Você está na página 1de 76

Installation

Marine Generator Sets

Models:
9--32EOZD/7--28EFOZD

TP-6711 7/09
2 TP-6711 7/09
Table of Contents

Safety Precautions and Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5


Section 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Section 2 Location and Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.1 General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.2 Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.3 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Section 3 Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1 Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2 Cooling System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2.1 Intake Through-Hull Strainer (Seacock Cover) . . . . . . . . . . . . . . . . . . . . . 13
3.2.2 Seacock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2.3 Seawater Strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2.4 Water Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.2.5 Closed Heat Exchanger (9--32EOZD/7--28EFOZD Models) . . . . . . . . . . 15
Section 4 Exhaust System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.1 Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.2 Exhaust Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4.3 Exhaust System Location, Mounting, and Installation . . . . . . . . . . . . . . . . . . . . . . . 18
4.3.1 Above-Waterline Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.3.2 Mid/Below-Waterline Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Section 5 Fuel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.1 Fuel Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.2 Fuel Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.3 Fuel Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.4 Fuel/Water Separator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.5 Fuel Pump Lift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.6 Fuel Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Section 6 Electrical System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.1 AC Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
6.2 Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6.2.1 Circuit Breaker Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
6.2.2 Circuit Breaker Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.3 Installation In Steel or Aluminum Vessels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
6.4 Installation Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
6.5 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.6 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
6.7 Remote Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Section 7 Installation Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Section 8 Reconnection/Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
8.1 Four-Lead Reconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
8.1.1 100--120-Volt Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
8.1.2 100--120/200--240-Volt Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
8.1.3 200--240-Volt Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
8.2 Twelve-Lead Reconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
8.3 ADC 2100 Adjustment after Reconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
8.3.1 Configuration Mode Time Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
8.3.2 Controller Software Version Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
8.3.3 Setting the System Voltage and Frequency . . . . . . . . . . . . . . . . . . . . . . . 58
8.3.4 Adjusting the Voltage, Gain, and Volts/Hz, and Engine Speed . . . . . . . 64
8.3.5 Voltage Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
8.3.6 Frequency Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

TP-6711 7/09 Table of Contents 3


Appendix A Generator Selection and Wattage Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
Appendix B Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Appendix C Generator Set Output Ratings Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

4 Table of Contents TP-6711 7/09


Safety Precautions and Instructions

IMPORTANT SAFETY INSTRUCTIONS. Accidental Starting Engine Backfire/Flash


Electromechanical equipment,
including generator sets, transfer Fire
switches, switchgear, and accessories, WARNING
can cause bodily harm and pose WARNING
life-threatening danger when
improperly installed, operated, or
maintained. To prevent accidents be
aware of potential dangers and act
safely. Read and follow all safety
precautions and instructions. SAVE Accidental starting. Fire.
THESE INSTRUCTIONS. Can cause severe injury or death. Can cause severe injury or death.
Disconnect the battery cables before Do not smoke or permit flames or
This manual has several types of safety working on the generator set.
precautions and instructions: Danger, sparks near fuels or the fuel system.
Remove the negative (--) lead first
Warning, Caution, and Notice. when disconnecting the battery.
Reconnect the negative (--) lead last Servicing the fuel system. A flash
when reconnecting the battery. fire can cause severe injury or death.
DANGER Do not smoke or permit flames or
sparks near the fuel injection system,
Disabling the generator set. fuel line, fuel filter, fuel pump, or other
Danger indicates the presence of a
Accidental starting can cause potential sources of spilled fuels or fuel
hazard that will cause severe
severe injury or death. Before vapors. Catch fuels in an approved
personal injury, death, or substantial
working on the generator set or container when removing the fuel line
property damage.
connected equipment, disable the or fuel system.
generator set as follows: (1) Move the
generator set master switch to the OFF Servicing the air cleaner. A sudden
WARNING backfire can cause severe injury or
position. (2) Disconnect the power to
the battery charger. (3) Remove the death. Do not operate the generator
Warning indicates the presence of a battery cables, negative (--) lead first. set with the air cleaner/silencer
hazard that can cause severe Reconnect the negative (--) lead last removed.
personal injury, death, or substantial when reconnecting the battery. Follow
property damage. Combustible materials. A sudden
these precautions to prevent starting of flash fire can cause severe injury or
the generator set by an automatic death. Do not smoke or permit flames
transfer switch, remote start/stop or sparks near the generator set. Keep
CAUTION switch, or engine start command from a the compartment and the generator set
remote computer. clean and free of debris to minimize the
Caution indicates the presence of a risk of fire. Catch fuels in an approved
hazard that will or can cause minor Disabling the generator set.
Accidental starting can cause container. Wipe up spilled fuels and
personal injury or property damage. engine oil.
severe injury or death. Before
NOTICE working on the generator set or Combustible materials. A fire can
equipment connected to the set, cause severe injury or death.
Notice communicates installation, disable the generator set as follows:
operation, or maintenance information Generator set engine fuels and fuel
(1) Press the generator set on/off vapors are flammable and explosive.
that is safety related but not hazard button to shut down the generator set.
related. Handle these materials carefully to
All indicator lamps dim. (2) Disconnect minimize the risk of fire or explosion.
the power to the battery charger, if Equip the compartment or nearby area
Safety decals affixed to the equipment
equipped. (3) Remove the battery with a fully charged fire extinguisher.
in prominent places alert the operator
cables, negative (--) lead first. Select a fire extinguisher rated ABC or
or service technician to potential
Reconnect the negative (--) lead last BC for electrical fires or as
hazards and explain how to act safely.
when reconnecting the battery. Follow recommended by the local fire code or
The decals are shown throughout this
these precautions to prevent the an authorized agency. Train all
publication to improve operator
starting of the generator set by the personnel on fire extinguisher
recognition. Replace missing or
remote start/stop switch. operation and fire prevention
damaged decals.
procedures.

TP-6711 7/09 Safety Precautions and Instructions 5


Exhaust System Fuel System Hazardous Noise
WARNING WARNING CAUTION

Carbon monoxide.
Can cause severe nausea, Explosive fuel vapors. Hazardous noise.
fainting, or death. Can cause severe injury or death. Can cause hearing loss.

The exhaust system must be Use extreme care when handling, Never operate the generator set
leakproof and routinely inspected. storing, and using fuels. without a muffler or with a faulty
exhaust system.
Carbon monoxide symptoms. The fuel system. Explosive fuel
Carbon monoxide can cause severe vapors can cause severe injury or
nausea, fainting, or death. Carbon death. Vaporized fuels are highly Hazardous Voltage/
monoxide is a poisonous gas present in explosive. Use extreme care when
exhaust gases. Carbon monoxide is an handling and storing fuels. Store fuels
Moving Parts
odorless, colorless, tasteless, in a well-ventilated area away from
nonirritating gas that can cause death if spark-producing equipment and out of WARNING
inhaled for even a short time. Carbon the reach of children. Never add fuel to
monoxide poisoning symptoms include the tank while the engine is running
but are not limited to the following: because spilled fuel may ignite on
D Light-headedness, dizziness contact with hot parts or from sparks.
D Physical fatigue, weakness in Do not smoke or permit flames or
joints and muscles sparks to occur near sources of spilled Hazardous voltage. Moving parts.
D Sleepiness, mental fatigue, fuel or fuel vapors. Keep the fuel lines Can cause severe injury or death.
inability to concentrate and connections tight and in good
or speak clearly, blurred vision condition. Do not replace flexible fuel Operate the generator set only when
D Stomachache, vomiting, nausea lines with rigid lines. Use flexible all guards and electrical enclosures
If experiencing any of these symptoms sections to avoid fuel line breakage are in place.
and carbon monoxide poisoning is caused by vibration. Do not operate the
possible, seek fresh air immediately generator set in the presence of fuel Servicing the generator set when it
and remain active. Do not sit, lie down, leaks, fuel accumulation, or sparks. is operating. Exposed moving parts
or fall asleep. Alert others to the Repair fuel systems before resuming can cause severe injury or death.
possibility of carbon monoxide generator set operation. Keep hands, feet, hair, clothing, and
poisoning. Seek medical attention if test leads away from the belts and
the condition of affected persons does Draining the fuel system. Explosive pulleys when the generator set is
not improve within minutes of breathing fuel vapors can cause severe injury running. Replace guards, screens, and
fresh air. or death. Spilled fuel can cause an covers before operating the generator
explosion. Use a container to catch fuel set.
Inspecting the exhaust system. when draining the fuel system. Wipe up
Carbon monoxide can cause severe spilled fuel after draining the system. Grounding electrical equipment.
nausea, fainting, or death. For the Hazardous voltage can cause
safety of the crafts occupants, install a severe injury or death. Electrocution
carbon monoxide detector. Never is possible whenever electricity is
operate the generator set without a present. Ensure you comply with all
functioning carbon monoxide detector. applicable codes and standards.
Inspect the detector before each Electrically ground the generator set,
generator set use. transfer switch, and related equipment
and electrical circuits. Turn off the main
Operating the generator set. Carbon
circuit breakers of all power sources
monoxide can cause severe nausea,
before servicing the equipment. Never
fainting, or death. Be especially
contact electrical leads or appliances
careful if operating the generator set
when standing in water or on wet
when moored or anchored under calm
ground because these conditions
conditions because gases may
increase the risk of electrocution.
accumulate. If operating the generator
set dockside, moor the craft so that the
exhaust discharges on the lee side (the
side sheltered from the wind). Always
be aware of others, making sure your
exhaust is directed away from other
boats and buildings.
6 Safety Precautions and Instructions TP-6711 7/09
Disconnecting the electrical load. Testing live electrical circuits. NOTICE
Hazardous voltage can cause Hazardous voltage or current can Fuse replacement. Replace fuses
severe injury or death. Disconnect cause severe injury or death. Have with fuses of the same ampere rating
the generator set from the load by trained and qualified personnel take and type (for example: 3AB or 314,
turning off the line circuit breaker or by diagnostic measurements of live ceramic). Do not substitute clear
disconnecting the generator set output circuits. Use adequately rated test glass-type fuses for ceramic fuses.
leads from the transfer switch and equipment with electrically insulated Refer to the wiring diagram when the
heavily taping the ends of the leads. probes and follow the instructions of the ampere rating is unknown or
High voltage transferred to the load test equipment manufacturer when questionable.
during testing may cause personal performing voltage tests. Observe the
injury and equipment damage. Do not following precautions when performing NOTICE
use the safeguard circuit breaker in voltage tests: (1) Remove all jewelry.
Saltwater damage. Saltwater quickly
place of the line circuit breaker. The (2) Stand on a dry, approved electrically
deteriorates metals. Wipe up saltwater
safeguard circuit breaker does not insulated mat. (3) Do not touch the
on and around the generator set and
disconnect the generator set from the enclosure or components inside the
remove salt deposits from metal
load. enclosure. (4) Be prepared for the
surfaces.
system to operate automatically.
Short circuits. Hazardous (600 volts and under)
voltage/current can cause severe
injury or death. Short circuits can
cause bodily injury and/or equipment
damage. Do not contact electrical
Hot Parts
connections with tools or jewelry while
making adjustments or repairs. WARNING
Remove all jewelry before servicing the
equipment.
Testing the voltage regulator.
Hazardous voltage can cause
severe injury or death. High voltage Hot coolant and steam.
is present at the voltage regulator heat Can cause severe injury or death.
sink. To prevent electrical shock do not
touch the voltage regulator heat sink Before removing the pressure cap,
when testing the voltage regulator. stop the generator set and allow it to
(PowerBoostt, PowerBoostt III, and cool. Then loosen the pressure cap
PowerBoostt V voltage regulator to relieve pressure.
models only)
Electrical backfeed to the utility.
Hazardous backfeed voltage can Notice
cause severe injury or death.
Connect the generator set to the
building/marina electrical system only NOTICE
through an approved device and after
the building/marina main switch is This generator set has been
turned off. Backfeed connections can rewired from its nameplate voltage
cause severe injury or death to utility to
personnel working on power lines
and/or personnel near the work area.
Some states and localities prohibit
unauthorized connection to the utility
246242
electrical system. Install a
ship-to-shore transfer switch to prevent
interconnection of the generator set NOTICE
power and shore power.
Voltage reconnection. Affix a notice
to the generator set after reconnecting
the set to a voltage different from the
voltage on the nameplate. Order
voltage reconnection decal 246242
from an authorized service
distributor/dealer.

TP-6711 7/09 Safety Precautions and Instructions 7


Notes

8 Safety Precautions and Instructions TP-6711 7/09


Section 1 Introduction

Information in this publication represents data available marine generator set. For operating instructions, refer
at the time of print. Kohler Co. reserves the right to to the operation manual.
change this publication and the products represented
without notice and without any obligation or liability Marine generator set installations must comply with all
whatsoever. applicable regulations and standards.
x:in:001:002:a
Use the specification sheets as a guide in planning your
The safe and successful operation of a marine power installation. Use current dimension drawings and wiring
system depends primarily on the installation. See diagrams.
Figure 1-1. Use this manual as a guide to install the

1 2
18

3
17

16
4

15

5
14
9

13
8
12 6

11 7
10

585711

1. Exhaust mixer elbow (exhaust/water outlet) (not shown) 11. Hose clamps
2. Heat exchanger (not shown) 12. Fuel supply line *
3. Coolant recovery tank (located on the unit on some models) 13. Fuel/water separator (see Section 5 for more information)
4. Seawater strainer * 14. Mounting tray
5. Seawater pump (seawater inlet) 15. Battery/battery storage box
6. Seawater line * 16. Battery cables
7. Seacock * 17. Exhaust hose or exhaust line *
8. Craft stringers 18. Electrical leads (AC output leads/remote start panel leads)
9. Fuel feed pump (fuel inlet) *
10. Fuel return line * * Indicated components must conform to USCG regulations.

Figure 1-1 Typical Generator Set Location and Mounting (Without Sound Shield)

Note: See text for complete explanation of installation Note: Use two hose clamps on each end of all flexible
requirements. exhaust hose connections.

TP-6711 7/09 Section 1 Introduction 9


Notes

10 Section 1 Introduction TP-6711 7/09


Section 2 Location and Mounting

2.1 General Considerations Allow clearance for vibration and cooling during
operation. Allow a minimum of 38 mm (1.5 in.)
The key to installation is location. Before making final clearance on all sides (top, front, rear, and sides) of a
plans for locating a generator set, consider the generator set without an optional sound shield. Refer to
following. the instruction sheet for minimum clearances for
sound-shielded units. Also, allow space for the power
Installation Location Considerations takeoff (PTO) option, if equipped.

1. Choose a location that allows adequate space for


cooling and exhaust system installation, fuel 2.3 Mounting
system installation, ventilation, and service access
Mount the generator set as high as possible to avoid
to the generator set (engine and generator).
contact with bilge splash and lower-lying vapors and to
2. Use craft stringers or other available structural allow for downward pitch of the exhaust line toward the
members capable of supporting the generator sets exhaust outlet.
weight.
Kohler Co. recommends mounting the generator set on
3. Seal the generator sets engine room from the a flat board attached to the craft stringers. Craft
cabin to prevent exhaust gases and fuel vapors stringers generally provide the best generator set
from entering the cabin. support. Ensure that the structural members can
support the generator sets weight and withstand its
See the current generator set specification sheet or vibration.
Section 7 of this manual for generator set dimensions
and weights. See Figure 1-1 for a typical installation. The generator set includes vibration mounts and a
mounting tray or skid. If desired, install additional
vibration isolating pads underneath the generator sets
2.2 Location base.
Locate the generator set to allow easy service access to Use the four mounting holes in the mounting tray to
the generator sets engine, controller, cooling, and fuel mount the generator set securely to the craft.
system components. The engine compartment is often
the ideal location for the generator set if the propulsion For angular operating limits, consult the operation
engine(s) does not obstruct access to the generator set manual.
and controller.

Marine Generator Set Installations in


European Union Member Countries
This generator set is specifically intended and approved
for installation below the deck in the engine
compartment. Installation above the deck and/or
outdoors would constitute a violation of European Union
Directive 2000/14/EC noise emission standard.

TP-6711 7/09 Section 2 Location and Mounting 11


Notes

12 Section 2 Location and Mounting TP-6711 7/09


Section 3 Cooling System

3.1 Ventilation 3.2.1 Intake Through-Hull Strainer


(Seacock Cover)
Engine combustion, generator cooling, and expulsion of
flammable and lethal fumes require ventilation. Provide Install a screened-intake, through-hull strainer to
ventilation compliant with USCG Regulations governing prevent entry of foreign objects. Use perforated,
sizing of vents and other considerations. slotted-hole, or unrestricted-hole design strainers. See
Figure 3-2 for examples of typical strainers. The inner
As a rule, size each inlet- and outlet-vent area to a diameter of the strainer opening must be equal to or
minimum of 13 sq. cm/30.5 cm (2 sq. in. per ft.) of the greater than the inner diameter of the water-line hose to
crafts beam. Should this rule conflict with USCG the seawater pump.
Regulations, follow USCG Regulations. For applications
with screened inlets, double the size (4 sq. in. per ft.) of
the hull/deck openings. Extend the vent ducts to bilges to
expel heavier-than-air fumes.

For generator sets mounted in the engine compartment,


1
increase the air flow to allow for the generator sets
requirements. Install optional detection devices to
cause alarm, warning, or engine shutdown should
dangerous fumes accumulate in the compartment.
2
See the generator set specification sheet that shipped
with the generator set for air requirements. The air intake
silencer/cleaner provides combustion air to the engine.
3
Do not compromise the recommended minimum
clearance of 38 mm (1.5 in.) between a duct opening and 4
enclosure wall. The engine/generator performance will
decline if you compromise these guidelines. See
Figure 3-1 for allowable intake restriction.

Note: ISO 3046 derates apply. See Appendix C.

5
Allowable 1. Inside packing 1-789
Model 2. Outside packing
Intake Restriction
3. Seacock cover
635 mm H2O 4. Direction of vessel movement
9--32EOZD/7--28EFOZD
(6.23 kPa) or less 5. Typical intake through-hull strainers

Figure 3-1 Combustion Air Intake Restriction Figure 3-2 Seacock Installation

Do not align the strainer (in relation to the crafts direction


3.2 Cooling System Components of travel) with any other through-hull intakes. See
Figure 3-3. Flush mount the recommended through-hull
The marine generator sets cooling system requires the strainer. Install slotted-hole-design strainers with the
following components. slots parallel to the direction of the vessels movement.

TP-6711 7/09 Section 3 Cooling System 13


2
1

4 3
2
Note: Position the intakes in relation to the vessels 3
1-789
travel so neither is in the wake of the other.

1. Generator set intake


2. Main engine intake
3. Aft (rearward) 1-789
1. Seawater pump
4. Fore (forward) 2. Seawater strainer
3. Seacock
Figure 3-3 Intake Strainer
Figure 3-4 Seawater Strainer
Do not use a speed scoop or cup design intake
through-hull strainer because it can cause a ramming
effect and force water upward, past the seawater pump, 3.2.4 Water Lines
and into the engine cylinders when the vessel is moving Water lines from the seacock to the engine-driven
and the generator set is shut down. seawater pump are usually constructed of flexible hose.
Connect a flexible section of hose to the seawater pump
Do not use hulls incorporating sea chests or other
to allow the generator set to vibrate during operation.
designs that provide a positive pressure to the raw water
Support a nonflexible water line within 102 mm (4 in.) of
pump for the intake through-hull strainers. Positive
its connection to the flexible section.
pressure forces water past the raw water pump and into
the engine. A sea chest is a concave molded-in-the-hull Keep the seawater hose as straight and short as
chamber that aligns to the vessels direction of travel. A possible. If the hose is too long, usually over 4.6 m
sea chest configuration applies positive pressure similar (15 ft.), water suction problems may occur. See
to a scoop-type through-hull strainer. Section 7 for the inlet water line hose size and the
seawater connection to the seawater pump inlet. Avoid
3.2.2 Seacock running the inlet pipe above the generator. See
Figure 3-5 for the seawater hose connection to the
Mount the seacock to the hull, assemble it to the intake, seawater pump inlet.
and ensure that it is accessible for operation. Figure 3-2
shows a typical installation.

Avoid overcaulking the seacock. Excess caulk reduces


water flow and, in some cases, develops a barrier that
can force water upward, past the seawater pump, and
into the engine cylinders when the vessel is moving and
the generator set is shut down.

3.2.3 Seawater Strainer


Mount the seawater strainer to the seacock or
permanent structure at a point not higher than the
seawater pump. Ensure that the strainer is accessible
for service. See Figure 3-4 for a typical installation.

Some seawater strainers include a seacock and an


intake through-hull strainer.
1
Maximum seawater inlet pressure at the seawater pump TP-5586-6
1. Seawater pump inlet
is 34.5 kPa (5 psi). Excessive pressure will cause water
ingestion. Figure 3-5 Seawater Inlet Connection (Located at
the Inlet to the Seawater Pump), Typical

14 Section 3 Cooling System TP-6711 7/09


3.2.5 Closed Heat Exchanger
(9--32EOZD/7--28EFOZD Models)
A closed heat exchanger is the best cooling method for
most applications. See Figure 3-6 or Figure 3-7 for a
typical installation. Provide space to access the
water-cooled exhaust manifold pressure cap.

2
1
3

8 5

14

Arrow Description
10 Direction of Flow
Seawater
Freshwater (Coolant/Antifreeze)

11

12

13

TP-5586-6

1. Engine block 8. Thermostat closed


2. Exhaust manifold 9. Heat exchanger
3. Exhaust mixer elbow 10. Engine-driven seawater pump
4. Outlet flapper (exhaust/water discharge) 11. Seawater strainer
5. Silencer (customer supplied) 12. Seacock
6. Thermostat open 13. Intake strainer
7. Thermostat 14. Engine-driven water pump

Figure 3-6 Typical Closed/Heat Exchanger Cooling System (9/10/28/32EOZD, and 7/8.5/9/25/28EFOZD Models)

TP-6711 7/09 Section 3 Cooling System 15


1 2
3
4 5
7
6

9
14

13

12

11 Seawater
Freshwater (Coolant/Antifreeze)

10

TP-5592-6

1. Oil cooler 8. Silencer (customer-supplied)


2. Engine block 9. Exhaust outlet
3. Thermostat 10. Intake strainer
4. Water-cooled manifold 11. Seacock
5. Heat exchanger 12. Seawater strainer
6. Exhaust mixer elbow 13. Engine-driven seawater pump
7. Water-cooled turbocharger 14. Engine-driven water pump

Figure 3-7 Typical Closed/Heat Exchanger Cooling System (13--24EOZD and 11--20EFOZD Models)

16 Section 3 Cooling System TP-6711 7/09


Section 4 Exhaust System

Operating the generator set. Carbon monoxide can cause


WARNING severe nausea, fainting, or death. Be especially careful if
operating the generator set when moored or anchored under
calm conditions because gases may accumulate. If operating
the generator set dockside, moor the craft so that the exhaust
discharges on the lee side (the side sheltered from the wind).
Always be aware of others, making sure your exhaust is
Carbon monoxide. directed away from other boats and buildings.
Can cause severe nausea,
fainting, or death. Note: Do not use copper tubing in diesel exhaust
systems. Sulfur in diesel exhaust causes rapid
The exhaust system must be
leakproof and routinely inspected. deterioration of copper tubing exhaust systems,
resulting in exhaust/water leakage.
Carbon monoxide symptoms. Carbon monoxide can
cause severe nausea, fainting, or death. Carbon monoxide
is a poisonous gas present in exhaust gases. Carbon 4.1 Types
monoxide is an odorless, colorless, tasteless, nonirritating gas
that can cause death if inhaled for even a short time. Carbon
Kohlerr generator sets covered in this manual use
monoxide poisoning symptoms include but are not limited to either wet or dry exhaust systems. Dry exhaust systems
the following: are common in commercial applications. See the
D Light-headedness, dizziness engine manual for specifications.
D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue, 4.2 Exhaust Lines
inability to concentrate
or speak clearly, blurred vision Use water-cooled exhaust lines in all marine
D Stomachache, vomiting, nausea
installations. Keep the lines as short and straight as
If experiencing any of these symptoms and carbon monoxide
poisoning is possible, seek fresh air immediately and remain possible. NFPA 302 Fire Protection Standard for
active. Do not sit, lie down, or fall asleep. Alert others to the Pleasure and Commercial Motor Craft, Clause 4-3,
possibility of carbon monoxide poisoning. Seek medical recommends using two corrosion-resistant hose
attention if the condition of affected persons does not improve clamps with a minimum width of 13 mm (1/2 in.) on each
within minutes of breathing fresh air. end of the flexible exhaust hose connections.
Inspecting the exhaust system. Carbon monoxide can Kohler Co. requires a downward pitch of at least 13 mm
cause severe nausea, fainting, or death. For the safety of per 30.5 cm (1/2 in. per running foot). Use a flexible
the crafts occupants, install a carbon monoxide detector. exhaust hose that conforms to UL Standard 1129 for the
Never operate the generator set without a functioning carbon
engines wet exhaust components between the mixer
monoxide detector. Inspect the detector before each
generator set use. elbow and the exhaust outlet.

TP-6711 7/09 Section 4 Exhaust System 17


4.3 Exhaust System Location, Locate the exhaust outlet at least 10 cm (4 in.) above the
waterline when the craft is loaded to maximum capacity.
Mounting, and Installation Install an exhaust port with the flap at the exhaust
Note: Should any information regarding installation (transom) outlet to prevent water backup in following
conflict with USCG Regulations, follow USCG seas or when moving astern (backward). A lift in the
Regulations. exhaust piping before the piping exits the craft prevents
backwash. See Figure 4-3, item 1. Support the exhaust
Mount the silencer independently to eliminate stress on lines to prevent the formation of water pockets.
the exhaust system and the exhaust manifold/mixer
elbow. See Section 7 for the mixer elbow water line hose Exhaust system installation guidelines for various
size. See Figure 4-1 for the exhaust connection to the generator set locations follow. Information and
mixer elbow. Provide an adequate hose length from the illustrations of stern- (rear) exhaust installations also
exhaust mixer to the silencer to allow for generator set apply to side-exhaust installations. Where exhaust lines
movement. require passage through bulkheads, use port (left)- or
starboard (right)- side exhaust outlets, also in
applications in which long exhaust lines to the transom
(rear) could cause excessive back pressure. See
Figure 4-2 for allowable back pressures.

Allowable
Exhaust Back
Pressure,
kPa
Model (mm H2O)
14/15EOZD
9.81 (1000)
11.5/13EFOZD

9/23/24EOZD
11.77 (1200)
7/20EFOZD

10/13/20/28/32EOZD
15.30 (1560)
8.5/9/11/17/17.5/25/28EFOZD

Figure 4-2 Allowable Exhaust Back Pressures


1
TP-5586-6
1. Water/exhaust outlet

Figure 4-1 Mixer Elbow/Exhaust Connection,


Typical

18 Section 4 Exhaust System TP-6711 7/09


4.3.1 Above-Waterline Installation hose pitch of at least 13 mm per 30.5 cm (0.5 in. per
running foot). Some silencers require two support
Install a customer-supplied silencer with the silencers brackets or hanger straps for installation to stringers or
outlet at a maximum of 3 m (10 horizontal ft.) from the other suitable structure. Follow the instructions
center of the engines exhaust outlet. See Figure 4-3. provided with the silencer. Install any lift (see
Mount a typical silencer with the inlet and outlet Figure 4-3, item 1) in the exhaust line below the engine
horizontal and with the drain plug down. Use an exhaust exhaust manifold outlet.

4
5
6
3

2
1
7

18
13
9
16
Waterline

17 12

10

15 14
19 11
TP-5856-4

1. Slight lift improves silencing and prevents water backwash 15. Maximum distance between silencer and exhaust outlet of
into the silencer (keep below the level of the exhaust 1.5 m (5 ft.)
manifold outlet) 16. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in.
2. Silencer (customer-supplied) per ft.)
3. Exhaust manifold outlet 17. Minimum exhaust outlet distance above waterline of 10 cm
4. Exhaust mixer elbow (4 in.). Note: Vessel fully loaded.
5. Heat exchanger (locations vary by model) 18. Maximum silencer vertical lift of 1.2 m (4 ft.)
6. Coolant recovery tank (located on the unit on some models) 19. If the total exhaust length exceeds 4.6 m (15 ft.), Kohler
7. Locate the coolant recovery tank at the same height as the recommends increasing the exhaust hose to the next
heat exchanger larger diameter. See Figure 4-2 and Figure 4-5.
8. Maximum seawater pump lift of 1 m (3 ft.)
9. Seawater strainer Note: Data applies to both rear- and side-exhaust installations.
10. Seacock
11. Intake strainer Note: Use two hose clamps on each end of all flexible exhaust
12. Engine-driven seawater pump hose connections.
13. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in.
per ft.)
14. Maximum distance between silencer and exhaust mixer Note: Read the text for complete explanation of dimensions
elbow of 3 m (10 ft.) and other installation considerations.

Figure 4-3 Typical Above-Waterline Installation

TP-6711 7/09 Section 4 Exhaust System 19


4.3.2 Mid/Below-Waterline Installation
2
Follow USCG Regulations for installing an antisiphon
provision to prevent raw water entry into the engine.
Use the siphon break if the exhaust manifold outlet is
located less than 23 cm (9 in.) above the waterline when
the craft is loaded to maximum capacity. Install the
siphon break at least 31 cm (1 ft.) above the waterline
using the instructions provided with the siphon break kit.
3
Note: An improperly installed siphon break will cause
engine damage and may void the warranty.
1
Install the siphon break above the highest point in the 1. Heat exchanger
exhaust line between the heat exchanger and the 2. Exhaust mixer
exhaust mixer. See Figure 4-4 for the siphon break 3. Cut hose and connect siphon break and hardware
connection. Support the siphon break and hoses to Figure 4-4 Siphon Break Connection, Typical
maintain their position and function. Allow a slight offset
to clear the stringers or other permanent structures. Mount a typical silencers base no more than 1.2 m (4 ft.)
Protect the siphon break air inlet from dirt and debris. below the highest point in the exhaust line. Attach a
separate wood mounting base to the hull stringers or
Note: To prevent water leakage on the generator set, do other suitable structures. Use the silencer
not mount the siphon break directly over the manufacturers recommendation for securing the
generator set. silencer to the hull. Mount the silencer with the outlet not
more than 3 m (10 horizontal ft.) from the engines
Note: Ensure that the siphon breaks cap is tight before
exhaust manifold outlet. Use a USCG-type certified
operating the generator set.
marine exhaust hose.

Exhaust Hose
Diameter
Models without Sound Shield Models with Sound Shield mm (in.)
9/10EOZD 9/10EOZD
51 (2.0)
7/9EFOZD 7/9EFOZD
13/14/15/20/23/24/28/32EOZD 13/14/15/20/23/24/28/32EOZD
76 (3.0)
11/11.5/13/17/17.5/20/25/28EFOZD 11/11.5/13/17/17.5/20/25/28EFOZD

Figure 4-5 Exhaust Hose Sizes

20 Section 4 Exhaust System TP-6711 7/09


Note: Read the text for complete explanation of
dimensions and other installation
considerations.
1
Note: Use two hose clamps on each end of all
flexible exhaust hose connections. 2
Note: Data applies to both rear- and side-exhaust 3
installations.
Note: Damage caused by water ingestion will not
be covered by the generator warranty. 24

7
25

23 9
10

6
4 8
5

20
11

Waterline
26
22 16
19 12
15

21

13

18 17 14

1. Cap 17. Maximum distance between silencer and exhaust mixer elbow
2. Reed valve of 3 m (10 ft.)
3. Mounting base 18. Maximum distance between silencer and exhaust outlet of
4. Maximum silencer vertical lift of 1.2 m (4 ft.) 1.5 m (5 ft.)
5. Exhaust mixer elbow distance above waterline; if less than 19. Silencer (customer-supplied)
23 cm (9 in.), a siphon break is required 20. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm
6. Minimum siphon break distance above waterline of 30.5 cm (0.5 in. per ft.)
(1 ft.) 21. Maximum distance between exhaust outlet and generator of
7. Siphon break
4.6 m (15 ft.)
8. Exhaust mixer elbow
22. Minimum exhaust outlet distance above waterline of 10 cm
9. Heat exchanger (locations vary by model)
10. Coolant recovery tank (located on the unit on some models) (4 in.)
11. Indicates the coolant recovery tank is at the same height as the 23. Exhaust hose
heat exchanger 24. Gas/water separator (optional). Install directly above the
12. Seawater strainer canister muffler.
13. Seacock 25. Distance above waterline for drain outlet from silencer must be
14. Intake strainer equal to or greater than water drain (item 18) to be greater
15. Engine-driven seawater pump than 30.5 cm (1 ft.)
16. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per ft.) 26. Water drain distance below waterline

Figure 4-6 Typical Mid- and Below-Waterline Installation with Optional Gas/Water Separator

TP-6711 7/09 Section 4 Exhaust System 21


1

2
7 8
3
9
10

6
22
5

4 11
Waterline 20

21 16
12

19

15
13

18 17 14 TP-5856-4

23

1. Cap 17. Maximum distance between silencer and exhaust mixer elbow
2. Reed valve of 3 m (10 ft.)
3. Mounting base 18. Maximum distance between silencer and exhaust outlet of
4. Maximum silencer vertical lift of 1.2 m (4 ft.) 1.5 m (5 ft.)
5. Exhaust mixer elbow distance above waterline; if less than 19. Silencer (customer-supplied)
23 cm (9 in.), a siphon break is required 20. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm
6. Minimum siphon break distance above waterline of 30.5 cm (0.5 in. per ft.)
(1 ft.) 21. Minimum exhaust outlet distance above waterline of 10 cm
7. Siphon break (4 in.)
8. Exhaust mixer elbow 22. Exhaust hose (see Figure 4-5 for hose sizes)
9. Heat exchanger (locations vary by model) 23. If the total exhaust length exceeds 4.6 m (15 ft.), Kohler
10. Coolant recovery tank (located on the unit on some models) recommends increasing the exhaust hose to the next larger
11. Indicates the coolant recovery tank is at the same height as the diameter. See Figure 4-2 and Figure 4-5.
heat exchanger Note: Read the text for complete explanation of dimensions and
12. Seawater strainer other installation considerations.
13. Seacock
Note: Use two hose clamps on each end of all flexible exhaust
14. Intake strainer
hose connections.
15. Engine-driven seawater pump
16. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per ft.) Note: Data applies to both rear- and side-exhaust installations.

Figure 4-7 Typical Mid- and Below-Waterline Installation

22 Section 4 Exhaust System TP-6711 7/09


Note: Read the text for complete explanation of
dimensions and other installation considerations. 1
Note: Use two hose clamps on each end of all flexible 2
exhaust hose connections. 3
Note: Data applies to both rear- and side-exhaust
installations.
Note: Damage caused by water ingestion will not be
covered by the generator warranty.

10

19 11

25 6
24 15

5
16 16
26
4

22 20 16 23 12

18 17
27 13
21

14

1. Cap 17. Maximum distance between silencer and exhaust mixer


2. Reed valve elbow of 3 m (10 ft.)
3. Mounting base 18. Water drain distance below waterline
4. Maximum silencer internal vertical lift of 1.2 m (4 ft.) 19. Combination silencer that contains lift muffler and gas water
5. Exhaust mixer elbow distance above waterline; if less than separating sections in single component (customer-supplied)
23 cm (9 in.), a siphon break is required 20. Distance above waterline for drain outlet from silencer must
6. Minimum siphon break distance above waterline of 30.5 cm be equal to or greater than water drain (item 18) to be greater
(1 ft.) than 30.5 cm (1 ft.)
7. Siphon break 21. Exhaust outlet to be diameter appropriate so exhaust back
8. Exhaust mixer pressure does not exceed limit at engine exhaust manifold
9. Heat exchanger 22. Minimum exhaust outlet distance above waterline of 10 cm
10. Coolant recovery bottle (4 in.)
11. Indicates the coolant recovery tank is at the same height as 23. Exhaust hose
the heat exchanger 24. Height of internal lift tube to be below generator exhaust
12. Seawater strainer manifold
13. Seacock 25. Kohler recommends generator be located at elevation that
14. Intake strainer exhaust mixer elbow is above silencer exhaust outlet
15. Engine-driven seawater pump 26. Seawater pump lift
16. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. 27. Waterline
per ft.)

Figure 4-8 Exhaust System with Combination Silencer/Gas Water Separator

TP-6711 7/09 Section 4 Exhaust System 23


Notes

24 Section 4 Exhaust System TP-6711 7/09


Section 5 Fuel System

2
WARNING

Explosive fuel vapors.


Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.

Note: Do not modify the tank or the propulsion engine


fuel system. Equip the craft with a tank that
allows one of the two pickup arrangements.
1-788
Note: Fuel system installations must conform to USCG
Regulations. 1. Fuel line to propulsion engine
2. Fuel line to generator set
Note: Use pipe sealant on all threaded fittings to Figure 5-1 Multiple Dip Tube Arrangement
prevent fuel leakage. Use pipe sealant that
m:is:102:001
resists gasoline, grease, lubrication oil, common
bilge solvents, salt deposits, and water.

5.1 Fuel Tank


Most marine generator sets draw fuel from the same fuel
tank as the crafts propulsion engine(s). If the tanks fuel
pickup opening allows a multiple dip tube, use a multiple
dip tube arrangement. See Figure 5-1. The multiple dip
tube arrangement incorporates a shorter dip tube for the
generator set and a longer dip tube for the propulsion
engine. With this arrangement, the generator set runs
out of fuel before the propulsion engine during a low fuel
supply situation. Equip the fuel system with a fuel/water
separator to remove any accumulated dirt and water.

TP-6711 7/09 Section 5 Fuel System 25


5.2 Fuel Lines 5.3 Fuel Filters
Return the generator set fuel return line to the fuel tank. Conform to USCG Regulations regarding inline fuel
Locate the fuel return line as far as practical from the fuel filters or strainers.
pickup to allow the tank fuel to cool the return fuel before
delivery back to the fuel injectors. Incoming fuel cools
the injectors to achieve maximum engine efficiency. 5.4 Fuel/Water Separator
Note: Do not tee into the main propulsion engines fuel For 9--32EOZD and 7--28EFOZD models, install a
line. fuel/water separator between the fuel tank and the
electric fuel pump. The fuel/water separator must
Note: Fuel Return Dip Tube (9--32EOZD/ contain a primary filter of 30--50 micron filtration
7--28EFOZD Models). Kohler Co. recommends capability, sized for at least 15 gph to allow for the return
utilizing a fuel return dip tube located below the fuel flow.
fuel supply dip tube. This will prevent air from
entering the return lines, draining the fuel
injection pump, and thus causing starting failure 5.5 Fuel Pump Lift
or hard starting of the generator set. The dip tube
depth should be at least as deep as the main See Figure 5-3 for fuel pump lift capabilities.
engine fuel pick-up dip tube.
Fuel Pump Lift
Under no circumstances should the propulsion engine Model m (ft.)
and generator set share pickup or return lines (through a
9--32EOZD
tee arrangement) that would allow the larger engine to 1.2 (4)
7--28EFOZD
starve fuel from the smaller engine. It is possible that the
operation of either engine could completely drain the Figure 5-3 Fuel Pump Lift
fuel line of the other engine and make starting difficult.

Use a flexible hose section to connect the metallic line 5.6 Fuel Consumption
from the fuel tank to the engines fuel pump inlet
Consult the current generator set specification sheets
connection point. Also, use a flexible hose section to
for generator set fuel consumption rates.
connect the metallic line from the fuel tank to the fuel
return connection point. The flexible section allows the
generator set to vibrate during operation.

Fuel Line
ID Size
Model mm (in.)

9--32EOZD and 7--28EFOZD 9.7 (3/8)

Figure 5-2 Fuel Line ID Size (Max.)

See Figure 5-2 for the ID size of the customer-supplied


fuel line that connects to the fuel pump and fuel return.
Route the fuel lines from the fuel tank in a gradual incline
to the enginedo not exceed the height of the generator
set and do not route fuel lines above the generator set.
Comply with USCG Regulation 46CFR182.20
regarding fuel lines and supports.

See Section 7 for fuel feed pump inlet connection and


fuel return line connection.

26 Section 5 Fuel System TP-6711 7/09


Section 6 Electrical System

WARNING 1
2

Hazardous voltage. Moving parts.


Can cause severe injury or death.
3
Operate the generator set only when
all guards and electrical enclosures
are in place.

Electrical backfeed to the utility. Hazardous backfeed 5


voltage can cause severe injury or death. Connect the
generator set to the building/marina electrical system only
through an approved device and after the building/marina 4
main switch is turned off. Backfeed connections can cause 1. Line side connections from generator 585771
severe injury or death to utility personnel working on power 2. AC circuit breaker
lines and/or personnel near the work area. Some states and 3. L1/L2 phase (black) leads. Load side customer
localities prohibit unauthorized connection to the utility connection points.
electrical system. Install a ship-to-shore transfer switch to 4. L0 neutral (white) lead
prevent interconnection of the generator set power and shore 5. GRD ground (green) lead
power.
Figure 6-1 AC Voltage Connections in Junction Box

6.1 AC Voltage Connections 9--24EOZD Models

Make AC connections to the generator set inside the


junction box. Typically, the generator set connects to a
ship-to-shore transfer switch that allows the use of
shore/utility power when docked or generator set power
when docked or at sea. The wiring then connects to a
main circuit breaker box (panel board) that distributes
branch circuits throughout the craft. See Figure 6-1 for
AC voltage connections to the generator set. See
Section 8 for reconnection of the generator set.
1, 2

Top View
(Shown with junction box cover removed)
28/32EOZD Models

2 1

1. Neutral (L0) connection


2. Ground (GRD) connection

Figure 6-2 Neutral and Ground Connections


(9--32EOZD Models Shown)

TP-6711 7/09 Section 6 Electrical System 27


6.2 Circuit Protection Number
Amps Voltage of Poles Model(s)
The AC circuit breakers (optional) protect the wiring 18 480 3 8.5EFOZD, 10EOZD (3 ph.)
from the AC circuit breakers to the vessels distribution 480 3 10EOZD (3 ph.)
panel. AC circuit breakers trip when they detect a fault in 30
600 3
11.5EFOZD, 14EOZD,
the output circuit. 17.5EFOZD, 20EOZD (3 ph.)
33 240 2 7EFOZD
After correcting the fault, reset the AC circuit breaker(s) 240 1 7EFOZD
35
by placing them in the ON position. Restart the unit. Do 480 3 10EOZD (3 ph.)
not start the unit under load. See Figure 6-3 for AC 11.5EFOZD, 17.5EFOZD,
40 600 3 20EFOZD (3 ph.), 25EFOZD (3 ph.),
circuit breaker ratings. The units voltage configuration 24EOZD
determines the circuit breaker selection. 1 9EFOZD
42 240
2 9EOZD, 9EFOZD, 10EOZD
Note: Circuit breaker ampere rating and availability are
1 11EFOZD
subject to change. 240
2 11EFOZD
50 480 3 11.5EFOZD, 14EOZD
6.2.1 Circuit Breaker Considerations 25EFOZD (3 ph.), 28EFOZD (3 ph.),
600 3
28EOZD (3 ph.), 32EOZD (3 ph.)
Mounting location. Mount the circuit breakers in the 1 13EFOZD
generator sets junction box. See Section 6.2.2. 240
2 11.5EFOZD, 13EOZD, 13EFOZD
60
17.5EFOZD, 20EOZD (3 ph.),
Sizing. Use the generator set voltage/frequency 600 3
28EFOZD (3 ph.)
configuration to determine the circuit breaker 240 2 14EOZD, 15EOZD
amperage. If the generator set voltage configuration 70 17.5EFOZD, 20EOZD (3 ph.),
600 3
changes, change the circuit breaker to provide optimum 20EFOZD (3 ph.)
protection. 1 9EOZD, 17EFOZD, 17.5EFOZD
240
2 17EFOZD
80
For circuit breaker application and selection 480 3
20EFOZD (3 ph.), 25EFOZD (3 ph.),
information, contact an authorized distributor/dealer. 24EOZD
85 240 1 10EOZD
Have a qualified electrician or technician install circuit 1 20EFOZD (1 & 3 ph.)
breakers and reconnect the generator set. Comply with 240 20EOZD (1 & 3 ph.),
2
90 20EFOZD (1 ph.)
all governing standards and codes.
25EFOZD (3 ph.), 24EOZD,
480 3
28EFOZD (3 ph.), 28EOZD (3 ph.)
23EOZD, 24EOZD,
240 2
25EFOZD (1 & 3 ph.)
100
28EFOZD (3 ph.), 28EOZD (3 ph.),
480 3
32EOZD (3 ph.)
2 28EFOZD (1 & 3 ph.)
240
3 32EOZD (3 ph.), 28EFOZD ( 3 ph.)
125 28EFOZD (1 & 3 ph.),
2
28EOZD (1 & 3 ph.)
600
28EFOZD (3 ph.),
3
32EOZD (3 ph.)
240 2 32EOZD (1 & 3 ph.)
150
600 2 32EOZD (1 & 3 ph.)

Figure 6-3 AC Circuit Breaker Ratings, Listed By


Amps

28 Section 6 Electrical System TP-6711 7/09


Short circuits. Hazardous voltage/current can cause
WARNING severe injury or death. Short circuits can cause bodily injury
and/or equipment damage. Do not contact electrical
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment.

Electrical backfeed to the utility. Hazardous backfeed


voltage can cause severe injury or death. Connect the
Accidental starting.
generator set to the building/marina electrical system only
Can cause severe injury or death.
through an approved device and after the building/marina
Disconnect the battery cables before main switch is turned off. Backfeed connections can cause
working on the generator set. severe injury or death to utility personnel working on power
Remove the negative (--) lead first lines and/or personnel near the work area. Some states and
when disconnecting the battery. localities prohibit unauthorized connection to the utility
Reconnect the negative (--) lead last
electrical system. Install a ship-to-shore transfer switch to
when reconnecting the battery.
prevent interconnection of the generator set power and shore
power.
Disabling the generator set. Accidental starting can
cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator 6.2.2 Circuit Breaker Installation
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger. 1. Place the generator set master switch in the OFF
(3) Remove the battery cables, negative (--) lead first. position.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the 2. Disconnect the generator set engine starting
generator set by an automatic transfer switch, remote
battery, negative (--) lead first.
start/stop switch, or engine start command from a remote
computer.
3. Remove the screws and remove the access cover.

WARNING 4. Remove the screws and nuts to remove the circuit


breaker cover plate. Save the mounting hardware.

5. Install the circuit breaker from the inside of the


cutout panel and mount it using existing screws
Hazardous voltage. Moving parts. removed in step 4. Position the circuit breaker with
Can cause severe injury or death. the ON in the normal upright position or to the left
side. Cover the cutout opening, if applicable, with
Operate the generator set only when the circuit breaker cover plate. Use existing screws
all guards and electrical enclosures to mount the cover plate. See Figure 6-4.
are in place.
6. See Section 8 for voltage reconnection.
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible Note: Kohlerr marine diesel generator sets are
whenever electricity is present. Ensure you comply with all fully frequency adjustable and voltage
applicable codes and standards. Electrically ground the reconnectable. To determine reconnection
generator set, transfer switch, and related equipment and
electrical circuits. Turn off the main circuit breakers of all
options, check the models specification
power sources before servicing the equipment. Never contact sheet.
electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of 7. Install insulation boots over stator lead terminals if
electrocution. the kit includes insulation boots.

Note: See Section 8 for wiring instructions.

TP-6711 7/09 Section 6 Electrical System 29


8. Make the recommended connections for the Note: Wire material. Use stranded copper for all
following four reconnection systems using circuit wiring. Use wire gauges and insulation,
breakers: conductor temperature ratings, sheath
stripping, conductor support and protection,
Two-pole circuit breaker with a single-voltage conductor terminals and splices, and
system (example: 120-volt, 3-wire). Attach overcurrent protection (circuit breakers,
stator leads marked 2 and 4 to the side of the circuit fuses) that conform to standards and codes.
breaker marked LINE. Install the jumper lead
across the LINE side of circuit breaker terminals Note: Follow USCG Regulations CFR33, Part 183
(see Section 8). Attach stator leads 1 and 3 to L0. (Pleasurecraft) and CFR46 (Commercial
Craft) for marine applications.
Single-pole circuit breaker with a 120-volt,
2-wire, single-voltage system. Attach stator Note: Wire protection. Use plastic bushings,
leads marked 2 and 4 to the side of the circuit rubber grommets, and/or cable ties as
breaker marked LINE (see Section 8). Attach stator necessary to protect and secure wiring from
leads 1 and 3 to L0. sharp objects, the exhaust system, and any
moving parts.
Two-pole circuit breaker with a dual-voltage
system (example: 120/240-volt, 3-wire). Attach 11. Replace the controller cover or circuit breaker box
stator leads marked 1 and 4 to the side of the circuit access panel.
breaker marked LINE. Do not use a jumper lead
(see Section 8). Attach stator leads 2 and 3 to L0. 12. Reconnect the generator set engine starting
battery, negative (--) lead last.
EOZD/EFOZD Models (with ADC 2100):
Single-pole circuit breaker with a 240-volt, 13. Make voltage or frequency adjustments according
2-wire, single-voltage system. Attach the stator to Section 8.
lead marked 1 to the side of the circuit breaker
marked LINE (see Section 8). Bolt together leads Note: Voltage/frequency adjustable. Some
2 and 3 and tape to insulate from ground. Attach four-lead generator sets are not
the stator lead marked 4 to L0. voltage/frequency adjustable. To determine
adjustment possibilities, check the models
9. Connect the stator lead(s) used for neutral specification sheet or service manual. If you
connection to the L0 stud. See the illustrations in are reconnecting the generator set from a
Section 8. single-voltage to a dual-voltage
configuration (example: from 120-volt to
10. Connect the side of the circuit breaker marked 120/240-volt) or a dual voltage to a single
LOAD to the ship-to-shore switch or craft wiring. voltage (example: from 120/240-volt to
Attach insulation boots to the black leads if the kit 120-volt) with the same primary voltage, do
includes insulation boots. With a single-pole circuit not adjust the voltage/frequency
breaker use one black lead (L1). With a two-pole adjustment. Adjust the voltage/frequency
circuit breaker use two black leads, L1 and L2. for frequency changes or setting changes of
Connect the neutral (white) lead to the L0 stud. the primary voltage (example: from 120-volt
Connect the equipment ground (green) lead to to 100-volt). Refer to the models
GRD stud. specification sheet for reconnection
capability.

30 Section 6 Electrical System TP-6711 7/09


5

1 5

3
4 1 1
1 2
3 3 3

2 2
2

6 5
5

GM30331-

1. Circuit breaker 4. Cover plate


2. Circuit breaker plate 5. Use existing hardware
3. Circuit breaker mounting hardware 6. Screw (qty. 2) and nut (qty. 2)

Figure 6-4 Circuit Breaker Mounting (9--32EOZD and 7--28EFOZD Models)

6.3 Installation In Steel or 6.4 Installation Regulations


Aluminum Vessels The U.S. Coast Guard governs generator set
Installation of a generator set in a vessel constructed of installation in U.S. pleasurecraft and commercial
a material capable of conducting current (e.g., steel or vessels. Refer to the applicable regulations below:
aluminum) is subject to considerations not normally
encountered in fiberglass or wood vessels. These U.S. Pleasurecraft Installation
differences include equipment grounding, grounding of Regulations
neutral conductors, ground-fault protection, and
isolation of galvanic currents. Title 33CFR, Chapter I, U.S. Coast Guard, Part 183

Note: Isolated ground kits are available as options for 1. Subpart IElectrical Equipment
steel- or aluminum-hulled vessels. Consult your
local dealer/distributor for more information. 2. Subpart JFuel Systems

The scope of these topics is too extensive to be fully


U.S. Commercial Vessel Installation
discussed here. Consult your local marine authority for
more information.
Regulations
Title 46CFR, Chapter I, U.S. Coast Guard
Before installing the generator set, check the available
wiring diagrams in the operation manual to become 1. Part 111Electrical Systems
familiar with the electrical system.
2. Part 182Machinery Installation
m:sc:001:001

TP-6711 7/09 Section 6 Electrical System 31


6.5 Battery Kohler Co. recommends using one 12-volt battery (or
two for 24-volt systems, as the spec requires) to start the
Batteries and their installation must conform to USCG generator. See Figure 6-6 for minimum cold cranking
Regulations 183.420 (a) through (g). Provide generator amps (CCA) recommendations.
sets with batteries separate from the propulsion
engines whenever possible. The starting/charging 12-Volt Starting Battery Size CCA
systems of both the generator set and the engine must at --18C (0F) or 100 Amp. Hr.
have a common negative (--) ground.
Models CCA
USCG Regulation 183.415, Grounding, requires 9--15EOZD, and 7--13EFOZD 500
connection of a common conductor to each grounded
20/23/24EOZD, and
cranking-motor circuit. Size the conductor to match the 650
17/17.5/20EFOZD
larger of the engines two battery cables. Figure 6-5 lists
28/32EOZD and 25/28EFOZD 800
recommended minimum cable sizes for generator set
battery connections at various generator set-to-battery Figure 6-6 Battery Recommendations
distances. Connecting a common conductor to each
grounded cranking motor circuit prevents the starting
motor current from using alternative electrical paths 6.6 Wiring
should the cranking motor ground circuit be restricted or
open because of oxidation or loose hardware. Use only stranded copper wire. Conform to USCG
Alternative electrical paths include metallic fuel lines Regulations 183.425 through 183.460 for wire gauges
that can pose a hazard. See Section 7 for locations of and insulation, conductor temperature ratings, sheath
the battery connections to the generator set. stripping, conductor support and protection, conductor
terminals and splices, and over-current protection
Required Battery Cable
(circuit breakers, fuses). Use rubber grommets and
(Minimum) cable ties as necessary to protect and secure the wire
from sharp objects, the exhaust system, and moving
Distance (from battery to
2.5 m (8.3 ft.) 5 m (16.4 ft.) parts.
generator set)
Battery Voltage 12V 24V 12V 24V
9EOZD/7EFOZD #2 -------- #1 --------
10--24EOZD/8.5--20EFOZD #2 #4 # 1/0 #2
28--32EOZD/25--28EFOZD #2 #4 # 1/0 #2

Figure 6-5 Battery Cable Sizing Recommendations

32 Section 6 Electrical System TP-6711 7/09


6.7 Remote Connection Component Amp Part No. Kohler Part No.
Plug 350735-1 229998
Kohler Co. offers several remote panels for connection
to the generator set. Contact your local Kohlerr Pin 350218-6 241618
distributor/dealer for detailed descriptions. See Cable Seal 794280-1 GM29252
Figure 6-7 for the location of the remote start panel Interface Seal 794279-1 GM29507
connection to the generator set controller. Kohler Co. Cavity Plug 770377-1 GM28769
also offers wiring harnesses in various lengths with a
Figure 6-8 Connector Components (EOZD/EFOZD
connector keyed to the controller box connector. A
Models)
pigtail harness is also offered which includes the
appropriate connector on one end and has pigtails that Note: Gauge senders. Gauge senders are available
the installer can use to connect to a customer-supplied for most generator sets. If using customer-
start/stop switch or separate lights and hourmeter. supplied gauges, be sure they are compatible
Consult wiring diagrams, ADVs, and instruction sheets with generator set senders. Contact an
for connection information/details. authorized Kohlerr service distributor/dealer.
Gauges and senders are available as service
9--32EOZD and 7--28EFOZD Models. These models items from an authorized Kohlerr service
use a 12-pin connector for the remote interface distributor/dealer.
connection. See Figure 6-7 for the connectors location.
See Figure 6-8 for the correct customer-supplied plug
and pin part numbers.

ADV6843b-a
1. Remote interface connector

Figure 6-7 Remote Interface Connector,


EOZD/EFOZD Models, Typical (Shown
on Sound-Shielded Units)

TP-6711 7/09 Section 6 Electrical System 33


Notes

34 Section 6 Electrical System TP-6711 7/09


Section 7 Installation Drawings

Use the drawings in this section for installation Model No. Drawing Page
purposes. Consult the supplier and verify that the 9EOZD and 7EFOZD ADV-7385A- 36
drawings are the most current for your specifications.
with sound shield ADV-7385B- 37
Installation drawings show exhaust outlet locations, fuel
with keel cooling ADV-7385C- 38
inlet and return connections, siphon break locations,
10EOZD and 8.5/9EFOZD ADV-7384A- 39
and battery connections. See Figure 7-1 for installation
drawing identification. with sound shield ADV-7384B- 40
with keel cooling ADV-7384C- 41
13/14/15EOZD and
11/11.5/13EFOZD ADV-7383A- 42
with sound shield ADV-7383B- 43
with keel cooling ADV-7383C- 44
20/23/24EOZD and
17/17.5/20EFOZD ADV-7382A-B 45
with sound shield ADV-7382B-B 46
with keel cooling for models
ADV-7382C-B 47
20EOZD and 17/17.5EFOZD
with keel cooling for models
ADV-7382D-B 48
23/24EOZD and 20EFOZD
28/32EOZD and 25/28EFOZD ADV-7381A-A 49
with sound shield ADV-7381B-A 50
with keel cooling ADV-7381C-A 51
with electric clutch ADV-7381D-A 52

Figure 7-1 Installation Drawings

TP-6711 7/09 Section 7 Installation Drawings 35


NOTE: Dimensions are shown in mm [in.]. ADV-7385A-

Figure 7-2 Dimension Drawing, 9EOZD and 7EFOZD

36 Section 7 Installation Drawings TP-6711 7/09


NOTE: Dimensions are shown in mm [in.]. ADV-7385B-

Figure 7-3 Dimension Drawing, 9EOZD and 7EFOZD with Sound Shield

TP-6711 7/09 Section 7 Installation Drawings 37


NOTE: Dimensions are shown in mm [in.]. ADV-7385C-

Figure 7-4 Dimension Drawing, 9EOZD and 7EFOZD with Keel Cooling

38 Section 7 Installation Drawings TP-6711 7/09


NOTE: Dimensions are shown in mm [in.]. ADV-7384A-

Figure 7-5 Dimension Drawing, 10EOZD and 8.5/9EFOZD

TP-6711 7/09 Section 7 Installation Drawings 39


NOTE: Dimensions are shown in mm [in.].
ADV-7384B-

Figure 7-6 Dimension Drawing, 10EOZD and 8.5/9EFOZD with Sound Shield

40 Section 7 Installation Drawings TP-6711 7/09


NOTE: Dimensions are shown in mm [in.]. ADV-7384C-

Figure 7-7 Dimension Drawing, 10EOZD and 8.5/9EFOZD with Keel Cooling

TP-6711 7/09 Section 7 Installation Drawings 41


NOTE: Dimensions are shown in mm [in.]. ADV-7383A-

Figure 7-8 Dimension Drawing, 13/14/15EOZD and 11/11.5/13EFOZD

42 Section 7 Installation Drawings TP-6711 7/09


NOTE: Dimensions are shown in mm [in.]. ADV-7383B-

Figure 7-9 Dimension Drawing, 13/14/15EOZD and 11/11.5/13EFOZD with Sound Shield

TP-6711 7/09 Section 7 Installation Drawings 43


NOTE: Dimensions are shown in mm [in.]. ADV-7383C-

Figure 7-10 Dimension Drawing, 13/14/15EOZD and 11/11.5/13EFOZD with Keel Cooling

44 Section 7 Installation Drawings TP-6711 7/09


NOTE: Dimensions are shown in mm [in.]. ADV-7382A-B

Figure 7-11 Dimension Drawing, 20/23/24EOZD and 17/17.5/20EFOZD

TP-6711 7/09 Section 7 Installation Drawings 45


NOTE: Dimensions are shown in mm [in.]. ADV-7382B-B

Figure 7-12 Dimension Drawing, 20/23/24EOZD and 17/17.5/20EFOZD with Sound Shield

46 Section 7 Installation Drawings TP-6711 7/09


NOTE: Dimensions are shown in mm [in.]. ADV-7382C-B

Figure 7-13 Dimension Drawing, 20EOZD and 17/17.5EFOZD with Keel Cooling

TP-6711 7/09 Section 7 Installation Drawings 47


NOTE: Dimensions are shown in mm [in.]. ADV-7382D-B

Figure 7-14 Dimension Drawing, 23/24EOZD and 20EFOZD with Keel Cooling

48 Section 7 Installation Drawings TP-6711 7/09


NOTE: Dimensions are shown in mm [in.]. ADV-7381A-A

Figure 7-15 Dimension Drawing, 28/32EOZD and 25/28EFOZD

TP-6711 7/09 Section 7 Installation Drawings 49


NOTE: Dimensions are shown in mm [in.]. ADV-7381B-A

Figure 7-16 Dimension Drawing, 28/32EOZD and 25/28EFOZD with Sound Shield

50 Section 7 Installation Drawings TP-6711 7/09


NOTE: Dimensions are shown in mm [in.]. ADV-7381C-A

Figure 7-17 Dimension Drawing, 28/32EOZD and 25/28EFOZD with Keel Cooling

TP-6711 7/09 Section 7 Installation Drawings 51


NOTE: Dimensions are shown in mm [in.]. ADV-7381D-A

Figure 7-18 Dimension Drawing, 28/32EOZD and 25/28EFOZD with Electric Clutch

52 Section 7 Installation Drawings TP-6711 7/09


Section 8 Reconnection/Adjustments

WARNING WARNING

Hazardous voltage. Moving parts.


Accidental starting. Can cause severe injury or death.
Can cause severe injury or death.
Operate the generator set only when
Disconnect the battery cables before all guards and electrical enclosures
working on the generator set. are in place.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last Grounding electrical equipment. Hazardous voltage can
when reconnecting the battery. cause severe injury or death. Electrocution is possible
whenever electricity is present. Ensure you comply with all
applicable codes and standards. Electrically ground the
Disabling the generator set. Accidental starting can generator set, transfer switch, and related equipment and
cause severe injury or death. Before working on the electrical circuits. Turn off the main circuit breakers of all
generator set or connected equipment, disable the generator power sources before servicing the equipment. Never contact
set as follows: (1) Move the generator set master switch to the electrical leads or appliances when standing in water or on wet
OFF position. (2) Disconnect the power to the battery charger. ground because these conditions increase the risk of
(3) Remove the battery cables, negative (--) lead first. electrocution.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.

TP-6711 7/09 Section 8 Reconnection/Adjustments 53


8.1 Four-Lead Reconnection 8.1.2 100--120/200--240-Volt
Configurations
The following information illustrates the reconnection of
four-lead generator sets. In all cases, conform to the The 100--120/200--240-volt configuration does not use
National Electrical Code (NEC). a jumper lead. If the unit was originally wired for straight
100--120 volt, 3-wire, remove the jumper lead (see
NOTICE Figure 8-1 for location). Select a two-pole circuit
Voltage reconnection. Affix a notice to the generator set after breaker. Application of two single-pole circuit breakers
reconnecting the set to a voltage different from the voltage on
the nameplate. Order voltage reconnection decal 246242
does not conform to NEC requirements for supplying a
from an authorized service distributor/dealer. 200--240-volt load, even if the breakers are
mechanically attached together. Leads L1 and L2 are
for different phases; never connect them together.
8.1.1 100--120-Volt Configurations
If the installation requires a factory two-pole circuit L0 (Neutral)
breaker, do not connect the load-side terminals of the L0
GRD.
circuit breaker together; see Figure 8-1. If the Ground
installation requires a 100--120-volt, 2-wire system, use
L1
a single-pole circuit breaker. See Figure 8-2. When Load
Side
connecting stator phase leads together, size the output
Single-Pole
lead (L1) to handle the amperage. Use a jumper lead on Circuit
the line side of the circuit breaker to balance the load of Line Breaker
the generator set. Side

L0 (Neutral)
L0
GRD.
Ground 4 3 2 1
L1
Stator Leads
L2
Load 60 Hz 50 Hz
Side L0--L1 100--120 Volt 100--120 Volt
Two-Pole L0--L2 100--120 Volt 100--120 Volt
Line Circuit
Side Breaker Figure 8-2 100--120-Volt, 2-Wire Configuration

L0 (Neutral)
L0

Jumper Ground GRD.


lead L1
L2
Load
4 3 2 1 Side
Factory
Figure 8-1 100--120-Volt, 3-Wire Configuration Two-Pole
Line Circuit
Side Breaker

100--120/200--240-Volt,
4 3 2 1 3-Wire
Stator Leads
60 Hz 50 Hz
L0--L1 100--120 Volt 100--120 Volt
L0--L2 100--120 Volt 100--120 Volt
L1--L2 200--240 Volt 200--240 Volt

Figure 8-3 100--120/200--240-Volt, 3-Wire


Configuration

54 Section 8 Reconnection/Adjustments TP-6711 7/09


8.1.3 200--240-Volt Configurations
The 200--240-volt configuration does not use a jumper
lead. If the unit was originally wired for straight 100--120
volt, 3-wire, remove the jumper lead (see Figure 8-1 for
location). See Figure 8-4 for EOZD/EFOZD models
equipped with the ADC 2100.

L0 (Neutral)
L0
Ground GRD.
L1
Load
Side

Line Single-Pole
Side Circuit
Breaker

Tape to insulate
from ground

4 1 3 2
200--220--240 Volt
Stator Leads 2 Wire

60 Hz 50 Hz
L0--L1 200-240 Volt 200--220--240 Volt

Figure 8-4 200--220--240-Volt, 2-Wire Configuration


for EOZD/EFOZD Models with
ADC 2100

TP-6711 7/09 Section 8 Reconnection/Adjustments 55


Electroswitch
2-Wire Generator Sets 3-Wire Generator Sets

L1 L1
2 1 3 4 2 1 3 4
To Generator To Shore
Set Power
L2 L2
6 5 7 8 To Generator 6 5 7 8 To Shore
Set Power
L0
10 9 11 12

To Load

To Load

Kraus Naimler/American Solenoid


(Early Rectangular Design)

2-Wire Generator Sets 3-Wire Generator Sets

L1 L1
To Generator 1 2 6 5 To Shore 1 2 6 5
Set Power
L2 L2
3 4 8 7 To Generator 3 4 8 7 To Shore
Set Power
L0
9 10 14 13

To Load

To Load

Kraus Naimler/American Solenoid


(Newer Round Design)

2-Wire Generator Sets 3-Wire Generator Sets

L1 L1
3 2 4 1 To Shore 3 2 4 1
To Generator
Set Power
L2 L2
7 6 8 5 To Generator 7 6 8 5 To Shore
Set Power
L0
11 10 12 9

To Load
To Load

TP-5399-5

Figure 8-5 Marine Manual (Ship-to-Shore) Transfer Switch

56 Section 8 Reconnection/Adjustments TP-6711 7/09


The following information illustrates the reconnection of
Kraus Naimler/American Solenoid
twelve-lead generator sets. In all cases, conform to the
4-Wire, 3-Phase Generator Sets
National Electrical Code (NEC).

L1 L1 Reconnect the stator leads of the generator set to


3 2 4 1 change output phase or voltage. Refer to the following
procedure and connection schematics. Follow all safety
L2 L2 precautions at the front of this manual and in the text
To Generator 7 6 8 5 To Shore during the reconnection procedure.
Set Power

L3 L3 NOTICE
11 10 12 9 Voltage reconnection. Affix a notice to the generator set after
reconnecting the set to a voltage different from the voltage on
the nameplate. Order voltage reconnection decal 246242
L0 L0
from an authorized service distributor/dealer.
15 14 16 13

Twelve-Lead Reconnection Procedure


L1 L2 L3 L0 1. Place the generator master switch in the OFF
To Load position.
I-940

Figure 8-6 Marine Manual (Ship-to-Shore) Transfer 2. Disconnect generator set engine starting battery,
Switch, continued negative (--) lead first.

3. Disconnect power to battery charger, if equipped.


8.2 Twelve-Lead Reconnection
4. Use Figure 8-7 to determine the generator set
The reconnection procedure details voltage voltage configuration. Note the original voltage
reconnections only. If the generator set requires and reconnect the generator set as needed.
frequency changes, adjust the governor and voltage
regulator. See the generator set service manual for
information regarding frequency adjustment.

115/230

115/230
230
EM-250000

Note: Current Transformers (CTs) are not used on all sets. CT dot or HI toward generator.

Figure 8-7 Generator Reconnection

TP-6711 7/09 Section 8 Reconnection/Adjustments 57


8.3 ADC 2100 Adjustment after 8.3.3 Setting the System Voltage and
Reconnection Frequency

The controller is factory-set for the generator set voltage Follow the instructions in Figure 8-8 to enter the
and frequency. If the generator set is reconnected to a configuration mode while the engine is not running and
different voltage and frequency, follow the procedures in select the new voltage and frequency setting. The
this section to reconfigure the controller to the new settings are shown in Figure 8-9. An X in the Display
voltage and/or frequency. Set the system voltage and column in Figure 8-8 indicates a number from 0 to 9.
frequency and then adjust the voltage, gain, and engine
Press the Select button to step through to the Save
speed.
mode as shown in Figure 8-8. Do not change any other
parameters. If any other parameters are changed
8.3.1 Configuration Mode Time Out inadvertently while navigating the controller menus,
reset them to the settings shown in Figure 8-9 and then
The controller will automatically exit the configuration save the settings. When SAVE is displayed, press the
mode without saving any changes after about up arrow to save the new settings or the down arrow to
11 seconds if no buttons are pressed. Start the discard the changes and exit the configuration mode
configuration procedure over again from the beginning if without saving.
the controller exits the configuration mode before the
settings have been saved. Pressing the Select button when SAVE is displayed
returns to the first parameter, system voltage/frequency
8.3.2 Controller Software Version (Uu).
Number

The application software for controller operation is


factory-loaded onto the Advanced Digital Control. At
times, it may be necessary to check the software version
number for troubleshooting purposes.
The controllers application software version number is
displayed on the LED screen during the key sequence to
enter the configuration mode, after the Select button has
been pressed and held for about five seconds. For
example, u3.20 will be displayed for software
version 3.20.

Note: The engine type (EC) and the engine data input
type (ED) are factory set and should only be
changed by an authorized Kohler
dealer/distributor. Incorrect settings will make
your unit non-functional.

58 Section 8 Reconnection/Adjustments TP-6711 7/09


With the generator set engine stopped, hold the Select button while moving the generator set master
switch to the RUN position. (The generator set engine will not start.)
Button Sequence Notes Display *
Hold the Select button:
To enter the configuration mode. Hold the XX.XX
select button until the display shows the
Wait 5 seconds, then press: software version number(approximately 5
seconds), and continue to hold while pressing
the up and down arrows as shown.

Press: Uu0X
To select the nominal system
or voltage/frequency according to Figure 8-9.

Press:
To step through the other parameters to the SAVE
SAVE mode. (Do not change any other
Press: parameters.)
To save changes. YES

or
To discard changes without saving. no

TP6195

* X in this display indicates a number from 0 to 9. See Figure 8-9. A bold X indicates the digit that changes during adjustment.

Figure 8-8 Setting the Nominal System Voltage and Frequency (only) after Generator Reconnection

TP-6711 7/09 Section 8 Reconnection/Adjustments 59


Volts, Engine Data Battery CANbus
Hz Market Type Inputs Voltage Comm.
Freq.
Marine Diesel Model Hz Voltage, Phases Uu* Uc Ec Ed[ Bt Cn]
230 V, 1 Ph, 2 W 2 1 (std.)
7EFOZD 50 115/230 V, 1 Ph, 3 W 6 0 1 or 12
240 V, 1 Ph, 2 W 13 3 (ops) [
8.5EFOZD
50 230/400 V, 3 Ph, 4 W, Wye 3
(3 Ph)
1 (std.)
230 V, 1 Ph, 2 W 2 0 2 or 12 or 24
9EFOZD 115/230 V, 1 Ph, 3 W 6 3 (ops) [
50
(1 Ph)
240 V, 1 Ph, 2 W 13
120/240 V, 1 Ph, 3 W 1 1 (std.)
9EOZD 60 120 V, 1 Ph, 3 W 0 0 1 or 12
120 V, 1 Ph, 2 W 0 3 (ops) [
120/240 V, 1 Ph, 3 W 1
10EOZD 120 V, 1 Ph, 3 W 0
60
(1 Ph)
120 V, 1 Ph, 2 W 0
0
120/240 V, 3 Ph, 4 W, Delta 10 (No Can),
10EOZD 127/220 V, 3 Ph, 4 W, Wye 16 1 or 6
EOZD 60
(3 Ph) (J1939),
EFOZD 220/380 V, 3 Ph, 4 W, Wye 19
7 or 9
240/416 V, 3 Ph, 4 W, Wye 20 (Smartcraft)
230 V, 1 Ph, 2 W 2 ]
11EFOZD 50 115/230 V, 1 Ph, 3 W 6
240 V, 1 Ph, 2 W 13 1 (std.)
115/230 V, 1 Ph, 3 W 6 0 2 or 12 or 24
115/230 V, 3 Ph, 4 W, Delta 14 3 (ops) [
110/190 V, 3 Ph, 4 W, Wye 17
11.5EFOZD 120/208 V, 3 Ph, 4 W, Wye 18
50
(3 Ph)
220/380 V, 3 Ph, 4 W, Wye 21
230/400 V, 3 Ph, 4 W, Wye 3
240/416 V, 3 Ph, 4 W, Wye 22
13EOZD 60 120/240 V, 1 Ph, 3 W 1
230 V, 1 Ph, 2 W 2
13EFOZD 50 115/230 V, 1 Ph, 3 W 6
240 V, 1 Ph, 2 W 13
* Use voltage/frequency parameters Uu07--Uu23 only with ADC application program version 1.20 or higher.
[ See Figure 8-10 for Ed settings with optional sender kits.
] See Figure 8-11 for Cn settings with optional digital gauges (gauges are available on selected models only).
Note: Replacement controllers from Kohler Aftermarket Parts are shipped with factory settings for the 8.5/12RES.
Note: Setting the Ec parameter automatically selects the Ed parameter for the standard data inputs for that engine.
If you change Ec, check the Ed setting.

60 Section 8 Reconnection/Adjustments TP-6711 7/09


Volts, Engine Data Battery CANbus
Hz Market Type Inputs Voltage Comm.
Freq.
Marine Diesel Model Hz Voltage, Phases Uu* Uc Ec Ed[ Bt Cn]
120/240 V, 1 Ph, 3 W 1
120/208 V, 3 Ph, 4 W, Wye 11
14EOZD 127/220 V, 3 Ph, 4 W, Wye 16
60
(3 Ph) 120/240 V, 3 Ph, 4 W, Delta 10
139/240 V, 3 Ph, 4 W, Wye 10
277/480 V, 3 Ph, 4 W, Wye 4
15EOZD 60 120/240 V, 1 Ph, 3 W 1
230 V, 1 Ph, 2 W 2
17EFOZD 115/230 V, 1 Ph, 3 W 6
50
(1 Ph)
240 V, 1 Ph, 2 W 13
115/230 V, 1 Ph, 3 W 6
115/230 V, 3 Ph, 4 W, Delta 14
110/190 V, 3 Ph, 4 W, Wye 17 0 2
17.5EFOZD 120/208 V, 3 Ph, 4 W, Wye 18
50
(3 Ph)
220/380 V, 3 Ph, 4 W, Wye 21
230/400 V, 3 Ph, 4 W, Wye 3
240/416 V, 3 Ph, 4 W, Wye 22
20EOZD
60 120/240 V, 1 Ph, 3 W 1
(1 Ph)
0
120/240 V, 1 Ph, 3 W 1 (No Can),
120/208 V, 3 Ph, 4 W, Wye 11 1 (std.) 1 or 6
EOZD
or 12 or 24 (J1939),
EFOZD 20EOZD 127/220 V, 3 Ph, 4 W, Wye 16
60 3 (ops) [ 7 or 9
(3 Ph) 120/240 V, 3 Ph, 4 W, Delta 10 (Smartcraft)
139/240 V, 3 Ph, 4 W, Wye 10 ]
277/480 V, 3 Ph, 4 W, Wye 4
230 V, 1 Ph, 2 W 2
20EFOZD 50 115/230 V, 1 Ph, 3 W 6
240 V, 1 Ph, 2 W 13
115/230 V, 1 Ph, 3 W 6
115/230 V, 3 Ph, 4 W, Delta 14
110/190 V, 3 Ph, 4 W, Wye 17
20EFOZD 120/208 V, 3 Ph, 4 W, Wye 18
50
(3 Ph)
220/380 V, 3 Ph, 4 W, Wye 21 2 w.o.
230/400 V, 3 Ph, 4 W, Wye 3 preheater
0
or 9 w/
240/416 V, 3 Ph, 4 W, Wye 22 preheater
23EOZD 60 120/240 V, 1 Ph, 3 W 1
120/240 V, 1 Ph, 3 W 1
120/208 V, 3 Ph, 4 W, Wye 11
24EOZD 127/220 V, 3 Ph, 4 W, Wye 16
60
(3 Ph) 120/240 V, 3 Ph, 4 W, Delta 10
139/240 V, 3 Ph, 4 W, Wye 10
277/480 V, 3 Ph, 4 W, Wye 4
* Use voltage/frequency parameters Uu07--Uu23 only with ADC application program version 1.20 or higher.
[ See Figure 8-10 for Ed settings with optional sender kits.
] See Figure 8-11 for Cn settings with optional digital gauges (gauges are available on selected models only).
Note: Replacement controllers from Kohler Aftermarket Parts are shipped with factory settings for the 8.5/12RES.
Note: Setting the Ec parameter automatically selects the Ed parameter for the standard data inputs for that engine.
If you change Ec, check the Ed setting.

TP-6711 7/09 Section 8 Reconnection/Adjustments 61


Volts, Engine Data Battery CANbus
Hz Market Type Inputs Voltage Comm.
Freq.
Marine Diesel Model Hz Voltage, Phases Uu* Uc Ec Ed[ Bt Cn]
230 V, 1 Ph, 2 W 2
25EFOZD 115/230 V, 1 Ph, 3 W 6
50
(1 Ph)
240 V, 1 Ph, 2 W 13
115/230 V, 1 Ph, 3 W 6
115/230 V, 3 Ph, 4 W, Delta 14
110/190 V, 3 Ph, 4 W, Wye 17
25EFOZD 120/208 V, 3 Ph, 4 W, Wye 18
50
(3 Ph)
220/380 V, 3 Ph, 4 W, Wye 21
230/400 V, 3 Ph, 4 W, Wye 3
240/416 V, 3 Ph, 4 W, Wye 22
230 V, 1 Ph, 2 W 2
28EFOZD 115/230 V, 1 Ph, 3 W 6
50
(1 Ph)
240 V, 1 Ph, 2 W 13
115/230 V, 1 Ph, 3 W 6
115/230 V, 3 Ph, 4 W, Delta 14
110/190 V, 3 Ph, 4 W, Wye 17 0
28EFOZD 120/208 V, 3 Ph, 4 W, Wye 18 (No Can),
50
(3 Ph) 1 (std.) 1 or 6
EOZD 220/380 V, 3 Ph, 4 W, Wye 21 0 7 or 12 or 24 (J1939),
EFOZD
230/400 V, 3 Ph, 4 W, Wye 3 3 (ops) [ 7 or 9
240/416 V, 3 Ph, 4 W, Wye 22 (Smartcraft)
]
28EOZD
60 120/240 V, 1 Ph, 3 W 1
(1 Ph)
120/240 V, 1 Ph, 3 W 1
120/208 V, 3 Ph, 4 W, Wye 11
28EOZD 127/220 V, 3 Ph, 4 W, Wye 16
60
(3 Ph) 120/240 V, 3 Ph, 4 W, Delta 10
139/240 V, 3 Ph, 4 W, Wye 10
277/480 V, 3 Ph, 4 W, Wye 4
32EOZD
60 120/240 V, 1 Ph, 3 W 1
(1 Ph)
120/240 V, 1 Ph, 3 W 1
120/208 V, 3 Ph, 4 W, Wye 11
32EOZD 127/220 V, 3 Ph, 4 W, Wye 16
60
(3 Ph) 120/240 V, 3 Ph, 4 W, Delta 10
139/240 V, 3 Ph, 4 W, Wye 10
277/480 V, 3 Ph, 4 W, Wye 4
* Use voltage/frequency parameters Uu07--Uu23 only with ADC application program version 1.20 or higher.
[ See Figure 8-10 for Ed settings with optional sender kits.
] See Figure 8-11 for Cn settings with optional digital gauges (gauges are available on selected models only).
Note: Replacement controllers from Kohler Aftermarket Parts are shipped with factory settings for the 8.5/12RES.
Note: Setting the Ec parameter automatically selects the Ed parameter for the standard data inputs for that engine.
If you change Ec, check the Ed setting.

Figure 8-9 Controller Parameter Settings, Marine Diesel Models

62 Section 8 Reconnection/Adjustments TP-6711 7/09


Optional Sender Kits and Ed Setting Power Modes

The installation of optional sender kits may require a Use Figure 8-11 to determine power down times.
change to the Ed (engine data inputs) setting. See
Figure 8-10 for the Ed settings with optional sender kits. With the generator set master switch in the AUTO
No Change means the installation of the kit does not position, there are three possible controller power
require a change to the Ed setting. modes:

Note: The Ec setting can affect the Ed setting. If you D 48-hour power down. If the ADC 2100
change the Ec setting, check the Ed setting and communication parameter setting is Cn00 or Cn07,
change it if necessary to match the value shown the controller will power down after 48 hours of
in the tables for your unit. inactivity. If the generator set has been started, the
controller will power down 48 hours after the
Note: Installation of an optional electronic governor kit generator set stops.
with a magnetic pickup does not require a change
to the Ed setting. D Continuous power mode. If the ADC 2100
communication parameter setting is Cn01, the
Model Sender Kit Ed controller will not power down. The controller
None 1
remains powered at all times to maintain CAN
9--32EOZD communications and allow remote start
GM32112-KA1 and -KP1 * 3
7--28EFOZD commands from the CAN gauge.
GM50552-KA1 [ No Change
* OP and WT sender kits D 1-hour power down. If the ADC 2100
[ Oil pressure sender kits communication parameter setting is Cn06 or Cn09,
] Electronic governor kit the controller will power down after 1 hour of
Figure 8-10 Ed Settings with Optional Sender Kits inactivity. In this mode, a remote start/stop switch
or the generator set master switch must be used to
activate the controller after it has powered down.
Cn Communication Parameter
ADC 2100 application code version 1.21 or higher
See Figure 8-11 for communication parameter settings. is required for the 1-hour power down option.
If your generator set is connected to a remote digital
gauge, refer to Figure 8-11 or the instruction sheet Note: After controller power down, a remote digital
provided with the gauge to determine the gauge will not have power and therefore will not
communication parameter Cn setting. be able to send a start signal to activate the
controller.

Power
Note: Kohlers 2-inch digital gauge allows wake-up of
Gauge Cn Down CAN the controller remotely.
Gauge Kit Description Setting Time Description
None Cn00 48
No CAN
Hours
GM32337-KP1 Remote Cn01 Never/
Digital Gauge None J1939
(3 inch)
Cn06 1 Hour
GM46035-KP1 Remote Cn07 48
Digital Gauge Hours
(3 inch)
Smartcraft
GM50822-KP1 Remote Cn09 1 Hour
Digital Gauge
(2 inch)

Figure 8-11 Communication Parameter Cn Settings


(optional gauges are available on
selected models only)

TP-6711 7/09 Section 8 Reconnection/Adjustments 63


8.3.4 Adjusting the Voltage, Gain, and Voltage Adjustment Procedure
Volts/Hz 1. With the generator set off, connect a digital
After setting the system voltage and frequency, check voltmeter to the output leads or an electrical outlet
the output voltage and frequency and adjust, if on the load side of the generator set. Set the meter
to measure voltage.
necessary, using the following procedures. Follow the
instructions in Figure 8-18 to adjust the voltage, gain, 2. Start the generator set by moving the generator set
volts/Hz while the engine is running. An X in the Display master switch to the RUN position.
column in Figure 8-18 indicates a number from 0 to 9.
Use the up arrow to increase a setting or the down arrow 3. Use the ADC controller to adjust the voltage
to decrease the setting. (parameter 1P) until the output voltage reaches the
desired value. See Figure 8-12.
Pressing the Select button when SAVE is displayed
returns to the first parameter, voltage adjust (1P). Approximate
Voltage Change per Step, VAC
Note: A digital multimeter that measures voltage and Measured
Voltage, VAC Coarse Adjust Fine Adjust
frequency is required for these adjustments.
85--132 5 0.5
180--251 7 0.7
8.3.5 Voltage Adjustment
Figure 8-12 Voltage Adjustment

WARNING 4. Adjust the voltage stability (gain, parameter 2P) to


minimize light flicker.

5. Readjust the voltage, if necessary.

Hazardous voltage. Moving parts. Volts per Hertz (Hz) Adjustments


Can cause severe injury or death.
The cut-in frequency is pre-set for 58 Hz (60 Hz system)
Operate the generator set only when or 48 Hz (50 Hz system). When the frequency falls
all guards and electrical enclosures below the cut-in, output voltage is reduced to relieve the
are in place.
engine. The amount of the voltage reduced is set by the
3P parameter. Monitor engine speed and output voltage
Short circuits. Hazardous voltage/current can cause as loads are applied.
severe injury or death. Short circuits can cause bodily injury
and/or equipment damage. Do not contact electrical
D If there is excessive droop in engine speed and little
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment. droop in voltage, increase the 3P value.

Grounding electrical equipment. Hazardous voltage can D If there is little engine speed droop but excessive
cause severe injury or death. Electrocution is possible voltage droop, decrease the 3P value.
whenever electricity is present. Ensure you comply with all
applicable codes and standards. Electrically ground the The amount of voltage droop is approximately 0.5% of
generator set, transfer switch, and related equipment and system voltage for each step of 3P, including each cycle
electrical circuits. Turn off the main circuit breakers of all
(Hz) below the cut-in frequency.
power sources before servicing the equipment. Never contact
electrical leads or appliances when standing in water or on wet
ground because these conditions increase the risk of Voltage Droop for Each Engine
electrocution. 3P Below Cut-in Frequency
0 0
1 0.5%
2 1.0%
3 1.5%
4 2.0%
5 2.5%
6 3.0%
7 3.5%
8 4.0%
9 4.5%
Figure 8-13 Voltage Droop Adjustments

64 Section 8 Reconnection/Adjustments TP-6711 7/09


1. Readjust the voltage stability (gain, parameter 2P),
if necessary.

2. Readjust the voltage (parameter 1P), if necessary.

3. Stop the generator set.

1
8.3.6 Frequency Adjustment
The engine speed determines the generator output
2
frequency; 60 Hz units operate at 1800 rpm and 50 Hz
units run at 1500 rpm. Adjust the engine governor to
change the output frequency using the following
procedure.

Frequency Adjustment Procedure


607146
To check the engine speed, use a frequency meter
1. Speed adjusting screw
connected to the load leads or use a hand tachometer. If 2. Locking nut
adjustment is needed, loosen the locking nut on the
Figure 8-14 Governor Adjustment
speed adjusting screw. Turn the screw clockwise to
increase the speed (and frequency). To decrease the
speed, turn the screw counterclockwise. Tighten the
locking nut when the correct setting is reached. See
Figure 8-14.

TP-6711 7/09 Section 8 Reconnection/Adjustments 65


Controller Configuration Mode (Use with Figure 8-9, Controller Parameters):

Hold the Select button: Display:


Move the generator set master switch to the RUN . 0
position. (The generator set engine will not start.)

Wait about 5 seconds until the display shows the


program version number. (The number may be 1 0 4
different than the one shown here.)

Press the down arrow key and then the up arrow


key 3 times to enter the configuration mode.
(This is the controller password.)
Uu 0 x

Now release the Select button.


Press:

To set the voltage/frequency setting see Figure 8-9. Uu 0 x


or

To step to the next parameter, unit configuration


Uc.

To set the unit configuration setting to Uc00, if


or
necessary.
Uc 0 0

To step to the next parameter, engine type Ec.

To set the engine type, if necessary.


or
E c 0 x
To step to the next parameter, advanced Ad n c
configuration mode or save mode selection.

Now either save your settings or enter the Advanced Configuration Mode to
set the engine data inputs, battery voltage, and communications.

Press:
To enter advanced configuration mode. E d 0 x
Go to Figure 8-16.
OR:
or To proceed to the save mode without
entering the advanced configuration mode. S AV E
Go to Figure 8-17.

Note: Shaded boxes show which number in the controller display changes when the up or down arrow
key is pressed. x denotes any number from 0 to 9.

Figure 8-15 Configuration Mode (system voltage/frequency, unit configuration, and engine type parameters)

66 Section 8 Reconnection/Adjustments TP-6711 7/09


Pressing the up arrow key at the Adnc display (See Figure 8-15) puts you
into the Advanced Configuration Mode.
Press:

or To set the engine data input type. E d 0 x

To enter battery voltage selection mode.

or To toggle between 12 and 24 VDC. 12-volt models B t 1 2


24-volt models B t 2 4
To enter communications selection mode.

or
To set the communications parameter. C n 0 x

To enter SAVE mode. Go to Figure 8-17.


S AV E
Note: Shaded boxes show which number in the controller display changes when the up or down arrow
key is pressed. x denotes any number from 0 to 9.
Figure 8-16 Advanced Configuration Mode (engine data input types, battery voltage, and engine
communications)

There are 3 options when the display says SAVE: S AV E


Press:
To return to the first parameter, system voltage/frequency
Uu, to check or change settings before saving. See Uu 0 x
Figure 8-15.
or

To save changes. Y E S
or
To discard changes without saving. n o

Yesor no flashes when the up or down arrow is pressed and then


the controller exits the configuration mode. The display returns to
the runtime hours.
x x x x
Note: Be sure to save your settings before exiting the configuration mode. The controller reverts to the
last saved settings when the master switch is moved to the OFF/RESET position.

* x in the runtime hours display above denotes any number from 0 to 9.

Now move the master switch to OFF/RESET.

Figure 8-17 Save Mode (after configuring generator set parameters)

TP-6711 7/09 Section 8 Reconnection/Adjustments 67


Output Voltage Adjustment Mode: Display :*
Move the generator set master switch to the RUN position. The generator set x x x x
engine starts and the controller display shows the engine runtime hours.
Hold:
Wait about 5 seconds until the display changes from runtime hours
to the program version number.
x. x x
Press the down arrow key and then the up arrow key 3 times to enter the
adjustment mode. (This is the controller password.)
1 P x x

The controller is now in the voltage coarse adjustment mode.

Press:

or
To raise or lower the voltage in large increments 1 P x x
(approximately 5--7 volts per step).

To enter fine voltage adjustment mode.


1 P x x
To raise or lower the voltage in smaller increments
or
(approximately 0.5--0.7 volts per step).

To enter coarse voltage stability (gain) adjustment mode.


2 P x x
To raise or lower the voltage stability (gain) in large
or increments.

To enter fine voltage stability (gain) adjustment mode.


2 P x x
or To raise or lower the voltage stability (gain) in smaller
increments.

To enter volts/Hz adjustment mode.


3 P 0 x
or To raise or lower the volts/Hz:
0.5% per step 00 = 0; 09 = 4.5%

* Shaded boxes show which character in the controller display changes for each adjustment. x in the
examples above denotes any number from 0 to 9. The actual values may vary from model-to-model. TP6196

Figure 8-18 Output Voltage and Frequency Adjustments

68 Section 8 Reconnection/Adjustments TP-6711 7/09


Appendix A Generator Selection and Wattage Requirements

Consider total wattage requirements (lights, motors, are DC powered by a 12-volt battery. Make sure the
appliances) when selecting a generator set or when calculated total wattage includes only lights actually on
sizing wattage usage in which available space and the generator set AC circuit.
construction limit the size of the generator set.
Air Conditioners
Motors
The starting characteristics of air conditioners vary
When figuring generator set capacity requirements for greatly; one 12,000 Btu unit has, for example, lower
loads that include electric motors, consider the high starting requirements than a 10,000 Btu unit of another
current demanded by the motors during startup. The variety. When using only one unit, there is usually no
inrush or starting current is typically 2--3 times higher starting problem, provided the lighting and appliance
than that required when the motor reaches normal load is not too high when starting the unit.
operating speed. Allow reserve for inrush demands plus
other loads which could be on the line as the electric Simultaneous starting of two air conditioning units,
motor starts. Use Figure 1 as a guide when selecting however, can present problems if the generator set
generator set capacity requirements involving motor capacity is marginal. Because of the variation in starting
loads. characteristics among air conditioners, this publication
makes no statements regarding multiple-motor starting
Motor Starting (Inrush) Running capabilities of the generator set covered. Consider
HP Watts Watts delayed starting or use of easy-starting devices on air
1/4 750 330 conditioner units whenever simultaneously starting
more than one motor.
1/3 1000 400
1/2 1500 600 See Figure 2 for typical air conditioner requirements.
3/4 2000 750 Information will vary with manufacturer.
1 3300 1100
2 4000 2000 Appliances
3 5000 3000
Generator sets often furnish AC for appliances such as
Figure 1 Motor Requirements TV, stereo, electric water heater, etc. With the exception
of the resistance-type loads such as the water heater,
Lighting requirements for appliances are usually low. Do not
overlook such loads when figuring total requirements.
To calculate lighting load, add the wattage of each Allow reserve capacity for anticipated appliance loads to
generator set-operated lamp. Note that not all of the avoid overloading a generator set.
lights or lamps are on the generator set AC circuit; some

Air Conditioner Size (Btu/Hr.)


7,000 9,000 12,000 16,000 24,000
Voltage 115 230 115 230 115 230 115 230 230
Full load amps 9.3 4.8 9.9 5.0 11.8 6.3 16.3 8.0 11.6
Rated load amps 7.7 4.0 7.0 3.5 8.9 4.8 13.0 6.2 10.2
Locked rotor amps 34.0 20.0 40.0 20.0 50.0 31.0 75.0 36.0 56.0
Starting (inrush) watts 3910 4600 4600 4600 5750 7130 8630 8280 12,900
Running watts 886 920 805 805 1020 1100 1500 1430 2350

Figure 2 Typical Marine Air Conditioner Requirements, 60 Hz

TP-6711 7/09 Appendix 69


Appendix B Abbreviations

The following list contains abbreviations that may appear in this publication.
A, amp ampere CG center of gravity fglass. fiberglass
ABDC after bottom dead center CID cubic inch displacement FHM flat head machine (screw)
AC alternating current CL centerline fl. oz. fluid ounce
A/D analog to digital cm centimeter flex. flexible
ADC analog to digital converter CMOS complementary metal oxide freq. frequency
adj. adjust, adjustment substrate (semiconductor) FS full scale
ADV advertising dimensional cogen. cogeneration ft. foot, feet
drawing Com communications (port) ft. lbs. foot pounds (torque)
AHWT anticipatory high water conn. connection ft./min. feet per minute
temperature cont. continued g gram
AISI American Iron and Steel CPVC chlorinated polyvinyl chloride ga. gauge (meters, wire size)
Institute crit. critical
ALOP anticipatory low oil pressure gal. gallon
CRT cathode ray tube gen. generator
alt. alternator CSA Canadian Standards
Al aluminum genset generator set
Association GFI ground fault interrupter
ANSI American National Standards CT current transformer
Institute Cu copper GND, ground
(formerly American Standards gov. governor
Association, ASA) cu. in. cubic inch
cw. clockwise gph gallons per hour
AO anticipatory only
CWC city water-cooled gpm gallons per minute
API American Petroleum Institute
cyl. cylinder gr. grade, gross
approx. approximate, approximately
D/A digital to analog GRD equipment ground
AR as required, as requested
DAC digital to analog converter gr. wt. gross weight
AS as supplied, as stated, as
suggested dB decibel HxWxD height by width by depth
ASE American Society of Engineers dBA decibel (A weighted) HC hex cap
ASME American Society of DC direct current HCHT high cylinder head temperature
Mechanical Engineers DCR direct current resistance HD heavy duty
assy. assembly deg., degree HET high exhaust temperature
ASTM American Society for Testing dept. department hex hexagon
Materials dia. diameter Hg mercury (element)
ATDC after top dead center DI/EO dual inlet/end outlet HH hex head
ATS automatic transfer switch DIN Deutsches Institut fur Normung HHC hex head cap
auto. automatic e. V. HP horsepower
aux. auxiliary (also Deutsche Industrie hr. hour
A/V audiovisual Normenausschuss) HS heat shrink
avg. average DIP dual inline package hsg. housing
AVR automatic voltage regulator DPDT double-pole, double-throw HVAC heating, ventilation, and air
AWG American Wire Gauge DPST double-pole, single-throw conditioning
AWM appliance wiring material DS disconnect switch HWT high water temperature
bat. battery DVR digital voltage regulator Hz hertz (cycles per second)
BBDC before bottom dead center E, emer. emergency (power source) IC integrated circuit
BC battery charger, battery EDI electronic data interchange ID inside diameter, identification
charging EFR emergency frequency relay IEC International Electrotechnical
BCA battery charging alternator e.g. for example (exempli gratia) Commission
BCI Battery Council International EG electronic governor IEEE Institute of Electrical and
BDC before dead center EGSA Electrical Generating Systems Electronics Engineers
BHP brake horsepower Association IMS improved motor starting
blk. black (paint color), block EIA Electronic Industries in. inch
(engine) Association in. H2O inches of water
blk. htr. block heater EI/EO end inlet/end outlet in. Hg inches of mercury
BMEP brake mean effective pressure EMI electromagnetic interference in. lbs. inch pounds
bps bits per second emiss. emission Inc. incorporated
br. brass eng. engine ind. industrial
BTDC before top dead center EPA Environmental Protection int. internal
Agency int./ext. internal/external
Btu British thermal unit
EPS emergency power system I/O input/output
Btu/min. British thermal units per minute
ER emergency relay IP iron pipe
C Celsius, centigrade
ES engineering special, ISO International Organization for
cal. calorie engineered special
CARB California Air Resources Board Standardization
ESD electrostatic discharge J joule
CB circuit breaker est. estimated
cc cubic centimeter JIS Japanese Industry Standard
E-Stop emergency stop k kilo (1000)
CCA cold cranking amps etc. et cetera (and so forth)
ccw. counterclockwise K kelvin
exh. exhaust kA kiloampere
CEC Canadian Electrical Code
cfh cubic feet per hour
ext. external KB kilobyte (210 bytes)
F Fahrenheit, female
cfm cubic feet per minute

70 Appendix TP-6711 7/09


kg kilogram MW megawatt rms root mean square
kg/cm2 kilograms per square mW milliwatt rnd. round
centimeter F microfarad ROM read only memory
kgm kilogram-meter N, norm. normal (power source) rot. rotate, rotating
kg/m3 kilograms per cubic meter NA not available, not applicable rpm revolutions per minute
kHz kilohertz nat. gas natural gas RS right side
kJ kilojoule NBS National Bureau of Standards RTV room temperature vulcanization
km kilometer NC normally closed SAE Society of Automotive
kOhm, k kilo-ohm NEC National Electrical Code Engineers
kPa kilopascal NEMA National Electrical scfm standard cubic feet per minute
kph kilometers per hour Manufacturers Association SCR silicon controlled rectifier
kV kilovolt NFPA National Fire Protection s, sec. second
kVA kilovolt ampere Association SI Systeme international dunites,
kVAR kilovolt ampere reactive Nm newton meter International System of Units
kW kilowatt NO normally open SI/EO side in/end out
kWh kilowatt-hour no., nos. number, numbers sil. silencer
kWm kilowatt mechanical NPS National Pipe, Straight SN serial number
L liter NPSC National Pipe, Straight-coupling SPDT single--pole, double--throw
LAN local area network NPT National Standard taper pipe SPST single--pole, single--throw
L x W x H length by width by height thread per general use spec, specs
lb. pound, pounds NPTF National Pipe, Taper-Fine specification(s)
lbm/ft3 pounds mass per cubic feet NR not required, normal relay sq. square
LCB line circuit breaker ns nanosecond sq. cm square centimeter
LCD liquid crystal display OC overcrank sq. in. square inch
ld. shd. load shed OD outside diameter SS stainless steel
LED light emitting diode OEM original equipment std. standard
manufacturer stl. steel
Lph liters per hour
OF overfrequency tach. tachometer
Lpm liters per minute
opt. option, optional TD time delay
LOP low oil pressure
OS oversize, overspeed TDC top dead center
LP liquefied petroleum OSHA Occupational Safety and Health
LPG liquefied petroleum gas TDEC time delay engine cooldown
Administration TDEN time delay emergency to
LS left side OV overvoltage normal
Lwa sound power level, A weighted oz. ounce TDES time delay engine start
LWL low water level p., pp. page, pages TDNE time delay normal to
LWT low water temperature PC personal computer emergency
m meter, milli (1/1000) PCB printed circuit board TDOE time delay off to emergency
M mega (106 when used with SI pF picofarad TDON time delay off to normal
units), male PF power factor temp. temperature
m3 cubic meter
ph., phase term. terminal
m3/min. cubic meters per minute TIF telephone influence factor
mA milliampere PHC Phillips head crimptite (screw)
PHH Phillips hex head (screw) TIR total indicator reading
man. manual tol. tolerance
max. maximum PHM pan head machine (screw)
PLC programmable logic control turbo. turbocharger
MB megabyte (220 bytes)
PMG permanent-magnet generator typ. typical (same in multiple
MCM one thousand circular mils locations)
MCCB molded-case circuit breaker pot potentiometer, potential
ppm parts per million UF underfrequency
meggar megohmmeter UHF ultrahigh frequency
MHz megahertz PROM programmable read-only
memory UL Underwriters Laboratories, Inc.
mi. mile psi pounds per square inch UNC unified coarse thread (was NC)
mil one one-thousandth of an inch pt. pint UNF unified fine thread (was NF)
min. minimum, minute PTC positive temperature coefficient univ. universal
misc. miscellaneous PTO power takeoff US undersize, underspeed
MJ megajoule PVC polyvinyl chloride UV ultraviolet, undervoltage
mJ millijoule qt. quart V volt
mm millimeter VAC volts alternating current
qty. quantity
mOhm, m VAR voltampere reactive
milliohm R replacement (emergency)
power source VDC volts direct current
MOhm, M rad. radiator, radius VFD vacuum fluorescent display
megohm
MOV metal oxide varistor RAM random access memory VGA video graphics adapter
MPa megapascal RDO relay driver output VHF very high frequency
mpg miles per gallon ref. reference W watt
mph miles per hour rem. remote WCR withstand and closing rating
MS military standard RFI radio frequency interference w/ with
m/sec. meters per second RH round head w/o without
MTBF mean time between failure RHM round head machine (screw) wt. weight
MTBO mean time between overhauls rly. relay xfmr transformer
mtg. mounting

TP-6711 7/09 Appendix 71


Appendix C Generator Set Output Ratings Procedure

Kohler Co. develops the kilowatt output rating of a Kohlerr generator set installation. Figure 1 outlines the
marine generator set based upon the calculations calculations. Figure 2 contains examples of how heat
specified in ISO 3046 and ISO 8528-1. The calculations variables affect generator set ratings.
correct for environmental variables encountered in a

Generator Output corrected = Generator Output observed x Correction Factor


Output power is expected to be within 5% of the specified rating when corrected to reference conditions.
Correction factors are determined using the following formulas:
1. For naturally aspirated compression-ignition engines (power limited by excess air):
C.F. = [1.175 (29.2 / Dry Barometer in. Hg)1 (Temperature _F + 460/537).75 -- .175]
x Alternator Efficiency Reference / Alternator Efficiency Observed
2. For turbocharged compression ignition engines:
C.F. = [1.175 (29.2 / Barometer Observed in. Hg).7 (Temperature _F + 460/537)2 -- .175]
x Alternator Efficiency Reference / Alternator Efficiency Observed
3. For turbocharged and intercooled compression ignition engines:
C.F. = [1.175 (29.2 / Barometer Observed in. Hg).7 (Temperature _F + 460/537)1.2 -- .175]
x Alternator Efficiency Reference / Alternator Efficiency Observed
Reference conditions:
Temperature: 77_F; Pressure: 29.2 in. Hg dry barometer.
Kohler sound shield increases ambient intake air approx. 12_F
Approximate derates:
Temperature: approximately 1% per 10_F (turbocharged engines have a greater derate);
Pressure (altitude): approximately 4% per 1000 ft. (1 in. Hg)

Figure 1 Generator Output

KEY

60 Hz 8.0
50 Hz 7.9
7.8
7.7
7.6
7.5
7.4
7.3
7.2
7.1
7.0
6.9
6.8
6.7
6.6
6.5
6.4
6.3
6.2
6.1
6.0
5.9
5.8
5.7
5.6
5.5
75 77 80 85 90 95 100 105 110 115 120
Temperature (_F)

Figure 2 Example: 6.5EFOZ/8EOZ kW Derates (ISO 3046/ISO 8258-1)

72 Appendix TP-6711 7/09


TP-6711 7/09 73
74 TP-6711 7/09
TP-6711 7/09 75
KOHLER CO. Kohler, Wisconsin 53044
Phone 920-565-3381, Fax 920-459-1646
For the nearest sales/service outlet in the
US and Canada, phone 1-800-544-2444
KohlerPower.com
Kohler Power Systems
Asia Pacific Headquarters
TP-6711 7/09 7 Jurong Pier Road
Singapore 619159
E 2009 by Kohler Co. All rights reserved. Phone (65)6264-6422, Fax (65)6264-6455

Você também pode gostar