System Title ID Subsyst and Facility(ies) Typical System Components Functional Description Comments, Usage Old LANL Terms
(default sort) Drawing Authorized Examples, Source (Reference Only)
Acronyms to Use of Acro
Airborne ARD Any Continuous air monitors (CAMs), Monitors airborne contamination both on a real- RLUOB calling Airb.
Radiation fixed head air samplers (FAS), time basis, including alarms, and by collecting Contam. Det.
Detection critical flow venturis, vacuum samples for periodic analysis. CMRR NF system
pumps, piping, valves, more specific than
instrumentation Radiation
Monitoring
Argon Gas AR TA55 only: Any Piping, valves, storage bottles Provides argon gas to labs and process equipment Periodic table of the
AR100, AR35 throughout the facility. elements
(psi)
Argon/6% REGEN Any TA55
Hydrogen Regen
Gas
Automated AACS Any Turnstiles, badge readers, Monitors and controls all access through selected TA-55, RLUOB. ACS
Access Control personal identification number entrances and exits. Falls under SEC
(PIN) entry keypads (RAPs), OpSys.
biometric devices, door strikes,
electric latches, door
openers/closers/holders
1 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Boiler BLR BLR1 BLR2 Powerhse Boiler, fans, indicators, Produces steam. For small packaged
BLR3 only transmitters, pumps, valves, boilers, use STM for
OpSys and boiler
will be an
equipment item.
ASME, IEEE 803.1,
NCS/UDS.
Boiler Feed BFW Powerhse Heaters, valves, gauges, Supplies water to powerhouse boilers. ASME, ASHRAE
Water only indicators, valves 134, NCS/UDS.
Breathing Air BA Any Piping, storage bottles, breathing Provides respiratory protection and air quality to TA55 uses BRAR. Self-Contained
air stations, distribution manifolds, workers in accordance with ANSI Z88.2. This may Breathing
pressure-demand regulators, full- be accomplished by self-contained breathing air Apparatus-SCBA
face respirators, oil-free apparatus or a pressurized mobile or centralized
compressor, valves, hoses, distribution system.
instrumentation, SCBAs.
Building BLDG Any Structural members, interior and Provides protection to personnel and equipment by Widespread. IEEE Building
exterior walls (incl. fire barriers), providing fire barriers to separate the facility into 803.1, ASME, Structure,
formed or pre-stressed concrete, fire areas and shelter from the environment for NCS/UDS, NECA Building-
masonry, structural steel, doors equipment and personnel. For nuclear facilities, 100. BG, Building
(fire, security, etc.), windows, can reduce doses by providing a confinement Structure-BGS,
roofs. and/or shielding barrier. SH, shielding,
confinement
Building BAS Any Sensors, including differential Provides for online continuous monitoring and NCS/UDS. Facility
Automation pressure, temperature, loss of control of primarily commercial-type HVAC Management
power, switch positions, relay equipment and key parameters. Usually applied to System-FMS,
contacts, flow, etc., one facility and performs both discrete and Alarm Monitoring-
microprocessor, control console, continuously variable functions. Also see Facility AM, Building
CRT, alarms Control. Management
BMS, Distributed
Control DCS,
Direct Digital -
DCC
2 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Caustic Waste CWS Any Holding tank, pumps, filters, Collects caustic liquid waste and chemically TA-55; CMRR NF
System instrumentation contaminated wastewater, transfers to yard piping. CW generated
specifically from
laboratory
operations Cat I
Building Module
203
Chemical Supply CSG Any Bottles, manifolds, piping for CO2, Supplies compressed gases RLW Bal of plant
- Compressed argon, N2, O2, P-10
Gas
Chemical Supply CSP Any Tanks, pumps, piping for HCl, Delivers chemicals to facility SSCs RLW Bal of plant
- Process NaOH, lime, Fe2(SO4)3,
Mg(OH)2, etc.
Chilled Water CW Supply CWS Any Chillers, piping, valves, heat Provides chilled water to facility and process Central
Return -- exchangers, evaporative heat equipment for heat removal. (Tower Water and Circulating
CWR exchangers, pumps, Refrigeration are other systems that may be Chilled Water,
instrumentation related). Chilled Water-CH.
Similar:
Secondary CW
Closed-Circuit CCTV Any Cameras, video screens Permits remote viewing for operational or security CEF
Television needs
Combustion Gas CGTG Powerhse The Opsys, comprised of the 5 Provides an independent electrical generating unit
Turbine only Systems below (TA-55 style providing 13.5kV.
Generator CMMS use)
3 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
CGTG Cooling CGTGC Powerhse Pumps, valves, piping, surge tank, Cools components and fluids of the CGTG
only fin-fan cooler, instrumentation, and
a temperature control PLC
CGTG Drive CGTGDT Powerhse The major rotating and power- Produce electricity by burning natural gas in a gas
Train only producing components of the generator (jet engine); its exhaust gases drive a
CGTG: gas generator, power power turbine which drives an electrical generator
turbine, reduction gear, electric
generator, exciter, and hydraulic
starter
CGTG Main CGTGML Powerhse Pumps, valves, filters on skid Lubricates power turbine, gearbox, electric
Lubrication only generator, etc
CGTG Support CGTGS Powerhse Main PLC, gas chromatograph, Supports CGTG operation and maintenance with
only tanks, sumps, inlet combustion air functions not provided by the four other CGTG
filters, ventilation filters, ventilation systems
fans, instrumentation, stack, and
structure
Combustion Gas CGTGGL Powerhse Pumps, valves, filters on skid Lubricates the gas generator (jet engine)
Turbine Gas only
Generator
Lubrication
Comet COMET DAF only Support stand, two stacked Comet is a general purpose critical assembly NCERC
hydraulic rams and a stepper machine used to move nuclear materials into a
motor drive. critical configuration.
Compressed Air CA Any Compressors, valves, piping, Supplies air for motive power source for tools and Also see Instrument Plant air
instrumentation, air dryers, equipment, and oxygenation of effluent. Air, Breathing Air,
controls Process air.
Condensate CON High Pr Any Traps, piping, pumps Removes liquid from the steam system and See Equipment
CONHP Low transports it to a drain or boiler for reheating. High Drains (DRE) for
Pr CONLP Pressure is > 15 psig. cooling coil and
Pumped other non-steam
CONPMP condensate.
4 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Credited CRIT Any Safes, carts Equipment called out in the DSA and needing to be TA55
Criticality Safety controlled at an SS level for the credited crit safety
program
Criticality Alarm CAS Any Criticality detectors, monitors Monitors and alarms areas for criticality conditions. TA-55; CMRR NF in
the Cat I Building
and vaults
Deionized Water DIW Supply Any Piping, valves, filters, Provides de-ionized water for labs in the facility RLUOB. From
DIWS, Return instrumentation, storage vessels. (generally at 18 megohms resistivity or equivalent NCS/UDS.
DIWR, Drain microsiemens conductivity).
DIWD
Demineralizer DEMIN Any Filters, RO units, pumps, mixing Reduces the dissolved mineral content of water syst RLUOB historical: DIWTR
Water valves, tanks, chemical injection
equip
Diesel Exhaust DE CMRR NF Silencers, expansion joints, Exhausts diesel engine exhaust from the diesel For many, Engine
only flexible connections generators and diesel fire pumps to outside the Generator (EG) is
facility. The silencers provide noise reduction sufficent granularity
through exhaust gas silencing. without this.
5 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Effluent EFL Any Tanks, piping, pumps, valves, Performs effluent processing. SERF also returns TA-3 Pwrhse, SERF.
transmitters, CO2 injection. non-potable water to the SCC. From ASME.
Sanitary Effluent Reclamation
Facility (SERF) installation
includes mixers, reverse osmosis.
Electrical ED EDEA1-X; Any Switchgear, transformers, Distributes nominal 13.5kV or 4160 V electrical Medium Voltage
Distribution EDG1-3 substations, switches, electrical power to various LANL facilities; includes both the MV, 13.5 or
(powerplant ducts, overhead and underground 115/13.5kV and stepdown-from-13.5 kV 13.8kV Power
gen); power lines transformers. Typically owned by Utilities. Distribution, 4.16
EDPFXX kV
(various PF
ckts); EDS1-
XXX; EDSS1,
2 (serve PP);
EDLA3
EDLA4 (LA
Cty); EDTC1,
2 (LAC ties)
Electrical Power EP Any Electrical distribution equipment, This system distributes < 600 Vac (e.g., 480Y/277 Widespread. Low Voltage LV
MCCs, transformers, switchgear, V and 208Y/120 V) power within a facility. RLUOB using EP
breakers, cable, raceway, transfer for 480Y277V+;
switches, panel boards, meters, EPL (low) for under
instrumentation and control, and 480.
UPS (can be own system)
Elevators and ELV Any Lifting cage, doors, hydraulic Provides in-place people and material lifting, can TA55 just for Elevators-EV,
Lifts pump, motor, cable, lifting ram, include personnel and freight elevators, elevators. Building
controls dumbwaiters, and fixed drum lifts. Elevators-BGE
6 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Enclosures-- GARPS CMRR NF GARP unit, vacuum pump, blower, Purifies and recirculates glovebox atmosphere to Truly an ENCL
Glovebox piping, instrumentation, getter remove water and oxygen. Subsystem,
Atmosphere beds, filters, control system, appears on CMRR
Regenerable moisture and oxygen analyzers. NF ENCL SDD and
Purification field tags.
Engine DG Any Diesel, gas, natural gas or LP A diesel, gasoline, LP, or natural gas engine- For RLUOB, called D/G, diesel,
Generator engine, generator, cooling water, driven generator that provides an auxiliary source Diesel Eng Gen. generator,
instrumentation, starting battery, of 480 Volt electrical power for the Electrical Power For CMRR NF, a emergency,
distribution panel, circuit breakers, System; starts upon loss of normal power. Ref Diesel Exhaust standby, backup
ATS DOE-STD-3003, Backup Power Sources for DOE system was also power, set
Facilities. required. IEEE
803.1 mod.
Environmental ECS ECOPS -- Any Temperature control components Provides a thermally controlled environment to WETF
Chamber System Environment'l such as freezer, refrigerator, store tritium containment vessels (TCVs) over an
Chamber heater, testing equipment. adjustable range of temperatures. ECOPS
Over- ECOPS has instrumentation and removes power from an EC in the event of a
temperature controls temperature excursion above the setpoint.
Protection
System
Equipment DRE Any Condensate drain funnels, Collects condensate from the HVAC air handling CMRR Aux
Drains condensate collection sump, sump unit cooling coils and transfers it to Sanitary Waste.
pumps
Exhaust EX Any Ductwork, fans, motors, dampers, Remove air from building spaces and dicharge to See HVAC as other Exhaust Air
non-centralized simple atmosphere. May reduce the concentration of option
instrumentation, HEPA filters radioactive particulate and hazardous materials in
spaces and airstream.
7 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Facility Gases FGA WETF only Air compressors, compressed air Supplies and distributes liquid nitrogen [liquid, low- Legacy Opsys; use
and Air receiver tanks, reducing and pressure (LP) gas, and high-pressure (HP) gas] of discrete systems
regulating valves, compressed and compressed gases for facility and process preferred
gas cylinders, a breathing air loads including compressed air (high-pressure and
supply trailer, a liquid nitrogen instrument air), oxygen, breathing air, ultra-high-
supply tank and Dewar, and purity helium (UHPHE), ultra-high-purity argon
distribution piping (UHPAR), hydrogen-argon mixture, deuterium, and
calibration gas that is 70 ppm oxygen with a
balance of nitrogen
Facility FMS Basic Process CMRR only Primary sensors, including Provides for online continuous monitoring, CMRR RLUOB and
Management Control differential pressure, temperature, alarming and control of key facility processes. It NF are authorized
System loss of power, switch positions, performs both discrete and continuous functions to use this versus
(BPCS) relay contacts, flow, etc, control limited to one particular facility. BPCS is industrial BAS alone and/or
Building console, input/output cabinets, grade PLC for utilities. BAS is commercial grade FCS.
Automation processor racks, system electrical for RLUOB control.
System (BAS) and network cabling, network
switches, servers, historian,
printers, alarms
8 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Fire Suppression FSGB CMRR NF Heat detector, piping, suppression Supplies suppression agent to extinguish fires Truly an FP
Glove Box only agent tank, instrumentation, internal to gloveboxes. Provides local audible and Subsystem,
audible and visible alarms. visual alarms as well as interfaces with the FMS. appears in CMRR
NF ENCL SDD and
on field tags.
Flat-top FLATOP DAF Support table, two hydraulic rams The Flat-Top critical assembly is a benchmark NCERC
and three stepper motor driven critical assembly consisting of a natural uranium
control rod drives. reflector and two fissile cores, one enriched
uranium, one plutonium.
Floor Drains DRF Any Sumps Collect and retain a limited volume of fire water in CMRR NF
the CMRR NF floor drain sumps on the Basement
Level during fire events in the Auxiliary Building,
Security Category I Building, and Vault Building
Glovebox SPRTC TA55 only GB stands (legs, bracing, Credited support for PF-4 GBs
Support Stands anchorage)
Credited
9 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Glovebox SPRTNC RLUOB GB stands (legs, bracing, Non-credited support for GBs.
Support Stands anchorage)
Non-Credited
Glovebox GBS TA55/RLUO Gloveboxes Confine and in some cases shield radioactive RLUOB, TA-55
Systems B only material. (OpSys)
(OpSys)
Gloveboxes GB TA55 only Gloveboxes. Confine and in some cases shield radioactive See also
(System) material. Enclosures
Godiva GODIVA DAF only Core, hydraulic ram-driven safety A prompt burst critical assembly. The core NCERC
block, compressed air cylinder- consists of a stack of high enriched uranium rings
driven burst rod, 2 stepper-motor- and plates.
driven control rods.
Hazardous HAZW Any Various non-destructive assay Provides for the accumulation, treatment, CMRR NF
Waste equipment (i.e., trash compactor) packaging, manual transfer, staging, and shipment
of Analytical Chemistry and Materials
Characterization (AC/MC) solid process wastes
and for other industrial and sanitary or recyclable
wastes such as printer toner cartridges.
10 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Heating HVAC See also Any Supply and exhaust ventilation, Supplies and distributes tempered air for the NCS/UDS, NECA Differential
Ventilation & Air Exhaust (EX) heating and cooling coils, HEPA general comfort of workers and to support ongoing 100. RLUOB may Pressure
Conditioning for exhaust- filters, ductwork, dampers, motors, activities. May remove air from laboratory research be using HVACE for Monitoring-DPM,
only systems, fans, and non-centralized simple processes, machinery operations, and personnel entry fac. Alarm-
CHVAC for instrumentation. occupancy. May reduce the concentration of HA, HVAC
RLW radioactive particulate and hazardous materials in Control Air-HCA,
contaminated occupied spaces and building exhaust. HV,
system Graphite
Collection, HEPA
Ventilation,
Recirculating
HVAC, Ventilation
HVAC -- CMRR HVAD CMRR NF Supply and exhaust fans, filters, Supplies filtered air and exhausts air to maintain CMRR NF HVAC
Aux Bldg only cooling and heating coils, room temperatures for diesel generator, electrical Subsystem: Aux
dampers, ductwork, louvers, equipment rooms, battery rooms, inverter rooms. Bldg HVAC SS-A,
motors, instrumentation Tempered supply air may also be provided based SS-B, Security, and
on design temperature requirements. Also, limits NS Electrical
hydrogen concentration in battery rooms and oil Equipment Room
fumes in diesel engine rooms by providing exhaust HVAC Systems
fans.
HVAC -- CMRR HVAF CMRR NF Intake and exhaust louvers, Provides an airflow path for diesel-driven fire-water CMRR NF HVAC
Aux Bldg Fire only ductwork, dampers pumps. Subsystem
Pump
HVAC - CMRR HVAL CMRR NF Supply and exhaust fans, filtration Provides tempered air to locker/changing rooms, CMRR NF HVAC
Aux Bldg Locker only units, cooling and heating coils, showers, toilet, and adjoining spaces for the Subsystem
Room dampers, ductwork, motors, and comfort of laboratory workers.
instrumentation.
HVAC -- CMRR HVAM CMRR NF Supply and exhaust fans, filtration Provides tempered air to mechanical equipment CMRR NF HVAC
Aux Bldg Mech only units, cooling and heating coils, rooms to meet equipment temperature and Subsystem
Room dampers, ductwork, motors, and ventilation requirements.
instrumentation.
HVAC -- CMRR HVAS CMRR NF Supply and exhaust fans, filtration Provides tempered air to meet temperature CMRR NF HVAC
Aux Bldg only units, cooling and heating coils, requirements in telecommunication and server Subsystem
Server/Telecom/ dampers, ductwork, motors, and rooms.
Elec Rm instrumentation.
11 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
HVAC -- CMRR HVAE CMRR NF Supply and exhaust fans, filtration Supplies and distributes tempered air within the CMRR NF HVAC
ECF only units, cooling and heating coils, ECF for the general comfort of security and office Subsystem: Entry
dampers, ductwork, motors, and workers. May also provide special make-up air Control Facility
instrumentation. filtration to protect security forces in the event that
chemical, biological, or radiological attack agents
are used.
HVAC -- CMRR HVZ1 CMRR NF Exhaust fans, HEPA filters, Maintains a negative pressure in primary CMRR NF HVAC
NF Zone 1 Exh only filtration units, dampers, ductwork, confinement enclosures by exhaust air. Filtration Subsystem
motors, and instrumentation reduces the concentration of potential radioactive
particulate release to the atmosphere.
HVAC -- CMRR HVZ2 CMRR NF Supply and exhaust fans, heating Same as current HVAC system except for CMRR NF HVAC
NF Zone 2 Supp only and cooling coils, HEPA filters, secondary confinement areas. Subsystem
and Exh filtration units, ductwork, dampers,
and instrumentation
HVAC -- CMRR HVZ3 CMRR NF Supply and exhaust fans, heating Same as current HVAC system except for tertiary CMRR NF HVAC
NF Zone 3 Bsmt, only and cooling coils, HEPA filters, confinement areas. Subsystem
Recirc., and PF-4 filtration units, ductwork, dampers,
Tnl and instrumentation
HVAC -- CMRR HVFO CMRR NF Supply and exhaust fans, heating Provides ventilation air to limit fume concentration CMRR NF HVAC
Fuel Oil Vault only coils, ductwork, dampers, filters, and temperature in fuel oil storage rooms and Subsystem
motors, and instrumentation. vaults.
HVAC -- CMRR HVAV CMRR NF Supply and return/exhaust fans, Provides tempered air to remove decay heat from CMRR NF HVAC
NF Vault only HEPA filters, filtration units, SNM vault areas. Filtration reduces the Subsystem
cooling and heating coils, concentration of potential radioactive particulate in
dampers, ductwork, motors, and occupied spaces and from atmospheric release.
instrumentation.
HVAC -- CMRR HVSM CMRR NF Supply/exhaust fans, dampers, Provides for the management/control of smoke by CMRR NF HVAC
HVAC Smoke only ductwork, motors, and providing pressure differentials to prevent smoke Subsystem
Management instrumentation migration into primary egress pathways such as
stairwells in the event of a fire.
HVAC, Office HVACOB RLUOB only Outside air intake filter plenums Provides conditioned air to meet the temperature,
Bldg and fans, Air handling units, humidity, airflow and exhaust demands of the office
cooling and heating coils and and operational control room areas during normal
control valves, ductwork, relief air operations
fans for pressure control and
exhaust air fans for restrooms etc
12 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
HVAC, HVACRL RLUOB only Zone 2 space outside air intake The once through, cascading pressure system
Radiological Lab filter plenums, fans, ductwork, has two functions: The Zone 2 segment provides
Phoenix valves, exhaust fans and conditioned air into the laboratory work spaces to
HEPA filter plenums. Zone 1 hood meet temperature, humidity; laboratory air
and glovebox exhaust ductwork, exchange flow rates, negative pressures and
exhaust fans, and HEPA filter HEPA filtered exhaust demands of the laboratory.
plenums The Zone 1 segment provides a HEPA filtered
exhaust path from the gloveboxes and hoods to
the exhaust stack
HVAC, Central HVACUB RLUOB only Air handling unit with fan and Single air handling unit configured in a
Utility Building cooling coils, ductwork and recirculating air arrangement using outside make-
dampers up air and an exterior exhaust for building pressure
control, designed to maintain an acceptable
environment for equipment and maintenance
activities
Heating Water HW Supply HWS Any Provides hot water to the Heating, Ventilation, and TA55; RLUOB may Central
Return -- Air Conditioning (HVAC) heating booster coils in call it Heated Water Circulating Hot
HWR the HVAC air supply distribution ducts (250 Water, Tempered
degrees maximum). RLUOB also uses Primary Water-REPWTR,
Heating Water (HW) Hot Heating
Water-HWH
Helium Gas HE Any Storage bottles, manifolds, Provides helium gas to laboratories and process Periodic table of the Inert gas
regulators, piping, valves equipment throughout the facility (HE not to be elements
confused with High Explosives).
High Explosives HEP Any Casting equip, presses, lathes and Provides forming and machining equipment for
Processing mills, scales high explosives processing.
Hoists and HC TA55 only
Cranes
HVAC HVACCF TA55 only
Confinement
Hydrochloric Acid HCL Any TA55
Hydrogen Gas H2 Any Storage bottles, manifolds, Provides hydrogen gas to laboratories and process Periodic table of the
regulators, piping, valves equipment. elements
Hydrogen H2O2 Any TA55
Peroxide Feed
13 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Industrial Safety IS Any Eyewashes, safety showers, Provides tempered water for diluting or cooling RLW. RLUOB
windsocks, maybe other chemical or thermal tissue contacts/burns, wind calling IS
components. direction indication, etc. Emergency
Eyewash & Shower.
TA55 calls it Ind
Safety System.
Irrigation IRG Any Piping, valves, sprinklers heads, Provides water for plants outside buildings.
timers
Laboratory Dry DV Any Dry vacuum pumps, filters, Provides a utility dry vacuum service for RLUOB, CMRR NF
Vacuum discharge silencers, laboratories for control and cleanup of
instrumentation contaminants inside enclosures.
Laboratory LRW RLUOB only Pumps, control valves, piping Distribute heated water throughout lab
Reheat Water
14 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Laboratory Wet WV Any Wet vacuum pumps, wet vacuum Provides a utility wet vacuum service for RLUOB, CMRR NF
Vacuum traps, seal water tanks, laboratories for control and cleanup of
instrumentation contaminants inside enclosures.
Lightning LP Any Air terminals, conductors, Aids in protecting personnel and equipment Widespread. Ref Building Lightning
Protection counterpoise, connectors, against excessive voltages caused by lightning NFPA 780. Protection Roof-
supports, grounding cable flashes; accomplishes this task by creating an BGL, Lightning
equipotential mass with as low an impedence to Protection-LP,
natural earth ground as possible. Lightning
Detection
15 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Long-Term Vault LVS CMRR NF Shielded storage cells for storage Stores SNM in a shielded criticality-safe
Storage only of containerized materials with configuration and allows for SNM container heat
optional liners, shield plugs, and removal.
cooling air ducts.
LLW Exterior RLWECS RLWTF only Low-level Exterior RLW collection Collects low-level radioactive waste solutions in
Collection system vaults and piping TAs 50, 48, 55, 03,
System
LLW Interior RLWICS RLWTF only LLW Interior Collection System, Collects RLW generated within the radiological
Collection Floor drains, sumps, sump pumps areas of the RLWTF
System
Make-up Water MKUP Powerhse Pumps, tanks, blower, indicators, Provides makeup water to powerhouse boilers ASME
only softeners, transmitters
Measuring & Test M&TE Any Flukes, multimeters, meggers, Provides a way for the CMMS to manage this
Equipment torque wrenches inventory.
Methane Gas CH4 Any
Miscellaneous MVP TA55 only
Vacuum Pumps
Mixed Gas GASMIX TA55 only
System
Mobile MBLEQ Any Heavy equipment, forklifts, Provides mobile personnel and material handling TA55.
Equipment manlifts, carts, hand trucks, functions not served by Cranes Hoists & Rigging,
trailers, robots, other specialized or for fixed handling, Elevators and Lifts.
vehicles. Use TOOLS for smaller
items and those generally not on
wheels.
16 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Natural Gas NG NG1-5 Any Piping, pressure Distributes natural gas (NG1-5, Utilities), becomes TA55 calls it Utility Natural Gas Utility
(distribution) regulators/stations; block, relief, NG just outside and within facilities for heating and Natural Gas Distribution, Site
High Pr and control valves; rectifiers, process equipment such as furnaces. High Pr > 5 (Building Supply) Natural Gas
NG Med meters, gauges, analyzers. NG1 psig; Low Pr < 14 W.C.
Pr NGM (TAs 3, 60), NG2 (TAs 6, 8, 9, 11,
Low Pr - 14-16, 22, 40), NG3 (TAs 33, 39),
NGL NG4 (TAs 2, 41, 53), NG5 (TAs
18, 21, 35, 36, 46, 48, 50-52, 54,
55, 59, 63, 64, 66)
Natural Gas NGC Powerhse Scrubbers (2), compressor, Produces high pressure natural gas for CGTG
Compression coalescing filter, receiver tank, fin-
fan cooler, piping, valves, motors
and switchgear, PLC, combustible
gas analyzer, instrumentation
Nitric Acid HNO3 Any Supply tanks, piping, valves, Stores and supplies nitric acid
pumps
Nitric Acid - HNO3P TA55 only Pencil tanks, piping, valves, and Transfer Pu-bearing nitric solutions between
Process flanges aqueous processes in gloveboxes, and store in
Solutions pencil tanks.
Nitric Acid CSTBS TA55 only
Storage Tank
and Berm
Nitrogen N2 TA55 only: Any Storage bottles, piping, manifolds, Provides gaseous nitrogen at various pressures for Periodic table of the
N2100, N235, valves use in process systems and laboratory use. elements
N2H2 Sometimes fed by LN.
Non-Potable NPW Cold NPWC Any Pumps, piping, valves, Provides non-potable water throughout the facility TA55, RLUOB. Industrial Water-
Water Hot instrumentation, fire hydrants for various equipment and system use. From ASHRAE 134. IW, Non-potable
NPWH Water-NW, Non-
Hot Recirc Potable Cold
NPWHR Water-NPCW,
Make-up Non-Potable Hot
--NPWMU Water-NPHW
Nuclear NESII Any Soil. Coupled with other controls An inactive waste handling or disposal area Area G
Environmental (depth, horizontal translation, characterized as nuclear site based on the rad
Site Inventory boundary/fence, postings, etc.), material inventory exceeding haz category 2/3
Isolation the NES inventory isolation thresholds per DOE-STD-1027. They are usually
system is the passive soil on top but not always material disposal areas (MDAs).
of the inventory (waste material
encapsulated in capped
containers) that separates the
inventory from the air above.
17 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Nuclear NI DAF only Log-N, linear channel, startup Monitors the neutron leakage that is generated in NCERC
Instrumentation counter, and area monitoring the critical configuration.
subsystems
Nuclear NMCA Any Counters, shufflers, detectors, Provides nuclear material measurement and/or Safeguards,
Materials Control mass spectrometers, instruments, detection functions. MC&A
and CPUs, alarms
Accountability
Oxygen OMS Any Sensors, cable, control panel, Monitors the oxygen content of the inert WETF
Monitoring annunciators gloveboxes to detect inleakage.
System
P-10 Gas P10 Any Regulators, valves, piping Provides P-10 gas (10% methane, balance argon) In CMRR NF, a
[argon/10% to contamination counting machines. subsystem in the
methane] virtual (used for
SDDs only)
Specialty Gas
(SGS) system.
Personnel PCD Any Handheld and fixed monitors and Protects and notifies workers of radiological
Contamination related instrumentation contamination acquired in Radiological Controlled
Detectors Areas.
Personnel PMON TA55 only
Monitoring
18 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Personnel Safety PSS Any Door lock solenoids, micro- Protect workers from radiation and explosive DARHT
System processor controls hazards by computer-controlled interlocks on
access doors and initiating accelerator beam drop
upon opening of access doors; also trips
Beamstop. Functionally, a combination of a
LANSCE-like radiation safety system (RSS) and a
high explosive safety system (HESS).
Planet PLANET DAF only Support stand, two stacked A general purpose critical assembly machine used NCERC
hydraulic rams, and a stepper to move nuclear materials into a critical
motor drive. configuration.
Portable HEPA HEPVAC Any Portable HEPA vacuums Cleaning in contamination areas TA55
Vacuums
Positive Pressure PPCCW Any TA55
Circulating
Chilled Water
Potable Water PW PWD1-12 Any Piping, backflow preventors, non- Provides potable water to and the fixtures for TA55 Domestic water,
Distribution safety showers, valves, regulators, drinking fountains, bathroom sinks and showers, Potable Water-
(Utilities) tanks, lavatories, and drinking and emergency eye wash and safety showers, and PO, Potable Cold
Cold PWC fountains. PWH includes water decontamination showers. The system includes Water-POC,
Hot heaters and downstream piping; the transmission lines and two distribution Water Utilities
PWH PWHR includes circulating pumps. subsystems supplying water to LANL facilities. Distribution
Hot Recirc - PWD includes hydrants.
PWHR
19 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Process Air PCA Any See Compressed Air Compressed air for processes. TA55
Supply
Process Cooling PCW Supply-PCWS Any Piping, valves, heat exchangers, May be a closed loop or a once-through cooling Circulating
Water Return pumps, instrumentation system. It is the primary cooling loop in contact Cooling Water-
PCWR with process equipment, removing heat to an CCW, Process
intermediate cooling system or to the environment Water-PW,
as a once through system. Not a redundant term Process Cooling
to Chilled Water. Water-PW
Process Liquid PLW Hazardous Any Piping, drain fixtures, pumps, Collects and removes chemical and inorganic TA55, Industrial Liquid
Waste PLWH valves, storage tanks, waste solutions. Waste ILW, IWS,
Non-Haz instrumentation Collection-CO,
PLWNH Manholes-MH
Public Address PA Any Cable, speakers, headsets, Sounds an audible emergency evacuation alarm ASME, NCS/UDS. Public Address
paging stations, batteries, during all accidents involving potential nuclear TA55, also see LPS, and Intercom-PAI,
microphone preamplifier, line criticality events, and broadcasts emergency SPAS
driver, zone key card, alarm announcements for zone evacuation. Normal Life Safety-SA
generator, power amplifier, control operation may include site announcements and
panel, microphones, power supply system testing notifications.
Quartz QE Any Compressed fuel gas and oxygen, Fuses quartz around a sample.
Encapsulation torch
Radiation RM Any Continuous air monitors, fixed air Provides real time monitoring of work spaces for CEF, TA55 Radiation
Monitoring samplers, vacuum pumps, piping, airborne alpha particle-emitting radioactive Monitoring-RD,
instrumentation contamination and/or real-time monitoring of area, Air Sampling-AS,
equipment, and personnel for direct external beta, Air Sample
gamma, or neutron radiation exposure. Vacuum, Fixed
Head Air
Sampling,
Continuous Air
Monitoring-CAM,
Tritium
Monitoring-T2
20 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Radioactive and RADW Any Trash compactors and other Provides for the accumulation, containment, TA-55, CMRR NF
Mixed Solid handling equipment. For CMRR staging, treatment, packaging, and shipment of
Waste NF, also NDA and Mat'l Mgmt Lab low-level waste (LLW), transuranic (TRU) waste,
Module equip. mixed waste, and TRU-mixed waste.
Radioactive RLWBLP RLWTF only Building and non-process systems Houses and supports RLWTF
Liquid Waste
Balance of Plant
Radioactive RLWCS VAULT Any Piping, drain fixtures, valves, Collects low-level radioactive waste solutions in Acid Drains-
Liquid Waste Vent -- RLWV instrumentation, vaults, SCADA TAs 50, 48, 55, 03, 21, 53, 59, and 00. ACID, Collection-
Collection CO, Manholes-
System MH, RLW
Radioactive RLWLLW SUBSYSTEM RLWTF only Sumps, tanks, piping, Provides the interim storage, treatment of the low- SUBSYST,
Liquid Waste S, CON'T: instrumentation, valves, control level radioactive liquid waste streams from several CON'T: RVF-
Low Level Waste INF-Influent panels, clarifiers, process vent LANL facilities, discharge of the cleaned water, and Rotary Vacuum
SUBSYSTEMS: Storage; IX: filters, process filters, ion disposal of the final solidified wastes in the Filter; RPF-RP
CUF: Centrifugal Ion Exchange, exchange equipment, reverse Radioactive Liquid Waste Treatment Facility Filter; RVF-Rotary
Ultra Filter; CL: LLWSTO-Low osmosis units, sampling systems, Vacuum Filter;
Clarifiers; CIP: Level Storage; pumps, membrane separators, SRO-Secondary
Clean-in-place; MF-Media evaporators RO; SWL-Seal
EDR: Electro Filters; RO- Water; TUF-
Dialysis Reverse Tubular Ultra
Reversal; Osmosis, PIX- Filter; WEVP-
EFFEVP: Effluent Perchlorate Waste
Evaporation; Ion Exchange; Evaporation;
GRVF: Gravity POL-Polish WM2-WM 2
Filter and Sample Influent - Effluent
Effluent; RO- Dist; WMRM-
Reverse Waste Mitigation
Osmosis; Risk Mgmt; ZLD -
Zero Liquid
Discharge
Radioactive RLWTRU RLWTF only Piping, tanks, pumps, filters, Collects, stores, and treats liquids and sludge
Liquid Waste valves containing transuranic waste
Transuranic
RLBCS RLUOB only See RLW, RLBECS systems Opsys for RLUOB low-level radioactive
RLUOB
radioactive liquid
waste collection
system
21 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
RLUOB RLBECS RLUOB only Piping, new vault on Pecos Drive, Forced transfer RLW from tanks/pumps inside to
radioactive liquid and connections made in an exterior, then via gravity to RLWCS (LANL site
waste exterior existing WM-70 vault collection system).
collection system
RLW RLUOB only Two tanks, four lift station pumps, Collect and store RLW inside RLUOB
gravity drain lines
RLUOB
radioactive liquid
waste interior
collection system
Radiological RADMON TA55 only
Monitoring
Radio RC Any Amplifiers, antennas, coax, Relay RF comm. within building (hand held 2 way RLUOB
Communications multiplexers radios, cell phones)
Real Time RTR Any X-ray tube assembly, imaging Provides nondestructive, nuclear waste inspection, CMRR NF
Radiography system, enclosure for radiation enabling characterization of containerized waste.
protection, waste container
handling system, audio/video
recording system and an operator
control panel and data acquisition
station.
Red Network REDNET Any Cable, raceway, switchboards, Provides for transmission of classified computer- Classified Info
panels, relays based information over copper cable and fiber Network. CDIN.
optic lines within the facility and between the
facility and TA-3-1498, the central electronic
switching point for LANL telecommunications and
networking.
Refrigeration RFN Hot Discg Any Chillers, piping, valves, heat Provides mechanical cooling for HVAC or chilled
RFND exchangers, evaporative heat water systems. Its components can also be
Liquid RFNL exchangers, pumps, bounded within those systems as an alternative to
Pr Relief instrumentation use of this system.
RFNR
Suction
RFNS
22 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Roads and RG Any Roads, parking lots, driveways, Provides vehicle and pedestrian surfaces and
Grounds traffic control devices, grounds, controls, erosion control, and aesthetic functions.
guardrails, barriers
Sanitary Sewer SS Main lines: Any Piping, manholes, lift stations, Outside buildings, collects and delivers the Owned by Utilities. Site Sanitary
SS1-13 pumps, oil separators, tanks, sanitary sewer effluent to the wastewater treatment NCS/UDS Sewer Collection
valves, gauges. plant at TA-46. After treatment by Efluent System Wastewater
(& SERF) at TA-46 it is considered treated effluent.
Sanitary Waste SW Treated Any Piping, sinks, floor drain fixtures, Sanitary plumbing inside building that discharges Sanitary Waste-
Effluent sump pumps into the Sanitary Sewer system. SW, Sanitary
SWTE Waste-SAN,
Vent -- SWV Waste Water-
WSTWTR
Building Drain BD
SCRAM SCRAM SCRAM DAF only Buttons, interlocks, horns, Provides an automatic shutdown of the critical NCERC
Safety System beacons. assemblies due to a trip of the Nuclear
(SSS), Instruments, an operator pushing a manual
Operational SCRAM button, or a door being opened during
Interlock remote operation. Also provides warning horns
System (OIS) and beacons that indicate a critical assembly
operation is underway.
Secondary SCW RLUOB only Pumps, control valves, piping Distribute chilled water throughout building for
Chilled Water HVAC
Secondary SHW RLUOB only Pumps, control valves, piping Distribute heated water throughout building for
Heating Water HVAC
Security SEC PIDAS, ACSD, Any Guard stations, fences, locking Protect special nuclear material (SNM) from theft TA55, Security-SE,
ECF, ARGUS. devices, radio communications, or diversion and to protect material and facilities Intrusion Alarm-
See also microwave detection systems, from sabotage, provide protection of and deny IA, Personnel
ACS, IDAS metal detectors, tamper indicating access to classified material. Access Security
switches, security lighting System-PASS,
Security &
Alarms-SEC,
BRASS, ARGUS
Shielding SHLD Any Concrete, steel, high density Protect workers from radiological hazards DARHT. ASME
concrete, doors
Sodium Citrate NACIT Any
Feed
23 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Shelves, Storage STRGC TA-55 only. Credited shelves, storage racks, Stores SNM, prevents criticality including during a
Racks and Others use cages, Kardex seismic event.
Cages STOR
Short-Term Vault SVS Any Storage compartments, shelving, Stores the volume of working inventory of nuclear CMRR NF
Storage shielding, and material handling materials.
systems such as hand trucks, and
dollies.
Stack Radiation SRM Any Sample probes, detectors, record Monitors exhaust stack emissions for radioactivity Can use AS for Air
Monitoring sampler, vacuum pumps, piping, both on a real-time basis, including alarms, and by Sampling. RLUOB
valves, instrumentation collecting samples for periodic analysis. calling SRM Stack
Monitoring. CMRR
NF using SRM
since more specific
and descriptive.
Steam STM STMH Any Piping, valves, pressure vessels, Provides steam to various systems and processes. NCS/UDS. TA55 Steam Supply
(heating heaters (radiators), steam traps, High Pressure is > 15 psig. calls it Steam Steam
steam) Hi instrumentation System. Distribution
Pr STMHP
Lo Pr --
STMLP
24 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Supervisory SCADA Any PLC, microprocessor, remote Provides remote equipment monitoring and on/off TA55 call this Equipment
Control and Data terminal units, CRT, control functions. It may also provide off-site SCADA Reporting Surveillance-ES,
Acquisition instrumentation cable, equipment notification to facility operations personnel for Equipment
sensors, computerized phone abnormal equipment and system conditions. It is Surveillance
dialer usually associated with multiple facilities. System-ESS,
MIZER, alarm
monitoring
Telecommunicati TEL Any Cable, raceway, switchboards, Provides for transmission of telephonic information See REDNET for Telephone & Data
ons panels, relays and non-classified computer-based information classified telecom. Communications-
over copper cable and fiber optic lines within the TA55 also uses COM
facility and to TA-3-1498, the central electronic TELS as an Opsys.
switching point for LANL telecommunications and
networking. The OpenNet.
Tepid Water PWT Any Safety showers, eye wash Supply 85F water to safety showers and eye wash RLUOB
stations, recirculation pump and stations
HX
Tools TOOLS Any Powered and hand tools and light Enable or improve a person's ability to perform
equipment for indoor and outdoor manual tasks.
use, includes small earthmoving
and tamping, landscaping; small
pumps, welders, and generators;
M&TE such as multimeters
(Flukes), torque wrenches,
Metrotechs
Tower Water TW Supply TWS Any Pumps, piping, valves, fans, Removes heat from condensers and rejects it to TA55 Cooling Water-CT
Return cooling tower, basin, structure, the atmosphere by evaporative cooling via a
TWR Drain - instrumentation cooling tower.
TWD
Transuranic TRU TCS - TRU RLWTF only Sumps, tanks, piping, Provides the collection, interim storage, and SUBSYSTEMS,
Liquid Waste Collection instrumentation, valves, control treatment of the transuranic-containing caustic and CON'T: TLT -
System, TINF panels, drum tumbler, process acid waste streams from TA-55 in the Radioactive TRU Liquid
- TRU Influent vent filters, pressure filters, Liquid Waste Treatment Facility. Treatment, TST -
Storage sampling systems TRU Sludge
Treatment
25 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Tritium TCV WETF only Primary and secondary vessels, Storage and transport of tritium at the Weapons
containment getter, molecular sieve. Engineering Tritium Facility (WETF). Becomes
vessels [Elemental tritium is stored as gas part of the TGHS when it is connected to the TGHS
or on a getter material within a and the valve on the vessel is opened. A
primary containment vessel (which secondary containment vessel becomes an
may or may not be enclosed in a integral part of the TGCS secondary containment
secondary containment vessel) or when connected to the TGCS (glovebox).
as tritiated water adsorbed on
molecular sieve within a primary
containment vessel.]
Tritium Gas TGCS WETF only Gloveboxes, antechambers, Secondary confinement for tritium-containing
Containment associated piping, load-in/load-out process equipment at WETF facility.
ports, gloves, pumps, and external
secondary containment piping
[e.g., mass spectrometer sample
loop and Function Tester (FT) gas-
transfer secondary containment
lines)
Tritium Gas TGHS HIS - Hot-Inlet WETF only Pressure piping, transfer pumps, Primary tritium containment system for most of the
Handling System MGS pressure vessels, and other operations at the WETF. Designed to process
- Mixed Gas equipment. hydrogen isotopes (protium, deuterium, and
Station (He, tritium) and helium-3 (tritium decay product). HIS
D2) is sample intro for mass spec.
Tritium TMS Any Room, stack, glovebox, process, Measure various tritium concentrations and WETF, TA-55
Monitoring and portable monitors; pumps, provide appropriate instrumentation and control
System filters, flow controllers (PCV) signals (local and remote)
Tritium Waste TWTS WETF only LPR tank; gas-transfer pumps; Collects gas streams from various systems that
Treatment vacuum pump; catalytic reactors handle tritium at the WETF and recovers the
and associated controllers; tritium.
oxygen injectors to the CRs; heat
exchangers; MSDs and
associated controllers; AL-M1
containers ; various valves, filters,
piping, rupture disks, and
instrumentation; oxygen flow
monitor
26 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
Turbine TG TG1-3 Powerhse Steam or gas driven turbine, A steam- or gas-turbine-driven generator that IEEE 803.1 Turbine
Generator generator, meters, steam traps, provides an auxiliary source of 480 Volt electrical Generator
valves, piping, indicators, pumps, power for the Electrical Power System; typically
fans, filters starts only upon loss of normal power.
Uninterruptible UPS Any Various combinations of Used to supply an uninterrupted source of power TA55, WETF. Also Emergency,
Power Supply rectifier/charger, battery transfer to important instrumentation and control systems see Stationary standby, backup
and bypass switches, and an for loss-of-normal-power conditions. They also Battery System. power BP
inverter. (Ref DOE-STD-3003, provide continuous, quality power for systems ASME, NCS/UDS,
Backup Power Sources for DOE sensitive to disturbances occurring in an electrical IEEE 1100, NECA
Facilities). power distribution system caused by switching, 100
faults, or power transfer. UPSs solely dedicated to
supporting another system or subsystem (e.g.,
Emergency Lighting) shall be part of that system.
Vacuum VAC Vacuum Pump Any Vacuum pumps, piping valves, Provides utility vac service for programmatic See also Laboratory Vacuum-VA,
Discharge - instrumentation processes and activities; may provide vac for Dry Vac, Wet Vac. Laboratory Vac,
VACPD Radiation Monitoring System. From ASME, TA55, RLUOB. Dry Vac, Vac
ASHRAE 134, NCS/UDS. Cleaning-VC
Vault Type Room VTR Any Structural assemblies, detection, Provides barriers to entry and/or access to includes so-called
alarms classified materials or information Super VTRs
Ventilation VNT TA55 only
Ventilation, Non- NNHVAC TA55 only
Nuclear
Ventilation, PF-4 HVAC TA55 only
Waste WASTE Any Trash compactors, other handling Provides for the accumulation, containment,
Management equipment. staging, treatment, packaging, and shipment of
solid non-rad and rad waste -- low-level waste
(LLW), transuranic (TRU) waste, mixed waste,
and/or TRU-mixed.
Water Systems WS TA55 only Opsys that includes storm water sys, etc.
Wet Vacuum WETVAC TA55 only
Xenon Gas XE Any
27 of 28 Rev: 3/29/2013
LANL Engineering Standards Manual STD-342-100 Chapter 1, Section 210 Attachment 1, System List
1219W, 295W, 297W, 3013W, 400FRN, 40MM, 40MMTK, ACHAR, ACHEM, ACTCER, ALNO3, ALNO3M, AO, APS, AQCL, AQN, ARIES, ASPEC, ASR, ATDIS, ATLIX, AUGER, BLML,
BOSTO, BRAR, BRUSH, CAL, CALAT, CALC, CALCDO, CALCL, CALDOR, CALOR, CAMS, CARTS, CASDIS, CAST, CENTOR, CF, CGAS, CL2, CLDEL, CLDET, CLEAR, CLF3, CM1750,
CMMC, CMMH, CMUR, CNTRC, COAL, CONCAN, CONF, CONT, CPV, CRIMP, CRUC, CRUCC, CRUCNC, CRUSH, DCARC, DISS, DISSCL, DMO2, DMO3, DOR, DRYOPS, DTO,
DYEPEN, EBEAM, ECM, EDDIS, EDDY, EDGBRK, EHS, ELDE, ELTEST, ENCLBE, EPMA, ER, EV, EVB, FDENSE, FEXT, FGPREP, FMASS, FMLATH, FND, FRBAR, FRNOPS, FRS,
FSTF, FSTFH2, FSTFRC, GASS, GBA, GC, GPE, GPHSW, GRAN, GSPEC, GTE, GTF, HAAS, HELKCK, HERE, HEUOPS, HF, HGAS, HIP, HSACHE, HSCAN, HSCHAR, HSFF, HSFURN,
HSUT, HYDCL, HYDFLO, HYDHY, HYDPRE, HYTEC, IAS, ICPAES, IFIT, IFITAT, IFITRD, INCAN, INERT, INSP, IPGW, IRNDA, IRO, IS, ISO, IX, IXPRV, KOHM, KRX, LAR, LAZSMP, LCS,
LEAKS, LIBS, LSPEC, LSRWLD, LVEBW, MACH, MC, MCL, MCPP, MDMU, MDRILL, MET, METWG, MHARD1, MHARD2, MHARD3, MIS, MISHR, MISS, MISSC, MOXW, MSAXIS,
MTCHAR, NACITM, NAOHM, NARS, NBC, NDA, NDAPDC, NDE, NDMOS, NER, NNMACH, NPCCW, NSC, OSRP, OSSR, OSSRS, OUTCAN, OXCL, OXPRE, PANI, PARSA, PELFAB,
PELPR, PIGMA, PITD, PMO, PMODO, PPMS, PROFO, PRTPRS, PRTSAN, PSAA, PSAACW, PSF, PSPROD, PSSHIP, PSTEST, PTEST, PV, PWDPRP, PYRO, PYROLS, QED, R5,
RADSCB, RADSOB, RADSU, RBLATH, RDGRPH, RESIN, RESINM, RFXCAL, RFXIX, RFXOXP, RIPS, RM, ROLMIL, SAFES, SAI, SALTS, SBPREP, SCNTR, SEM, SEMOIM, SF2I, SGS,
SH2, SHADOW, SHEFF, SMNT, SMPFAB, SNAP, SRL, SUBLT, SX, TAYLOR, TBASE1, TBASE2, TFCCFT, TGSC, TGSD, TNC, TOFMS, TSCM, TYPEB, UCAL, UEE, UFPF, ULTRAC,
UOPS, UOX, UT, UVVIS, VBM, VCCW, VWBC, VWBCS, VWBL, WCAS, WELD, WGCHAR, WND, XPS, XRD, YBLAZR
28 of 28 Rev: 3/29/2013