Illumination of Type A control building

ILLUMINATION DESIGN CALCULATION FOR


TYPE A CONTROL BUILDING

Project : Expansion of Distribution Networks in the Eastern Region of Nepal


Contract no : ICB - PMD - DSAEP - 071/72-04 (Lot 1)
1. Input Data: (For Battery Charger Room )

Required level of Luminiosity, lux Rlus 150


Work Plane Height, m Hw 0.8
Heigh of the fitting above work plane, m Hc 2.3
Reflection factor for white color ceiling, % Rf 70
Reflection factor for white color wall, % Rw 70
Length of the room, m RL 3.8
Width of the room, m RW 3.3
Height of the room, m RH 3.75
Area of the room, Sq m RA RL RW = 12.54

Room index RL RW
RI = 0.768
RL + RW Hc
From the table,
Utilization factor corresponding to the rood index: Uf 0.37
Maintenace Factor Mf 0.7
2. Light Fixture Sample:

Selecting Flourescent/LED light 4 ft long


Wattage of each lamp, watt W 44
Lumen per watt of each lamp, lm/watt eff 102.27
Number of lamps per fixtures NF 1
Lumen of each fixtures, lm L eff W NF = 4.5 10 3

3. Calculations:
Rlus RA
N = 1.614
Number of Fixture L Uf Mf
N2
Selecting number of Fixture
N L Uf Mf
Actual value of Illumination, lux Eav = 185.88
RA

Design Calculation by:

----------------------
Er. Santosh Gairhe
Senior Electrical Engineer
Tripureswar Conductor - Jaya Durge Engineering J/V