IEEE Std C37.121-2012
(Revision of
IEEE Std C37.121-1989)

IEEE Guide for SwitchgearUnit


SubstationRequirements

Sponsor

Switchgear Committee
of the
IEEE Power and Energy Society

Approved 5 December 2012


IEEE-SA Standards Board

Approved 28 October 2014


American National Standards Institute

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
Abstract: The basis for the coordination of equipment in unit substations by assisting in the
selection of components is intended as the use of this guide. A variety of designs for unit
substations are possible using various combinations of incoming sections, transformer sections,
outgoing sections, and transition sections. It is intended that the incoming, outgoing, transformer,
and transition sections included in a unit substation meet the basic requirements of applicable
industry standards for those sections. This guide covers three-phase unit substations for step-
down operation in the range of 112.5 kVA or greater at primary voltages of 601 V through 38 kV.

Keywords: control, dead-front switchboard, distribution, fuse, IEEE C37.121, metal-clad


switchgear, metal-enclosed switchgear, metering, mobile unit substation, molded-case circuit
breaker, motor control center, power circuit breaker, primary unit substation, radial substation,
rectifier-type substation, secondary selective substation, secondary unit substation, spot-network
substation, substation, surge protection, switchgear, transformer, transition section, unit
substation

The Institute of Electrical and Electronics Engineers, Inc.


3 Park Avenue, New York, NY 10016-5997, USA

Copyright 2013 by the Institute of Electrical and Electronics Engineers, Inc.


All rights reserved. Published 22 February 2013. Printed in the United States of America.

IEEE is a registered trademark in the U.S. Patent & Trademark Office, owned by the Institute of Electrical and Electronics
Engineers, Incorporated.

National Electrical Code and NEC are both registered trademarks of the National Fire Protection Association, Inc.

PDF: ISBN 978-0-7381-8186-8 STD98116


Print: ISBN 978-0-7381-8187-5 STDPD98116

IEEE prohibits discrimination, harassment and bullying. For more information, visit http://www.ieee.org/web/aboutus/whatis/policies/p9-26.html.
No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior written permission
of the publisher.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
Notice and Disclaimer of Liability Concerning the Use of IEEE Documents: IEEE Standards documents are developed
within the IEEE Societies and the Standards Coordinating Committees of the IEEE Standards Association (IEEE-SA)
Standards Board. IEEE develops its standards through a consensus development process, approved by the American National
Standards Institute, which brings together volunteers representing varied viewpoints and interests to achieve the final product.
Volunteers are not necessarily members of the Institute and serve without compensation. While IEEE administers the process
and establishes rules to promote fairness in the consensus development process, IEEE does not independently evaluate, test, or
verify the accuracy of any of the information or the soundness of any judgments contained in its standards.

Use of an IEEE Standard is wholly voluntary. IEEE disclaims liability for any personal injury, property or other damage, of
any nature whatsoever, whether special, indirect, consequential, or compensatory, directly or indirectly resulting from the
publication, use of, or reliance upon any IEEE Standard document.

IEEE does not warrant or represent the accuracy or content of the material contained in its standards, and expressly disclaims
any express or implied warranty, including any implied warranty of merchantability or fitness for a specific purpose, or that
the use of the material contained in its standards is free from patent infringement. IEEE Standards documents are supplied "AS
IS."

The existence of an IEEE Standard does not imply that there are no other ways to produce, test, measure, purchase, market, or
provide other goods and services related to the scope of the IEEE standard. Furthermore, the viewpoint expressed at the time a
standard is approved and issued is subject to change brought about through developments in the state of the art and comments
received from users of the standard. Every IEEE standard is subjected to review at least every ten years. When a document is
more than ten years old and has not undergone a revision process, it is reasonable to conclude that its contents, although still of
some value, do not wholly reflect the present state of the art. Users are cautioned to check to determine that they have the
latest edition of any IEEE standard.

In publishing and making its standards available, IEEE is not suggesting or rendering professional or other services for, or on
behalf of, any person or entity. Nor is IEEE undertaking to perform any duty owed by any other person or entity to another.
Any person utilizing any IEEE Standards document, should rely upon his or her own independent judgment in the exercise of
reasonable care in any given circumstances or, as appropriate, seek the advice of a competent professional in determining the
appropriateness of a given IEEE standard.

Translations: The IEEE consensus development process involves the review of documents in English only. In the event that
an IEEE standard is translated, only the English version published by IEEE should be considered the approved IEEE standard.

Official Statements: A statement, written or oral, that is not processed in accordance with the IEEE-SA Standards Board
Operations Manual shall not be considered the official position of IEEE or any of its committees and shall not be considered to
be, nor be relied upon as, a formal position of IEEE. At lectures, symposia, seminars, or educational courses, an individual
presenting information on IEEE standards shall make it clear that his or her views should be considered the personal views of
that individual rather than the formal position of IEEE.

Comments on Standards: Comments for revision of IEEE Standards documents are welcome from any interested party,
regardless of membership affiliation with IEEE. However, IEEE does not provide consulting information or advice pertaining
to IEEE Standards documents. Suggestions for changes in documents should be in the form of a proposed change of text,
together with appropriate supporting comments. Since IEEE standards represent a consensus of concerned interests, it is
important to ensure that any responses to comments and questions also receive the concurrence of a balance of interests. For
this reason, IEEE and the members of its societies and Standards Coordinating Committees are not able to provide an instant
response to comments or questions except in those cases where the matter has previously been addressed. Any person who
would like to participate in evaluating comments or revisions to an IEEE standard is welcome to join the relevant IEEE
working group at http://standards.ieee.org/develop/wg/.

Comments on standards should be submitted to the following address:

Secretary, IEEE-SA Standards Board


445 Hoes Lane
Piscataway, NJ 08854
USA

Photocopies: Authorization to photocopy portions of any individual standard for internal or personal use is granted by The
Institute of Electrical and Electronics Engineers, Inc., provided that the appropriate fee is paid to Copyright Clearance Center.
To arrange for payment of licensing fee, please contact Copyright Clearance Center, Customer Service, 222 Rosewood Drive,
Danvers, MA 01923 USA; +1 978 750 8400. Permission to photocopy portions of any individual standard for educational
classroom use can also be obtained through the Copyright Clearance Center.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
Notice to users

Laws and regulations


Users of these documents should consult all applicable laws and regulations. Compliance with the
provisions of this standard does not imply compliance to any applicable regulatory requirements.
Implementers of the standard are responsible for observing or referring to the applicable regulatory
requirements. IEEE does not, by the publication of its standards, intend to urge action that is not in
compliance with applicable laws, and these documents may not be construed as doing so.

Copyrights
This document is copyrighted by the IEEE. It is made available for a wide variety of both public and
private uses. These include both use, by reference, in laws and regulations, and use in private self-
regulation, standardization, and the promotion of engineering practices and methods. By making this
document available for use and adoption by public authorities and private users, the IEEE does not waive
any rights in copyright to this document.

Updating of IEEE documents


Users of IEEE Standards documents should be aware that these documents may be superseded at any time
by the issuance of new editions or may be amended from time to time through the issuance of amendments,
corrigenda, or errata. An official IEEE document at any point in time consists of the current edition of the
document together with any amendments, corrigenda, or errata then in effect. In order to determine whether
a given document is the current edition and whether it has been amended through the issuance of
amendments, corrigenda, or errata, visit the IEEE-SA Website at http://standards.ieee.org/index.html or
contact the IEEE at the address listed previously.

For more information about the IEEE Standards Association or the IEEE standards development process,
visit IEEE-SA Website at http://standards.ieee.org/index.html.

Errata
Errata, if any, for this and all other standards can be accessed at the following URL:
http://standards.ieee.org/findstds/errata/index.html. Users are encouraged to check this URL for errata
periodically.

Patents
Attention is called to the possibility that implementation of this standard may require use of subject matter
covered by patent rights. By publication of this standard, no position is taken by the IEEE with respect to
the existence or validity of any patent rights in connection therewith. If a patent holder or patent applicant
has filed a statement of assurance via an Accepted Letter of Assurance, then the statement is listed on the
IEEE-SA Website at http://standards.ieee.org/about/sasb/patcom/patents.html. Letters of Assurance may
indicate whether the Submitter is willing or unwilling to grant licenses under patent rights without

iv
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
compensation or under reasonable rates, with reasonable terms and conditions that are demonstrably free of
any unfair discrimination to applicants desiring to obtain such licenses.

Essential Patent Claims may exist for which a Letter of Assurance has not been received. The IEEE is not
responsible for identifying Essential Patent Claims for which a license may be required, for conducting
inquiries into the legal validity or scope of Patents Claims, or determining whether any licensing terms or
conditions provided in connection with submission of a Letter of Assurance, if any, or in any licensing
agreements are reasonable or non-discriminatory. Users of this standard are expressly advised that
determination of the validity of any patent rights, and the risk of infringement of such rights, is entirely
their own responsibility. Further information may be obtained from the IEEE Standards Association.

v
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
Introduction

This introduction is not part of IEEE Std C37.121-2012, IEEE Guide for SwitchgearUnit SubstationRequirements.

C37.121-1989 was originally developed by a working group sponsored by the Power Switchgear
Assemblies Technical Committee of the Switchgear Section (8SG) of the National Electrical Manufacturers
Association (NEMA/SG/5). The document was transferred from NEMA to the IEEE Power and Energy
Society Switchgear Committee, Switchgear Assemblies Subcommittee, in January of 2003. IEEE Std
C37.121 was reaffirmed by the IEEE Standards Association Standards Board in 2006.

The Switchgear Assemblies Subcommittee Task Force, created to review this document, determined that
this document did not meet the intent of a standard as it references applicable IEEE Standards for all
requirements that must be met by each component of a Unit Substation. Based on this review, the Task
Force recommended that this document be changed from a Standard to a Guide. The recommendation was
accepted by the Switchgear Assemblies Subcommittee.

In the revision of this document from a standard to a guide, the document has been revised to reflect needed
technical changes and to update the reference documents to the latest revisions. Other significant changes
are as follows:

Subclauses 1.1 and 1.3 of IEEE Std C37.121-1989 have been combined to form the Scope and
subclauses 1.2 and 1.4 have been combined to form the Purpose of the new document.
Clause 2, Normative references, has been changed to remove dates and all informative standard
references have been moved to Annex A.
Clause 3, Definitions, has been arranged in alphabetical order.
Table 1 has been redrawn and Table 2 through Table 5 have been combined into a new Table 2
Primary unit substation transformers and Table 3Secondary unit substation transformers.
Metal-enclosed bus as described in IEEE Std C37.23 has been added to Clause 6Incoming
section, Clause 7Outgoing section, 11.2Unusual service conditions, and 11.5.2Loading
guides.
All of the existing referenced figures in Clause 6, Clause 7, and Clause 10 have been redrawn, and
moved into their respective sections. Figures that had previously shown a fused and unfused figure
have now been combined to show a figure with a fuse (when used) designation.
Clause 8, Ratings, has been updated to reflect the latest rating names and definitions.

vi
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
Participants
At the time this guide was submitted to the IEEE-SA Standards Board for approval, the C37.121 Working
Group had the following membership:

James Smith, Chair


Douglas Edwards, Vice-Chair

P. Barnett D. Hrncir A. Morgan


Paul Barnhart A. Jivanani Charles Morse
J. Baskins Harry Josten Ted Olsen
Ted Burse M. Lafond R. Parthasarathi
L. Farr D. Lemmerman A. Patel
M. Flack A. Livshitz P. Sullivan
Keith Flowers D. Mazumdar C. Tailor
S. Gohil S. Meiners J. Toney

The following members of the individual balloting committee voted on this guide. Balloters may have
voted for approval, disapproval, or abstention.

William Ackerman Scott Hietpas Bansi Patel


Peter Balma Andrew Jones Christopher Petrola
Paul Barnhart Harry Josten Iulian Profir
Robert Beavers John Kay Robert Puckett
George Becker Chad Kennedy Reynaldo Ramos
Steven Bezner Yuri Khersonsky John Roach
Wallace Binder Joseph L. Koepfinger Michael Roberts
Ted Burse Jim Kulchisky Thomas Rozek
William Bush Saumen Kundu Bartien Sayogo
William Byrd Chung-Yiu Lam Gil Shultz
Stephen Conrad Albert Livshitz Veselin Skendzic
Gary Donner Frank Mayle James Smith
Edgar Dullni Kenneth McClenahan James Smith
Douglas Edwards Gary Michel Jeremy Smith
Gary Engmann Georges Montillet Jerry Smith
Patrick Fitzgerald Charles Morse Gary Stoedter
Keith Flowers Jerry Murphy James Swank
Frank Gerleve K. R. M. Nair David Tepen
David Gilmer Dennis Neitzel Wayne Timm
Mietek Glinkowski Arthur Neubauer Joe Uchiyama
James Graham Michael S. Newman John Vergis
Randall Groves Joe Nims Yingli Wen
Timothy Hayden Ted Olsen Kenneth White
Jeffrey Helzer Lorraine Padden Larry Yonce
Gary Heuston Mirko Palazzo Jian Yu

vii
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
When the IEEE-SA Standards Board approved this guide on 5 December 2012, it had the following membership:

Richard H. Hulett, Chair


John Kulick, Vice Chair
Robert Grow, Past Chair
Konstantinos Karachalios, Secretary

Satish Aggarwal Alexander Gelman Oleg Logvinov


Masayuki Ariyoshi Paul Houz Ted Olsen
Peter Balma Jim Hughes Gary Robinson
William Bartley Young Kyun Kim Jon Walter Rosdahl
Ted Burse Joseph L. Koepfinger* Mike Seavey
Clint Chaplin David J. Law Yatin Trivedi
Wael Diab Thomas Lee Phil Winston
Jean-Philippe Faure Hung Ling Yu Yuan

*Member Emeritus
Also included are the following nonvoting IEEE-SA Standards Board liaisons:

Richard DeBlasio, DOE Representative


Michael Janezic, NIST Representative

Catherine Berger
IEEE Standards Program Manager, Document Development

Erin Spiewak
IEEE Program Manager, Technical Program Development

viii
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
Contents

1. Overview .................................................................................................................................................... 1
1.1 Scope ................................................................................................................................................... 1
1.2 Purpose ................................................................................................................................................ 2

2. Normative references.................................................................................................................................. 2

3. Definitions .................................................................................................................................................. 4

4. Service conditions ...................................................................................................................................... 5


4.1 General ................................................................................................................................................ 5
4.2 Usual service conditions ...................................................................................................................... 5
4.3 Unusual service conditions .................................................................................................................. 6

5. Transformer section .................................................................................................................................... 6


5.1 Primary unit substation transformers ................................................................................................... 6
5.2 Secondary unit substation transformers ............................................................................................... 7

6. Incoming section ........................................................................................................................................ 7


6.1 High-voltage (or primary) bushings on the transformer cover ............................................................ 7
6.2 Primary terminal chamber on the transformer ..................................................................................... 8
6.3 Metal-enclosed bus .............................................................................................................................. 8
6.4 Metal-clad or metal-enclosed switchgear ............................................................................................ 8
6.5 Metal-enclosed interrupter switchgear ................................................................................................. 9
6.6 Cutout, fuse, or fuse link.....................................................................................................................10

7. Outgoing section........................................................................................................................................11
7.1 Metal-clad switchgear .........................................................................................................................11
7.2 Metal-enclosed interrupter switchgear ................................................................................................11
7.3 Metal-enclosed bus .............................................................................................................................11
7.4 Metal-enclosed, low-voltage, power circuit breaker switchgear ........................................................11
7.5 Molded-case, circuit-breaker, dead-front switchboards ......................................................................11
7.6 Motor control centers..........................................................................................................................12

8. Ratings .......................................................................................................................................................12
8.1 Rated power frequency .......................................................................................................................12
8.2 Rated kVA ..........................................................................................................................................12
8.3 Rated high voltage (or primary voltage) and rated low voltage (or secondary voltage) .....................12
8.4 Rated continuous current ....................................................................................................................12
8.5 Rated short-time withstand current .....................................................................................................12
8.6 Rated momentary withstand current ...................................................................................................13
8.7 Rated power frequency withstand voltages ........................................................................................13
8.8 Rated lightning impulse withstand voltage (BIL) ...............................................................................13

9. Construction ..............................................................................................................................................13
9.1 Phase and polarity arrangements ........................................................................................................13
9.2 Phase sequence ...................................................................................................................................14
9.3 Metal barriers......................................................................................................................................14
9.4 Interlocks ............................................................................................................................................14
9.5 Grounding ...........................................................................................................................................14
9.6 Nameplates .........................................................................................................................................14
9.7 Drawings Diagrams Instructions ..................................................................................................15

ix
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
9.8 Coordination .......................................................................................................................................15

10. Typical arrangements ..............................................................................................................................16


10.1 Primary unit substations ...................................................................................................................16
10.2 Secondary unit substations ...............................................................................................................18

11. Guide for selection, application, installation and maintenance of unit substations .................................22
11.1 Application considerations ...............................................................................................................22
11.2 Unusual service conditions ...............................................................................................................22
11.3 System conditions .............................................................................................................................22
11.4 Location transformer selection ......................................................................................................23
11.5 Load requirements ............................................................................................................................23
11.6 Miscellaneous design considerations ................................................................................................24
11.7 Installation, field-testing, operation, and maintenance .....................................................................26

Annex A (informative) Bibliography ............................................................................................................29

x
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Guide for SwitchgearUnit
SubstationRequirements

IMPORTANT NOTICE: IEEE Standards documents are not intended to ensure safety, health, or
environmental protection, or ensure against interference with or from other devices or networks.
Implementers of IEEE Standards documents are responsible for determining and complying with all
appropriate safety, security, environmental, health, and interference protection practices and all
applicable laws and regulations.

This IEEE document is made available for use subject to important notices and legal disclaimers.
These notices and disclaimers appear in all publications containing this document and may
be found under the heading Important Notice or Important Notices and Disclaimers
Concerning IEEE Documents. They can also be obtained on request from IEEE or viewed at
http://standards.ieee.org/IPR/disclaimers.html.

1. Overview

1.1 Scope

This guide covers three-phase unit substations for step-down operation in the range of 112.5 kVA or greater
at primary voltages of 601 V through 38 kV.

This guide does not cover the following installations:

a) Substations in which the transformer section includes load-tap-changing equipment.


b) Substations in which the transformer section is described and defined as network, subway,
vault, or underground in IEEE Std C57.12.24 [B14] and IEEE Std C57.12.40 [B18].
c) Substations in which the transformer section is described and defined as pad-mounted in
ANSI C57.12.22 and IEEE Std C57.12.27 [B16].
d) Gas-insulated substations as described in IEEE Std C37.122 [B13].
e) Rectifier-type substations.
f) Mobile unit substations.
g) Installations in ships, watercraft, railway rolling stock, aircraft, or automotive vehicles.
h) Installations for mines.

1
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

i) Installations of railways for generation, transformation, transmission, or distribution of power used


exclusively for operation of rolling stock, or for installations used exclusively for signaling and
railway communication purposes.
j) Installations of communication equipment that is under the exclusive control of communication
utilities, located outdoors or in building spaces used exclusively for such installations.
k) Installations under the exclusive control of electric utilities for the purpose of communication, or
metering; or for the generation, control, transformation, transmission, and distribution of electric
energy located in buildings used exclusively by utilities for such purposes or located outdoors on
property owned or leased by the utility or on public highways, streets, roads, etc; or outdoors by
established rights on private property.

1.2 Purpose

The guide is intended for use as the basis for the coordination of equipment in unit substations by assisting
in the selection of components. A variety of designs for unit substations are possible using various
combinations of incoming sections, transformer sections, outgoing sections, and transition sections.

It is intended that the incoming, outgoing, transformer, and transition sections included in a unit substation
shall meet the basic requirements of applicable industry standards for those sections. In addition, this guide
provides suggested requirements when used as part of a unit substation.

2. Normative references
The following referenced documents are indispensable for the application of this document (i.e., they must
be understood and used, so each referenced document is cited in text and its relationship to this document is
explained). For dated references, only the edition cited applies. For undated references, the latest edition of
the referenced document (including any amendments or corrigenda) applies.

ANSI C37.51, American National Standard for SwitchgearMetal-Enclosed Low-Voltage AC Power


Circuit Breaker Switchgear AssembliesConformance Test Procedures. 1

ANSI C84.1, American National Standard for Electric Power Systems and EquipmentVoltage Ratings
(60 Hz). 2

ANSI/UL 845, Motor Control Centers. 3

ANSI/UL 891, Dead-Front Switchboards.

IEEE Std C37.010, IEEE Application Guide for AC High-Voltage Circuit Breakers Rated on a
Symmetrical Current Basis. 4, 5

IEEE Std C37.20.1, IEEE Standard for Metal-Enclosed Low-Voltage Power Circuit Breaker Switchgear.

1
NEMA publications are available from Global Engineering Documents, 15 Inverness Way East, Englewood, CO 80112, USA.
(http://global.ihs.com).
2
ANSI publications are available from the Sales Department, American National Standards Institute, 25 West 43rd Street, 4th Floor,
New York, NY 10036, USA (http://www.ansi.org ).
3
UL Standards are available from Comm-2000, 1414 Brook Drive, Downers Grove, IL 60515, USA (http://www.comm-2000.com ).
4
IEEE publications are available from the Institute of Electrical and Electronic Engineers, Service Center, 445 Hoes Lane, Piscataway,
NJ 08854, USA (http://www.standards.ieee.org ).
5
The IEEE standards or products referred to in this clause are trademarks of the Institute of Electrical and Electronics Engineers, Inc.

2
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

IEEE Std C37.20.2, IEEE Standard for Metal-Clad Switchgear.

IEEE Std C37.20.3, IEEE Standard for Metal-Enclosed Interrupter Switchgear.

IEEE Std C37.23, IEEE Standard for Metal-Enclosed Bus.

IEEE Std C37.24, IEEE Guide for Evaluating the Effect of Solar Radiation on Outdoor Metal-Enclosed
Switchgear.

IEEE Std C37.40, IEEE Standard Service Conditions and Definitions for High-Voltage Fuses,
Distribution Enclosed Single-Pole Air Switches, Fuse Disconnecting Switches, and Accessories.

IEEE Std C57.12.00, IEEE Standard General Requirements for Liquid-Immersed Distribution, Power,
and Regulating Transformers.

IEEE Std C57.12.01, IEEE Standard General Requirements for Dry-Type Distribution and Power
Transformers Including Those with Solid Cast and/or Resin Encapsulated Windings.

IEEE Std C57.12.10, IEEE Standard Requirements for Liquid-Immersed Power Transformers.

IEEE Std C57.12.51, IEEE Standard for Ventilated Dry-Type Power Transformers, 501 kVA and Larger,
Three-Phase, with High-Voltage 601 V to 34 500 V; Low-Voltage 208Y/120 V to 4160 VGeneral
Requirements.

IEEE Std C57.12.52, Standard for Sealed Dry-Type Power Transformers, 501 kVA and Larger, Three-
Phase, with High-Voltage 601 to 34500 Volts, Low-Voltage 208Y/120 to 4160 VoltsGeneral
Requirements.

IEEE Std C57.91, IEEE Guide for Loading Mineral-Oil-Immersed Transformers.

IEEE Std C57.94, IEEE Recommended Practice for Installation, Application, Operation, and
Maintenance of Dry-Type General Purpose Distribution and Power Transformers.

IEEE Std C57.96, IEEE Guide for Loading Dry-Type Distribution and Power Transformers.

IEEE Std C57.142, IEEE Guide to Describe the Occurrence and Mitigation of Switching Transients
Induced by Transformers, Switching Device, and System Interaction.

IEEE Std C62.22, IEEE Guide for the Application of Metal-Oxide Surge Arresters for Alternating
Current Systems.

NEMA C37.57, SwitchgearMetal-Enclosed Interrupter Switchgear AssembliesConformance Testing.

NEMA C37.55, SwitchgearMedium-Voltage Metal-Clad AssembliesConformance Test Procedures.

NFPA 70, National Electrical Code (NEC). 6

NFPA 70B, Recommended Practices for Electrical Equipment Maintenance.

UL 1562, Transformers, Distribution, Dry-TypeOver 600 Volts.

6
The NEC is published by the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269, USA
(http://www.nfpa.org ). Copies are also available from the Institute of Electrical and Electronics Engineers, 445 Hoes Lane,
Piscataway, NJ 08854, USA (http://standards.ieee.org ).

3
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

3. Definitions
For the purposes of this document, the following terms and definitions apply. The IEEE Standards
Dictionary: Glossary of Terms & Definitions should be referenced for terms not defined in this clause. 7

articulated unit substation: A unit substation in which the incoming, transforming, and outgoing sections
are manufactured as one or more subassemblies intended for connection in the field.

barrier: A partition within the enclosure and part of the contained equipment, used for the insulation or
isolation of electric circuits or electric arcs.

conformance tests: Certain performance tests to demonstrate compliance with the applicable standards.
The test specimen is normally subjected to all planned routine tests prior to initiation of the conformance
test program.

NOTEThe conformance tests may, or may not, be similar to certain design tests. Demonstration of margin
(capabilities beyond the standards) is not required. 8
design tests: Tests performed to determine the adequacy of the design of a particular type, style, or model
of any unit of equipment, or its component parts, to meet its assigned ratings and to operate satisfactorily
under normal service conditions or under any specified conditions. Such tests may also be used to
demonstrate compliance with applicable standards of the industry.

NOTE 1Design tests are performed on representative apparatus or prototypes to verify the validity of design analysis
and calculation methods, and to substantiate the ratings assigned to all other apparatus of basically similar design.
These tests are not intended to be performed on every design or during normal production. The applicable portion of
these design tests may also be used to evaluate modifications of a previous design to assure that performance has not
been adversely affected. Test data from previous similar designs may be used for current designs when appropriate.
Once made, design tests need not be repeated unless the design is so changed as to modify performance.

NOTE 2Design tests are sometimes called type tests.


enclosure: A surrounding case or housing used to provide a degree of protection to the enclosed conductors
or equipment, and to provide a degree of protection to personnel against incidentally contacting live parts.

high voltage: A general term that pertains to the primary voltage, or primary-voltage side, of a transformer
or of a unit substation.

incoming section: Equipment that includes necessary mechanical and electrical connecting parts for
coordination in a unit substation on the high-voltage (or primary) side of a transformer section.

low voltage: A general term that pertains to the secondary voltage, or secondary-voltage side, of a
transformer or of a unit substation.

other tests: Tests, so identified in individual product standards, that may be specified by the user in
addition to routine tests. (Examples: Impulse; insulation power factor; audible sound)

outgoing section: Equipment that includes necessary mechanical and electrical connecting parts for
coordination into a unit substation on the low-voltage (or secondary) side of a transformer section.

primary unit substation: A unit substation in which the low-voltage section is rated above 1000 V.

7
The IEEE Standards Dictionary: Glossary of Terms & Definitions is available at http://shop.ieee.org.
8
Notes in text, tables, and figures are given for information only and do not contain requirements needed to implement the standard.

4
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

production tests: Tests performed during production for quality control by the manufacturer(s) on every
device, or on representative samples, or on parts or materials, as required to verify that the manufactured
product meets the design specifications and applicable standards.

NOTE 1Certain quality assurance tests on identified critical parts of repetitive high-production devices may be
performed on a planned statistical sampling basis.

NOTE 2Production tests are sometimes called routine tests.


secondary unit substation: A unit substation in which the low-voltage section is rated 1000 V and below.

substation: An assemblage of equipment in which the incoming, transforming, and outgoing sections are
manufactured as one or more subassemblies, through which electric energy in bulk is passed for the
purpose of switching or modifying its characteristics.

transformer section: A three-phase power transformer used for step-down operation that includes
necessary mechanical and electrical connecting parts for coordination in a unit substation.

transition (throat) section: A mechanical, electrical, and coordinated connection between a transformer
section and an incoming section, or between a transformer section and an outgoing section, or between
different types of incoming sections, or between different types of outgoing sections. A transition (throat)
section may be:
a) Integral parts of two adjacent sections,
b) An integral part of one section, or
c) A separate section.
unit substation: A substation consisting primarily of one or more transformers that are mechanically and
electrically connected to, and coordinated in design with, incoming and outgoing equipment.
NOTEFor this guide, the term unit substation shall be limited to mean articulated unit substation only.

4. Service conditions

4.1 General

A variety of designs for unit substations are possible using various combinations of incoming sections,
transformer sections, and outgoing sections. The design of individual sections of a unit substation must be
compatible with the service conditions in which they are applied.

4.2 Usual service conditions

Unit substations conforming to this guide should be suitable for operation at their nameplate ratings under
the following usual conditions:

a) Temperature
1) The effect of solar radiation is negligible. (The principles stated in IEEE Std C37.24 may be
used for guidance.)
2)  
  
  
qC except that, when the transformer is liquid-
immersed, the minimum temperature of the liquids uppermost layers is qC.

5
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

3) The maximum ambient air temperature is +40qC.


4) The average ambient air temperature in any 24-hour period is not more than +30qC.
b) Altitude. The maximum altitude is 1000 m (3300 ft). See IEEE Std C37.20.1, IEEE Std C37.20.2,
IEEE Std C37.20.3, and IEEE Std C57.12.00 or IEEE Std C57.12.01 for corrections to dielectric
strength and continuous-current rating at altitudes greater than 1000 m (3300 ft).

4.3 Unusual service conditions

For unit substations that are to be applied under conditions other than those in 4.2, see 11.2 for guidance.

5. Transformer section
Transformer sections should meet the requirements of this guide and shall comply with the requirements of
their applicable standards, including the standard kVA ratings listed in Table 1. Furthermore, the rated high
voltage and rated low voltage shall be used in combination with the standard kVA ratings that are listed in
Table 2 and Table 3. Primary unit substation transformers should be of the types in 5.1. Secondary unit
substation transformers should be of the types in 5.2.

5.1 Primary unit substation transformers

5.1.1 Liquid-immersed without load-tap-changing

These transformers shall meet the following requirements:

a) Voltage and kVA combinations as indicated in Column 1, Column 2, and Column 5 of Table 2
b) The requirements of IEEE Std C57.12.10 and IEEE Std C57.12.36 [B17]

5.1.2 Liquid-immersed with load-tap-changing

These transformers are not covered in this guide.

5.1.3 Ventilated dry-type, including those with solid-cast or resin-encapsulated windings

These transformers shall meet the following requirements:

a) Voltage and kVA combinations as indicated in Column 1, Column 2, and Column 3 of Table 2
b) The requirements of IEEE Std C57.12.01 and IEEE Std C57.12.50 and the requirements for solid
cast-resin units

5.1.4 Sealed dry-type

These transformers shall meet the following requirements:

a) Voltage and kVA combinations as indicated in Column 1, Column 2, and Column 4 of Table 2
b) The requirements of IEEE Std C57.12.01, IEEE Std C57.12.52, and UL 1562

6
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

5.2 Secondary unit substation transformers

5.2.1 Liquid-immersed without load-tap changing


These transformers shall meet the following requirements:

a) Voltage and kVA combinations as indicated in Column 1, Column 2, and Column 5 of Table 3
b) The requirements of IEEE Std C57.12.10 and IEEE Std C57.12.36 [B17]

5.2.2 Ventilated dry-type, including those with solid-cast or resin-encapsulated windings

These transformers shall meet the following requirements:

a) Voltage and kVA combinations as indicated in Column 1, Column 2, and Column 3 of Table 3
b) The requirements of IEEE Std C57.12.51

5.2.3 Sealed dry-type

These transformers shall meet the following requirements:

a) Voltage and kVA combinations as indicated in Column 1, Column 2, and Column 4 of Table 3
b) The requirements of IEEE Std C57.12.01 or IEEE Std C57.12.52, and UL 1562

6. Incoming section
Incoming sections should meet the requirements of this guide and shall comply with the requirements of
their applicable specifying standards. Incoming sections may include the components described in 6.1 to
6.6.

NOTEFigure 1 to Figure 10 are shown with the high-voltage section on the left of the figures and the low-voltage
section on the right.

6.1 High-voltage (or primary) bushings on the transformer cover

These bushings shall meet the thermal, mechanical, and dielectric requirements of the applicable
transformer standard. A typical example is shown in Figure 1.

9
Figure 1 Bushings on transformer cover

9
Figure 1 to Figure 10 are shown with the high-voltage section on the left of the figures and the transformer section on the right.

7
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

6.2 Primary terminal chamber on the transformer

This chamber shall meet the thermal, mechanical, and dielectric requirements of the applicable transformer
standard. A typical example is shown in Figure 2.

9
Figure 2 Terminal chamber

6.3 Metal-enclosed bus

Metal-enclosed bus shall meet the requirements of IEEE Std C37.23.

6.4 Metal-clad or metal-enclosed switchgear

This switchgear shall meet the requirements of IEEE Std C37.20.2 and NEMA C37.55 or IEEE Std
C37.20.1 and ANSI C37.51 as applicable. Typical Metal-Clad or Metal-Enclosed Switchgear examples are
shown in Figure 3 through Figure 6.

9
Figure 3 Metal-clad or metal-enclosed switchgear For one incoming line

8
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

9
Figure 4 Metal-clad or metal-enclosed switchgear For two incoming lines

Figure 5 Metal-clad or metal-enclosed switchgear


9
For two incoming lines, selector function

9
Figure 6 Metal-clad or metal-enclosed switchgear For one incoming line, looped

6.5 Metal-enclosed interrupter switchgear

This switchgear shall meet the requirements of IEEE Std C37.20.3 and NEMA C37.57. Typical examples
are shown in Figure 7 through Figure 9.

9
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

9, 10
Figure 7 Interrupter or disconnect switches Single circuit

9, 10
Figure 8 Interrupter or disconnect switches Dual circuit

9, 10
Figure 9 Interrupter or disconnect switches Selector circuit

6.6 Cutout, fuse, or fuse link

This equipment shall meet the applicable service requirements of the components covered in IEEE Std
C37.40. A typical example is shown in Figure 10.

10
Metal-Enclosed Interrupter Switchgear, the switching devices and fuses may be non-draw-out.

10
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

9, 10
Figure 10 Interrupter cutouts Fused or unfused

7. Outgoing section
Outgoing sections should meet the requirements of this guide and shall comply with the requirements of
their applicable specifying standards. Because of the complexity of outgoing arrangements, it is not
practical to present typical examples here. Outgoing sections may include the components listed in 7.1
through 7.6.

7.1 Metal-clad switchgear

This switchgear shall meet the requirements of IEEE Std C37.20.2 and NEMA C37.55.

7.2 Metal-enclosed interrupter switchgear

This switchgear shall meet the requirements of IEEE Std C37.20.3 and NEMA C37.57.

7.3 Metal-enclosed bus

Metal-enclosed bus shall meet the requirements of IEEE Std C37.23.

7.4 Metal-enclosed, low-voltage, power circuit breaker switchgear

This switchgear shall meet the requirements of IEEE Std C37.20.1 and ANSI C37.51.

7.5 Molded-case, circuit-breaker, dead-front switchboards

These switchboards shall meet the requirements of ANSI/UL 891.

11
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

7.6 Motor control centers

These control centers shall meet the requirements of ANSI/UL 845.

8. Ratings
The rating of each section of a unit substation shall comply with the applicable standards for its
components (referenced in Clause 5, Clause 6, and Clause 7) and shall be equal to or greater than the rating
of the unit substation. The kVA, high-voltage, and low-voltage ratings of the transformer section shall be
the basis for those ratings of the unit substation. Other sections shall be coordinated with those ratings. The
unit substation shall have the ratings listed in 8.1 through 8.3.

8.1 Rated power frequency

The rated power frequency of a unit substation shall be the frequency of the circuit for which it is designed.

8.2 Rated kVA

The rated kVA of a unit substation shall be the maximum rated kVA of the three-phase power transformer
in accordance with Table 1. The kVA rating of a double-ended unit substation shall be the total kVA of the
two transformers.

8.3 Rated high voltage (or primary voltage) and rated low voltage (or secondary
voltage)

In combination with the rated kVA of a unit substation, the rated voltages shall be as follows:

a) For primary unit substations, as indicated in Table 2


b) For secondary unit substations, as indicated in Table 3

8.4 Rated continuous current

The rated continuous current for high-voltage and low-voltage equipment of a unit substation shall be equal
to the respective high-voltage and low-voltage full-load currents of the transformer section.

8.5 Rated short-time withstand current

The rated short-time withstand current of a unit substation is the rms short-circuit current that is intended to
be carried for a specified period of time without causing electrical, thermal, or mechanical damage. The
current shall be the rms value determined over the specified period of time.

The rated short-time withstand current rating of a unit substation shall be the rated short-circuit current
(carrying) rating of the high-voltage interrupting device. If no high-voltage interrupting device is present,
the rated short-time withstand current rating of the unit substation shall be the through-fault current of the
transformer, in terms of primary amperes.

12
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

8.6 Rated momentary withstand current

The rated momentary withstand current of a unit substation is the maximum rms total current that it is
required to withstand. The current is the rms value, including the dc component, at the major peak of the
maximum cycle as determined from the envelope of the current wave of the maximum offset phase during
a test period of at least 10 cycles. The symmetrical current is the rated short-time current and the peak
current value is 2.6 times its rated short-time current at the major peak of the maximum cycle (this is also
referred to as the peak withstand current).

The rated momentary withstand current of a unit substation shall be the rated short circuit current withstand
rating of the high-voltage interrupting device. If no high-voltage interrupting device is present, the rated
momentary withstand current rating of the unit substation shall the through-fault current of the transformer,
in terms of primary amperes.

8.7 Rated power frequency withstand voltages

The rated power frequency withstand voltage of a unit substation is the maximum alternating-current
voltage that it is intended to withstand for one minute. The alternating-current voltage shall have a crest
value equal to 1.41 times the rms value, shall be as close to a sine wave as practical, and shall have a
frequency not less than the rated frequency.

The rated power frequency withstand voltage of the unit substation, on its high-voltage end, shall be the
lesser rating of adjacent high-voltage sections.

The rated power frequency withstand voltage of the unit substation, on its low-voltage end shall be the
lesser rating of adjacent low-voltage sections.

8.8 Rated lightning impulse withstand voltage (BIL)

The rated lightning impulse withstand voltage of the unit substation on its high-voltage end shall be the
lesser rating of adjacent high-voltage sections. The rated lightning impulse withstand voltage of the unit
substation on its low-voltage end shall be the lesser rating of adjacent low-voltage sections. Lightning
impulse voltage ratings levels are not applicable to low-voltage equipment below 1000 V.

9. Construction
The construction of all sections of a unit substation should be coordinated and the sections shall be
compatible with each other.

9.1 Phase and polarity arrangements

As viewed from the main switching-device side of the operating mechanism, the phase arrangement on
buses and primary connections of all sections should be 1, 2, 3 counting from front to back, top to bottom,
or left to right.

However, the following exception should be noted. For other arrangements of unit substations, the
transformer bushing phasing may be other than 1, 2, 3 counting from front to back, top to bottom, or left to

13
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

right. With these arrangements, a phase transposition shall be made at the connection to the outgoing and
incoming sections so that 1, 2, 3 phasing is maintained in these sections.

Panel devices should be mounted with 1, 2, 3 phasing counting from left to right and top to bottom, as
viewed from the front of the panel.

9.2 Phase sequence

The phase sequence on connection diagrams (see 9.7) should be such that, when considering voltages to
neutral on a polyphase system with respect to the element of time, the voltage of phase 1 will reach a
maximum before the voltage of phase 2, phase 2 before phase 3, and so forth, in numerical order. This
sequence should be designated as phase sequence in the order 1, 2, 3 and so forth.

9.3 Metal barriers

Metal barriers should be provided to segregate the incoming section from the transformer and the outgoing
sections from the transformer.

9.4 Interlocks

Where transformer line currents exceed the load-interrupting capability of the incoming line-section
equipment, interlocking should be provided to prevent opening the equipment on currents in excess of its
rating. Such interlocking should be effected either mechanically or by a combination of mechanical and
electrical devices.

9.5 Grounding

The ground bus for each section of the unit substation should have a provision for connection to a station
ground by suitable conductors.

9.6 Nameplates

Each incoming, outgoing, and transformer section shall have a nameplate in accordance with its applicable
standard. The nameplate should be mounted so as to be visible after normal installation.

14
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

9.7 Drawings Diagrams Instructions

The drawings, diagrams, and instructions supplied with each unit substation should include, as applicable,
all or a combination of the following drawings, depending on the type and complexity of the equipment:

a) General arrangement (outline) and foundation plan


b) One-line and/or three-line diagram 11
c) Schematic/elementary diagram11
d) Connection/wiring diagram11
e) Interconnection diagram11
f) Terminal diagram
g) Control-metering-relay panel arrangement and bills of material
h) Instruction books containing information about receiving, handling, storage, installation, operating,
and maintenance, covering all sections and all devices mounted on or within the substation

9.8 Coordination

9.8.1 Mechanical coordination and connection

If the transition (throat) section is connected to a metal-enclosed bus, it should be the responsibility of the
manufacturer of the bus duct to match the termination facilities provided by the manufacturers of the
transformer and incoming or outgoing section, unless otherwise mutually determined by the affected
manufacturers, with the approval of the purchaser.

If the transition (throat) section consists of a close-coupled throat arrangement, it should be the
responsibility of the transformer manufacturer to match the termination facilities provided by the
manufacturers of the incoming and outgoing sections unless otherwise mutually predetermined by the
affected manufacturers, with the approval of the purchaser.

If the transition (throat) section is a compartment between equipment, such as low-voltage metal-enclosed
switchgear, metal-clad switchgear, or metal-enclosed-interrupter switchgear, the responsibility for
matching should be mutually determined by the affected manufacturers of this equipment, with the
approval of the purchaser.

Flexible connections should be provided for the connection between the incoming, outgoing, or transition
(throat) sections and the bushings of the transformer except for exposed cover-mounted transformer
bushings.

9.8.2 Secondary and control wire interconnections between sections

For adjacent and close-coupled sections, wiring and necessary details should be provided, and wire should
be isolated from power circuits rated over 600 volts ac, nominal. Isolation should be by grounded metal
enclosures, metal barriers, metal conduit, electrical metallic tubing, or other approved means, except for
short lengths of wire at, for example, instrument transformer terminals, temperature-measuring terminals,
secondary devices, and fan-control equipment.

11
These diagrams are defined in IEEE Std 315 [B9].

15
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

For remote sections, each section should be provided with terminal blocks and terminal-block details for
users external interconnections.

10. Typical arrangements


Because of the varied ratings and types of equipment, there are many possible arrangements for unit
substations. These are listed in10.1 and 10.2, and illustrated in Figure 11 through Figure 23.

10.1 Primary unit substations

A primary unit substation is usually one of the following types:

a) Radial (see Figure 11)


b) Distributed-Network (see Figure 12)
c) Spot-Network (see Figure 13)
d) Secondary (low voltage) selective (see Figure 14)
e) Duplex (see Figure 15)

Also see Figure 16 for typical alternate arrangements of two-transformer sections.

12
Figure 11 Primary unit substation Radial type

12
Figure 11 and Figure 12 are shown with the transformer section on the left of the figure and the outgoing section on the right of the
figure.

16
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

12
Figure 12 Primary unit substation Distributed network type

13
Figure 13 Primary unit substation Spot network type

13
Figure 14 Primary unit substation Secondary selective type

13
Figure 13 to Figure 15 are shown with the transformer sections on the left and right of the figure and the outgoing section in the
middle of the figure.

17
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

13
Figure 15 Primary unit substation Duplex type (breaker-and-a-half scheme)

Figure 16 Primary unit substation


Transformer unit substation (alternate arrangements)

10.2 Secondary unit substations

A secondary unit substation is usually one of the following types:

a) Radial (see Figure 17 and Figure 18)


b) Distributed-Network (see Figure 19)
c) Spot-Network (see Figure 20)
d) Secondary (low voltage) selective (see Figure 21, Figure 22, and Figure 23)

18
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

Figure 17 Secondary unit substation Radial type

Figure 18 Secondary unit substation Radial type with reverse arrangement

19
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

Figure 19 Secondary unit substation


Distributed network type with indoor-outdoor arrangement

Figure 20 Secondary unit substation Spot network type

Figure 21 Secondary unit substation Secondary select type

20
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

Figure 22 Secondary unit substation


Secondary select type with common rrawout aisle arrangement

Figure 23 Secondary unit substation


Secondary select type with indoor-outdoor arrangement

21
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

11. Guide for selection, application, installation, and maintenance of unit


substations

11.1 Application considerations

In applying unit substations, the following subjects may require consideration:

a) Service conditions, that is, environmental considerations


b) System conditions, for example, voltage, frequency, and available short-circuit currents
c) Installation conditions, for example, restricted access or exposure to the general public
d) Load requirements, including duty cycles if applicable

11.2 Unusual service conditions

a) Significant solar radiation


b) Ambient temperature outside the limits in 4.2
c) Altitudes above 1000 m (3300 ft)
d) Surrounding environment containing volatile organic compounds, moisture and dust.
e) Exposure to abnormal vibration, natural or man-made
f) Local conditions affecting grounding resistance

For metal-enclosed switchgear equipment (which may be used as the incoming or outgoing sections of unit
substations) guidelines and requirements for responding to unusual service conditions are given in
IEEE Std C37.20.1, IEEE Std C37.20.2, IEEE Std C37.20.3, and IEEE Std C37.23. Information concerning
unusual service conditions for transformers is included in IEEE Std C57.12.00 and IEEE Std C57.12.01.

11.3 System conditions

11.3.1 Voltage and frequency

The voltage operating ranges of a unit substation are dependant on the high-voltage and low-voltage ratings
of the included transformer. When the voltage variation is greater than acceptable for the application, then
the use of equipment load regulation should be considered. (The application of that equipment is not
covered in this guide.)

11.3.2 Short-circuit considerations

Short-circuit current valuesshort-time and momentarymust be calculated for the incoming and
outgoing sections to permit the selection and coordination of switching and protective devices, and also to
provide proper protection for the transformer.

Procedures for making the calculations are included in standards such as IEEE Std C37.010 and IEEE Std
141 [B6].

22
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

The E/X Simplified Method, described in IEEE Std C37.010, is usually satisfactory.

Short-circuit values for common substations and conditions are given in IEEE Std 141[B6].

While interrupting ratings of protective devices are based on symmetrical current, it is only necessary when
applying these devices to consider the maximum symmetrical short-circuit current, since the product
standards covering testing take into account the maximum possible asymmetry.

The short-time withstand current and momentary withstand current ratings of a unit substation are defined
in Clause 8. In planning the unit substation, its rating should be made at least equal to the calculated
available short-circuit current values. Due consideration should be given to possible future system changes
that might demand increases in the calculated available values.

11.4 Locationtransformer selection

The physical location of the unit substation is of major importance in determining the type of transformer to
be used for a particular installation.

11.4.1 Indoor and outdoor locations

Less-flammable liquid-insulated transformers, nonflammable fluid-insulated transformers and sealed


transformers are, in general, suitable for use both indoors and outdoors.

Liquid-immersed transformers insulated with flammable liquids are normally suitable only for outdoor
locations. They may be installed indoors only when located in fireproof vaults and where local codes
permit. See electrical code information in NFPA 70 and NFPA 70B. Ventilated dry-type transformers are
normally suitable only for indoor locations, except when mounted in a specifically designed enclosure for
outdoor application.

11.4.2 Environmental conditions

Environmental conditions such as dust, moisture, and fumes may be important factors in the selection of
transformer types.

11.4.3 Audible sound level

If the normal sound level is a factor at the location and operation of any transformer, special consideration
should be given to the sound abatement in the form of barriers or low-noise transformers.

11.4.4 Grounding

It is necessary to take grounding considerations into account when installing unit substations. Refer to
IEEE Std 141 [B6] and IEEE Std 142 [B7] for grounding instructions.

11.5 Load requirements

The load capacity of a unit substation is determined by the kVA rating of the included transformer(s).

23
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

11.5.1 Transformer kVA rating

The kVA rating of the transformer section should, at a minimum, be sufficient to handle the immediate
required load. Consideration should be given to any future load growth that might be required by expanding
or changing facilities. When substantial load growth is anticipated, it is usually desirable to install, initially,
a single transformer substation with a main circuit breaker that can be expanded readily to a two-
transformer (double-ended) substation when the additional capacity is needed.

For application of demand factors and diversity factors to the total connected load, refer to IEEE Std 141
[B6] and IEEE Std 142 [B7]. Fan-cooling may be used to provide higher kVA ratings to meet load growth.
For secondary-selective systems or network systems, fan-cooling is often used to provide higher ratings
during periods when one or more transformers are out of service.

Other requirements for the selection and rating of equipment could involve unusual loading conditions, for
example, the starting of large motors, or the operation of welding equipment or sensitive loads such as
computers and scientific instruments.

11.5.2 Loading guides

Consult the following:

a) For liquid-immersed transformers, consult IEEE Std C57.91.


b) For dry-type transformers, consult IEEE Std C57.96.
c) For metal-enclosed switchgear assemblies, consult IEEE Std C37.20.1, IEEE Std C37.20.2,
IEEE Std C37.20.3 and IEEE Std C37.23.

11.6 Miscellaneous design considerations

11.6.1 Incoming section

In unit substation applications, it is desirable to be able to electrically isolate the transformer from the
incoming circuit. An exception occurs when the transformer of the unit substation is the only load on the
incoming circuit; in this case the switching device at the source of the circuit may serve to isolate the
transformer electrically.

However, the switching device, whether a fused switch or a relayed circuit breaker, must provide proper
protection for the transformer to prevent damage from short-circuit current (short-time withstand or
momentary withstand) due to abnormal secondary fault conditions.

11.6.2 Transformer section

The selection of transformers for unit substations is based on such factors as location (see 11.4) and load
requirements (see 11.5). Other considerations include surge protection, supplementary cooling, and
maintenance requirements.

11.6.2.1 Surge protection

When connected to circuits that are subject to lightning or other transients, surge protection should be
considered. Surge protection should limit voltage surges to values below the impulse-withstand ratings of

24
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

the unit substation. See IEEE Std C62.22 for specific information concerning surge protection. See IEEE
Std C57.142 for information on mitigation of switching transients.

If the unit substation is to operate in an environment that requires a greater lightning impulse-withstand
capability, surge arresters should be used to ensure that the equipment is properly protected at the required
lightning impulse level.

11.6.2.2 Forced-air cooling

The forced-air cooling rating of the transformer is often a factor in determining the transformer to be
selected. For single-ended unit substations, the forced-air cooling rating of the transformer is based on the
system total load. For double-ended unit substations, the load conditions when each transformer may have
to supply the total load of the substation during an emergency or during maintenance should be considered.

11.6.2.3 Maintenance requirements

For information on maintenance requirements and techniques, see the manufacturers literature and the
following guides:

a) For liquid-immersed transformers: IEEE Std C57.93 [B22], IEEE Std C57.104 [B23], and
IEEE Std C57.106 [B24].
b) For dry-type transformers: IEEE Std C57.94.

Differences in the maintenance requirements of the various types of transformer sections may be a factor in
determining the type of transformer to be used for a particular application.

Maintenance of liquid-immersed transformers should at least include periodic checking of the tank for
pressure-tightness, and sample-testing of the liquid for dielectric strength and other characteristics.
Dielectric strength can sometimes be restored by filtering.

Maintenance of sealed transformers should include periodic inspections for pressure-tightness. An


indication of positive pressure on the transformer pressure gauge is generally sufficient, since these units
are usually sealed with positive gas-pressure.

If a unit substation component, such as switchgear or dry-type transformer, is to be stored or, after
installation, deenergized for a significant period of time in humid conditions, a space-heater should be
provided within the housing, and left energized from a suitable power source.

11.6.3 Outgoing section

11.6.3.1 Selection of low-voltage protective devices

Circuit breakers are generally recommended for circuit protection for flexibility in operation. They can be
reclosed quickly where a sustained interruption of power cannot be tolerated.

Current-limiting devices can be utilized where reenergizing speed is not critical, or where high interrupting
capability (up to 200 000 A) is needed, or both. Their speed of operation and current-limiting action can
provide protection to coordinate equipment in circuits that have high available short-circuit currents. When
current-limiting devices are used, the ratings of protected equipment must be coordinated with the

25
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

maximum let-through energy and the peak let-through current of the device. Where there may be damage
from single-phasing, the protective device needs to open all three phases.

11.6.3.2 Transformer main secondary fused switch or circuit breaker

A transformer main secondary protective device should be used for the following reasons:

a) In case of emergency, it is quicker and simpler to deenergize the entire load by opening a
transformer main secondary protective device at each substation than to open each feeders
protective device. Conversely, in case of trouble in the primary cable or transformer, it is often
desirable to disconnect the low-voltage bus from the transformers and to supply the bus from an
alternate source.
b) It provides fault-protection for the bus and backup-protection for the feeder devices. In addition,
where a main secondary protective device is present, it may provide overload protection for a
transformer, and less-sensitive primary protection may be used. This is particularly true for ground-
fault protection.
c) Where interlocking is used, it provides for, and simplifies, key-interlocking between the primary
switch and secondary switchgear.
d) When a transformer main secondary relayed circuit breaker is used, coordination with primary
protective devices is more readily obtainable.
e) It provides flexibility. Note that a main secondary protective device is essential for several of the
circuit arrangements in Figure 11 through Figure 23. A radial-type unit substation that includes a
main fused switch or circuit breaker can later be expanded into one of the more elaborate circuit
arrangements without extensive field modification.

11.6.3.3 Continuous-current rating of transformer secondary protective devices and


connections

The transformer main secondary circuit breakers, or fuse switches and connections, should have
continuous-current ratings that are approximately 25 percent greater than the continuous-current rating of
the transformer. This is recommended because transformers often carry short-time loads above their
nameplate ratings due to short duty cycles or low-ambient temperatures.

When selecting the continuous-current rating of the transformers main secondary protective devices and
connections, consideration should also be given to whether the transformer has, or will have, a continuous
supplementary-cooled rating.

11.6.4 Protective relaying

See IEEE Std C37.90 [B10] and IEEE Std C37.91 [B11], for general guidance in the applications of
protective relays for unit substations.

11.7 Installation, field-testing, operation, and maintenance

The installation and field-testing of unit substations should, in general, be performed in accordance with
manufacturers instructions (refer to NFPA 70B and IEEE Std C37.20.1, IEEE Std C37.20.2, and IEEE Std
C37.20.3. Meggering is recommended when equipments have been stored in damp and dirty locations. If
the megger readings are less than the manufacturers recommendations, a drying-out and cleaning of the

26
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

insulation system is recommended. When dielectric testing is performed, it should be conducted at the
reduced values specified for field- testing in the applicable referenced standards.

When various sections of the unit substation have to be assembled in the field, the connections should be
made in strict accordance with the manufacturers drawings and instructions.

Operation and maintenance instructions are also furnished by the manufacturer and should be followed.
Note that additional maintenance may be required when equipment is installed in unusual service
environments (see 11.2). General maintenance requirements for transformers are shown in 11.6.2.3.

a
Table 1 Standard three-phase transformer kVA ratings from 112.5 kVA 10 000 kVA
b c
Self-Cooled Forced-Air-Cooled
(kVA) (kVA)
Liquid- Ventilated Dry- Sealed Dry- Liquid- Ventilated Dry- Sealed Dry-
Immersed Type Type Immersed Type Type
Col. 1 Col. 2 Col. 3 Col. 4 Col. 5 Col. 6
112.5 112.5
150 150
225 225
300 300 400
500 500 667
750 750 750 862 1 000
1 000 1 000 1 000 1 150 1 333
1 500 1 500 1 500 1 725 2 000
2 000 2 000 2 000 2 300 2 667
2 500 2 500 2 500 3 125 3 333
3 750 3 750 3 750 4 687 5 000
5 000 5 000 5 000 6 250 6 667
7 500 7 500 7 500 9 375 10 000
10 000 10 000 10 000 12 500 13 333
a Based on an average winding temperature rise, due to resistance, of: 65 C rise for liquid-immersed
transformers; 150 C rise for dry-type transformers. (Other rises of 115 C and 80 C are also available for
ventilated-dry-type transformers.)
b For transformers rated above 2500 kVA, the forced-air-cooled rating is generally 125% for liquid immersion,
and 133% for ventilated dry-types.
c When a future forced-air-cooled rating is planned, self-cooled transformers shall be specified to have provision
for future addition of equipment for fan-cooling.

27
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

abc
Table 2 Primary unit substation transformers
Voltages Transformer type
(V) (kVA)
Rated HV Rated LV Ventilated Dry- Sealed Dry-Type Liquid-
Type Immersed
Col. 1 Col. 2 Col. 3 Col. 4 Col.5
6 900 2 400 --- --- 1 0003 750
7 200 4 160 --- --- 1 0003 750
4 160Y/2 400 --- --- 1 0003 750
12 000 2 400 7507 500 7505 000 1 0007 500
12 470 4 160 7507 500 7505 000 1 0007 500
13 200 4 160Y/2 400 7507 500 7505 000 1 0007 500
13 800
23 000 2 400 1 5007 500 1 5005 000 1 0007 500
4 160 1 5007 500 1 5005 000 1 0007 500
4 160Y/2 400 1 5007 500 1 5005 000 1 0007 500
34 500 2 400 1 5007 500 1 5005 000 1 0007 500
4 160 1 5007 500 1 5005 000 1 0007 500
4 160Y/2 400 1 5007 500 1 5005 000 1 0007 500
a Voltages listed are as shown in ANSI C84.1. Voltages in individual transformer product standards
may differ.
b All voltages are delta unless otherwise indicated.
c When a dash connects kVA ratings, include all intervening kVA ratings as shown in Table 1.

abc
Table 3 Secondary unit substation transformers
Voltages Transformer type
(V) (kVA)
Rated HV Rated LV Ventilated Dry- Sealed Dry-Type Liquid-
Type Immersed
Col. 1 Col. 2 Col. 3 Col. 4 Col.5
2 400 208Y/120 112.51 000 7501 000 112.51 000
480 112.51 500 7501 500 112.52 000
480/277 112.51 500 7501 500 112.52 000
4 160 208Y/120 112.51 000 7501 000 112.51 000
4 800 480 112.51 500 7501 500 112.52 500
480/277 112.51 500 7501 500 112.52 500
6 900 208Y/120 112.51 000 7501 000 112.51 000
7 200 480 112.52 500 7502 500 112.53 750
480/277 112.52 500 7502 500 112.53 750
12 000 208Y/120 112.51 000 7501 000 112.51 000
12 470 480 112.52 500 7502 500 112.53 750
13 200 480/277 112.52 500 7502 500 112.53 750
13 800
23 000 208Y/120 3001 000 7501 000 112.51 000
480 3002 500 10002 500 112.53 750
480/277 3002 500 10002 500 112.53 750
34 500 208Y/120 3001 000 7501 000 112.51 000
480 3002 500 1 0002 500 112.53 750
480/277 3002 500 1 0002 500 112.53 750
a Voltages listed are as shown in ANSI C84.1. Voltages in individual transformer product
standards may differ.
b All voltages are delta unless otherwise indicated.
c When a dash connects kVA ratings, include all intervening kVA ratings as shown in Table 1.

28
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

Annex A

(informative)

Bibliography

[B1] ANSI C57.12.22, American National Standard for Pad-Mounted, Compartmental-Type, Self-Cooled,
Three-Phase Distribution Transformers With High-Voltage Bushings, 2500 kVA and Smaller; High
Voltage, 34 500 GrdY/19 920 Volts and Below; Low Voltage, 480 Volts and Below.
[B2] ANSI C57.12.50, American National Standard Requirements for Ventilated Dry-Type Distribution
Transformers, 1 to 500 kVA, Single-Phase, and 15 to 500 kVA, Three-Phase, with High-Voltage 601 to 34
500 Volts, Low-Voltage 120 to 600 Volts.
[B3] ANSI C57.12.55, American National Standard for TransformersUsed in Unit Installations,
Including Unit SubstationsConformance Standard.
[B4] ANSI C57.12.57, American National Standard for TransformersVentilated Dry-Type Network
Transformers 2500 kVA and Below, Three-Phase, with High-Voltage 34500 Volts and below, Low-
Voltage 216Y/125 and 480Y/277 VoltsRequirements.
[B5] IEEE Std 4, IEEE Standard Techniques for High-Voltage Testing.
[B6] IEEE Std 141, IEEE Recommended Practice for Electric Power Distribution for Industrial Plants.
[B7] IEEE Std 142, IEEE Recommended Practice for Grounding of Industrial and Commercial Power
Systems.
[B8] IEEE Std 241, IEEE Recommended Practice for Electric Power Systems in Commercial
Buildings.
[B9] IEEE Std 315, Supplement to Graphic Symbols for Electrical and Electronics Diagrams.
[B10] IEEE Std C37.90, IEEE Standard for Relays and Relay Systems Associated with Electric Power
Apparatus.
[B11] IEEE Std C37.91, IEEE Guide for Protecting Power Transformers.
[B12] IEEE Std C37.100, IEEE Standard Definitions for Power Switchgear.
[B13] IEEE Std C37.122, IEEE Standard for High-Voltage Gas-Insulated Substations rated above 52 kV.
[B14] IEEE Std C57.12.24, IEEE Standard for Submersible, Three-Phase Transformers, 3750 kVA and
Smaller: High Voltage, 34 500 GrdY/19 920 Volts and Below; Low Voltage, 600 Volts and Below.
[B15] IEEE Std C57.12.26, IEEE Standard for Pad-Mounted, Compartmental-Type, Self-Cooled, Three-
Phase Distribution Transformers for Use with Separable Insulated High-Voltage Connectors (34 500
GrdY/19 920 Volts and Below, 2500 kVA and Smaller).
[B16] IEEE Std C57.12.27, IEEE Conformance Requirements for Liquid-Filled Distribution Transformers
Used in Pad-Mounted Installations, Including Unit Substations.
[B17] IEEE Std C57.12.36, IEEE Standard Requirements for Liquid-Immersed Distribution Substation
Transformers.
[B18] IEEE Std C57.12.40, IEEE Requirements for Secondary Network Transformers Subway and Vault
Types (Liquid Immersed).
[B19] IEEE Std C57.12.70, IEEE Standard Terminal Markings and Connections for Distribution and
Power Transformers.
[B20] IEEE Std C57.12.80, IEEE Standard Terminology for Power and Distribution Transformers.

29
Copyright 2013 IEEE. All rights reserved.

Authorized licensed use limited to: University of Missouri-Kansas City. Downloaded on October 08,2015 at 19:06:07 UTC from IEEE Xplore. Restrictions apply.
IEEE Std C37.121-2012
IEEE Guide for SwitchgearUnit SubstationRequirements

[B21] IEEE Std C57.13, IEEE Standard Requirements for Instrument Transformers.
[B22] IEEE Std C57.93, IEEE Guide for Installation and Maintenance of Liquid-Immersed Power
Transformers.
[B23] IEEE Std C57.104, IEEE Guide for the Interpretation of Gases Generated in Oil-Immersed
Transformers.
[B24] IEEE Std C57.106, IEEE Guide for Acceptance and Maintenance of Insulating Oil in Equipment.
[B25] IEEE Std C62.1, Surge Arresters IEEE Standard for Gapped Silicon-Carbide Surge Arresters for
AC Power Circuits. 14
[B26] NEMA ICS-2, Industrial Control and Systems Controllers, Contactors and Overload Relays Rated
600 Volts.
[B27] NEMA SG2, High-Voltage Fuses.