ADMINISTRATION & CANTEEN BUILDING
PROJECT
DOCUMENT NO:
TITLE :
For Review
PT SOMIT TRAKONAD
ENGINEERING & CONSTRUCTION CS-HVAC-01
SHEET 2 OF 12
DOC. NO. :
REV
DISTRIBUTION ORDER
DDO Attachment
Project Director OWNER
Project Manager Head Office
Engineering Manager Site Office
Procurement Manager
Construction Manager
Chief Construction Control
Chief QA & QC
Chief Safety
Civil Lead Eng.
Electrical Lead Eng.
Instrument Lead Eng.
Mechanical Lead Eng.
Piping Lead Eng.
Process Lead Eng.
SHEET 3 OF 12
DOC. NO. :
REV
CONTENS
PAGE
A. Introduction 4
B. Abbreviations 4
C. Reference 4
D. Software 5
E. Design Criteria 5
F. Design Metodh 6
A. Introduction
This calculation for requirement of HVAC Engineering project of:
Project : ADMINISTRATION & CANTEEN BUILIDNG PROJECT
Client : PT. CEMINDO GEMILANG
Location : BAYAH BANTEN
Scope : Ventilating and Air Conditioning (VAC)
B. Abbreviations
- ASHRAE : American Society Of Heating, Refrigerating and Air-
Conditioning Engineers
- SMACNA : Sheet Methal American Contractors Nation Association
- NFPA : National Fire Protection Association
- ARI : Association Refrigeration International
C. Reference
ASHRAE Fundamental Handbook 1997
Chapter 28 NONRESIDENTIAL COOLING AND HEATING LOAD
CALCULATIONS
ASHRAE Handbook : GRP 158 Cooling & Heating Load Calculation Manual
ASHRAE Std 62 2001
Except contrary stated anywhere in the specification or construction drawings,
the following standards shall apply for this project :
iii. ARI 360 - Commercial and Industrial Unitary Air Conditioning Equipment
testing and rating standard. (above 135,000 btuh)
viii. ARI 210 / 240 - Unitary Air-Conditioning Equipment and Air- Source Heat
Pump Equipment. (all under 135,000 btuh)
ix. ARI 370 - Sound Rating of Large Outdoor Refrigerating and Air
Conditioning Equipment.(all above 135,000 Btuh)
E. Design Criteria
Indoor Condition
RH : Not Conditoned
Air Change Per Hour (ACH)
F. Design Metodh
Calculation Metodh is Cooling Load Temperature Difference reffer to ASHRAE GRP-158.
Note:
1. Refer To ASHRAE GRP 158 table 3.1 Chapter 3
2. Refer To ASHRAE GRP158 table 3.3 Chapter 3
3. Refer To ASHRAE GRP 158 table 3.1 Chapter 3
SHEET 9 OF 12
DOC. NO. :
REV
Table 4 Typical Thermal Properties of Common Building and Insulating MaterialsDesign Valuesa
Resistancec (R)
Conductivityb Conductance For Thickness Specific
Density, (k), (C), 1/k, Listed (1/C), Heat,
Description kg/m3 W/(mK) W/(m2 K) Km/W Km2 /W kJ/(kgK)
BUILDING BOARD
Asbestos-cement board .................................................. 1900 0.58 1.73 1.00
Asbestos-cement board ......................................3.2 mm 1900 187.4 0.005
Asbestos-cement board ......................................6.4 mm 1900 93.7 0.011
Gypsum or plaster board....................................9.5 mm 800 17.6 0.056 1.09
Gypsum or plaster board..................................12.7 mm 800 12.6 0.079
Gypsum or plaster board..................................15.9 mm 800 10.1 0.099
Plywood (Douglas fir)d .................................................. 540 0.12 8.66 1.21
Plywood (Douglas fir)........................................6.4 mm 540 18.2 0.055
Plywood (Douglas fir)........................................9.5 mm 540 12.1 0.083
Plywood (Douglas fir)......................................12.7 mm 540 9.1 0.11
Plywood (Douglas fir)......................................15.9 mm 540 7.3 0.14
Plywood or wood panels ..................................19.0 mm 540 6.1 0.16 1.21
Vegetable fiber board
Sheathing, regular densitye .......................12.7 mm 290 4.3 0.23 1.30
..................................................................19.8 mm 290 2.8 0.36
Sheathing intermediate densitye................12.7 mm 350 5.2 0.19 1.30
Nail-base sheathinge .................................12.7 mm 400 5.3 0.19 1.30
Shingle backer.............................................9.5 mm 290 6.0 0.17 1.30
Shingle backer.............................................7.9 mm 290 7.3 0.14
Sound deadening board.............................12.7 mm 240 4.2 0.24 1.26
Tile and lay-in panels, plain or acoustic ................. 290 0.058 17. 0.59
....12.7 mm 290 4.5 0.22
....19.0 mm 290 3.0 0.33
Laminated paperboard .................................. 480 0.072 13.9 1.38
Homogeneous board from repulped paper.... 480 0.072 13.9 1.17
Hardboarde
Medium density ....................................................... 800 0.105 9.50 1.30
High density, service-tempered grade and service
grade...................................................................... 880 0.82 8.46 1.34
High density, standard-tempered grade.................... 1010 0.144 6.93 1.34
Particleboarde
Low density.............................................................. 590 0.102 9.77 1.30
Medium density ....................................................... 800 0.135 7.35 1.30
High density ............................................................. 1000 0.170 5.90 1.30
Underlayment.............................................15.9 mm 640 6.9 0.14 1.21
Waferboard..................................................................... 590 0.01 11.0
Wood subfloor..................................................19.0 mm 6.0 0.17 1.38
BUILDING MEMBRANE
Vaporpermeable felt ................................................... 94.9 0.011
Vaporseal, 2 layers of mopped 0.73 kg/m2 felt .......... 47.4 0.21
Vaporseal, plastic film................................................ Negl.
FINISH FLOORING MATERIALS
Carpet and fibrous pad ................................................... 2.73 0.37 1.42
Carpet and rubber pad.................................................... 4.60 0.22 1.38
Cork tile .............................................................3.2 mm 20.4 0.049 2.01
Terrazzo...............................................................25 mm 71.0 0.014 0.80
Tileasphalt, linoleum, vinyl, rubber ........................... 113.6 0.009 1.26
vinyl asbestos ........................................................... 1.01
ceramic..................................................................... 0.80
Wood, hardwood finish .......................................19 mm 8.35 0.12
INSULATING MATERIALS
Blanket and Battf,g
Mineral fiber, fibrous form processed
from rock, slag, or glass
approx. 75-100 mm ............................................ 6.4-32 0.52 1.94
approx. 90 mm ................................................... 6.4-32 0.44 2.29
approx. 90 mm ................................................... 19-26 0.38 2.63
approx. 140-165 mm.......................................... 6.4-32 0.30 3.32
approx. 140 mm ................................................. 10-16 0.27 3.67
approx. 150-190 mm.......................................... 6.4-32 0.26 3.91
approx. 210-250 mm.......................................... 6.4-32 0.19 5.34
approx. 250-330 mm.......................................... 6.4-32 0.15 6.77
Board and Slabs
Cellular glass.................................................................. 136 0.050 19.8 0.75
Glass fiber, organic bonded............................................ 64-140 0.036 27.7 0.96
Expanded perlite, organic bonded.................................. 16 0.052 19.3 1.26
Expanded rubber (rigid)................................................. 72 0.032 31.6 1.68
Expanded polystyrene, extruded (smooth skin surface)
(CFC-12 exp.) ............................................................. 29-56
25.6 2001 ASHRAE Fundamentals Handbook (SI)
Table 4 Typical Thermal Properties of Common Building and Insulating MaterialsDesign Valuesa (Continued)
Resistancec (R)
Conductivityb Conductance For Thickness Specific
Density, (k), (C), 1/k, Listed (1/C), Heat,
Description kg/m3 W/(mK) W/(m2 K) Km/W Km2 /W kJ/(kgK)
Expanded polystyrene, extruded (smooth skin surface)
(HCFC-142b exp.)h ..................................................... 29-56 0.029 34.7 1.21
Expanded polystyrene, molded beads............................ 16 0.037 26.7
20 0.036 27.7
24 0.035 28.9
28 0.035 28.9
32 0.033 30.2
Cellular polyurethane/polyisocyanuratei
(CFC-11 exp.) (unfaced) ............................................. 24 0.023-0.026 43.3-38.5 1.59
Cellular polyisocyanuratei (CFC-11 exp.)
(gas-permeable facers) ................................................ 24-40 0.023-0.026 43.3-38.5 0.92
Cellular polyisocyanuratej (CFC-11 exp.)
(gas-impermeable facers)............................................ 32 0.020 48.8 0.92
Cellular phenolic (closed cell) (CFC-11, CFC-113 exp.)k 32 0.017 56.8
Cellular phenolic (open cell).................................... 29-35 0.033 30.5
Mineral fiber with resin binder ................................ 240 0.042 23.9 0.71
Mineral fiberboard, wet felted
Core or roof insulation ............................................. 260-270 0.049 20.4
Acoustical tile .......................................................... 290 0.050 19.8 0.80
Acoustical tile .......................................................... 340 0.053 18.7
Mineral fiberboard, wet molded
Acoustical tilel ......................................................... 370 0.060 16.5 0.59
Wood or cane fiberboard
Acoustical tilel ...........................................12.7 mm 4.5 0.22 1.30
Acoustical tilel ...........................................19.0 mm 3.0 0.33
Interior finish (plank, tile)................................... 240 0.050 19.8 1.34
Cement fiber slabs (shredded wood with Portland
cement binder) ............................................................ 400-430 0.072-0.076 13.9-13.1
Cement fiber slabs (shredded wood with magnesia
oxysulfide binder) ....................................................... 350 0.082 12.1 1.30
Loose Fill
Cellulosic insulation (milled paper or wood pulp) ........ 37-51 0.039-0.046 25.6-21.7 1.38
Perlite, expanded............................................................ 32-66 0.039-0.045 25.6-22.9 1.09
66-120 0.045-0.052 22.9-19.4
120-180 0.052-0.060 19.4-16.6
Mineral fiber (rock, slag, or glass)g
approx. 95-130 mm .................................................. 9.6-32 1.94 0.71
approx. 170-220 mm................................................ 9.6-32 3.35
approx. 190-250 mm................................................ 9.6-32 3.87
approx. 260-350 mm................................................ 9.6-32 5.28
Mineral fiber (rock, slag, or glass)g
approx. 90 mm (closed sidewall application) .......... 32-56 2.1-2.5
Vermiculite, exfoliated ................................................... 110-130 0.068 14.8 1.34
64-96 0.063 15.7
Spray Applied
Polyurethane foam ......................................................... 24-40 0.023-0.026 43.3-38.5
Ureaformaldehyde foam ................................................ 11-26 0.032-0.040 31.5-24.7
Cellulosic fiber............................................................... 56-96 0.042-0.049 23.9-20.4
Glass fiber ...................................................................... 56-72 0.038-0.039 26.7-25.6
Reflective Insulation
Reflective material ( < 0.5) in center of 20 mm cavity
forms two 10 mm vertical air spacesm ........................ 1.76 0.57
METALS
(See Chapter 38, Table 3)
ROOFING
Asbestos-cement shingles .............................................. 1900 27.0 0.037 1.00
Asphalt roll roofing........................................................ 1100 36.9 0.026 1.51
Asphalt shingles ............................................................. 1100 12.9 0.077 1.26
Built-up roofing ..................................................10 mm 1100 17.0 0.058 1.46
Slate ....................................................................13 mm 114 0.009 1.26
Wood shingles, plain and plastic film faced .................. 6.0 0.166 1.30
PLASTERING MATERIALS
Cement plaster, sand aggregate...................................... 1860 0.72 1.39 0.84
Sand aggregate ..............................................10 mm 75.5 0.013 0.84
Sand aggregate ..............................................20 mm 37.8 0.026 0.84
Thermal and Water Vapor Transmission Data 25.7
Table 4 Typical Thermal Properties of Common Building and Insulating MaterialsDesign Valuesa (Continued)
Resistancec (R)
Conductivityb Conductance For Thickness Specific
Density, (k), (C), 1/k, Listed (1/C), Heat,
Description kg/m3 W/(mK) W/(m2 K) Km/W Km2 /W kJ/(kgK)
Gypsum plaster:
Lightweight aggregate ..................................13 mm 720 17.7 0.056
Lightweight aggregate ..................................16 mm 720 15.2 0.066
Lightweight aggregate on metal lath.............19 mm 12.1 0.083
Perlite aggregate............................................................. 720 0.22 4.64 1.34
Sand aggregate ......................................................... 1680 0.81 1.25 0.84
Sand aggregate ..............................................13 mm 1680 63.0 0.016
Sand aggregate ..............................................16 mm 1680 51.7 0.019
Sand aggregate on metal lath ........................19 mm 43.7 0.023
Vermiculite aggregate .............................................. 720 0.24 4.09
MASONRY MATERIALS
Masonry Units
Brick, fired clay ............................................................. 2400 1.21-1.47 0.83-0.68
2240 1.07-1.30 0.94-0.77
2080 0.92-1.12 1.08-0.89
1920 0.81-0.98 1.24-1.02 0.79
1760 0.71-0.85 1.42-1.18
1600 0.61-0.74 1.65-1.36
1440 0.52-0.62 1.93-1.61
1280 0.43-0.53 2.31-1.87
1120 0.36-0.45 2.77-2.23
Clay tile, hollow
1 cell deep ........................................................75 mm 7.10 0.14 0.88
1 cell deep ......................................................100 mm 5.11 0.20
2 cells deep.....................................................150 mm 3.75 0.27
2 cells deep.....................................................200 mm 3.07 0.33
2 cells deep.....................................................250 mm 2.56 0.39
3 cells deep.....................................................300 mm 2.27 0.44
Concrete blocksn, o
Limestone aggregate
200 mm, 16.3 kg, 2210 kg/m3 concrete, 2 cores......
Same with perlite filled cores ............................... 2.73 0.37
300 mm, 25 kg, 2210 kg/m3 concrete, 2 cores.........
Same with perlite filled cores ............................... 1.53 0.65
Normal mass aggregate (sand and gravel) 200 mm
15-16 kg, 2020-2180 kg/m3 concrete, 2 or 3 cores 5.1-5.8 0.20-0.17 0.92
Same with perlite filled cores ............................... 2.84 0.35
Same with vermiculite filled cores ....................... 3.0-4.1 0.34-0.24
300 mm, 22.7 kg, 2000 kg/m3 concrete, 2 cores...... 4.60 0.217 0.92
Medium mass aggregate (combinations of normal
and low mass aggregate) 200 mm, 12-13 kg,
1550-1790 kg/m3 concrete, 2 or 3 cores .................. 3.3-4.4 0.30-0.22
Same with perlite filled cores ............................... 1.5-2.5 0.65-0.41
Same with vermiculite filled cores ....................... 1.70 0.58
Same with molded EPS (beads) filled cores ......... 1.82 0.56
Same with molded EPS inserts in cores................ 2.10 0.47
Low mass aggregate (expanded shale, clay, slate or
slag, pumice) 150 mm
7.3-7.7 kg, 1360-1390 kg/m3 concrete, 2 or 3 cores 3.0-3.5 0.34-0.29
Same with perlite filled cores ............................... 1.36 0.74
Same with vermiculite filled cores ....................... 1.87 0.53
200 mm, 8.6-10.0 mm, 1150-1380 kg/m3 concrete, 1.8-3.1 0.56-0.33 0.88
Same with perlite filled cores ............................... 0.9-1.3 1.20-0.77
Same with vermiculite filled cores ....................... 1.1-1.5 0.93-0.69
Same with molded EPS (beads) filled cores ......... 1.19 0.85
Same with UF foam filled cores ........................... 1.25 0.79
Same with molded EPS inserts in cores................ 1.65 0.62
300 mm, 14.5-16.3 kg, 1280-1440 kg/m3 concrete,
2 or 3 cores............................................................ 2.2-2.5 0.46-0.40
Same with perlite filled cores ............................... 0.6-0.9 1.6-1.1
Same with vermiculite filled cores ....................... 0.97 1.0
Stone, lime, or sand
Quartzitic and sandstone ......................................... 2880 10.4 0.10
2560 6.2 0.16
2240 3.5 0.29
1920 1.9 0.53 0.79
Calcitic, dolomitic, limestone, marble, and granite .... 2880 4.3 0.23
2560 3.2 0.32
2240 2.3 0.43
1920 1.6 0.63 0.79
1600 1.1 0.90
25.8 2001 ASHRAE Fundamentals Handbook (SI)
Table 4 Typical Thermal Properties of Common Building and Insulating MaterialsDesign Valuesa (Continued)
Resistancec (R)
Conductivityb Conductance For Thickness Specific
Density, (k), (C), 1/k, Listed (1/C), Heat,
Description kg/m3 W/(mK) W/(m2 K) Km/W Km2 /W kJ/(kgK)
Gypsum partition tile
75 by 300 by 760 mm, solid..................................... 4.50 0.222 0.79
75 by 300 by 760 mm, 4 cells .................................. 4.20 0.238
100 by 300 by 760 mm, 3 cells ................................ 3.40 0.294
Concreteso
Sand and gravel or stone aggregate concretes (concretes 2400 1.4-2.9 0.69-0.35
with more than 50% quartz or quartzite sand have 2240 1.3-2.6 0.77-0.39 0.8-1.0
conductivities in the higher end of the range)............. 2080 1.0-1.9 0.99-053
Limestone concretes ...................................................... 2240 1.60 0.62
1920 1.14 0.88
1600 0.79 1.26
Gypsum-fiber concrete (87.5% gypsum, 12.5%
wood chips) 816 0.24 4.18 0.88
Cement/lime, mortar, and stucco ................................... 1920 1.40 0.71
1600 0.97 1.04
1280 0.65 1.54
Lightweight aggregate concretes
Expanded shale, clay, or slate; expanded slags; 1920 0.9-1.3 1.08-0.76
cinders; pumice (with density up to 1600 kg/m3); 1600 0.68-0.89 1.48-1.12 0.84
and scoria (sanded concretes have conductivities in 1280 0.48-0.59 2.10-1.69 0.84
the higher end of the range) ........................................ 960 0.30-0.36 3.30-2.77
640 0.18 5.40
Perlite, vermiculite, and polystyrene beads ................ 800 0.26-0.27 3.81-3.68
640 0.20-0.22 4.92-4.65 0.63-0.96
480 0.16 6.31
320 0.12 8.67
Foam concretes .............................................................. 1920 0.75 1.32
1600 0.60 1.66
1280 0.44 2.29
1120 0.36 2.77
Foam concretes and cellular concretes .......................... 960 0.30 3.33
640 0.20 4.92
320 0.12 8.67
SIDING MATERIALS (on flat surface)
Shingles
Asbestos-cement ......................................................... 1900 27.0 0.037
Wood, 400 mm, 190 mm exposure ............................. 6.53 0.15 1.30
Wood, double, 400 mm, 300 mm exposure ................ 4.77 0.21 1.17
Wood, plus insul. backer board, 8 mm........................ 4.03 0.25 1.30
Siding
Asbestos-cement, 6.4 mm, lapped .............................. 27.0 0.037 1.01
Asphalt roll siding....................................................... 36.9 0.026 1.47
Asphalt insulating siding (12.7 mm bed.)................... 3.92 0.26 1.47
Hardboard siding, 11 mm ........................................... 8.46 0.12 1.17
Wood, drop, 20 by 200 mm......................................... 7.21 0.14 1.17
Wood, bevel, 13 by 200 mm, lapped........................... 6.98 0.14 1.17
Wood, bevel, 19 by 250 mm, lapped........................... 5.40 0.18 1.17
Wood, plywood, 9.5 mm, lapped ................................ 9.60 0.10 1.22
Aluminum, steel, or vinylp, q, over sheathing
Hollow-backed ......................................................... 9.31 0.11 1.22q
Insulating-board backed...........................................
9.5 mm nominal ....................................................... 3.12 0.32 1.34
9.5 mm nominal, foil backed ................................... 1.93 0.52
Architectural (soda-lime float) glass.............................. 56.8 0.018 0.84
WOODS (12% moisture content)e,r
Hardwoods 1.63s
Oak.............................................................................. 659-749 0.16-0.18 6.2-5.5
Birch............................................................................ 682-726 0.167-0.176 6.0-5.7
Maple .......................................................................... 637-704 0.157-0.171 6.4-5.8
Ash .............................................................................. 614-670 0.153-0.164 6.5-6.1
Softwoods 1.63s
Southern pine .............................................................. 570-659 0.144-0.161 6.9-6.2
Douglas fir-Larch........................................................ 536-581 0.137-0.145 7.3-6.9
Southern cypress ......................................................... 502-514 0.130-0.132 7.7-7.6
Hem-Fir, Spruce-Pine-Fir ........................................... 392-502 0.107-0.130 9.3-7.7
West coast woods, Cedars........................................... 347-502 0.098-0.130 10.3-7.7
California redwood ..................................................... 392-448 0.107-0.118 9.4-8.5
SHEET 12 OF 12
DOC. NO. :
REV
1 Administration Ground Floor GF- Lobby, Resepsionist#1 290.0 3.2 928.0 5,280 24C+1
Zone GF-01 GF- Security Monitor#1 9.0 3.2 28.8 329 24C+1
GF- Ruang Tunggu#1 26.0 3.2 83.2 550 24C+1
Total 325.0 6,159 176.50 543 Split Duct
Zone GF-02-2 GF- Area Staff #2 93.0 3.2 297.6 3,883 24C+1
GF- Storage HSE#1 17.0 3.2 54.4 392 24C+1
GF- Manager#5 12.0 3.2 38.4 370 24C+1
GF- Musholah#1 27.7 3.2 88.6 805 24C+1
GF- ATM # 1 17.5 3.2 56.0 343 24C+1
Total 167.2 5,793 79.00 472 Split Duct
Zone GF-05 GF- Docter#1 16.0 3.2 51.2 823 16.60 1,038 24C+1 Wall Mounted
Zone GF-06 GF- Patient#1 21.3 3.2 68.2 171 5.00 235 24C+1 Wall Mounted
Zone GF-07 GF- Server#1 11.0 3.2 35.2 665 13.40 1,218 24C+1 Wall Mounted
Zone 1F-02 1F- Grand Meeting#1 38.0 3.2 121.6 1,126 24C+1
1F- Area Staff#1 293.5 3.2 939.2 4,390 24C+1
1F- Manager#1 12.0 3.2 38.4 537 22C+1
1F- Manager#2 12.0 3.2 38.4 447 24C+1
1F- Manager#3 12.0 3.2 38.4 447 24C+1
1F- Manager#4 12.0 3.2 38.4 447 24C+1
1F- File#1 24.0 3.2 76.8 419 24C+1
1F- File Storage#2 26.5 3.2 84.8 568 24C+1
Total 430.0 8,381 225 522 Split Duct
Zone 1F-03-2 1F- Area Staff#2 223.0 3.2 713.6 3,883 24C+1
1F- File Storage#1 12.5 3.2 40.0 392 24C+1
Total 235.5 4,275 114 484 Split Duct
Second Floor 2F- Lobby, Secretary#1 286.0 3.2 915.2 4,916 22C+1
Zone 2F-01 2F- Security Monitor#1 9.4 3.2 30.1 323 24C+1
2F- Exce Dining#1 25.0 3.2 80.0 784 24C+1
Total 320.4 6,023 137 427 Split Duct
Zone 2F-02 2F- Ruang Tunggu#1 164.5 3.2 526.4 1,540 24C+1
2F- Director#1 49.0 3.2 156.8 1,045 24C+1
2F- Komisaris#1 53.0 3.2 169.6 873 24C+1
2F- Komisaris#2 53.0 3.2 169.6 714 24C+1
2F- Director#2 35.0 3.2 112.0 718 24C+1
2F- Director#3 37.5 3.2 120.0 1,126 24C+1
2F- Director#4 40.7 3.2 130.2 937 24C+1
Total 432.7 6,953 207 477 Split Duct
Zone 2F-03 2F- Grand Meeting#1 100.0 3.2 320.0 2,658 24C+1
2F- Function#1 116.6 3.2 373.1 3,133 24C+1
Total 216.6 5,791 257 1,188 Split Duct
Air Conditioning Summary
Area Air Flow Cooling Load
No. Building Location Room Height volume btuh/m2 Design Temp. Type
(m2) CFM (MBH)
Lantai 3 Zone 3F-01 3F-File Storage#1 24.0 3.2 76.8 520 24C+1
3F-Hall#1 260.0 3.2 832.0 4,435 24C+1
Total 284.0 4,955 143 502
Lantai 4 Zone 4F-01 4F-Lift Room# 4.0 3.2 12.8 787 16.40 4,100 24C+1 Wall Mounted
VENTILATION SUMMARY
Area Height Volume Ventilation Rated EF ESP Power Electricity
No. Building Code Room ACH Qty Type
(m2) (m) (m3) (CFM) (CFM) (In WG) (Watt) (V/Ph/Hz)
Administration
Lantai Dasar GF-1 Pompa 6.0 3.2 19.2 10 112.9 120.0
GF- Me 12.7 3.2 40.6 10 239.1 240.0
360.0 0.4 230 220V/1Ph/50Hz 1 Axial Fan - duct inline
GF- Toilet Male 16.0 3.2 51.2 10 301.2 310.0
GF- Toilet Female 16.0 3.2 51.2 10 301.2 310.0
620.0
GF- Wudhu 4.0 3.2 12.8 10 75.3 80.0
GF- Pantry 4.0 3.2 12.8 15 112.9 120.0
GF- Janitor 3.0 3.2 9.6 10 56.5 60.0
GF- Toilet Clinik 5.0 3.2 16.0 10 94.1 100.0 0.4 70 220V/1Ph/50Hz 1 Axial Fan - duct inline
360.0 0.4 230 220V/1Ph/50Hz 1 Axial Fan - duct inline
GF- Electric#1 (630 kva x 15 39.3 3.2 125.8 42.5 3144.0 3150.0 0.4 220V/1Ph/50Hz 1 Axial Fan - duct inline
cfm/kva = 3150 cfm) 1980
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load ........................................................ 14.7 Tons Load occurs at ................................................... Jan 1600
Total coil load ...................................................... 176.5 MBH OA DB / WB .................................................... 91.0 / 80.5 F
Sensible coil load ................................................ 128.3 MBH Entering DB / WB ............................................ 78.3 / 67.5 F
Coil CFM at Jan 1600 .......................................... 6483 CFM Leaving DB / WB ............................................. 59.9 / 58.9 F
Max block CFM .................................................... 6483 CFM Coil ADP .................................................................... 57.8 F
Sum of peak zone CFM ....................................... 6483 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.727 Resulting RH ................................................................ 55 %
ft/Ton .................................................................. 237.8 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 50.5 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F
Actual max CFM ................................................... 6483 CFM Fan motor BHP .......................................................... 0.76 BHP
Standard CFM ...................................................... 6445 CFM Fan motor kW ............................................................ 0.56 kW
Actual max CFM/ft ............................................... 1.85 CFM/ft Fan static ................................................................... 0.40 in wg
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GF-LOBBY '' IN ZONE '' Zone GF-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 91.0 F / 80.5 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 756 ft 49792 - 756 ft - -
Wall Transmission 452 ft 1437 - 452 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 756 ft 12574 - 756 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 224 ft 9618 - 224 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 204 W 444 - 0 0 -
Task Lighting 250 W 778 - 0 0 -
Electric Equipment 800 W 2538 - 0 0 -
People 29 5740 5947 0 0 0
Infiltration - 4685 11721 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 8761 1767 0% 0 0
>> Total Zone Loads - 96367 19434 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GF-LOBBY '' IN ZONE '' Zone GF-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 214 0.403 - 791 - 0
WINDOW 1 378 1.212 0.880 6287 25154 0
DOOR 22 0.300 - 89 - 0
DOOR GLASS 43 0.580 0.880 343 2867 0
WNW EXPOSURE
WALL 214 0.403 - 646 - 0
WINDOW 1 378 1.212 0.880 6287 24638 0
DOOR 22 0.300 - 89 - 0
DOOR GLASS 43 0.580 0.880 343 2808 0
ENE EXPOSURE
WALL 24 0.403 - 0 - 0
DOOR 30 0.300 - 124 - 0
DOOR GLASS 65 0.580 0.880 514 2442 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' GF-RUANG TUNGGU#1 '' IN ZONE '' Zone GF-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 65 ft 5717 - 65 ft - -
Wall Transmission 65 ft 345 - 65 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 65 ft 742 - 65 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 632 - 0 0 -
People 7 1282 840 0 0 0
Infiltration - 40 108 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 913 95 0% 0 0
>> Total Zone Loads - 10045 1043 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' GF-RUANG TUNGGU#1 '' IN ZONE '' Zone GF-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 65 0.403 - 345 - 0
WINDOW 1 65 0.892 0.631 742 5717 0
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' GF-SECURITY MONITOR#1 '' IN ZONE '' Zone GF-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 88.5 F / 79.9 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 86 W 190 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1400 W 4777 - 0 0 -
People 2 490 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 546 41 0% 0 0
>> Total Zone Loads - 6003 451 - 0 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' GF-SECURITY MONITOR#1 '' IN ZONE '' Zone GF-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................... 632 CFM
Uncorrected Outdoor Airflow Rate .............................................................. 570 CFM
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load ........................................................ 15.0 Tons Load occurs at ................................................... Feb 1600
Total coil load ...................................................... 179.5 MBH OA DB / WB .................................................... 91.0 / 80.5 F
Sensible coil load ................................................ 101.5 MBH Entering DB / WB ............................................ 81.9 / 71.9 F
Coil CFM at Feb 1600 .......................................... 4513 CFM Leaving DB / WB ............................................. 61.0 / 60.1 F
Max block CFM .................................................... 4513 CFM Coil ADP .................................................................... 58.6 F
Sum of peak zone CFM ....................................... 4513 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.566 Resulting RH ................................................................ 58 %
ft/Ton .................................................................. 116.9 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) .......................................................... 102.7 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F
Actual max CFM ................................................... 4513 CFM Fan motor BHP .......................................................... 0.53 BHP
Standard CFM ...................................................... 4487 CFM Fan motor kW ............................................................ 0.39 kW
Actual max CFM/ft ............................................... 2.58 CFM/ft Fan static ................................................................... 0.40 in wg
1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................. 1560 CFM
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GF-CLINIC#1 '' IN ZONE '' Zone GF-02A ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.4 F / 78.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 10522 - 97 ft - -
Wall Transmission 291 ft 1658 - 291 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 97 ft 853 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 54 ft 2019 - 54 ft 0 -
Floor Transmission 129 ft 0 - 129 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 432 W 936 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 55 152 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1789 77 0% 0 0
>> Total Zone Loads - 19679 844 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GF-CLINIC#1 '' IN ZONE '' Zone GF-02A ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WNW EXPOSURE
WALL 118 0.403 - 444 - 0
WINDOW 1 97 0.892 0.631 853 10522 0
NNE EXPOSURE
WALL 172 0.403 - 1214 - 0
DOOR 11 0.300 - 32 - 0
DOOR GLASS 43 0.580 0.880 246 1740 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' GF-NURSE#1 '' IN ZONE '' Zone GF-02A ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.3 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 379 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 637 - 0 0 -
People 2 377 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 139 24 0% 0 0
>> Total Zone Loads - 1532 264 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' GF-NURSE#1 '' IN ZONE '' Zone GF-02A ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' GF-AMBULANCE DRIVER#1 '' IN ZONE '' Zone GF-02A ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.3 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 48 W 105 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 637 - 0 0 -
People 1 201 205 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 94 21 0% 0 0
>> Total Zone Loads - 1037 226 - 0 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' GF-AMBULANCE DRIVER#1 '' IN ZONE '' Zone GF-02A ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' GF-RUANG TRAINING#1 '' IN ZONE '' Zone GF-02A ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.4 F / 78.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 226 ft 24551 - 226 ft - -
Wall Transmission 194 ft 647 - 194 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 226 ft 1991 - 226 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 864 W 1871 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1200 W 3789 - 0 0 -
People 98 17944 11760 0 0 0
Infiltration - 123 342 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 5092 1210 0% 0 0
>> Total Zone Loads - 56008 13312 - 0 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' GF-RUANG TRAINING#1 '' IN ZONE '' Zone GF-02A ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WNW EXPOSURE
WALL 194 0.403 - 647 - 0
WINDOW 1 226 0.892 0.631 1991 24551 0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load .......................................................... 6.6 Tons Load occurs at .................................................. Dec 0800
Total coil load ........................................................ 79.0 MBH OA DB / WB .................................................... 78.6 / 77.8 F
Sensible coil load .................................................. 63.1 MBH Entering DB / WB ............................................ 77.0 / 66.8 F
Coil CFM at Dec 0800 .......................................... 3673 CFM Leaving DB / WB ............................................. 61.0 / 60.1 F
Max block CFM .................................................... 3673 CFM Coil ADP .................................................................... 59.2 F
Sum of peak zone CFM ....................................... 3673 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.798 Resulting RH ................................................................ 56 %
ft/Ton .................................................................. 267.6 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 44.8 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F
Actual max CFM ................................................... 3673 CFM Fan motor BHP .......................................................... 0.43 BHP
Standard CFM ...................................................... 3651 CFM Fan motor kW ............................................................ 0.32 kW
Actual max CFM/ft ............................................... 2.08 CFM/ft Fan static ................................................................... 0.40 in wg
1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................... 267 CFM
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GF-AREA STAFF#2 '' IN ZONE '' Zone GF-02B ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 129 ft 14666 - 129 ft - -
Wall Transmission 301 ft 1143 - 301 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 129 ft 626 - 129 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 636 W 1304 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1600 W 4842 - 0 0 -
People 8 1354 1641 0 0 0
Infiltration - 44 372 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2398 201 0% 0 0
>> Total Zone Loads - 26377 2214 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GF-AREA STAFF#2 '' IN ZONE '' Zone GF-02B ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 301 0.403 - 1143 - 0
WINDOW 1 129 0.892 0.631 626 14666 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' GF-STORAGE-HSE#1 '' IN ZONE '' Zone GF-02B ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 65 ft 7333 - 65 ft - -
Wall Transmission 43 ft 114 - 43 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 65 ft 313 - 65 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 354 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 605 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 9 76 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 873 8 0% 0 0
>> Total Zone Loads - 9602 84 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' GF-STORAGE-HSE#1 '' IN ZONE '' Zone GF-02B ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 43 0.403 - 114 - 0
WINDOW 1 65 0.892 0.631 313 7333 0
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' GF-MANAGER#5 '' IN ZONE '' Zone GF-02B ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 32 ft 3666 - 32 ft - -
Wall Transmission 65 ft 240 - 65 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 32 ft 157 - 32 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 129 ft 0 - 129 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 354 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1211 - 0 0 -
People 3 508 615 0 0 0
Infiltration - 6 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 614 66 0% 0 0
>> Total Zone Loads - 6755 730 - 0 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' GF-MANAGER#5 '' IN ZONE '' Zone GF-02B ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 65 0.403 - 240 - 0
WINDOW 1 32 0.892 0.631 157 3666 0
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' GF-MUSHOLA#1 '' IN ZONE '' Zone GF-02B ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 10999 - 97 ft - -
Wall Transmission 54 ft 126 - 54 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 97 ft 470 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 354 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 605 - 0 0 -
People 5 794 600 0 0 0
Infiltration - 13 111 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1336 71 0% 0 0
>> Total Zone Loads - 14698 782 - 0 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' GF-MUSHOLA#1 '' IN ZONE '' Zone GF-02B ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 54 0.403 - 126 - 0
WINDOW 1 97 0.892 0.631 470 10999 0
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' GF-ATM#1 '' IN ZONE '' Zone GF-02B ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.0 F / 78.5 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 259 ft 1888 - 259 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 31 ft 1844 - 31 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 216 W 471 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1269 - 0 0 -
People 1 198 205 0 0 0
Infiltration - 15 27 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 568 23 0% 0 0
>> Total Zone Loads - 6252 255 - 0 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' GF-ATM#1 '' IN ZONE '' Zone GF-02B ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NNE EXPOSURE
WALL 215 0.403 - 1670 - 0
WNW EXPOSURE
WALL 44 0.403 - 218 - 0
DOOR 10 0.300 - 28 - 0
DOOR GLASS 22 0.580 0.880 121 1694 0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load ........................................................ 17.0 Tons Load occurs at .................................................. Dec 1500
Total coil load ...................................................... 203.9 MBH OA DB / WB .................................................... 90.4 / 80.6 F
Sensible coil load ................................................ 136.0 MBH Entering DB / WB ............................................ 79.8 / 69.3 F
Coil CFM at Dec 1500 .......................................... 6722 CFM Leaving DB / WB ............................................. 61.0 / 60.0 F
Max block CFM .................................................... 6722 CFM Coil ADP .................................................................... 58.9 F
Sum of peak zone CFM ....................................... 6722 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.667 Resulting RH ................................................................ 57 %
ft/Ton .................................................................. 243.3 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 49.3 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F
Actual max CFM ................................................... 6722 CFM Fan motor BHP .......................................................... 0.78 BHP
Standard CFM ...................................................... 6682 CFM Fan motor kW ............................................................ 0.58 kW
Actual max CFM/ft ............................................... 1.63 CFM/ft Fan static ................................................................... 0.40 in wg
1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................. 1185 CFM
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GF-MEETING#1 '' IN ZONE '' Zone GF-03 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 129 ft 11434 - 129 ft - -
Wall Transmission 43 ft 77 - 43 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 129 ft 1483 - 129 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 470 W 1019 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 24 4395 2880 0 0 0
Infiltration - 47 120 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1972 300 0% 0 0
>> Total Zone Loads - 21689 3300 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GF-MEETING#1 '' IN ZONE '' Zone GF-03 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 43 0.403 - 77 - 0
WINDOW 1 129 0.892 0.631 1483 11434 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' GF-SECRETARIS#1 '' IN ZONE '' Zone GF-03 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.3 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 86 W 189 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 637 - 0 0 -
People 1 201 205 0 0 0
Infiltration - 8 17 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 103 22 0% 0 0
>> Total Zone Loads - 1138 245 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' GF-SECRETARIS#1 '' IN ZONE '' Zone GF-03 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' GF-AREA STAFF#1 '' IN ZONE '' Zone GF-03 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 74.6 F / 73.5 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 452 ft 29508 - 452 ft - -
Wall Transmission 797 ft 1113 - 797 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 452 ft -385 - 452 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 2592 W 5414 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3800 W 11664 - 0 0 -
People 42 7465 8613 0 0 0
Infiltration - -13 615 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 5476 923 0% 0 0
>> Total Zone Loads - 60241 10151 - 0 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' GF-AREA STAFF#1 '' IN ZONE '' Zone GF-03 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 258 0.403 - 450 - 0
SSW EXPOSURE
WALL 237 0.403 - -45 - 0
WINDOW 1 129 0.892 0.631 -110 1649 0
NNE EXPOSURE
WALL 301 0.403 - 708 - 0
WINDOW 1 323 0.892 0.631 -275 27858 0
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' GF-MANAGER#1 '' IN ZONE '' Zone GF-03 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 40 ft 3573 - 40 ft - -
Wall Transmission 218 ft 1896 - 218 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 40 ft 463 - 40 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 129 ft 0 - 129 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 19 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 817 66 0% 0 0
>> Total Zone Loads - 8991 730 - 0 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' GF-MANAGER#1 '' IN ZONE '' Zone GF-03 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 151 0.403 - 1488 - 0
SSW EXPOSURE
WALL 67 0.403 - 408 - 0
WINDOW 1 40 0.892 0.631 463 3573 0
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' GF-MANAGER#2 '' IN ZONE '' Zone GF-03 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 4288 - 48 ft - -
Wall Transmission 59 ft 336 - 59 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 556 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 129 ft 0 - 129 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 19 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 742 66 0% 0 0
>> Total Zone Loads - 8163 730 - 0 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' GF-MANAGER#2 '' IN ZONE '' Zone GF-03 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 59 0.403 - 336 - 0
WINDOW 1 48 0.892 0.631 556 4288 0
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' GF-MANAGER#3 '' IN ZONE '' Zone GF-03 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 4288 - 48 ft - -
Wall Transmission 59 ft 336 - 59 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 556 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 129 ft 0 - 129 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 19 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 742 66 0% 0 0
>> Total Zone Loads - 8163 730 - 0 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' GF-MANAGER#3 '' IN ZONE '' Zone GF-03 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 59 0.403 - 336 - 0
WINDOW 1 48 0.892 0.631 556 4288 0
TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' GF-MANAGER#4 '' IN ZONE '' Zone GF-03 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 4288 - 48 ft - -
Wall Transmission 59 ft 336 - 59 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 556 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 129 ft 0 - 129 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 19 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 742 66 0% 0 0
>> Total Zone Loads - 8163 730 - 0 0
TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' GF-MANAGER#4 '' IN ZONE '' Zone GF-03 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 59 0.403 - 336 - 0
WINDOW 1 48 0.892 0.631 556 4288 0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load .......................................................... 1.4 Tons Load occurs at ................................................... Mar 1600
Total coil load ........................................................ 16.6 MBH OA DB / WB .................................................... 89.0 / 79.5 F
Sensible coil load .................................................. 14.8 MBH Entering DB / WB ............................................ 77.6 / 66.1 F
Coil CFM at Mar 1600 ............................................ 823 CFM Leaving DB / WB ............................................. 60.8 / 59.7 F
Max block CFM ...................................................... 823 CFM Coil ADP .................................................................... 58.9 F
Sum of peak zone CFM ......................................... 823 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.893 Resulting RH ................................................................ 54 %
ft/Ton .................................................................. 124.5 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 96.4 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F
Actual max CFM ..................................................... 823 CFM Fan motor BHP .......................................................... 0.05 BHP
Standard CFM ........................................................ 818 CFM Fan motor kW ............................................................ 0.04 kW
Actual max CFM/ft ............................................... 4.78 CFM/ft Fan static ................................................................... 0.20 in wg
1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ..................................................................... 30 CFM
Uncorrected Outdoor Airflow Rate ................................................................ 30 CFM
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GF-DOCTOR#1 '' IN ZONE '' Zone GF-04 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.4 F / 78.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 10522 - 97 ft - -
Wall Transmission 118 ft 697 - 118 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 97 ft 853 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 535 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 632 - 0 0 -
People 2 390 410 0 0 0
Infiltration - 20 60 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1365 47 0% 0 0
>> Total Zone Loads - 15013 517 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GF-DOCTOR#1 '' IN ZONE '' Zone GF-04 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WNW EXPOSURE
WALL 118 0.403 - 697 - 0
WINDOW 1 97 0.892 0.631 853 10522 0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
2 0.012
34
5
0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load .......................................................... 0.4 Tons Load occurs at ................................................... Jan 1600
Total coil load .......................................................... 5.0 MBH OA DB / WB .................................................... 91.0 / 80.5 F
Sensible coil load .................................................... 3.4 MBH Entering DB / WB ............................................ 79.7 / 69.0 F
Coil CFM at Jan 1600 ............................................ 171 CFM Leaving DB / WB ............................................. 60.9 / 60.0 F
Max block CFM ...................................................... 171 CFM Coil ADP .................................................................... 58.8 F
Sum of peak zone CFM ......................................... 171 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.689 Resulting RH ................................................................ 56 %
ft/Ton .................................................................. 552.2 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 21.7 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F
Actual max CFM ..................................................... 171 CFM Fan motor BHP .......................................................... 0.01 BHP
Standard CFM ........................................................ 170 CFM Fan motor kW ............................................................ 0.01 kW
Actual max CFM/ft ............................................... 0.74 CFM/ft Fan static ................................................................... 0.20 in wg
1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ..................................................................... 30 CFM
Uncorrected Outdoor Airflow Rate ................................................................ 30 CFM
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GF-PATIENT#1 '' IN ZONE '' Zone GF-05 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.3 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 541 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 1912 - 0 0 -
People 2 377 240 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 283 24 0% 0 0
>> Total Zone Loads - 3112 264 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GF-PATIENT#1 '' IN ZONE '' Zone GF-05 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load .......................................................... 1.1 Tons Load occurs at .................................................. Dec 1600
Total coil load ........................................................ 13.4 MBH OA DB / WB .................................................... 90.0 / 80.5 F
Sensible coil load .................................................. 12.5 MBH Entering DB / WB ............................................ 77.6 / 65.5 F
Coil CFM at Dec 1600 ............................................ 665 CFM Leaving DB / WB ............................................. 60.1 / 59.0 F
Max block CFM ...................................................... 665 CFM Coil ADP .................................................................... 58.2 F
Sum of peak zone CFM ......................................... 665 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.930 Resulting RH ................................................................ 52 %
ft/Ton .................................................................. 106.0 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) .......................................................... 113.3 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F
Actual max CFM ..................................................... 665 CFM Fan motor BHP .......................................................... 0.04 BHP
Standard CFM ........................................................ 661 CFM Fan motor kW ............................................................ 0.03 kW
Actual max CFM/ft ............................................... 5.61 CFM/ft Fan static ................................................................... 0.20 in wg
1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ..................................................................... 15 CFM
Uncorrected Outdoor Airflow Rate ................................................................ 15 CFM
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' GF-SERVER#1 '' IN ZONE '' Zone GF-07 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.3 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 54 ft 0 - 54 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 590 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3000 W 10236 - 0 0 -
People 1 201 205 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1103 21 0% 0 0
>> Total Zone Loads - 12129 226 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' GF-SERVER#1 '' IN ZONE '' Zone GF-07 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load ........................................................ 12.1 Tons Load occurs at .................................................. Dec 1600
Total coil load ...................................................... 145.4 MBH OA DB / WB .................................................... 90.0 / 80.5 F
Sensible coil load ................................................ 119.9 MBH Entering DB / WB ............................................ 77.8 / 66.5 F
Coil CFM at Dec 1600 .......................................... 6345 CFM Leaving DB / WB ............................................. 60.2 / 59.2 F
Max block CFM .................................................... 6345 CFM Coil ADP .................................................................... 58.3 F
Sum of peak zone CFM ....................................... 6345 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.825 Resulting RH ................................................................ 53 %
ft/Ton .................................................................. 291.8 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 41.1 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F
Actual max CFM ................................................... 6345 CFM Fan motor BHP .......................................................... 0.74 BHP
Standard CFM ...................................................... 6307 CFM Fan motor kW ............................................................ 0.55 kW
Actual max CFM/ft ............................................... 1.79 CFM/ft Fan static ................................................................... 0.40 in wg
1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................... 454 CFM
Uncorrected Outdoor Airflow Rate .............................................................. 292 CFM
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 1F-RECEPSIONIST#1 '' IN ZONE '' Zone 1F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 91.0 F / 80.5 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 978 ft 59965 - 978 ft - -
Wall Transmission 787 ft 3542 - 787 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 978 ft 15856 - 978 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 450 W 980 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1269 - 0 0 -
People 9 1759 1136 0 0 0
Infiltration - 459 1182 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 8383 232 0% 0 0
>> Total Zone Loads - 92214 2550 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 1F-RECEPSIONIST#1 '' IN ZONE '' Zone 1F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 216 0.403 - 807 - 0
WINDOW 1 441 1.212 0.880 7335 29346 0
WNW EXPOSURE
WALL 539 0.403 - 2671 - 0
WINDOW 1 441 1.212 0.880 7335 28744 0
ENE EXPOSURE
WALL 32 0.403 - 65 - 0
WINDOW 1 97 0.892 0.631 1187 1875 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 1F-R.TUNGGU#1 '' IN ZONE '' Zone 1F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 65 ft 5717 - 65 ft - -
Wall Transmission 65 ft 345 - 65 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 65 ft 742 - 65 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 6 1099 720 0 0 0
Infiltration - 40 112 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 958 83 0% 0 0
>> Total Zone Loads - 10539 916 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 1F-R.TUNGGU#1 '' IN ZONE '' Zone 1F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 65 0.403 - 345 - 0
WINDOW 1 65 0.892 0.631 742 5717 0
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' 1F-SECURITY MONITOR#1 '' IN ZONE '' Zone 1F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.3 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 86 W 189 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1400 W 4777 - 0 0 -
People 2 401 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 537 41 0% 0 0
>> Total Zone Loads - 5904 451 - 0 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' 1F-SECURITY MONITOR#1 '' IN ZONE '' Zone 1F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' 1F-GA#1 '' IN ZONE '' Zone 1F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.3 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 86 W 189 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 637 - 0 0 -
People 2 401 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 123 41 0% 0 0
>> Total Zone Loads - 1351 451 - 0 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' 1F-GA#1 '' IN ZONE '' Zone 1F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load ........................................................ 18.7 Tons Load occurs at .................................................. Dec 1400
Total coil load ...................................................... 224.5 MBH OA DB / WB .................................................... 90.0 / 80.5 F
Sensible coil load ................................................ 164.5 MBH Entering DB / WB ............................................ 78.6 / 68.2 F
Coil CFM at Dec 1400 .......................................... 8823 CFM Leaving DB / WB ............................................. 61.3 / 60.3 F
Max block CFM .................................................... 8823 CFM Coil ADP .................................................................... 59.3 F
Sum of peak zone CFM ....................................... 8823 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.733 Resulting RH ................................................................ 57 %
ft/Ton .................................................................. 247.4 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 48.5 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F
Actual max CFM ................................................... 8823 CFM Fan motor BHP .......................................................... 1.03 BHP
Standard CFM ...................................................... 8771 CFM Fan motor kW ............................................................ 0.77 kW
Actual max CFM/ft ............................................... 1.91 CFM/ft Fan static ................................................................... 0.40 in wg
1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................. 1064 CFM
Uncorrected Outdoor Airflow Rate ............................................................ 1007 CFM
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 1F-GRAND MEETING#1 '' IN ZONE '' Zone 1F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 129 ft 11434 - 129 ft - -
Wall Transmission 75 ft 307 - 75 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 129 ft 1483 - 129 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 518 W 1123 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 1895 - 0 0 -
People 13 2380 1560 0 0 0
Infiltration - 59 153 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1868 171 0% 0 0
>> Total Zone Loads - 20550 1884 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 1F-GRAND MEETING#1 '' IN ZONE '' Zone 1F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 75 0.403 - 307 - 0
WINDOW 1 129 0.892 0.631 1483 11434 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 1F-AREA STAFF#1 '' IN ZONE '' Zone 1F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 75.6 F / 75.1 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 549 ft 32418 - 549 ft - -
Wall Transmission 926 ft 1806 - 926 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 549 ft 703 - 549 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 2498 W 5124 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 8600 W 26026 - 0 0 -
People 40 6769 8200 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 7285 820 0% 0 0
>> Total Zone Loads - 80130 9020 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 1F-AREA STAFF#1 '' IN ZONE '' Zone 1F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NNE EXPOSURE
WALL 344 0.403 - 734 - 0
WINDOW 1 291 0.892 0.631 372 20888 0
ESE EXPOSURE
WALL 377 0.403 - 830 - 0
WINDOW 1 129 0.892 0.631 165 10087 0
SSW EXPOSURE
WALL 205 0.403 - 243 - 0
WINDOW 1 129 0.892 0.631 165 1443 0
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' 1F-MANAGER#1 '' IN ZONE '' Zone 1F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 4288 - 48 ft - -
Wall Transmission 210 ft 1824 - 210 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 556 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 19 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 891 66 0% 0 0
>> Total Zone Loads - 9800 730 - 0 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' 1F-MANAGER#1 '' IN ZONE '' Zone 1F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 151 0.403 - 1488 - 0
SSW EXPOSURE
WALL 59 0.403 - 336 - 0
WINDOW 1 48 0.892 0.631 556 4288 0
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' 1F-MANAGER#2 '' IN ZONE '' Zone 1F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 4288 - 48 ft - -
Wall Transmission 59 ft 336 - 59 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 556 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 19 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 742 66 0% 0 0
>> Total Zone Loads - 8163 730 - 0 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' 1F-MANAGER#2 '' IN ZONE '' Zone 1F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 59 0.403 - 336 - 0
WINDOW 1 48 0.892 0.631 556 4288 0
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' 1F-MANAGER#3 '' IN ZONE '' Zone 1F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 4288 - 48 ft - -
Wall Transmission 59 ft 336 - 59 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 556 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 19 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 742 66 0% 0 0
>> Total Zone Loads - 8163 730 - 0 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' 1F-MANAGER#3 '' IN ZONE '' Zone 1F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 59 0.403 - 336 - 0
WINDOW 1 48 0.892 0.631 556 4288 0
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' 1F-MANAGER#4 '' IN ZONE '' Zone 1F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 4288 - 48 ft - -
Wall Transmission 59 ft 336 - 59 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 556 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 19 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 742 66 0% 0 0
>> Total Zone Loads - 8163 730 - 0 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' 1F-MANAGER#4 '' IN ZONE '' Zone 1F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 59 0.403 - 336 - 0
WINDOW 1 48 0.892 0.631 556 4288 0
TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' 1F-FILE#1 '' IN ZONE '' Zone 1F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 72.5 F / 72.0 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 65 ft 5790 - 65 ft - -
Wall Transmission 86 ft 162 - 86 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 65 ft -137 - 65 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 259 W 537 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 610 - 0 0 -
People 0 0 0 0 0 0
Infiltration - -6 44 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 695 4 0% 0 0
>> Total Zone Loads - 7650 48 - 0 0
TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' 1F-FILE#1 '' IN ZONE '' Zone 1F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NNE EXPOSURE
WALL 86 0.403 - 162 - 0
WINDOW 1 65 0.892 0.631 -137 5790 0
TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' 1F-FILE STORAGE#2 '' IN ZONE '' Zone 1F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 0900 HEATING DATA AT DES HTG
COOLING OA DB / WB 72.5 F / 72.0 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 8685 - 97 ft - -
Wall Transmission 54 ft 68 - 54 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 97 ft -205 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 130 W 268 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 610 - 0 0 -
People 0 0 0 0 0 0
Infiltration - -7 48 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 942 5 0% 0 0
>> Total Zone Loads - 10361 53 - 0 0
TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' 1F-FILE STORAGE#2 '' IN ZONE '' Zone 1F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NNE EXPOSURE
WALL 54 0.403 - 68 - 0
WINDOW 1 97 0.892 0.631 -205 8685 0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
2
0.014
35 6 0.012
7
4 8
0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load ........................................................ 13.1 Tons Load occurs at ................................................... Feb 1600
Total coil load ...................................................... 156.9 MBH OA DB / WB .................................................... 91.0 / 80.5 F
Sensible coil load .................................................. 91.3 MBH Entering DB / WB ............................................ 81.7 / 71.5 F
Coil CFM at Feb 1600 .......................................... 4102 CFM Leaving DB / WB ............................................. 60.9 / 60.1 F
Max block CFM .................................................... 4102 CFM Coil ADP .................................................................... 58.6 F
Sum of peak zone CFM ....................................... 4102 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.582 Resulting RH ................................................................ 57 %
ft/Ton .................................................................. 106.2 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) .......................................................... 113.0 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F
Actual max CFM ................................................... 4102 CFM Fan motor BHP .......................................................... 0.48 BHP
Standard CFM ...................................................... 4078 CFM Fan motor kW ............................................................ 0.36 kW
Actual max CFM/ft ............................................... 2.95 CFM/ft Fan static ................................................................... 0.40 in wg
1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................. 1328 CFM
Uncorrected Outdoor Airflow Rate ............................................................ 1080 CFM
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 1F-MANAGER#5 '' IN ZONE '' Zone 1F-03A ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.4 F / 78.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 5261 - 48 ft - -
Wall Transmission 59 ft 222 - 59 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 427 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 15 43 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 815 66 0% 0 0
>> Total Zone Loads - 8962 724 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 1F-MANAGER#5 '' IN ZONE '' Zone 1F-03A ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WNW EXPOSURE
WALL 59 0.403 - 222 - 0
WINDOW 1 48 0.892 0.631 427 5261 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 1F-MANAGER#6 '' IN ZONE '' Zone 1F-03A ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.4 F / 78.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 5261 - 48 ft - -
Wall Transmission 59 ft 222 - 59 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 427 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 3 585 615 0 0 0
Infiltration - 15 43 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 815 66 0% 0 0
>> Total Zone Loads - 8962 724 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 1F-MANAGER#6 '' IN ZONE '' Zone 1F-03A ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WNW EXPOSURE
WALL 59 0.403 - 222 - 0
WINDOW 1 48 0.892 0.631 427 5261 0
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' 1F-RUANG TRAINING#1 '' IN ZONE '' Zone 1F-03A ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.4 F / 78.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 10522 - 97 ft - -
Wall Transmission 452 ft 3026 - 452 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 97 ft 853 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 432 W 936 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 1895 - 0 0 -
People 49 8972 5880 0 0 0
Infiltration - 70 197 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2627 608 0% 0 0
>> Total Zone Loads - 28901 6685 - 0 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' 1F-RUANG TRAINING#1 '' IN ZONE '' Zone 1F-03A ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NNE EXPOSURE
WALL 344 0.403 - 2633 - 0
WNW EXPOSURE
WALL 108 0.403 - 393 - 0
WINDOW 1 97 0.892 0.631 853 10522 0
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' 1F-MEETING#1 '' IN ZONE '' Zone 1F-03A ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.4 F / 78.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 129 ft 14029 - 129 ft - -
Wall Transmission 86 ft 254 - 86 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 129 ft 1137 - 129 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 738 W 1598 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 1895 - 0 0 -
People 17 3113 2040 0 0 0
Infiltration - 62 176 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 2209 222 0% 0 0
>> Total Zone Loads - 24297 2438 - 0 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' 1F-MEETING#1 '' IN ZONE '' Zone 1F-03A ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WNW EXPOSURE
WALL 86 0.403 - 254 - 0
WINDOW 1 129 0.892 0.631 1137 14029 0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load .......................................................... 9.5 Tons Load occurs at ................................................... Feb 1500
Total coil load ...................................................... 113.9 MBH OA DB / WB .................................................... 91.4 / 80.6 F
Sensible coil load .................................................. 84.8 MBH Entering DB / WB ............................................ 78.6 / 67.9 F
Coil CFM at Feb 1500 .......................................... 4500 CFM Leaving DB / WB ............................................. 61.0 / 60.0 F
Max block CFM .................................................... 4500 CFM Coil ADP .................................................................... 59.1 F
Sum of peak zone CFM ....................................... 4500 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.744 Resulting RH ................................................................ 57 %
ft/Ton .................................................................. 267.1 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 44.9 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F
Actual max CFM ................................................... 4500 CFM Fan motor BHP .......................................................... 0.52 BHP
Standard CFM ...................................................... 4473 CFM Fan motor kW ............................................................ 0.39 kW
Actual max CFM/ft ............................................... 1.78 CFM/ft Fan static ................................................................... 0.40 in wg
1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................... 493 CFM
Uncorrected Outdoor Airflow Rate .............................................................. 488 CFM
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 1F-AREA STAFF#2 '' IN ZONE '' Zone 1F-03B ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 452 ft 32877 - 452 ft - -
Wall Transmission 237 ft 686 - 237 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 452 ft 2192 - 452 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 1846 W 3785 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 6400 W 19368 - 0 0 -
People 32 5415 6562 0 0 0
Infiltration - 105 918 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 6443 748 0% 0 0
>> Total Zone Loads - 70871 8228 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 1F-AREA STAFF#2 '' IN ZONE '' Zone 1F-03B ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WNW EXPOSURE
WALL 11 0.403 - 0 - 0
WINDOW 1 194 0.892 0.631 939 3545 0
ESE EXPOSURE
WALL 226 0.403 - 686 - 0
WINDOW 1 258 0.892 0.631 1252 29332 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 1F-FILE STORAGE#1 '' IN ZONE '' Zone 1F-03B ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 48 ft 5500 - 48 ft - -
Wall Transmission 27 ft 63 - 27 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 48 ft 235 - 48 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 43 W 89 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 605 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 6 51 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 650 5 0% 0 0
>> Total Zone Loads - 7147 57 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 1F-FILE STORAGE#1 '' IN ZONE '' Zone 1F-03B ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 27 0.403 - 63 - 0
WINDOW 1 48 0.892 0.631 235 5500 0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load ........................................................ 11.4 Tons Load occurs at .................................................. Dec 1600
Total coil load ...................................................... 136.9 MBH OA DB / WB .................................................... 90.0 / 80.5 F
Sensible coil load ................................................ 116.9 MBH Entering DB / WB ............................................ 77.5 / 66.1 F
Coil CFM at Dec 1600 .......................................... 6341 CFM Leaving DB / WB ............................................. 60.3 / 59.2 F
Max block CFM .................................................... 6341 CFM Coil ADP .................................................................... 58.4 F
Sum of peak zone CFM ....................................... 6341 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.854 Resulting RH ................................................................ 54 %
ft/Ton .................................................................. 346.7 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 34.6 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F
Actual max CFM ................................................... 6341 CFM Fan motor BHP .......................................................... 0.74 BHP
Standard CFM ...................................................... 6303 CFM Fan motor kW ............................................................ 0.55 kW
Actual max CFM/ft ............................................... 1.60 CFM/ft Fan static ................................................................... 0.40 in wg
1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................... 335 CFM
Uncorrected Outdoor Airflow Rate .............................................................. 300 CFM
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 2F-LOBBY& SECRETARY#1 '' IN ZONE '' Zone 2F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 91.0 F / 80.5 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 978 ft 59965 - 978 ft - -
Wall Transmission 464 ft 1530 - 464 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 978 ft 15856 - 978 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 252 W 549 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1269 - 0 0 -
People 10 1858 1200 0 0 0
Infiltration - 538 1366 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 8157 257 0% 0 0
>> Total Zone Loads - 89722 2823 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 2F-LOBBY& SECRETARY#1 '' IN ZONE '' Zone 2F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 216 0.403 - 807 - 0
WINDOW 1 441 1.212 0.880 7335 29346 0
WNW EXPOSURE
WALL 216 0.403 - 658 - 0
WINDOW 1 441 1.212 0.880 7335 28744 0
ENE EXPOSURE
WALL 32 0.403 - 65 - 0
WINDOW 1 97 0.892 0.631 1187 1875 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 2F-SECURITY MONITOR#1 '' IN ZONE '' Zone 2F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.0 F / 80.3 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 86 W 189 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1400 W 4777 - 0 0 -
People 2 401 410 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 537 41 0% 0 0
>> Total Zone Loads - 5904 451 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 2F-SECURITY MONITOR#1 '' IN ZONE '' Zone 2F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' 2F-EXCE DINNING#1 '' IN ZONE '' Zone 2F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 65 ft 5717 - 65 ft - -
Wall Transmission 108 ft 653 - 108 ft 0 -
Roof Transmission 269 ft 2763 - 269 ft 0 -
Window Transmission 65 ft 742 - 65 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 8 1465 960 0 0 0
Infiltration - 39 108 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1302 107 0% 0 0
>> Total Zone Loads - 14317 1175 - 0 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' 2F-EXCE DINNING#1 '' IN ZONE '' Zone 2F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 108 0.403 - 653 - 0
WINDOW 1 65 0.892 0.631 742 5717 0
H EXPOSURE
ROOF 269 0.134 - 2763 - 0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load ........................................................ 17.2 Tons Load occurs at .................................................. Dec 1500
Total coil load ...................................................... 206.6 MBH OA DB / WB .................................................... 90.4 / 80.6 F
Sensible coil load ................................................ 158.2 MBH Entering DB / WB ............................................ 80.9 / 68.9 F
Coil CFM at Dec 1500 .......................................... 7739 CFM Leaving DB / WB ............................................. 61.9 / 60.8 F
Max block CFM .................................................... 7739 CFM Coil ADP .................................................................... 59.8 F
Sum of peak zone CFM ....................................... 7739 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.766 Resulting RH ................................................................ 58 %
ft/Ton .................................................................. 270.5 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 44.4 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F
Actual max CFM ................................................... 7739 CFM Fan motor BHP .......................................................... 0.90 BHP
Standard CFM ...................................................... 7693 CFM Fan motor kW ............................................................ 0.67 kW
Actual max CFM/ft ............................................... 1.66 CFM/ft Fan static ................................................................... 0.40 in wg
1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................... 877 CFM
Uncorrected Outdoor Airflow Rate .............................................................. 780 CFM
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 2F-R.TUNGGU#1 '' IN ZONE '' Zone 2F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 323 ft 14989 - 323 ft - -
Wall Transmission 646 ft 4323 - 646 ft 0 -
Roof Transmission 0 ft 0 - 0 ft 0 -
Window Transmission 323 ft 3708 - 323 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 1164 W 2521 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 28 5127 3360 0 0 0
Infiltration - 256 660 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 3219 402 0% 0 0
>> Total Zone Loads - 35406 4422 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 2F-R.TUNGGU#1 '' IN ZONE '' Zone 2F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 183 0.403 - 1075 - 0
WINDOW 1 129 0.892 0.631 1483 11434 0
NNE EXPOSURE
WALL 183 0.403 - 564 - 0
WINDOW 1 161 0.892 0.631 1854 2711 0
ESE EXPOSURE
WALL 280 0.403 - 2684 - 0
WINDOW 1 32 0.892 0.631 371 843 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 2F-Director#1 '' IN ZONE '' Zone 2F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 129 ft 11434 - 129 ft - -
Wall Transmission 75 ft 307 - 75 ft 0 -
Roof Transmission 527 ft 1625 - 527 ft 0 -
Window Transmission 129 ft 1483 - 129 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 173 W 374 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 4 780 820 0 0 0
Infiltration - 76 197 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1734 102 0% 0 0
>> Total Zone Loads - 19078 1118 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 2F-Director#1 '' IN ZONE '' Zone 2F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 75 0.403 - 307 - 0
WINDOW 1 129 0.892 0.631 1483 11434 0
H EXPOSURE
ROOF 527 0.134 - 1625 - 0
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' 2F-Director#2 '' IN ZONE '' Zone 2F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 74.6 F / 73.5 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 129 ft 11143 - 129 ft - -
Wall Transmission 75 ft 138 - 75 ft 0 -
Roof Transmission 570 ft 650 - 570 ft 0 -
Window Transmission 129 ft -110 - 129 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 346 W 722 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1228 - 0 0 -
People 4 711 820 0 0 0
Infiltration - -2 69 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1448 89 0% 0 0
>> Total Zone Loads - 15929 978 - 0 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' 2F-Director#2 '' IN ZONE '' Zone 2F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NNE EXPOSURE
WALL 75 0.403 - 138 - 0
WINDOW 1 129 0.892 0.631 -110 11143 0
H EXPOSURE
ROOF 570 0.134 - 650 - 0
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' 2F-Director#3 '' IN ZONE '' Zone 2F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 74.6 F / 73.5 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 8357 - 97 ft - -
Wall Transmission 108 ft 268 - 108 ft 0 -
Roof Transmission 404 ft 460 - 404 ft 0 -
Window Transmission 97 ft -83 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 432 W 902 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1228 - 0 0 -
People 4 711 820 0 0 0
Infiltration - -2 74 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1184 89 0% 0 0
>> Total Zone Loads - 13026 983 - 0 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' 2F-Director#3 '' IN ZONE '' Zone 2F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NNE EXPOSURE
WALL 108 0.403 - 268 - 0
WINDOW 1 97 0.892 0.631 -83 8357 0
H EXPOSURE
ROOF 404 0.134 - 460 - 0
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' 2F-Director#4 '' IN ZONE '' Zone 2F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 74.6 F / 73.5 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 8357 - 97 ft - -
Wall Transmission 118 ft 302 - 118 ft 0 -
Roof Transmission 438 ft 499 - 438 ft 0 -
Window Transmission 97 ft -83 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 432 W 902 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1228 - 0 0 -
People 4 711 820 0 0 0
Infiltration - -2 80 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1192 90 0% 0 0
>> Total Zone Loads - 13107 990 - 0 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' 2F-Director#4 '' IN ZONE '' Zone 2F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
NNE EXPOSURE
WALL 118 0.403 - 302 - 0
WINDOW 1 97 0.892 0.631 -83 8357 0
H EXPOSURE
ROOF 438 0.134 - 499 - 0
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' 2F-Komisaris#1 '' IN ZONE '' Zone 2F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 8576 - 97 ft - -
Wall Transmission 409 ft 3689 - 409 ft 0 -
Roof Transmission 570 ft 1758 - 570 ft 0 -
Window Transmission 97 ft 1112 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 653 W 1414 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 4 780 820 0 0 0
Infiltration - 83 213 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1867 103 0% 0 0
>> Total Zone Loads - 20542 1136 - 0 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' 2F-Komisaris#1 '' IN ZONE '' Zone 2F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 344 0.403 - 3402 - 0
SSW EXPOSURE
WALL 65 0.403 - 288 - 0
WINDOW 1 97 0.892 0.631 1112 8576 0
H EXPOSURE
ROOF 570 0.134 - 1758 - 0
TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' 2F-Komisaris#2 '' IN ZONE '' Zone 2F-02 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 8576 - 97 ft - -
Wall Transmission 118 ft 558 - 118 ft 0 -
Roof Transmission 570 ft 1758 - 570 ft 0 -
Window Transmission 97 ft 1112 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 653 W 1414 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1263 - 0 0 -
People 4 780 820 0 0 0
Infiltration - 83 213 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1554 103 0% 0 0
>> Total Zone Loads - 17098 1136 - 0 0
TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' 2F-Komisaris#2 '' IN ZONE '' Zone 2F-02 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 65 0.403 - 288 - 0
WINDOW 1 97 0.892 0.631 1112 8576 0
WNW EXPOSURE
WALL 54 0.403 - 270 - 0
H EXPOSURE
ROOF 570 0.134 - 1758 - 0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
2
0.014
35 6 8 0.012
7
4
0.010
0.008
0.006
0.004
0.002
0.000
30 40 50 60 70 80 90 100
Temperature ( F )
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load ........................................................ 21.4 Tons Load occurs at ................................................... Feb 1500
Total coil load ...................................................... 257.3 MBH OA DB / WB .................................................... 91.4 / 80.6 F
Sensible coil load ................................................ 150.6 MBH Entering DB / WB ............................................ 83.9 / 72.4 F
Coil CFM at Feb 1500 .......................................... 6095 CFM Leaving DB / WB ............................................. 60.9 / 60.0 F
Max block CFM .................................................... 6095 CFM Coil ADP .................................................................... 58.3 F
Sum of peak zone CFM ....................................... 6095 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.585 Resulting RH ................................................................ 57 %
ft/Ton .................................................................. 108.7 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) .......................................................... 110.4 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F
Actual max CFM ................................................... 6095 CFM Fan motor BHP .......................................................... 0.71 BHP
Standard CFM ...................................................... 6059 CFM Fan motor kW ............................................................ 0.53 kW
Actual max CFM/ft ............................................... 2.61 CFM/ft Fan static ................................................................... 0.40 in wg
1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................. 2161 CFM
Uncorrected Outdoor Airflow Rate ............................................................ 1830 CFM
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 2F-GRAND MEETING#1 '' IN ZONE '' Zone 2F-03 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Mar 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 89.4 F / 79.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 258 ft 27349 - 258 ft - -
Wall Transmission 161 ft 500 - 161 ft 0 -
Roof Transmission 1076 ft 3251 - 1076 ft 0 -
Window Transmission 258 ft 2736 - 258 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 1183 W 2563 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 1000 W 3158 - 0 0 -
People 24 4395 2880 0 0 0
Infiltration - 146 366 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 4410 325 0% 0 0
>> Total Zone Loads - 48505 3571 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 2F-GRAND MEETING#1 '' IN ZONE '' Zone 2F-03 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WNW EXPOSURE
WALL 161 0.403 - 500 - 0
WINDOW 1 258 0.892 0.631 2736 27349 0
H EXPOSURE
ROOF 1076 0.134 - 3251 - 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 2F-FUNCTION#1 '' IN ZONE '' Zone 2F-03 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Apr 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 87.4 F / 78.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 194 ft 21044 - 194 ft - -
Wall Transmission 581 ft 3521 - 581 ft 0 -
Roof Transmission 1255 ft 3292 - 1255 ft 0 -
Window Transmission 194 ft 1706 - 194 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 1123 W 2433 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 600 W 1895 - 0 0 -
People 98 17944 11760 0 0 0
Infiltration - 146 410 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 5198 1217 0% 0 0
>> Total Zone Loads - 57178 13387 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 2F-FUNCTION#1 '' IN ZONE '' Zone 2F-03 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
WNW EXPOSURE
WALL 237 0.403 - 888 - 0
WINDOW 1 194 0.892 0.631 1706 21044 0
NNE EXPOSURE
WALL 344 0.403 - 2633 - 0
H EXPOSURE
ROOF 1255 0.134 - 3292 - 0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load .......................................................... 5.3 Tons Load occurs at ................................................... Jan 0800
Total coil load ........................................................ 63.1 MBH OA DB / WB .................................................... 79.6 / 77.7 F
Sensible coil load .................................................. 54.4 MBH Entering DB / WB ............................................ 77.6 / 66.1 F
Coil CFM at Jan 0800 .......................................... 2929 CFM Leaving DB / WB ............................................. 60.3 / 59.2 F
Max block CFM .................................................... 2929 CFM Coil ADP .................................................................... 58.4 F
Sum of peak zone CFM ....................................... 2929 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.863 Resulting RH ................................................................ 53 %
ft/Ton .................................................................. 204.2 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 58.8 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F
Actual max CFM ................................................... 2929 CFM Fan motor BHP .......................................................... 0.34 BHP
Standard CFM ...................................................... 2912 CFM Fan motor kW ............................................................ 0.25 kW
Actual max CFM/ft ............................................... 2.73 CFM/ft Fan static ................................................................... 0.40 in wg
1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................... 140 CFM
Uncorrected Outdoor Airflow Rate .............................................................. 138 CFM
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 2F-Director#5 '' IN ZONE '' Zone 2F-04 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 129 ft 14666 - 129 ft - -
Wall Transmission 75 ft 183 - 75 ft 0 -
Roof Transmission 366 ft 276 - 366 ft 0 -
Window Transmission 129 ft 626 - 129 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 432 W 886 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1211 - 0 0 -
People 4 677 820 0 0 0
Infiltration - 16 144 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1854 96 0% 0 0
>> Total Zone Loads - 20394 1061 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 2F-Director#5 '' IN ZONE '' Zone 2F-04 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 75 0.403 - 183 - 0
WINDOW 1 129 0.892 0.631 626 14666 0
H EXPOSURE
ROOF 366 0.134 - 276 - 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 2F-Director#6 '' IN ZONE '' Zone 2F-04 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 10999 - 97 ft - -
Wall Transmission 97 ft 309 - 97 ft 0 -
Roof Transmission 406 ft 306 - 406 ft 0 -
Window Transmission 97 ft 470 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 432 W 886 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 400 W 1211 - 0 0 -
People 4 677 820 0 0 0
Infiltration - 18 160 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1487 98 0% 0 0
>> Total Zone Loads - 16362 1078 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 2F-Director#6 '' IN ZONE '' Zone 2F-04 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 97 0.403 - 309 - 0
WINDOW 1 97 0.892 0.631 470 10999 0
H EXPOSURE
ROOF 406 0.134 - 306 - 0
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' 2F-FILE STORAGE#1 '' IN ZONE '' Zone 2F-04 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 0800 HEATING DATA AT DES HTG
COOLING OA DB / WB 79.6 F / 77.7 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 97 ft 10999 - 97 ft - -
Wall Transmission 65 ft 171 - 65 ft 0 -
Roof Transmission 301 ft 227 - 301 ft 0 -
Window Transmission 97 ft 470 - 97 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 130 W 266 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 605 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 13 119 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 1275 12 0% 0 0
>> Total Zone Loads - 14027 131 - 0 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' 2F-FILE STORAGE#1 '' IN ZONE '' Zone 2F-04 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ESE EXPOSURE
WALL 65 0.403 - 171 - 0
WINDOW 1 97 0.892 0.631 470 10999 0
H EXPOSURE
ROOF 301 0.134 - 227 - 0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load ........................................................ 11.9 Tons Load occurs at .................................................. Dec 1500
Total coil load ...................................................... 142.6 MBH OA DB / WB .................................................... 90.4 / 80.6 F
Sensible coil load ................................................ 115.1 MBH Entering DB / WB ............................................ 81.5 / 68.2 F
Coil CFM at Dec 1500 .......................................... 5216 CFM Leaving DB / WB ............................................. 60.9 / 59.7 F
Max block CFM .................................................... 5216 CFM Coil ADP .................................................................... 58.7 F
Sum of peak zone CFM ....................................... 5216 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.807 Resulting RH ................................................................ 56 %
ft/Ton .................................................................. 257.3 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) ............................................................ 46.6 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F
Actual max CFM ................................................... 5216 CFM Fan motor BHP .......................................................... 0.61 BHP
Standard CFM ...................................................... 5185 CFM Fan motor kW ............................................................ 0.45 kW
Actual max CFM/ft ............................................... 1.71 CFM/ft Fan static ................................................................... 0.40 in wg
1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ................................................................... 296 CFM
Uncorrected Outdoor Airflow Rate .............................................................. 295 CFM
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 3F-FILE STORAGE#1 '' IN ZONE '' Zone 3F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 90.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 65 ft 5717 - 65 ft - -
Wall Transmission 75 ft 422 - 75 ft 0 -
Roof Transmission 258 ft 796 - 258 ft 0 -
Window Transmission 65 ft 742 - 65 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 130 W 281 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 632 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 39 101 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 863 10 0% 0 0
>> Total Zone Loads - 9490 111 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 3F-FILE STORAGE#1 '' IN ZONE '' Zone 3F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 75 0.403 - 422 - 0
WINDOW 1 65 0.892 0.631 742 5717 0
H EXPOSURE
ROOF 258 0.134 - 796 - 0
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' 3F-HALL#1 '' IN ZONE '' Zone 3F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 91.0 F / 80.5 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 588 ft 38725 - 588 ft - -
Wall Transmission 725 ft 4012 - 725 ft 0 -
Roof Transmission 2799 ft 8068 - 2799 ft 0 -
Window Transmission 588 ft 9782 - 588 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 0 ft 0 - 0 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 1008 W 2196 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 800 W 2538 - 0 0 -
People 26 5146 5332 0 0 0
Infiltration - 3124 7501 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 7359 1283 0% 0 0
>> Total Zone Loads - 80951 14116 - 0 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' 3F-HALL#1 '' IN ZONE '' Zone 3F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
SSW EXPOSURE
WALL 363 0.403 - 2209 - 0
WINDOW 1 294 1.212 0.880 4891 19563 0
WNW EXPOSURE
WALL 363 0.403 - 1803 - 0
WINDOW 1 294 1.212 0.880 4891 19162 0
H EXPOSURE
ROOF 2799 0.134 - 8068 - 0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Zone CFM ....................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space CFM ................... Individual peak space loads Sizing Data ..................................................... Calculated
Total coil load .......................................................... 1.4 Tons Load occurs at ................................................... Feb 1500
Total coil load ........................................................ 16.4 MBH OA DB / WB .................................................... 91.4 / 80.6 F
Sensible coil load .................................................. 15.5 MBH Entering DB / WB ............................................ 76.9 / 64.8 F
Coil CFM at Feb 1500 ............................................ 828 CFM Leaving DB / WB ............................................. 59.5 / 58.3 F
Max block CFM ...................................................... 828 CFM Coil ADP .................................................................... 57.5 F
Sum of peak zone CFM ......................................... 828 CFM Bypass Factor ......................................................... 0.100
Sensible heat ratio .............................................. 0.942 Resulting RH ................................................................ 51 %
ft/Ton .................................................................... 31.4 Design supply temp. .................................................. 58.0 F
BTU/(hr-ft) .......................................................... 381.7 Zone T-stat Check ................................................... 1 of 1 OK
Water flow @ 10.0 F rise ...................................... N/A Max zone temperature deviation ................................. 0.0 F
Actual max CFM ..................................................... 828 CFM Fan motor BHP .......................................................... 0.10 BHP
Standard CFM ........................................................ 823 CFM Fan motor kW ............................................................ 0.07 kW
Actual max CFM/ft ............................................. 19.23 CFM/ft Fan static ................................................................... 0.40 in wg
1. Summary
Ventilation Sizing Method .............................................. ASHRAE Std 62-2001
Design Ventilation Airflow Rate ..................................................................... 15 CFM
Uncorrected Outdoor Airflow Rate ................................................................ 15 CFM
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' 4F-LIFT ROOM '' IN ZONE '' Zone 4F-01 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 91.4 F / 80.6 F HEATING OA DB / WB 71.0 F / 59.3 F
OCCUPIED T-STAT 75.0 F OCCUPIED T-STAT 70.0 F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft 0 - 0 ft - -
Wall Transmission 0 ft 0 - 0 ft 0 -
Roof Transmission 22 ft 70 - 22 ft 0 -
Window Transmission 0 ft 0 - 0 ft 0 -
Skylight Transmission 0 ft 0 - 0 ft 0 -
Door Loads 0 ft 0 - 0 ft 0 -
Floor Transmission 0 ft 0 - 0 ft 0 -
Partitions 258 ft 0 - 258 ft 0 -
Ceiling 0 ft 0 - 0 ft 0 -
Overhead Lighting 72 W 156 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 200 W 682 - 0 0 -
People 1 195 205 0 0 0
Infiltration - 7 18 - 0 0
Miscellaneous - 11942 0 - 0 0
Safety Factor 10% / 10% 1305 22 0% 0 0
>> Total Zone Loads - 14357 245 - 0 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' 4F-LIFT ROOM '' IN ZONE '' Zone 4F-01 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft) (BTU/(hr-ft-F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
H EXPOSURE
ROOF 22 0.134 - 70 - 0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.074 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4718.5 BTU/(hr-CFM)
Site Altitude = 164.0 ft