonces el Cable ser: ()

= (0.0661 + 0.0943) 0.185 = 0.01223 + 0.01746 = 0.0213260

= + = 0.02861.87

. 46
= = .
3 0.028767
HALLAMOS LA CORRIENTE DE CORTOCIRCUITO EN EL PUNTO E.

Corriente del MATJA 350 HP 02 POLOS

350746
= = 395.78
3 4600.90.92

=1.25 = 494.73A

0.0309457395.780.9100
= = 3.14%
460240

Entonces el Cable ser: ()

= (0.1 + 0.0967) 0.045 = 0.0045 + 0.00435 = 0.0062644

= + = 0.03458.64

. 46
= = .
3 0.034

5. Dimensione y seleccione el cable ptimo de M.T

POR CAPACIDAD

1600
= = = . = 1.25 = .
3 310

= 63010.780.950.81 = .

> > > Por lo tanto cumple

POR CAIDA DE TENSION


= 3. . . ( + ) = 0.85 , = 31.8 , = 0.956

= 3 92.376 1.35 (0.078 0.85 + 0.2091 0.53) = 38.26

38.26
% = 100 % = . %
10000

< < < % Por lo tanto cumple

POR ESFUERZO TERMICO

20446
= 3002 = .
0.65

= 53.209 , = 12.367

> Por lo tanto cumple

6. Hallar estos cables alimentadores tipo N2XH triple para alimentar el TD (a 185 m
de TG). Ducto

35074625.84 3000016.26
= +
3 4600.90.92 3 4600.96

= 434.5

= 1.25 = 543.125

0.03091857435.50.9100
= = 8.53%
460400

el Cable ser: ()
7. Hallar estos cables alimentadores tipo N2XH triple para alimentar el MATJA de 350
HP 2 polos. Ducto

Corriente del MATJA 350 HP 02 POLOS

350746
= = 395.78
3 4600.90.92

=1.25 = 494.73A

0.0309457395.780.9100
= = 3.14%
460240

El Cable ser: ()

8. Hacer la compensacin centralizada en el punto C. Cables en ducto.

Hallamos la suma de corrientes de todas las cargas:

= 2.154533.04

Ahora hallamos Potencia total

= 321544606 cos(33.04) = 1439

Hallamos Q terico

= 1439(tan 33.04 tan 9.936)

= 683.85

Hallamos

480 2
= 683.85 ( ) = 744.6 745
460
Hallamos

460 2
= 745 ( ) = 684.21
480

Hallamos
684.21
= / 3 = = 858.76
3460

= 858.76

() = 1.3 = 1116.31

() = 1250

() = 1.4 = 1202

el cable:

( ) ; = . = A