1) The grid shall be buried under the waterproof layer by 0.6-0.8 mtr in the soil .
Notes :
2)
As per BS 7430:2011+A_1:2015 recommendations, the calculation for resistance to earth is done below using this
Rr () 162.9875
1)
Where :
The resistance RTOT of rods set out in a hollow square may be calculated from:
RTOT = 10.251
Rm = 10.8247
A is the actual area covered by the mesh, in square metres (m2); 650
L is the total length of strip used in the mesh, in metres (m). 234
It is important to note that the soil characteristics vary from each other from one location to another on the same site. Actual resistivity calculation should be under taken on
different locations on site in order to verify the calculation after installation of Earth Rods. Also the achieved resistance is based on assumptions of regular maintenance of the
earthing system as per the BS EN 62305 standard ensuring that the loop conductor is not broken or disconnected at any point within
the network. We hope the above is in line with the requirement and should you need any clarification, please do contact us.
Mohammad Ziad