Project : Golar Hilli FLNG

Doc. Title : Operation Philosophy - HVAC System

Doc. No. : C110-M406.01

Doc. Rev. : 3

Page No. : 98

Rev. Date : 03 / 06 / 2017

14.0 Cause and Action - HVAC System - Accommodation

Cause Action
( Closed, Trip, Malfunction, etc,. ) ( Close, Stop, Shutdown, etc,. )
Item Method Remark
Tag No. Service Tag No. Service

97-GK-101A Blower Fan A - AHU A 2 ways Interlocked


1 97-GE-1303 Damper - Supply Air Outlet - AHU A - Port 97-GE-1310 Damper - Return Air Inlet - AHU A 2 ways Interlocked
97-GE-1301 Damper - Fresh Air Duct - Port 2 ways Interlocked

97-GK-101B Blower Fan B - AHU B 2 ways Interlocked


2 97-GE-1304 Damper - Supply Air Outlet - AHU B - Stbd. 97-GE-1311 Damper - Return Air Inlet - AHU B 2 ways Interlocked
97-GE-1302 Damper - Fresh Air Duct - Stbd, 2 ways Interlocked

th
97-GE-1802 Damper - RAD - 7th Poop Deck ( S ) 1 way
3 97-GE-1801 Damper - SAD - 7 Poop Deck
97-GE-1701 Damper - RAD - 7th Poop Deck ( P ) 1 way

97-GE-1602 Damper - RAD - 6th Poop Deck ( P ) 1 way

th
97-GE-1603 Damper - RAD - 6th Poop Deck ( S ) 1 way
4 97-GE-1601 Damper - SAD - 6 Poop Deck
97-GE-1605 Damper - EAD - DB Room ( S ) 1 way
97-GE-1608 Damper - EAD - GYRO Room ( P ) 1 way

97-GK-001 Exhaust Air Fan - Battery Room 2 ways Interlocked


5 97-GE-1606 Damper - Exhaust Air Duct - Battery Room
97-GE-1604 Damper - Supply Air Duct - Battery Room 1 way Close

th
97-GE-1502 Damper - RAD - 5th Poop Deck ( P ) 1 way
6 97-GE-1501 Damper - SAD - 5 Poop Deck
97-GE-1503 Damper - RAD - 5th Poop Deck ( S ) 1 way

7 97-GE-1505 Damper - Air Inlet of Exhaust Air Fan A 97-GK-008A Exhaust Air Fan A - Sanitary Spaces 2 ways Interlocked

8 97-GE-1506 Damper - Air Inlet of Exhaust Air Fan B 97-GK-008B Exhaust Air Fan B - Sanitary Spaces 2 ways Interlocked
97-GE-1404 Damper - Air Outlet of Exhaust Air Fan 1 way
9 97-GE-1401 Damper - SAD - 4th Poop Deck 97-GE-1402 Damper - RAD - 4th Poop Deck ( P ) 1 way
97-GE-1403 Damper - RAD - 4th Poop Deck ( S ) 1 way

10 97-GE-1404 Damper - Air Outlet of Exhaust Air Fan 97-GK-002 Exhaust Air Fan - Hospital 2 ways Interlocked

11 97-GE-1208 Damper - EAD - Mess Room & Pantry 97-GK-004 Exhaust Air Fan - Mess Room & Pantry 2 ways Interlocked

12 97-GE-4201 Damper - SAD - Mess Room & Pantry 97-GE-1208 Damper - EAD - Mess Room & Pantry 1 way Close

13 97-GE-4204 Damper - EAD - Smoking Room 97-GK-003 Exhaust Air Fan - Smoking Room 2 ways Interlocked

14 97-GE-1306 Damper - SAD - 3nd Poop Deck ( P ) 97-GE-1305 Damper - SAD - 3nd Poop Deck ( S ) 1 way

15 97-GE-1308 Damper - SAD - 3nd Poop Deck ( P ) 97-GE-1307 Damper - SAD - 3nd Poop Deck ( S ) 1 way

16 97-GE-4202 Damper - SAD - 2nd Poop Deck 97-GE-4203 Damper - RAD - 2nd Poop Deck ( S ) 1 way
Project : Golar Hilli FLNG

Doc. Title : Operation Philosophy - HVAC System

Doc. No. : C110-M406.01

Doc. Rev. : 3

Page No. : 99

Rev. Date : 03 / 06 / 2017

14.0 Cause and Action - HVAC System - Accommodation

Cause Action
( Closed, Trip, Malfunction, etc,. ) ( Close, Stop, Shutdown, etc,. )
Item Method Remark
Tag No. Service Tag No. Service

97-GE-4002 Damper - RAD - 1st Deck 1 way Close

st
97-GE-4013 Damper - PRD - 1st Deck 1 way Close
17 97-GE-4001 Damper - SAD - 1 Deck
97-GE-4006 Damper - Exhaust Air Duct - Ship's Laundry 1 way Close
97-GE-2010 Damper - EAD - Gymnasium 1 way Close

18 97-GE-4003 Damper - SAD - Ship's Laundry 97-GE-4006 Damper - EAD - Ship's Laundry 2 ways Interlocked

19 97-GE-4004 Damper - Exhaust Air Fan A 97-GK-006A Exhaust Air Fan A - Ship's Laundry 2 ways Interlocked

20 97-GE-4005 Damper - Exhaust Air Fan B 97-GK-006B Exhaust Air Fan B - Ship's Laundry 2 ways Interlocked

97-GK-007 Exhaust Air Fan - Gymnasium 2 ways Interlocked


21 97-GE-2010 Damper - EAD - Gymnasium
97-GE-4009 Damper - SAD - Gymnasium 2 ways Interlocked

22 97-GE-2011 Damper - SAD - Main ERT Post 97-GE-2012 Damper - EAD - Main ERT Post 2 ways Interlocked

97-GE-1610
97-GE-1504
Damper - EAD - Sanitary Spaces at all
97-GE-1407 Accommodation Area - 6th Poop Deck to 97-GK-008A Exhaust Air Fan A - Sanitary Spaces
23 97-GE-1309 1st Deck. 97-GK-008B Exhaust Air Fan B - Sanitary Spaces 1 way Stop
Any 4 ( four ) or more of these dampers
97-GE-1205 fails and the exhaust air fan shall stop in
operation.
97-GE-4104
97-GE-4007

97-GK-006A Exhaust Air Fan A - Ship's Laundry 1 way Stop


24 97-GE-4006 Damper - Main Exhaust Air Stream - Laundry
97-GK-006B Exhaust Air Fan B - Ship's Laundry 1 way Stop

25 97-GK-101A Blower Fan A - AHU A 97-GD-101A Electric Heater A - AHU A 1 way


Off / Unable to On
26 97-GK-101B Blower Fan B - AHU B 97-GD-101B Electric Heater B - AHU B 1 way

97-GE-4101 Damper - SAD - 1st Poop Deck ( Port ) &


27 97-GE-4103 Damper - RAD - 1st Poop Deck 2 way Interlocked
st
97-GE-4102 Damper - SAD - 1 Poop Deck ( Stbd. )

Note : 1. Interlock implies both cause and action are interlocked with each other. Refer to vessel F&G philosophy for smoke, fire event and emergency operation.
For example : If damper is closed, the ventilation fan unable to start as well as if the ventilation fan is not operating and the respective damper shall be closed.
2. In auto mode, standby equipment shall be start automatically. If both duty and standby equipment fails and the system shall shut down.
3. Audio and visual alarm shall be provided for failure / malfunction of HVAC equipment, component, instrument, etc,.
Project : Golar Hilli FLNG

Doc. Title : Operation Philosophy - HVAC System

Doc. No. : C110-M406.01

Doc. Rev. : 3

Page No. : 100

Rev. Date : 03 / 06 / 2017

15.0 Cause and Action - HVAC System - Galley

Cause Action
( Closed, Trip, Malfunction, etc,. ) ( Close, Stop, Operate, Shutdown, etc,. )
Item Method Remark
Tag No. Service Tag No. Service

97-GK-201A Blower Fan A - AHU A 1 way Stop


1 97-GE-201 Damper - Fresh Air Duct
97-GK-201B Blower Fan B - AHU B 1 way Stop
97-GK-201A Blower Fan A - AHU A 1 way Stop
2 97-GE-204 Damper - Supply Air Duct
97-GK-201B Blower Fan B - AHU B 1 way Stop

3 97-GE-202 Damper - Air Inlet - AHU A 97-GK-201A Blower Fan A - AHU A Interlocked

4 97-GE-203 Damper - Air Inlet - AHU B 97-GK-201B Blower Fan B - AHU B Interlocked

97-GK-005A Exhaust Air Fan A 1 way Stop


5 97-GE-205 Damper - Exhaust Air Duct - Galley
97-GK-005B Exhaust Air Fan B 1 way Stop
97-GK-005A Exhaust Air Fan A 1 way Stop
6 97-GE-208 Damper - Exhaust Air Duct - 4th Poop Deck
97-GK-005B Exhaust Air Fan B 1 way Stop

7 97-GE-206 Damper - Air Inlet - Exhaust Air Fan A 97-GK-005A Exhaust Air Fan A Interlocked

8 97-GE-207 Damper - Air Inlet - Exhaust Air Fan B 97-GK-005B Exhaust Air Fan B Interlocked

97-GE-209 Damper - Exhaust Air Duct - Hood # 1,


97-GK-005A Exhaust Air Fan A 1 way Stop
97-GE-210 Damper - Exhaust Air Duct - Hood # 1 &
9
97-GE-211 Damper - Exhaust Air Duct - Hood # 2.
97-GK-005B Exhaust Air Fan B 1 way Stop
If all 3 dampers fail,
97-GK-005A Exhaust Air Fan A
10 97-ES-005 Local Start / E Stop - Exhaust Air Fan
97-GK-005B Exhaust Air Fan B

11 97-GK-201A Blower Fan A - AHU A 97-GD-201A Electric Heater A - AHU A 1 way


Off / Unable to On
12 97-GK-201B Blower Fan B - AHU B 97-GD-201B Electric Heater B - AHU B 1 way

97-GK-005A Exhaust Air Fan A 97-GK-201A Blower Fan A - AHU A Interlocked to be


configured in VCS.
13 2 ways
Both EAF or SAF
97-GK-005B Exhaust Air Fan B 97-GK-201B Blower Fan B - AHU B Fails.

Note : 1. Interlock implies both cause and action are interlocked with each other. Refer to vessel F&G philosophy for smoke, fire event and emergency operation.
For example : If damper is closed, the ventilation fan unable to start as well as if the ventilation fan is not operating and the respective damper shall be closed.
2. In auto mode, standby equipment shall be start automatically. If both duty and standby equipment fails and the system shall shut down.
3. Audio and visual alarm shall be provided for failure / malfunction of HVAC equipment, component, instrument, etc,.
Project : Golar Hilli FLNG

Doc. Title : Operation Philosophy - HVAC System

Doc. No. : C110-M406.01

Doc. Rev. : 3

Page No. : 101

Rev. Date : 03 / 06 / 2017

16.0 Cause and Action - HVAC System - Engine Control Room ( ECR ) and Workshop

Cause Action
( Closed, Trip, Malfunction, etc,. ) ( Close, Stop, Shutdown, etc,. )
Item Method Remark
Tag No. Service Tag No. Service

1 97-GE-302 Damper - Air Inlet - AHU A 97-GK-301A Blower Fan A - AHU A 2 ways Interlocked

2 97-GE-303 Damper - Air Inlet - AHU B 97-GK-301B Blower Fan B - AHU B 2 ways Interlocked

3 97-GE-308 Damper - Exhaust Air Duct from Workshop 97-GK-022 Exhaust Air Fan 2 ways Interlocked

97-GE-305 Damper - Return Air Duct from Workshop AHU continue in


4 97-GE-304 Damper - Supply Air Duct to Workshop 1 way
97-GK-022 Exhaust Air Fan operation.

97-GE-304 Damper - Supply Air Duct to Workshop AHU continue in


5 97-GE-305 Damper - Return Air Duct from Workshop 1 way
97-GK-022 Exhaust Air Fan operation.

97-GE-307 Damper - Return Air Duct from ECR 2 ways Interlocked


97-GK-301A Blower Fan A - AHU A

97-GK-301B Blower Fan B - AHU B


6 97-GE-306 Damper - Supply Air Duct to ECR
97-GE-304 Damper - Supply Air Duct to Workshop 1 way
97-GE-305 Damper - Return Air Duct from Workshop
97-GK-022 Exhaust Air Fan

7 97-GK-301A Blower Fan A - AHU A 97-GD-301A Electric Heater A - AHU A 1 way


Off / Unable to On
8 97-GK-301B Blower Fan B - AHU B 97-GD-301B Electric Heater B - AHU B 1 way

Note : 1. Interlock implies both cause and action are interlocked with each other. Refer to vessel F&G philosophy for smoke, fire event and emergency operation.
For example : If damper is closed, the ventilation fan unable to start as well as if the ventilation fan is not operating and the respective damper shall be closed.
2. In auto mode, standby equipment shall be start automatically. If both duty and standby equipment fails and the system shall shut down.
3. Audio and visual alarm shall be provided for failure / malfunction of HVAC equipment, component, instrument, etc,.
Project : Golar Hilli FLNG

Doc. Title : Operation Philosophy - HVAC System

Doc. No. : C110-M406.01

Doc. Rev. : 3

Page No. : 102

Rev. Date : 03 / 06 / 2017

17.0 Cause and Action - HVAC System - Electrical Compartment

Cause Action
( Closed, Trip, Malfunction, etc,. ) ( Close, Stop, Shutdown, etc,. )
Item Method Remark
Tag No. Service Tag No. Service

Damper - Supply Air Duct to UPS Room & Interlocked,


1 97-GE-402 97-GE-405 Damper - Return Air Duct from UPS Room 2 ways
Instrument Room Stop HVAC Unit

2 97-GE-403 Damper - Air Inlet - AHU A 97-GK-401A Blower Fan A - AHU A 2 ways Interlocked

3 97-GE-404 Damper - Air Inlet - AHU B 97-GK-401B Blower Fan B - AHU B 2 ways Interlocked

4 97-GE-406 Damper - Supply Air Duct to Telecom Room 97-GE-407 Damper - Return Air Duct from Telecom Room 2 ways Interlocked

5 97-GE-408 Damper - SAD to Instrument Room 1 97-GE-409 Damper - RAD from Instrument Room 1 2 ways Interlocked

6 97-GE-410 Damper - SAD to Instrument Room 2 97-GE-411 Damper - RAD from Instrument Room 2 2 ways Interlocked

7 97-GE-401 Damper - Fresh Air Intake 97-GE-412 Damper - Pressure Relief Duct from UPS Room 1 way Close

8 97-GK-401A Blower Fan A - AHU A 97-GD-401A Electric Heater A - AHU A 1 way


Off / Unable to On
9 97-GK-401B Blower Fan B - AHU B 97-GD-401B Electric Heater B - AHU B 1 way

Note : 1. Interlock implies both cause and action are interlocked with each other. Refer to vessel F&G philosophy for smoke, fire event and emergency operation.
For example : If damper is closed, the ventilation fan unable to start as well as if the ventilation fan is not operating and the respective damper shall be closed.
2. In auto mode, standby equipment shall be start automatically. If both duty and standby equipment fails and the system shall shut down.
3. Audio and visual alarm shall be provided for failure / malfunction of HVAC equipment, component, instrument, etc,.
Project : Golar Hilli FLNG

Doc. Title : Operation Philosophy - HVAC System

Doc. No. : C110-M406.01

Doc. Rev. : 3

Page No. : 103

Rev. Date : 03 / 06 / 2017

18.0 Cause and Action - HVAC System - New Battery Room

Cause Action
( Closed, Trip, Malfunction, etc,. ) ( Close, Stop, Shutdown, etc,. )
Item Method Remark
Tag No. Service Tag No. Service

1 97-GE-501 Damper - Fresh Air Inlet - AHU A 97-GK-501A Blower Fan A - AHU A 2 ways Interlocked

2 97-GE-502 Damper - Fresh Air Inlet - AHU B 97-GK-501B Blower Fan B - AHU B 2 ways Interlocked
97-GK-009A Exhaust Air Fan A 1 way Stop
3 97-GE-504 Damper - Exhaust Air Duct
97-GK-009B Exhaust Air Fan B 1 way Stop

97-GK-009A Exhaust Air Fan A & 97-GE-504 Damper - Exhaust Air Duct Shutdown HVAC
4 1 way
97-GK-009B Exhaust Air Fan B ( Both fan fails ) 97-GK-501A / B Blower Fan A / B - AHU A / B system

5 97-GK-501A Blower Fan A - AHU A 97-GD-501A Electric Heater A - AHU A 1 way


Off / Unable to On
6 97-GK-501B Blower Fan B - AHU B 97-GD-501B Electric Heater B - AHU B 1 way

Note : 1. Interlock implies both cause and action are interlocked with each other. Refer to vessel F&G philosophy for smoke, fire event and emergency operation.
For example : If damper is closed, the ventilation fan unable to start as well as if the ventilation fan is not operating and the respective damper shall be closed.
2. In auto mode, standby equipment shall be start automatically. If both duty and standby equipment fails and the system shall shut down.
3. Audio and visual alarm shall be provided for failure / malfunction of HVAC equipment, component, instrument, etc,.
Project : Golar Hilli FLNG

Doc. Title : Operation Philosophy - HVAC System

Doc. No. : C110-M406.01

Doc. Rev. : 3

Page No. : 104

Rev. Date : 03 / 06 / 2017

19.0 Cause and Action - Chilled Water System

Cause Action
( Closed, Trip, Malfunction, etc,. ) ( Close, Stop, Shutdown, etc,. )
Item Method Remark
Tag No. Service Tag No. Service

97-PA-001A Chilled Water Pump A Unable to start


1 49-FS-80003 Flow Switch - Chilled Water System
97-PA-001B Chilled Water Pump B Unable to start

2 49-FS-80001 Flow Switch - Chilled Water Circuit A


Unable to start
3 53-FS-80001 Flow Switch - Fresh Water Circuit A 97-GB-001A Fresh Water Cooled Chiller Unit A
( by JCI )
4 49-200MO-001 Motorized Valve - Chilled Water Circuit A

5 49-FS-80002 Flow Switch - Chilled Water Circuit B


Unable to start
6 53-FS-80002 Flow Switch - Fresh Water Circuit B 97-GB-001B Fresh Water Cooled Chiller Unit B
( by JCI )
7 49-200MO-002 Motorized Valve - Chilled Water Circuit B

Note : 1. Interlock implies both cause and action are interlocked with each other. Refer to vessel F&G philosophy for smoke, fire event and emergency operation.
For example : If valve is closed, the unit unable to start as well as if the unit is not operating and the respective valve shall be closed.
2. In auto mode, standby equipment shall be start automatically. If both duty and standby equipment fails and the system shall shut down.
3. Audio and visual alarm shall be provided for failure / malfunction of HVAC equipment, component, instrument, etc,.
Project : Golar Hilli FLNG

Doc. Title : Operation Philosophy - HVAC System

Doc. No. : C110-M406.01

Doc. Rev. : 3

Page No. : 105

Rev. Date : 03 / 06 / 2017

20.0 Cause and Action - Ventilation System - Emergency Generator Room

Cause Action
( Closed, Trip, Malfunction, etc,. ) ( Close, Stop, Shutdown, etc,. )
Item Method Remark
Tag No. Service Tag No. Service

1 97-GE-1409 Damper - Air Inlet of Normal Ventilation 97-GK-010 Ventilation Fan ( Normal Operation ) 2 ways Interlocked

2 97-GE-1410 Damper - Air Outlet of Normal Ventilation 97-GE-1409 Damper - Air Inlet of Normal Ventilation 1 way Close

Note : 1. Interlock implies both cause and action are interlocked with each other. Refer to vessel F&G philosophy for smoke, fire event and emergency operation.
For example : If damper is closed, the ventilation fan unable to start as well as if the ventilation fan is not operating and the respective damper shall be closed.
2. Audio and visual alarm shall be provided for failure / malfunction of HVAC equipment, component, instrument, etc,.
Project : Golar Hilli FLNG

Doc. Title : Operation Philosophy - HVAC System

Doc. No. : C110-M406.01

Doc. Rev. : 3

Page No. : 106

Rev. Date : 03 / 06 / 2017

21.0 Cause and Action - Ventilation System - Emergency Staircase Pressurization

Cause Action
( Closed, Trip, Malfunction, etc,. ) ( Close, Stop, Shutdown, etc,. )
Item Method Remark
Tag No. Service Tag No. Service

Damper - Fresh Air Duct of Emergency Ventilation Fan - Emergency Staircase


1 97-GE-1315 97-GK-023 2 ways Interlocked
Staircase Pressurization System - Port Pressurization System - Port

Damper - Fresh Air Duct of Emergency Ventilation Fan - Emergency Staircase


2 97-GE-1316 97-GK-024 2 ways Interlocked
Staircase Pressurization System - Stbd. Pressurization System - Stbd.

Note : 1. Interlock implies both cause and action are interlocked with each other. Refer to vessel F&G philosophy for smoke, fire event and emergency operation.
For example : If damper is closed, the ventilation fan unable to start as well as if the ventilation fan is not operating and the respective damper shall be closed.
2. Audio and visual alarm shall be provided for failure / malfunction of HVAC equipment, component, instrument, etc,.
Project : Golar Hilli FLNG

Doc. Title : Operation Philosophy - HVAC System

Doc. No. : C110-M406.01

Doc. Rev. : 3

Page No. : 107

Rev. Date : 03 / 06 / 2017

22.0 Cause and Action - Ventilation System - Aft. Store and Steering Gear Room

Cause Action
( Closed, Trip, Malfunction, etc,. ) ( Close, Stop, Shutdown, etc,. )
Item Method Remark
Tag No. Service Tag No. Service

1 97-GE-0001 Damper - Air Inlet of Supply Air Fan A 97-GK-016 Supply Air Fan A 2 ways Interlocked

2 97-GE-0002 Damper - Air Inlet of Supply Air Fan B 97-GK-017 Supply Air Fan B 2 ways Interlocked

3 97-GE-0003 Damper - Air Inlet of Supply Air Fan C 97-GK-018 Supply Air Fan C 2 ways Interlocked

4 97-GE-0004 Damper - Air Outlet of Exhaust Air Fan A 97-GK-019 Exhaust Air Fan A 2 ways Interlocked

5 97-GE-0005 Damper - Air Outlet of Exhaust Air Fan B 97-GK-020 Exhaust Air Fan B 2 ways Interlocked

6 97-GE-0006 Damper - Air Outlet of Exhaust Air Fan C 97-GK-021 Exhaust Air Fan C 2 ways Interlocked

Note : 1. Interlock implies both cause and action are interlocked with each other. Refer to vessel F&G philosophy for smoke, fire event and emergency operation.
For example : If damper is closed, the ventilation fan unable to start as well as if the ventilation fan is not operating and the respective damper shall be closed.
2. In auto mode, standby equipment shall be start automatically. If both duty and standby equipment fails and the system shall shut down.
3. Audio and visual alarm shall be provided for failure / malfunction of HVAC equipment, component, instrument, etc,.
Project : Golar Hilli FLNG

Doc. Title : Operation Philosophy - HVAC System

Doc. No. : C110-M406.01

Doc. Rev. : 3

Page No. : 108

Rev. Date : 03 / 06 / 2017

23.0 Cause and Action - HVAC System - Laboratory

Cause Action
( Closed, Trip, Malfunction, etc,. ) ( Close, Stop, Operate, Shutdown, etc,. )
Item Method Remark
Tag No. Service Tag No. Service

1 97-GE-5001 Damper - Fresh Air Inlet - HVAC Unit A 97-GK-603A Blower Fan A - HVAC Unit A 2 ways Interlocked

2 97-GE-5002 Damper - Fresh Air Inlet - HVAC Unit B 97-GK-603B Blower Fan B - HVAC Unit B 2 ways Interlocked
97-GK-603A Blower Fan A - HVAC Unit A 1 way Stop
3 97-GE-5003 Damper - Supply Air Duct
97-GK-603B Blower Fan B - HVAC Unit B 1 way Stop
97-GK-029A Exhaust Air Fan A 1 way Stop
4 97-GE-5004 Damper - Exhaust Air Duct
97-GK-029B Exhaust Air Fan B 1 way Stop

5 97-GK-603A Blower Fan A - AHU A 97-GD-003A Electric Heater A - AHU A 1 way


Off / Unable to On
6 97-GK-603B Blower Fan B - AHU B 97-GD-003B Electric Heater B - AHU B 1 way

Note : 1. Interlock implies both cause and action are interlocked with each other. Refer to vessel F&G philosophy for smoke, fire event and emergency operation.
For example : If damper is closed, the ventilation fan unable to start as well as if the ventilation fan is not operating and the respective damper shall be closed.
2. In auto mode, standby equipment shall be start automatically. If both duty and standby equipment fails and the system shall shut down.
3. Audio and visual alarm shall be provided for failure / malfunction of HVAC equipment, component, instrument, etc,.
Project : Golar Hilli FLNG

Doc. Title : Operation Philosophy - HVAC System

Doc. No. : C110-M406.01

Doc. Rev. : 3

Page No. : 109

Rev. Date : 03 / 06 / 2017

24.0 Cause and Action - Ventilation System - Lift Shaft and Lift Machinery Space

Cause Action
( Closed, Trip, Malfunction, etc,. ) ( Close, Stop, Shutdown, etc,. )
Item Method Remark
Tag No. Service Tag No. Service

1 97-GE-4027 Damper - Fresh Air Duct 97-GK-011 Fresh Air Fan 2 ways Interlocked

2 97-GE-1703 Damper - Exhaust Air Duct 97-GK-012 Exhaust Air Fan 1 way Stop

3 97-GK-011 Fresh Air Fan 97-GK-012 Exhaust Air Fan 1 way Stop

Note : 1. Interlock implies both cause and action are interlocked with each other. Refer to vessel F&G philosophy for smoke, fire event and emergency operation.
For example : If damper is closed, the ventilation fan unable to start as well as if the ventilation fan is not operating and the respective damper shall be closed.
2. Audio and visual alarm shall be provided for failure / malfunction of HVAC equipment, component, instrument, etc,.
Project : Golar Hilli FLNG

Doc. Title : Operation Philosophy - HVAC System

Doc. No. : C110-M406.01

Doc. Rev. : 3

Page No. : 110

Rev. Date : 03 / 06 / 2017

25.0 Cause and Action - Ventilation System - Miscellaneous Compartments at 1st Deck

Cause Action
( Closed, Trip, Malfunction, etc,. ) ( Close, Stop, Shutdown, etc,. )
Item Method Remark
Tag No. Service Tag No. Service

Ventilation System - Store

1 97-GE-4014 Damper - Fresh Air Duct 97-GK-025 Fresh Air Fan 2 ways Interlocked

2 97-GE-4015 Damper - Exhaust Air Duct 97-GK-026 Exhaust Air Fan 2 ways Interlocked

3 97-GK-025 Fresh Air Fan 97-GK-026 Exhaust Air Fan 1 way Stop

Ventilation System - Paint Store

4 97-GE-4022 Damper - Natural Fresh Air Inlet 97-GE-4023 Damper - Exhaust Air Duct 2 ways Interlocked

5 97-GE-4023 Damper - Exhaust Air Duct 97-GK-028 Exhaust Air Fan 2 ways Interlocked

Ventilation System -Bosun Store, Workshop, Ship's Store, Dry Powder Aggregate
97-GK-027 Fresh Air Fan 2 ways Interlocked
97-GE-4017 Damper - EAD - Bonsun Store 1 way
6 97-GE-4016 Damper - Fresh Air Duct 97-GE-4018 Damper - EAD - Workshop 1 way
97-GE-4019 Damper - EAD - Ship's Store 1 way
97-GE-4020 Damper - FAD - Dry Powder Aggregate 1 way

7 97-GE-4020 Damper - FAD - Dry Powder Aggregate 97-GE-4021 Damper - EAD - Dry Powder Aggregate 1 way

Note : 1. Interlock implies both cause and action are interlocked with each other. Refer to vessel F&G philosophy for smoke, fire event and emergency operation.
For example : If damper is closed, the ventilation fan unable to start as well as if the ventilation fan is not operating and the respective damper shall be closed.
2. Audio and visual alarm shall be provided for failure / malfunction of HVAC equipment, component, instrument, etc,.
Project : Golar Hilli FLNG

Doc. Title : Operation Philosophy - HVAC System

Doc. No. : C110-M406.01

Doc. Rev. : 3

Page No. : 111

Rev. Date : 03 / 06 / 2017

26.0 Cause and Action - Ventilation System - Engine Room and Machinery Area

Cause Action
( Closed, Trip, Malfunction, etc,. ) ( Close, Stop, Shutdown, etc,. )
Item Method Remark
Tag No. Service Tag No. Service

Ventilation System - Engine Room and Machinery Area - Port

1 97-GE-6003 Damper - Air Inlet of Fan 97-GK-6005 97-GK-6005 Supply Air Fan - Aft. Area - Port 2 ways Interlocked

2 97-GE-6005 Damper - Air Inlet of Fan 97-GK-6003 97-GK-6003 Supply Air Fan - Fwd. Area - Port 2 ways Interlocked

3 97-GE-6007 Damper - Air Outlet of Fan 97-GK-6007 97-GK-6007 Supply Air Fan - Comfort Ventilation - Port 2 ways Interlocked

4 97-GE-6011 Damper - Exhaust Air Outlet # 2 97-GK-6001 Exhaust Air Fan - Port 2 ways Interlocked

Ventilation System - Engine Room and Machinery Area - Stbd.

5 97-GE-6004 Damper - Air Inlet of Fan 97-GK-6006 97-GK-6006 Supply Air Fan - Aft. Area - Stbd. 2 ways Interlocked

6 97-GE-6006 Damper - Air Inlet of Fan 97-GK-6006 97-GK-6004 Supply Air Fan - Fwd. Area - Stbd. 2 ways Interlocked

7 97-GE-6008 Damper - Air Outlet of Fan 97-GK-6008 97-GK-6008 Supply Air Fan - Comfort Ventilation - Stbd. 2 ways Interlocked

8 97-GE-6010 Damper - Air Outlet of Fan 97-GK-6009 97-GK-6009 Exhaust Air Fan - Boiler Fan Motor Room 2 ways Interlocked

9 97-GE-6012 Damper - Exhaust Air Outlet # 2 97-GK-6002 Exhaust Air Fan - Stbd. 2 ways Interlocked

Note : 1. Interlock implies both cause and action are interlocked with each other. Refer to vessel F&G philosophy for smoke, fire event and emergency operation.
For example : If damper is closed, the ventilation fan unable to start as well as if the ventilation fan is not operating and the respective damper shall be closed.
2. Audio and visual alarm shall be provided for failure / malfunction of HVAC equipment, component, instrument, etc,.