The v7.x ABR driver can communicate with a SLC 5 or PLC 5 using a ControLogix Gateway. The gateway holds modules that
allow the SCADA server and your SLC 5 or PLC 5 to communicate with each other. The exact modules you need depends on
the hardware you are connecting. In general, 1756-DHRIO modules communicate with Data Highway Plus (DH+) devices and
1756-ENET modules communicate with Ethernet devices.
For example, if you want to communicate with a PLC 5 or SLC 5/03 on a Data Highway Plus (DH+) network, you need a KTX
or KTXD interface card in your SCADA server and two 1756-DHRIO modules in the ControLogix Gateway, as the following
figure shows.
However, if you want to communicate from an Ethernet network to a DH+ network, you can cable your hardware as shown
below.
To establish communication with a ControLogix Gateway
3. Select the RSLinx driver that you configured for the interface card.
NOTE: You should be able to communicate with the far end of the second DHRIO module by expanding the RSLinx tree
browser.