Você está na página 1de 8

Stud Shear Connectors in Composite Beams that Support

Slabs with Profiled Steel Sheeting


Stephen J Hicks, General Manager, Heavy Engineering Research AssociationStructural Systems, Auckland City, Manukau,
New Zealand; Andrew L Smith, Structural Engineer, Grubb Engineering Corporation, Alberta, Canada.
Contact: stephen.hicks@hera.org.nz
DOI: 10.2749/101686614X13830790993122

Abstract Ften is therefore affected by frictional


forces developing at the base of the
This paper presents the results from the final phase of a major UK research pro- slab at the interface between the test
gramme, where an 11,4-m span composite beam and companion push tests were slabs and the strong floor m P (where
undertaken to investigate the load-slip performance of multiple stud connectors. m is the friction coefficient); if these
The tests showed that the resistance of three studs per rib was no better than frictional forces are eliminated, Ften
two studs per rib, thereby indicating that the design equations in BS 5950-3.1 and increases, which has been shown to
ANSI/AISC 360-10 were unconservative by up to 45%. As a direct result of this reduce the shear resistance of the studs
work, an amendment was made to BS 5950-3.1 in 2010. by approximately 30%.3 Alternatively,
Although the beam tests demonstrated the ductile performance of studs in cur- some researchers1 have reduced the
rent UK-profiled steel sheeting, the problem remained that if new sheeting prod- tension forces in the studs by modify-
ucts were developed, it would be difficult to identify cases when the behaviour ing the standard test through the intro-
was poor unless beam tests were undertaken. In response to this problem, this duction of the tension tie Z shown in
paper also presents the development of an improved standard push test, which Fig. 1b.
reflects the conditions that exist in a real beam more closely. As opposed to other The characteristic resistance of a stud
international investigations, the improved test was calibrated directly against real embedded within a solid concrete slab
beam behaviour by considering the load-slip performance of the shear connec- has been evaluated from push test
tors within the three beam tests that were undertaken in the current research data and is determined in Eurocode 4,
programme. ANSI/AISC 360-104 and NZS 3404.15
Keywords: composite beams; shear connection; shear connectors; headed studs; by considering the possibility of stud
profiled steel sheeting; push test; push-out test; push-off test; resistance; reduc- shank failure or crushing of the con-
tion factor; ductility; slip capacity; safety; ANSI/AISC 360-10; Eurocode 4; BS crete. In Eurocode 4, the characteristic
5950-3.1; NZS3404.1; EN 1994-1-1. resistance of a stud is taken to be the
smaller of the following two equations:

PRK = 0,8Asc fu (1)


Introduction a distributed load q be introduced, the
vertical shear forces are affected such or
The forces that occur in the concrete that V = Vl Vr = q. If the distributed
flange of a composite beam are shown load q acts on the concrete flange, as (2)
in Fig. 1a. The compressive forces Fc, well as the longitudinal shear force Fl, where Asc is the cross-sectional area of
which reduce over the thickness of the a compression force q l exists at the the shank of the stud of diameter d, fu
concrete flange, are in equilibrium with interface between the concrete and the
the tensile forces Fsf within the trans- is the ultimate tensile strength of the
top flange of the steel beam. stud material, fck is the characteristic
verse reinforcement and with the lon-
gitudinal shear forces Fl in the studs. The load-slip performance of shear cylinder compressive strength of the
The forces Ften, resulting from the connectors has been historically estab- concrete and Ecm is the mean secant
inclination of the compressive forces lished from small-scale push specimens modulus of elasticity of the concrete.
Fc at the weld collar of the stud, and of the type shown in Fig. 1b. The inter- As opposed to using Eqs (1) and (2),
F are in equilibrium (the force F leads nal forces in the push specimen are the characteristic stud resistances
to transverse bending in the slab). shown to enable direct comparisons given in BS 5950-3.16 represent a lin-
Under constant vertical shear force to be made with those in a composite ear regression line through push test
where Vl = Vr, the components F and beam. The forces Fl are transferred data7 and are presented in tabular
Ften compensate for each other and, through the concrete in a similar way form as a function of stud diameter/
at the interface between the concrete as a composite beam (note the recess length against characteristic compres-
and the top flange of the steel beam, at the bottom of the slab is optional in sive cube strength.
only the shear forces Fl occur. Should the standard test in Eurocode 42). The
moment P e, resulting from the eccen- When studs are welded in sheeting
tric load introduction, causes tension with the ribs transverse to the sup-
Peer-reviewed by international ex- porting beams, the shear resistance is
perts and accepted for publication
in the studs and compression at the
by SEI Editorial Board interface between the concrete and reduced. To account for this effect, the
the flange of the steel section. In the characteristic resistance is determined
Paper received: March 4, 2013 Eurocode 4 standard test, the magni- by multiplying the resistance of a stud
Paper accepted: May 1, 2013 tude of the tension forces in the studs embedded within a solid concrete slab

246 Scientific Paper Structural Engineering International 2/2014


(b) 2P Questions have arisen on the appro-
priateness of using the reduction fac-
tors in Eqs (3) and (4), owing to the
fact that the failure mechanisms of
Fl
studs in profiled steel sheeting are
quite different to those experienced in
Fl
Nc Nc solid slabs, which are described by Eqs
(a)
(1) and (2); to remedy this situation,
attempts have been made to develop
Fl
F Fc
Ften
F mechanical models8 but, as yet, the
Fl Fsf
Fc resulting equations have not been
Ften
F Fc F P/2 P/2 adopted by any standards. For exam-
Vr
Fsf Fc
2P
ple, when push tests are conducted on
studs welded favourably or centrally
within the ribs of modern trapezoidal
Nc+Nc Nc+Nc
sheets (Fig. 2), a typical failure mode
V1 known as concrete pull-out occurs.9,10
Ften Fl Fl Ften In this case, the whole stud rotates and
1 is pulled out of the slab, carrying with
Ften Fl Fl Ften it a wedge-shaped pyramidal portion
of concrete (Fig. 2d); in these cases,
the axial tension in the stud can be sig-
Z
nificant, which has been measured in
some special test specimens to be in the
P e e P
order of 30% of the longitudinal shear
resistance.11 Due to the tension and
Fig. 1: Internal forces within (a) a composite beam and (b) a push test1
rotation of the stud, the concrete slab
can separate from the profiled steel
by a reduction factor k, which has welded in the unfavourable position as sheeting relatively early in push tests,
been evaluated from push tests of the shown in Fig. 2c), hp is the height of the which brings into question whether it
type shown in Fig. 1b. For Eurocode profiled steel sheeting, hsc is the height is entirely appropriate to neglect the
4, the reduction factor is applied to of the stud and kt,max is the upper limit compression at the interface between
both Eqs (1) and (2) and the smaller given in Table 1. the concrete and the steel section that
value is used in design. Conversely, for would occur in a composite beam sub-
For ANSI/AISC 360-10, the reduction jected to a uniformly distributed load
ANSI/AISC 360-10, k is only applied
factor for studs welded centrally within (Fig. 1a).
to the design equation for stud failure
a rib is proportional to:
(Eq. (1)), whereas for NZS 3404.1 it Another key performance character-
is only applied to the design equation kt = RgRp (4) istic that is evaluated from push tests
for crushing of the concrete (Eq. (2)). is the ductility of the shear connec-
According to Eurocode 4, BS 5950-3.1 where Rg is the group effect factor tors. The ductility is measured by the
and NZS 3404.1, the reduction factor (Rg = 1,0 for nr = 1; Rg = 0,85 for nr = slip capacity du, which is defined as the
for studs welded centrally within a rib 2; and Rg = 0,7 for nr 3) and Rp is the slip where the characteristic resistance
is proportional to: position effect factor (from Fig. 2, Rp PRk intersects the falling branch of the
= 0,75 when e 50 mm and Rp = 0,6 load-slip curve. The Eurocode 4 rules
kt = c/nr (b0/hp){(hsc/hp)1}but kt,max when e < 50 mm). for partial shear connection are based
(3)
where c is a calibration factor (in nr Eurocode 4 BS 5950-3.1 NZS 3404.1 BS5950-3.1+A1
Eurocode 4 and NZS 3404.1 c = 0,7 t 1,0 mm t > 1,0 mm
and in BS 5950-3.1 c = 0,85), nr is the 1 0,85 1,0 1,0 1,0 0,82
number of stud connectors in one rib 2 0,70 0,8 0,8 0,8 0,45
at a beam intersection, b0 is the aver-
3 0,6 0,6*
age breadth of the concrete rib for
trapezoidal profiles (which is taken as * Limited to nr = 3.
b0 = 2e in BS 5950-3.1 when studs are Table 1: Upper limits kt,max for the reduction factor kt for through-deck welded studs

Compression in slab e

hp,g hp,n hp,g hsc

Edge of Fl
Force from stud Ften
beam b0
(a) (b) (c) (d)

Fig. 2: Dimensions of profiled steel sheeting and studs in the (a) central; (b) favourable; (c) unfavourable position; and (d) concrete
pull-out failure

Structural Engineering International 2/2014 Scientific Paper 247


on two independent studies.12,13 These spacing in the beam test (correspond- to 110,5 mm. Two stud arrangements
studies assumed that, in solid con- ing to 677 mm, which is equivalent to were considered in the tests: nr = 2F
crete slabs and composite slabs using 4,8 overall slab depth). In addition, with a transverse spacing of 104,6 mm
profiled steel sheets prevalent in the although BS5950-3.1, ANSI/AISC (equivalent to 5,5d) and nr = 3F with a
1980s, the characteristic slip capacity 360-10 and NZS3404-1 permit nr = 3, transverse spacing of 75,3 mm (equiva-
of 19 mm diameter studs was approxi- the rules appear to be based on lim- lent to 4d). The slab was 140-mm-thick
mately duk = 6 mm. The required slip ited experimental evidence. To further normal-weight concrete and was rein-
was determined from numerical analy- investigate the performance of nr = 2F forced with one layer of A193 square
ses of composite beams using various and provide experimental data for nr mesh fabric, consisting of 7-mm-diam-
spans, cross sections and degrees of = 3F, a third full-scale composite beam eter wires at 200 mm cross centres. The
shear connection. The rules for par- specimen, together with six companion reinforcement was laid directly on the
tial shear connection in Eurocode 4 push tests, was constructed and tested deck (i.e. the top of the studs projected
were limited to situations where the to failure. Furthermore, to address the 11 mm above the mesh).
required slip did not exceed 6 mm. apparent deficiency that exists in the
For the beam test specimen, the steel
Studs were deemed to be ductile in current standard push specimen, a
section consisted of a 53321082 kg/m
those situations. new test was developed and calibrated
UKB using grade S355 steel supplied
against the results from the three beam
Push tests in Australia14 have sug- according to BS EN 10025-2.17 In a
tests. The remainder of this paper
gested that studs welded within the similar manner as the earlier tests,15
describes this work and its implica-
ribs of modern trapezoidal profiled the internal forces were evaluated from
tions on design.
steel sheeting possess lower resistance strain gauge measurements on the steel
and ductility than those assumed in beam, which were recorded at cross
current standards on composite con- Experimental Investigation sections corresponding to the shear
struction. To address these concerns, connector positions; these were accom-
tests on two full-scale composite beams To represent UK practice and provide panied with horizontally mounted
together with six companion push tests comparisons with the earlier beam transducers to monitor the slip at the
were undertaken.15 A variety of shear tests, a typical 60 mm deep trapezoidal interface between the underside of
connector arrangements were investi- sheet was fixed perpendicular to the the slab and the top flange of the steel
gated, which included (cf. Fig. 2) one longitudinal axis of the steel I-beam beam. The geometry of the steel section
stud per rib in the favourable (nr = 1F), (consisting of a Multideck 60-V2 pro- was measured at each of the 20 instru-
central (nr = 1C) and unfavourable file manufactured from S350GD+Z275 mented cross sections. The average
position (nr = 1U) and two studs per material according to BS EN 1032616). measured geometrical properties of the
rib in the favourable position (nr = 2F). As the limits to the reduction factor UKB section are presented in Table 2.
formulae in Eurocode 4 reduce for
Both beam specimens exhibited excel- sheet thicknesses t 1,0 mm (Table 1), The stressstrain relationship of the
lent ductility with measured slip capac- a 0,9-mm-thick sheet was used to materials was established from a mini-
ities exceeding the levels assumed in ensure that the lowest stud resistance mum of three tensile coupons taken
the development of the rules for par- was achieved in the tests (which is the from the steel section, profiled steel
tial shear connection. Furthermore, thinnest sheet currently employed in sheeting, studs and the reinforcement,
the performance of the beams gen- UK construction). The cross section of which were tested according to BS
erally supported the UK practice of the sheet was similar to that shown in EN 10002-1.18 The average measured
using the net height of the rib hp,n Fig. 2, with b0 = 150 mm, hp,n = 60,9 mm material properties are presented in
in Eq. (3). However, for nr = 2F, the and hp,g = 69,9 mm. Table 3.
characteristic resistance was lower
than anticipated, which led to a modi- The shear connectors consisted of 19 The normal force at each of the instru-
fied reduction factor formula being mm diameter 100-mm-long headed mented cross sections was evaluated
proposed.15 Furthermore, from com- studs (length-as-welded of approxi- by transforming the measured strains
parisons between the load-slip curves mately 95 mm). Due to the presence to stresses using the measured stress
from the beam tests and the compan- of a central stiffener within the rib of strain relationship for the steel, prior
ion push tests, it was shown that any the sheet, the studs were through-deck to integrating these derived stresses
brittleness exhibited in push tests was welded in the favourable position with over the measured cross-sectional area
as a result of a deficiency in the stan- the dimension e in Fig. 2 corresponding of the steel section. By plotting the
dard push specimen rather than the
shear connection. Location Steel section Profiled steel Reinforcement
Top flange Web Bottom flange sheeting bars
Although a modified reduction fac-
tor was proposed for nr = 2F, it was Mean yield strength 426,98 442,09 424,97 372,40 627,00
fym (N/mm)
believed that the performance of the
studs was adversely affected by local Note. Mean ultimate tensile strength of headed studs fum = 509,28 N/mm.
uplift effects from their longitudinal Table 3: Average measured steel properties

Height Top flange Bottom flange Web thickness tw Top flange Bottom flange Root radii Cross-sectional
h (mm) width bt (mm) width bb (mm) (mm) thickness tf,t (mm) thickness tf,b (mm) r (mm) area A (mm)
532 208,6 208,4 10,0 12,8 12,9 12,7* 10545,7
*Nominal dimension.
Table 2: Average measured cross-sectional properties for 533 210 82 kg/m UKB

248 Scientific Paper Structural Engineering International 2/2014


Position Age, t Mean cube Characteristic cube Mean cylinder Characteristic Mean secant
(days) strength fcm,cube, 100 strength fck,cube (N/mm) strength fcm cylinder strength modulus of elasticity
(N/mm) (N/mm) fck (N/mm) Ecm (kN/mm)
Composite beam 10 32,90 28,55* 30,84** 22,84* 19,6***
specimen 3
Companion push tests 13 33,83 29,65* 31,72** 23,72* 19,8****
14 34,53 30,47* 32,38** 24,38* 19,9****
*Calculated according to EN 1992-1-1.19
**Based on conversion factors according to Ref. [20].
***Calculated from initial stiffness of composite beam.
****Calculated according to EN 1992-1-1 for variation of modulus of elasticity with time.
Table 4: Measured concrete properties

Test ref. nr Pe,1 (kN) Pe,2 (kN) Pe,3 (kN) PRk (kN) cuk (mm) As can be seen from Fig. 3, the studs
MBP02 2 51,24* 51,39* 56,30 46,1 1,7 were through-deck welded in the 2F
and 3F position on the left- and right-
MBP03 3 36,79* 38,33 38,48 33,1 2,0
hand side of the beam, respectively.
*Concrete age 13 days.
Table 5: Characteristic resistance of studs welded in the favourable position (F) evaluated General Behaviour of the Beam
from the standard push test From the concrete modulus of elas-
ticity Ecm given in Table 4, the total
shrinkage strain was estimated from
change in normal force Nc at each of note that the characteristic resistance BS EN 1992-1-119 to be equivalent to
the instrumented cross sections with for nr = 2F is remarkably consistent a tensile normal force in the concrete
the corresponding measured slips from with the earlier push tests, where an of 222 kN. From linear-elastic partial
the horizontally mounted transducers, identical value was evaluated.15 shear connection theory, the shrink-
the in situ load-slip behaviour of the age force transferred by the end group
shear connectors was evaluated. Composite Beam Specimen 3 of studs was calculated to be 24 kN.
In the interests of providing the low- The composite beam was simply sup- In addition, it is estimated that con-
est degree of shear connection that is ported over a span of 11,4 m (Fig. 3) crete shrinkage resulted in a mid-span
permitted by the current standards in and, in a similar way as the earlier deflection of 4,6 mm.
order to obtain evidence of slip capac- beam tests,15 the beam was propped at
The props were left in place until the
ity, a low concrete strength class of third-points at the wet concrete stage
concrete was 6 days old (correspond-
C20/25 was specified. The gain in the so that the full self-weight load was
ing to fcm,cube,100 = 28,7 N/mm). Once
compressive concrete strength was applied to the shear connection once
the props were struck, the self-weight
monitored using 100 100 100 mm the props were removed. As well as
load on the composite cross section,
cubes that were stored under cover pre-loading the studs, this construction
which amounted to 96 kN, resulted
with the composite beam specimen. also ensured that the effects of ponding
in a measured mid-span deflection
A summary of the measured proper- were minimised to enable a constant
of 7,65 mm (excluding the estimated
ties are presented in Table 4. slab thickness to be assumed in the back
deflection caused by shrinkage). The
analysis of the test. A total slab width of
end-slips indicated that there was sym-
2850 mm was provided, which corre-
Companion Push Tests metry in the shear connector behav-
sponds exactly with the effective width
iour, with measured values of 0,070
Six nominally identical push speci- requirements given in current standards
mm and 0,073 mm at points A and D
mens were constructed using exactly of beam span/4. To remove the benefi-
in Fig. 3, respectively.
the same lorry load of concrete that cial effect of compression forces devel-
was used in the beam specimen so oping at the base of the studs from the The use of plastic theory to predict
that direct comparisons of the perfor- hogging bending moments that would the bending resistance is limited in
mance could be made. The push tests occur over a beam in a real building, most standards to shear spans where
consisted of three specimens with nr = the loads were conservatively applied the degree of shear connection h is
2F and nr = 3F, respectively. directly over the centre-line of the beam at least 40% (h = n/nf, where n is the
to simulate the bending moment from a number of studs provided and nf is the
Concrete pull-out failure occurred in uniformly distributed load. number of studs required for full shear
all the tests (Fig. 2d). The shear resis-
tances from each set of tests Pe,n are
given in Table 5 along with charac- 1430 2850 2840 2350 1430
teristic resistance and slip values cal- 354 354 400 300
culated in accordance with Annex B W W W W
of Eurocode 4 (taken as 0,9 times the
minimum test value, as the deviation
from the mean did not exceed 10%).
A B C D
As can be seen from Table 5, the char-
acteristic slip capacity is lower than the 2F studs welded in each of the 16 ribs 3F studs welded in each of the 16 ribs
at 354 mm and 323 mm cross-centres at 354 mm and 323 mm cross-centres
6 mm value given by Eurocode 4 for
ductile connectors. It is interesting to Fig. 3: General arrangement of composite beam test specimen (Units: mm)

Structural Engineering International 2/2014 Scientific Paper 249


nr Stud position Pe,min (kN) PRk (kN) duk (mm) Stiffness* ksc Eurocode 4 ANSI/AISC 360- BS5950-3.1 NZS3404.1
(kN/mm) PRk/PRk,n 10 PRk/PRk,n PRk/PRk,n PRk/PRk,n
1** F 123 111 9,6 83 2,19 (50,6) 1,38 (80,6) 1,27 (87,3) 1,73 (64,3)
C 107 96 11,9 31 1,90 (50,6) 1,19 (80,6) 1,10 (87,3) 1,49 (64,3)
U 89 76*** 6,0 46 0,94 (80,6) 1,32 (57,6)
2 F 65,5 58,9 7,2 109,7 1,20 (49,0) 0,66 (89,3) 0,75 (78,8) 0,99 (59,4)
3 F 64,2 40,2*** 6,0 327,2 0,55 (73,6) 0,68 (59,1) 0,83 (48,5)
Note. Calculated characteristic resistance values in kN are given in parenthesis
*Stiffness calculated according to Eurocode 4 as 0,7 PRk/s, where s is the slip at a load of 0,7 PRk
**Composite Beam Specimen 2
***down-rated to achieve characteristic slip capacity of 6 mm
Table 6: Characteristic properties of studs in the favourable (F), central (C) and unfavourable position (U) evaluated from beam tests

connection). From the measured geom- istic resistances presented in Table 6 studs, the characteristic resistance has
etry and material strengths presented have been taken to be 0,9 times the been down-rated in Table 6 in order to
in Tables 3 and 4, the tensile force in minimum failure load per stud Pe,min satisfy the Eurocode characteristic slip
the steel beam is Aa fym = 4576 kN. For according to Eurocode 4 Annex B. requirements when connectors may be
nr = 2F and taking the characteristic For completeness, the earlier results taken to be ductile.
resistance of 46,1 kN from Table 5, nf = for nr = 1 are also presented15 (the
4576/46,1 = 99 (following a similar cal- results for nr = 2F from the previous Development of an Improved
culation, nf = 138 for nr = 3F). However, beam test are not included, as it was Push Test
in the tests, 12 ribs were available up deemed that their performance was
to the points of maximum moment adversely affected by uplift from the Beam and companion push test load-
defined by B and C in Fig. 3, so for nr longitudinal spacing of 4,8 overall slip curves for studs with the lowest
= 2F, the number of studs provided n = slab depth). Owing to the shape of the recorded resistance are presented
2 12 = 24 and h = 24/99 = 0,24 (for nr load-slip curves for nr = 3F and nr = 1U in Fig. 4. As can be seen from these
= 3F, h = 3 12/138 = 0,26). This simple
calculation shows that the degree of (a) 70
shear connection provided in the tests Beam test
60
was below 40% and implies that failure Push test
of the shear connection would occur 50
while the steel beam remained partially
Load per stud (kN)

elastic. This behaviour was borne out in 40


the test, which was deliberate owing to
the fact that the beam test was intended 30
to provide evidence of slip capacity.
20
Under load, a very ductile failure of the
10
shear connection occurred along AB
before the steel beam was fully plastic 0
at B. At the maximum applied load, the 0 5 10 15 20 25
bending at point B was 1152,5 kNm at a 10
mid-span deflection of 260 mm (equiv-
alent to span/43). The maximum end 20
Slip (mm)
slip recorded at point A was 22,6 mm
and 12 mm at point D. By preventing (b) 70
additional slip along AB, the beam was Beam test
subjected to further vertical displace- 60 Push test
ment until a maximum moment of
1156,5 kNm was achieved at C, which 50
corresponded to a mid-span deflection
Load per stud (kN)

of 329 mm (equivalent to span/35). At 40


this point, an end slip of 20,4 mm was
achieved at point D, whereupon the 30
test was terminated owing to concerns
over the stability of the test rig from 20
the large curvatures. In a similar way
as the companion push tests, concrete 10

pull-out failure was later confirmed


0
in both beam specimens when the 0 5 10 15 20 25 30 35
concrete slab was carefully excavated
10
around the stud positions (Fig. 2d). Slip (mm)
From the load-slip curves evaluated Fig. 4: Load-slip curve for beam test compared to standard push test for (a) nr = 2F and
from the beam tests, the character- (b) nr = 3F

250 Scientific Paper Structural Engineering International 2/2014


plots, there appears to be no similar- tions and develop a new test, which bet- sured in the beam tests. It was consid-
ity in performance of studs in these ter reflects the conditions that exist in ered that the results with a 12% lateral
two types of specimens. The slips mea- a real beam. As good-quality load-slip load provided the closest match with
sured in the push tests are well below data existed from the present compos- the load-slip behaviour from the beam
the levels achieved in the beam and, if ite beam tests, the new test could be test. While it might be argued that this
considered in isolation, would suggest calibrated against this performance. lateral load does not impose the exact
that the studs should not be taken to However, rather than developing a stress conditions within the studs in the
be ductile. These observations were completely new specimen, it was pro- beam tests, it is felt that the improved
also made in the earlier beam tests for posed to modify the standard specimen push rig delivers more representative
nr = 1 and nr = 2.15 given in Annex B of Eurocode 4, in the performance of studs in a beam, while
From comparisons of the load-slip interest of developing a relationship still maintaining the simplicity of the
curves, it is clear that any brittleness with historical push test resistances. traditional push test.
exhibited in the push test is as a result Also, although a single-sided arrange- A further two tests with a lateral load
of a deficiency in the standard speci- ment was considered, this was disre- of 12% were conducted to evaluate the
men rather than the shear connection. garded due to concerns that such an characteristic values for nr = 1F and nr =
However, although the present tests arrangement would prevent the redis- 2F (which were subsequently given the
showed that the performance of studs tribution of load from one test slab to test reference A1D and A2DY, respec-
through-deck welded in current trap- the other, which occurs in the exist- tively). In a similar way as the earlier
ezoidal sheeting is ductile, the problem ing standard specimen.23 Finally, due tests, taking the characteristic value as
remained that, if new floor decks were to the possibility of different friction 0,9 times the minimum measured, the
developed, it would be difficult to iden- coefficients at the base of the test slabs following properties were evaluated:
tify cases when the behaviour would affecting the repeatability of the tests2 PRk = 101,2 kN and duk = 10,2 mm for
be brittle unless further beam tests (Fig. 1b), it was decided to develop a nr = 1F; and PRk = 63,8 kN and duk =
were undertaken. Moreover, although self-contained rig that could be disas- 8,7 mm for nr = 2F. By comparing these
helpful in evaluating the actual load- sembled and erected in different loca- values with those presented in Table 6,
slip performance of shear connectors, tions without the need of a strong floor. the improved push rig delivered perfor-
it would be difficult to conduct beam The improved push rig is shown in mance properties in good agreement
tests in sufficient numbers to investi- Fig. 5. The loading system consists of with the beam tests. The improved push
gate the sensitivity of different param- two vertical jacks applying the longi- rig was subsequently used to investi-
eters and evaluate the performance of tudinal shear force, accompanied with gate the effect of a number of key vari-
a design model using structural reli- two horizontal jacks applying a lateral ables on the load-slip arrangement of
ability analysis. force, which is uniformly distributed headed stud connectors. Further details
It was felt that the reason for the poor over the face of the test slabs through on specimens A1D and A2DY and the
performance in push tests is due to a grillage of UC sections. A total of 14 subsequent parametric investigation
the absence of the compression force specimens were constructed from a sin- are reported in Ref. [24].
at the interface between the concrete gle concrete mix using the same details Due to the favourable comparisons with
and the flange of the steel section, that had been provided in the previ- the three full-scale beams presented in
which exists in real composite beams ous beam tests with nr = 1F and nr = this paper, as well as similar levels of
from the floor loading (Fig. 1a). Earlier 2F. They were tested with the following lateral force being found to be appro-
work21 attempted to remedy this prob- levels of normal force (taken as a pro- priate in the earlier North American
lem by modifying the push test through portion of the longitudinal force): 0%, and Australian research programmes
the introduction of a normal force, 4%, 8%, 12% and 16%. The load-slip (which used different concrete strength
equivalent to 10% of the vertical load, curves for these tests are presented in classes, trapezoidal profiled steel sheet-
applied directly over the centre-line of Fig. 6 and compared against those mea- ing geometries, etc.), it is recommended
the steel section. The results from these
tests were compared favourably with
the performance of four 9,0 m span
companion beam tests and were sub- Vertical jacks applying
sequently used to develop the design longitudinal shear
force to shear studs
rules for stud connectors in the 2010 Three UC sections to distribute jack forces
AISC Specification.4 Similarly, the uniformly over face of test slabs
push test was modified in Australia to
a single-sided arrangement and tested
in the horizontal position.22 In the
Australian tests, the normal force was
A A
slightly smaller at 5% of the longitu-
dinal shear force but was applied uni-
formly along the edges of the specimen,
thereby applying a hogging moment
over the centre-line of the steel section Section A-A
to reflect the loading conditions on two Horizontal jacks applying
8,05-m span companion beam tests. lateral load to push specimen

In the present work, it was decided to


Elevation
draw inspiration from the earlier North
American and Australian modifica- Fig. 5: Improved push test rig

Structural Engineering International 2/2014 Scientific Paper 251


(a) 140 steel sheeting is proportional to 1/nr.
7th stud By considering Table 6, the reduction
4% horizontal
120 to the characteristic resistances mea-
8% horizontal
12% horizontal sured in the beam tests is 58,9/111 =
100 16% horizontal 0,53 for nr = 2 and 40,2/111 = 0,36 for
Load per stud (kN)

nr = 3. This simple calculation clearly


80 shows that the assumption that the
resistance is proportional to 1/nr is
60 inappropriate. Moreover, when con-
sidering the resistance of the shear
40 connection per rib, the resistance of
nr =2 is 6% greater than nr =1 (i.e.
20
20,53 1 = 6%), whereas the resis-
tance of nr =3 is only 8% greater than
0
nr =1 (i.e. 30,36 1 = 8%). This cal-
0 10 20 30 40 50 60 culation clearly shows that there is no
Slip (mm) benefit in providing more than nr =2,
(b) 120 which supports the Eurocode 4 reduc-
16th pair of studs tion factor formula limit. This finding,
15th pair of studs in part, led to the amendment given in
100 14th pair of studs BS 5950-3.1+A1.26 In this standard, the
4% horizontal
8% horizontal
variables in Eq. (3) are as follows (see
Load per stud (kN)

80 12% horizontal final column of Table 1 for kt,max): c =


16% horizontal 0,63 for nr = 1; c = 0,34 for nr =
2 and no guidance is given for nr = 3.
60

Conclusions
40
Full-scale composite beam and com-
20 panion push tests have been under-
taken with trapezoidal profiled steel
sheeting. Propped construction,
0 together with other unfavourable com-
0 5 10 15 20 25
Slip (mm) binations of variables, was adopted to
demonstrate the slip capacity that can
Fig. 6: Comparison of load-slip behaviour for the new improved test with that measured in be achieved in a beam, together with
beam tests for (a) nr = 1F and (b) nr = 2F the level of safety that exists in current
design standards. All specimens exhib-
ited excellent ductility with slip capaci-
that the improved push test may be are based on the characteristic mate- ties exceeding the levels assumed in
used with confidence for the common rial properties evaluated from mea- the development of the rules for par-
case when the loading is applied to the surements given in Table 4. tial shear connection in Eurocode 4.
concrete slab of a composite beam. For
special cases when the load is applied As can be seen from Table 6, the char- The performance of the beams gen-
directly to the steel beam (such as acteristic resistance for studs in the erally supports the UK practice of
may be encountered in crane beams), 1F, 1C and 1U position compare well using the net height of the rib hp,n
the tensile forces applied to the shear with the BS5950-3.1 predictions; how- in the reduction factor formulae.
connectors will be significant; in these ever, they become unconservative for However, for two and three studs per
cases, it may be more appropriate to studs in the 2F and 3F position (by rib, the performance in the beam test
reduce the lateral load from 12% to 25% and 32%, respectively). Similarly, was lower than anticipated by ANSI/
zero, which has been verified by other the ANSI/AISC predictions compare AISC 360-10, BS5950-3.1 and NZS
investigators from tests on composite favourably for 1F and 1C studs, but 3404.1. The results also demonstrate
beams and companion push tests.25 become unconservative by 34% for 2F that there is no further improvement
studs and by 45% for 3F studs; how- in resistance when providing three
ever, for this standard, all the predic- studs per rib, and this arrangement
Discussion tions are based on stud shank failure, should be used with caution when
which was not borne out in the tests. using plastic design. These findings, in
To examine the performance of the For Eurocode 4, the predictions are on part, led to the amendment given in
current standards with the beam tests, the safe side for nr =2 but appear to be BS 5950-3.1+A1.
predictions of the characteristic stud overly conservative for studs in the 1F,
resistance according to Eurocode 4, 1C and 1U position. Finally, the NZS From comparisons of the load-slip
ANSI/AISC 360-10, BS 5950-3.1 and 3404 predictions compare well with nr curves between the beam tests and
NZS3404-1 are presented in Table 6. =2 but are conservative for nr = 1 and the companion push tests, it is clear
By adopting the current UK practice unconservative for nr =3. that any brittleness exhibited in
of using hp,n in Eq. (3) (Fig. 2), the pre- the push test is as a result of a defi-
dicted characteristic stud resistances Equation (3) assumes that the reduc- ciency in the standard push specimen
for the net height of the sheet PRk,n tion of resistance of studs in profiled rather than the shear connection. To

252 Scientific Paper Structural Engineering International 2/2014


remedy this situation, an improved [5] NZS3404-1:1997. Steel Structures Standard. Technical Delivery Conditions, British Standards
push test has been developed, which Part 1, Incorporating Amendment No. 1 and 2, Institution: London.
Standards New Zealand: Wellington.
has been calibrated against real beam [17] BS EN 10025-2: 2004 Hot rolled products of
behaviour. [6] BS 5950-3.1: 1990. Structural Use of Steelwork structural steels. Technical Delivery Conditions
in Buildings: Part 3: Section 3.1: Code of Practice for Non-Alloy Structural Steels, British Standards
for Design of Simple and Continuous Composite Institution: London.
Acknowledgements Beams, British Standards Institution: London,
1990. [18] BS EN 10002-1: 2001. Metallic Materials
This paper is dedicated to Mr. Clifford Dyer, Tensile Testing Part 1: Method of Test at
who sadly passed away in February 2012 [7] Menzies JB. CP 117 and shear connectors in Ambient Temperature, British Standards
and was responsible for the formation of the steel-concrete composite beams made with nor- Institution: London.
Metal Cladding and Roofing Manufacturers mal-density or lightweight concrete. Struct. Eng.
1971; 49(3): 137154. [19] EN 1992-1-1:2004. Eurocode 2: Design
Association (MCRMA). Financial support for of Concrete Structures, Part 1-1, European
this investigation was provided by the Floor/ [8] Johnson RP. Calibration of resistance of Committee for Standardization: Brussels.
Deck Group of the MCRMA, Tata Steel shear connectors in troughs of profiled sheet-
Construction Services and Development ing. Proc. Instn. Civ. Eng., Struct. Bldg. 2008; 161: [20] Stark JWB, Van Hove BWEM. Statistical
together with Tata Steel Strip Products UK. 117126. analysis of push-out tests on stud connectors in
The authors wish to thank the help and composite steel and concrete structures, Part 2:
[9] Hawkins NM, Mitchell D. Seismic response Solid Concrete Slabs. TNO report BI-91-163,
assistance of Dr. R.E. McConnel, Mr. M.R. of composite shear connections. J. Struct. Eng. Delft, 1991.
Touhey and the technical staff of Cambridge 1984; 110(9): 21202136.
University Engineering Department whose [21] Easterling WS, Gibbings DR, Murray TM.
expertise ensured the success of the testing [10] Lloyd RM, Wright HD. Shear connection Strength of shear studs in steel deck on com-
programme. The authors also thank Prof. between composite slabs and steel beams. J. posite beams and joists. Eng. J. AISC, Second
R.P. Johnson of University of Warwick for Construct. Steel Res. 1990; 15: 255285. Quarter 1993; 4455.
his support and advice, together with Dr. J.W. [11] van der Sanden PGFJ. The behaviour of [22] Bradford MA, Filonov A, Hogan TJ, Ranzi
Rackham and Dr. W.I. Simms, formerly of a headed stud connection in a new push test G, Uy B. Strength and ductility of shear con-
The Steel Construction Institute. including a ribbed slab, Tests: Main report. BKO nection in composite T-beams. 8th International
Report 95-15, Eindhoven, 1996. Conference on Steel, Space & Composite
References [12] Johnson RP, Molenstra N. Partial shear con- Structures, Kuala Lumpar, Malaysia, 1517 May,
nection in composite beams for buildings. Proc. 2006; 1526.
[1] Roik K, Hanswille G. Zur Dauerfestigkeit
Inst. Civ. Eng. 1991; 91(Part 2): 679704. [23] Johnson RP. Designers Guide to Eurocode 4:
von Kopfbolzendbeln bei Verbundtrgern. Der
Bauingenieur 1987; 62: 273285. [13] Aribert J-M. Dimensionnement de poutres Design of Composite Steel and Concrete Structures,
mixtes en connection partielle. Mixed Structures 2nd edn, Thomas Telford: London, 2012; 257.
[2] EN 1994-1-1: 2004. Eurocode 4: Design of
Including New Materials. IABSE Symposium, [24] Smith AL, Couchman GH. Strength and
Composite Steel and Concrete Structures Part
Brussels, International Association for Bridge ductility of headed stud connectors in profiled
1-1: General Rules and Rules for Buildings,
and Structural Engineering Reports, 1990; 60: steel sheeting. J. Construct. Steel Res. 66: 2010;
European Committee for Standardization:
215220. 748754.
Brussels.
[14] Patrick M. Composite beam shear connection
[3] Hicks SJ, McConnel RE. The shear resistance [25] Ernst S, Bridge RQ, Wheeler A. Correlation
design and detailing practices for Australian steel
of headed studs used with profiled steel sheeting. of beam tests with pushout tests in steel-con-
decks, Report CCTR-CBSC-001-04, University
In Composite Construction in Steel and Concrete crete composite beams. J. Struct. Eng. 2010;
of Western Sydney, 2004; 15.
III, Buckner CD, Shahrooz BM (eds), ASCE: 136(2): 183192.
New York, 1997; 325338. [15] Hicks S. Strength and ductility of headed
[26] BS 5950-3.1: 1990+A1. Structural Use of
stud connectors welded in modern profiled steel
[4] American Institute of Steel Construction. Steelwork in Buildings: Part 3: Section 3.1: Code
sheeting. Struct. Eng. Int. 2009; 4: 415419.
ANSI/AISC 360-10. Specification for Structural of Practice for Design of Simple and Continuous
Steel Buildings, American Institute of Steel [16] BS EN 10326: 2004. Continuously hot- Composite Beams, British Standards Institution:
Construction: Chicago, 2010. dip coated strip and sheet of structural steels. London, 2010.

Being a Member of brings you together...

Companies,
increase their access to visibility within the worldwide structural engineering
community, and to new information, new perspectives and new contacts.

..tell your colleague.

www.iabse.org

Structural Engineering International 2/2014 Scientific Paper 253

Você também pode gostar