Escolar Documentos
Profissional Documentos
Cultura Documentos
CONTENTS
Page Page
1 Functions 2 10 Disassembly of the parts 47
2 Product Specifications 5 11 Trouble-shooting guide 51
3 Dimensions 9 12 Technical Data 53
4 Refrigeration Cycle Diagram 11 13 Exploded View 56
5 Block Diagram 12 14 Replacement Parts List 57
6 Wiring Diagram 13 15 Exploded View 58
7 Operation Details 14 16 Replacement Parts List 59
8 Installation 25 17 ELECTRONIC CIRCUIT DIAGRAM 60
9 2-way, 3-way Valve 40
1 Functions
Temperature Setting(16 C to 30 C)
Operation Mode Selection Auto Operation
Medium Speed
Low Speed
Automatic Speed
2
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
Indoor Unit
Signal Receiving Sound Control Indoor fan starts running when temperature
Operation Mode
Airflow Direction Control
Heating/Cooling/Soft Dry/Auto Operation
Automatic Airflow Direction Control
Time Delay Safety Control The louver automatically swings up and down
Airflow Direction Manual Control
The unit will restart operation after 3-4
minutes after each pause. Delayed On-timer Control
For cooling or soft dry mode, the unit
Automatic Restarting Control
starts 15 minutes before the set time with
7-minutes automatic restarting at Cooling the remote controller, but for heating mode
Operation 30 minutes before the set time.
3
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
Outdoor Unit
4
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
2 Product Specifications
Unit CS-SA9CKP CU-SA9CKP5
INTAKE
5
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
6
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
INTAKE
7
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
8
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
3 Dimensions
9
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
10
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
11
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
5 Block Diagram
12
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
6 Wiring Diagram
13
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
7 Operation Details
7.1. Cooling Mode Operation
When selecting the Cooling Mode Operation, the unit will operate according to the setting by the Remote Controller and the
operation is as the following.
Time Delay Safety Control
3 min. ---- The compressor is ceased for 3 minutes to balance the pressure in the refrigeration cycle.
(Protection of compressor).
7 min. ---- The unit will automatically operate in 7 minutes even if the room temperature is not reached.
(Prevention of raising the humidity)
Anti-freezing Control
If the outdoor fan motor does not run 50 seconds after the compressor starts, the compressor will cease and restart in 3
minutes.(Time Delay Safety Control is effective.)
Anti-reversing Control
If the compressor has been continuously running for 5 minutes, and the difference of temperature between intake air and
evaporator is continuously lower than 2.5C or below for 2 minutes, the compressor is ceased for 3 minutes then restarts. (Time
Delay Protection Control is effective.)
14
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
During Cooling Mode Operation, use remote controller to select Automatic Fan Speed.
Fan speed will be at the point between "high speed" and "medium speed".
Deodorization control.
15
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
When selecting Soft Dry mode operation, the operation will be cooling untill the room temperature reaches the set temp on the
remote control, and then Soft Dry will be actived. (During Soft Dry Mode the fan of indoor unit will operate at super low speed.)
Once soft Dry mode operation is turned off, indoor fan, compressor and outdoor fan will stop for 6 minutes.
During cooling mode operation, if the compressor ceased, it will not restart within 3 minutes.
Anti-reverse Control
During Soft Dry Operation, use remote controller to select Auto Fan Speed mode.
Indoor Fan Speed is at super low.
Deodorization control.
16
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
17
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
When selecting heating mode operation, the unit will operate according to the setting by the remote controller.
If the compressor stopped by switching off,turning off by remote controller, or power off, it will not restart within 3 minutes.
When room temperature reaches the set temperature on the remote controller, compressor stops and will not restart within 4
minutes.
3 minutes after the compressor stopped, indoor fan will stop for 1 minute. Then indoor fan will resume operation with the speed
at "super low".
When temperature of indoor heat exchanger rises to 51C, outdoor fan will stop when temperature of indoor heat exchanger
falls to 49C, outdoor fan will restart.
When temperature of indoor heat exchanger rises to 65C or above, compressor stops, and will restart 4 minutes later.
If the compressor has been running for 5 minutes, but the difference of temperature between intake air and indoor heat
exchanger is continuously lower than 5C or below for 2 minutes, compressor will stop and resume operation in 4 minutes.
18
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
When selecting automatic fan mode by remote controller during heating mode operation, the fan will operate at different speed
under different conditiors according to the temperature of indoor heat exchanger.
19
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
Deice Control
When deicing operation ends, compressor will stop for 30 seconds, and 4-way valve remains at cooling mode operation for
10 seconds.
20
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
21
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
First Determination:
Second Determination:
One hour after the above determination, the unit will operate according to the table below.
22
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
23
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
When set at airflow direction auto-control with remote controller, the louver swings up and down as shown in the table below.
The louver does not swing when the indoor fan stops during operation.
When stop the unit with remote controller,the discharge vent is closed with the louver.
When temperature of indoor heat exchanger reaches 38C during heating mode operation, if temperature falls to 35C, airflow
direction will change from the lower limit to horizontal.
The left and right airflow direction louver can be adjusted manually.
When the airflow direction set button is pressed,the automatic airflow is released and the airflow direction louver moves up and
down as shown in thetable below. The louver can be stopped by releasing the button at the desired position.
When the remote controller is used to stop the operation,the discharge vent is closed with airflow direction louver.
Notes:
24
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
8 Installation
8.1. Before Installation
WARNING
Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical
shock or fire.
Use the specified cable(1.5mm2) and connect tightly for indoor/putdoor connection.
Power supply connection to a circuit breaker for the permanent connection. Use an approved 10A circuit breaker for the
permanent connection. It must be a double pole switch with a minimum 3 mm contact gap.
The unit must be earthen, or it will cause fire or electric shock.
There should not be any heat source or steam near the unit.
There should not be and obstacles blocking the air circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
Recommended installation height for indoor unit shall be at least 2.3m.
OUTDOOR UNIT
If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not
obstructed.
There should not be any animal or plant which could be affected by hot air discharged.
Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
Do not place any obstacles which may cause a short circuit of the discharged air.
If piping length is over the common length, additional refrigerant should be added as shown in the table.
25
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
26
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
2. Piping and drainage of indoor unit Pipes: Gas side............. ...... 1/2" Flaring tools set
1) Prepare of piping........P.30 Gas side............. .......3/8" Specified torque wrenches
2) Connection of piping........P.31 Liquid side............. ...1/4" 18N.m.......Liquid side piping
For the right piping........P.31 Insulated drain hose 42N.m.......Gas side piping
For the left piping........P.32 Insulation materials 55N.m.......Gas side piping
Spanner.......Half union
3. In case of Embedded Piping Pipes: Gas side............. ...... 1/2" Flaring tools set
For the embedded piping........P.34 Gas side............. .......3/8" Specified torque wrenches
Liquid side............. ...1/4" 18N.m.......Liquid side piping
Insulated drain hose 42N.m.......Gas side piping
Insulation materials 55N.m.......Gas side piping
Spanner.......Half union
4. Connecting piping and cable to the Additional drain hose Specified torque wrenches
outdoor unit (Outer diameter......1.55mm) 18N.m.......Liquid side
1) Connecting the piping to the outdoor Connecting cable 42N.m.......Gas side
unit........P.35 (5-core wire/1.5mm 2) 55N.m.......Gas side
2) Connecting the cable........P.35 Locally approved cable
5. Air purging of the piping and indoor unit Installation materials provided Hexagonal wrench
1) Air purging........P.36 Tape provided Gas leak detector
27
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
28
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
To drill a hole in the wall and install a sleeve for tube assiy
Drill a 70mm hole sloping downward toward the outside of
the wall.
Insert the sleeve for tube assiy through the hole.
Fix the bushing to the sleeve.
Extrude 15mm of the sleeve then cut.
Caution
When the wall is horrow, please be sure to use the sleeve
for tube assy to prevent dangers caused by mice biting
the connecting cable.
29
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
Fig.A
30
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
31
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
1. Route the indoor tubing with the drain hose to the hole.
Pull out the drain hose.
Exchange the hose and cap.
32
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
33
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
8.5.4. Cut and flaring the embedded 8.5.8. Install the indoor unit fixly.
piping [REFERENCE Fig.B, Fig.C]
When determining the dimensions of the piping, slide the
unit all the way to the left on the installation plate.
Refer to the section cut and flaring the piping in the
directions for the outdoor unit. (see P.30)
Fig.C
34
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
1. Align the center of the piping and sufficiently tighten the flare nut with fingers.
2. Finally tighten the flare nut with torque wrench unit the wrench click.
When tightening the flare nut with torque wrench, ensure the direction for tightening follows the arrow of the wrench.
Caution
When connecting the piping, always use a torque wrench. Other
tools may cause damage to the flare nut because of improper
force.
1. Remove the top cover from the unit by loosening the four screws.
3. Connect the locally approved cable (1.5mm2) to the terminals on the control board individually.
4. Secure the cable onto the control board with the holder (clamber).
5. Attach the control board cover and the top cover to the original position with the screws.
35
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
5. Set the both 2-way and 3-way valves to open position with the hexagonal wrench for the unit operation.
36
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
8.8. Checking the drainage and connecting the cable to indoor unit
8.8.1. Checking the drainage
1. Remove the front grille from the cabinet
When removing the front grille for maintenance purposes,
etc, carry out by the following procedures.
a. Set the vertical airflow direction louver (1) to the
horizontal position.
b. Remove the two caps on the front grille as shown in the
illustration at right, and then remove the two mounting
screws.
c. Pull the lower section of the front grille toward you to
remove the front grille.
When reinstalling the front grille, first set the vertical airflow
direction louver to the horizontal position, and then carry out
by steps 3 and 2 in that order. At this time check to sure that
the fixing tabs on the top inside edge of the front grille are
securely inserted into the respective slots.
37
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
38
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
39
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
40
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
Procedure:
1. Recheck the piping connection.
2. Open the valve stem of the 2-way valve counter-clockwise,
wait 10 seconds and then set it to close position
Be sure to use a hexagonal wrench to operate the valve 7. Mount the valves stem nuts to the 3-way and 3-way valve.
stem.
8. Check for gas leakage
3. Check for gas leakage.
At this time, especially check for the leakage from the 2-
Check the flare connections for gas leakage. way and 3-way valves stem nuts, and from the service
4. Purge the air from the system port cap.
Set the 2-way valve to the open position and remove the Caution
cap from the 3-way valves service port. If gas leakage is found in step (3) above, take the following
measure.
Using hexagonal wrench to press the valve core pin, 1. If the gas leaks stop when the piping connections are tighten
discharge for 3 seconds and then wait for 1 minute further, continue working from step (4).
Repeat this for 3 times. 2. If gas leaks does not stop when the connections are
retighten, repair the location of the leak, discharge all of the
5. Use torque wrench to tighten the service port cap to a gas through the service port, and then recharge with the
torque of 1.8kg.m (18N.m) specified amount of gas from a gas cylinder.
41
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
Procedure
1. Confirm that both 2-way and 3-way valves are set to open 6. Operate the air conditioner at the cooling cycle and stop it
positions. when the gauge indicates 2 kg/cm2G (0.1Mpa).
Remove the valve stem caps and confirm that the valve If the unit cannot be operate at the cooling mode
stems are in the open position. operation (weather is rather cool), press the pump
Be sure using a hexagonal wrench to operate the valve down, switch on the indoor unit, so that the unit can be
stems. operated.
2. Operate the unit for 10-15 minutes. 7. Immediately set 3-way valve to the closed position.
3. Stop operation and wait for 3 minutes, then connect the Do this quick so that the gauge ends up indicating 3 to
charge set to the service port of the 3-way valves. 5 kg/cm2G. (0.3 to 0.5 Mpa).
Connect the charge hose with the push pin to the 8. Disconnect the charge set, and mount the 2-way and 3-way
service port. valve stems nuts and service port cap.
4. Air purging of the charge hose Use torque wrench to tighten the service port cap to a
torque 1.8kg.m (18N.m).
Open the low-pressure valve or the charge set slightly to
air purge from the charge hose. Be sure to check for gas leakage.
5. Set the 2-way valve to the close position.
42
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
Procedure
1. Confirm that both 2-way and 3-way valves are set to the 5. Discharge the refrigerant
closed position. Open the valve on the charging cylinder and discharge
2. Connect the charge set and a charging cylinder to the the refrigerant unit the gauge indicates 3 to 5 kg/cm2G
service port of the 3-way valve. (0.3 to 0.5 Mpa).
3. Air purging 6. Disconnect the charge set and the charging cylinder, and
Open the valves on the charge set and charging set the 2-way and 3-way valves to the open position.
cylinder, purge the air by loosening the flare nut on the Be sure to use a hexagonal wrench to operate the valve
2-way valve approximately 45for 3 seconds, then close stems.
it for 1 minutes; repeat this 3 times. 7. Mount the valve stem nuts and the service port cap.
After purging the air, use a torque wrench tightenting the Be sure to use a torque wrench to tighten the service
flare nut on the 2-way valve. port cap to a torque 1.5kg.m (18N.m).
4. Check for gas leakage Be sure to check for gas leakage.
Check the flare connections for gas leakage.
43
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
(Gas leakage)
Procedure
1. Confirm that both 2-way and 3-way valves are set to the open position.
2. Connect the charge set to the service port of the 3-way valve.
Leave the valve on the charge set closed.
Connect the charge hose with the push pin to the service port.
3. Open the valves (low side) on the charge set and discharge the refrigerant until the gauge indicates 0.5-1 kg/cm2G (0.05-
0.1Mpa).
If there is no air in the refrigerant cycle [the pressure when the air conditioner is not running is higher than 1kg/cm2G
(0.1Mpa)], discharge the refrigerant until the gauge indicates 0.5 to 1 kg/cm2G (0.05 to 0.1Mpa). If this is the case, it will not
be necessary to apply a evacuation.
Discharge the refrigerant gradually, if it is discharged too suddenly, the refrigerant oil will also be discharged.
44
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
Procedure
1. Connect the vacuum pump to the charge sets centre hose.
2. Evacuation for approximately 1 hour.
Confirm that the gauge needle has moved toward-76cmHg (-0.1Mpa) [vacuum of 4 mmHg or less].
3. Close the valve (low side) on the charge set, turn off the vacuum pump, and confirm that the gauge needle dose not move
(approximately 5 minutes after turning off the vacuum pump).
4. Disconnect the charge hose from the vacuum.
Vacuum oil
If the vacuum pump oil becomes dirty or depleted, replenish as needed.
45
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
(After evacuation)
Procedure
1. Connect the charge hose to the charging cylinder
Connect the charge hose which was disconnected from This is different from previous procedures.
Because you are charging with liquid refrigerant from the gas
the vacuum pump to the valve at the bottom of the side, absolutely do not attempt to charge with large amounts of
cylinder. liquid refrigerant while operating the air conditioner.
If you are using a gas cylinder also use a scale and
reverse the cylinder so that the system can be charged 4. Immediately disconnect the charge hose from the 3-way
with liquid. valves service port.
2. Purge the air from the charge hose Stopping part-way will allow the refrigerant to be
Open the valve at the bottom of the cylinder and use a discharged.
screwdriver to press the check valve on the charge set If the system has been charged with liquid refrigerant
to purge the air. (Be careful of the liquid refrigerant.) while operating the air conditioner, turn off the air
The procedure is the same if using a gas cylinder. conditioner before disconnecting the hose.
3. Open the valve (low side) on the charge set and charge the 5. Mount the valve stem nuts and the service port.
system with liquid refrigerant. Use a torque wrench to tighten the service port cap to a
If the system cannot be charged with the specified torque of 1.8kg. m (18N.m).
amount of refrigerant, it can be charge with a little at a Be sure to check for gas leakage.
time (approximately 150g each time) while operating the
air conditioner in the cooling cycle.
However, one time is not sufficient, wait approximately
1 minute and then repeat the procedure. (Pumping
down pin)
46
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
Fig 1
Fig 2
Removal procedure for the fan motor
1. Remove the connector CN-MTR of fan motor, and
connector CN-STM of step fan motor, loosen the
grounding wire (yellow-green),and pull the sensor out
from the socket.
(See Fig 1)
Fig 3
Fig 4
47
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
Fig 5
Remove the special tab, and pull the fan motor out.
(see Fig 6, Fig 7)
Fig 6
Fig 7
48
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
Fig 8
2. Loosen the bearing on the left side of the cross flow fan.
Fig 9
Fig 10
49
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
Fig 11
Remove the back lid of the remote controller and you will find terminal two s, it is possible to select from 2 types of
transmission codes by shorting the terminals.
Fig 12
50
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
11 Trouble-shooting guide
Refrigeration cycle system
In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of compressor or fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the standard
values for them are shown in the table to the right.
51
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
Insufficient refrigerant
(gas leakage)
Heat radiation
deficiency of the
outdoor unit
Insufficient compression
Electric current during operation becomes approximately 80% lower than the normal level.
Insufficient compressing of a compressor The discharge tube of the compressor becomes abnormally hot (normally 70~90C).
The difference between high pressure and low pressure becomes almost zero.
Electric current reaches a high level abnormally, and the value exceeds the limit of an ammeter.
In some cases, a breaker turns off.
Locked compressor
The compressor has a humming sound.
Electric current during operation becomes approximately 20% lower than the normal valve.
Inefficient switches of the 4-way valves
The temperature difference between from the discharge tube to the 4-way valve and from
suction tube to the 4-way valve becomes almost zero.
52
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
12 Technical Data
Thermostat characteristics
CS-SA9CKP/CU-SA12CKP5
53
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
Operating characteristics
CS-SA9CKP/CU-SA9CKP5
CS-SA12CKP/CU-SA12CKP5
54
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
13 Exploded View
CS-SA9CKP/CS-SA12CKP
55
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
56
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
15 Exploded View
CU-SA9CKP5/CU-SA12CKP5
57
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
58
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
W
TERMIMAL
(OUTDOOR UNIT)
A C220
F 50Hz 1(L) 2(N) 3 4 TERMIMAL 4-WAY VALVE
POWER SW.
BL W R BLUE THERMO FUSE
TRANSFORMER
A40C246 (102 C)
THERMO FUSE
(99 C)
3 1
3 1 SM-3
BR AC GR HOT FM B B
CN-T 1 2 3 1 CN-FUSE
AC AC
CT1 (VH2) (XH3 .WH )
A40322
RY-C
FUSE
CR4 A59015
250V DB1
SSR2
- + 12V
I 12V O I 5V O
+ + +
G C5 G C2
C1
~ 2200* 25V 100*
~ 35V 470* 10V
SSR1
ZNR2
D
~
Q6
+ - UN421F R21
SSR2 10K
R22 D3 D1
10K MA723TA MA165TA
1
2
+ RY-HOT
C21 R23 C11 3
33* 51K 0.01* 4
16V 5
Q7
6
+ - UN421F
UN421F 7
SSR1
8
RY-M 16 1 9
C 10
11
RY-H 15 2
Q3 12
13
BEEPER/A48004 14
14 3
BZ 15
FAN MOTOR (VH-7 . W )
R17 16
CN-FM RY-H 47* R15 IC
D2 17
Y 2W
1 ERA15-01 1K 18
2 RY-M 19
BR 20
3
4 21
O R29
22
5 2.2K
RY-C 23
BL 6 +
C16 24
7 R30
35V 25
B 470* 10K
26
CR3 A59015 Q1
27
2SC1741A
28
CR2 A59015 29
30
L2
A43036 31
CR1 A59015 32
(VH3.W )
CN-C
R
1
B 2
3
C-FM
A 1.0*F
450V
1 2 3 4 5
59
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
RISISTANCE
50
1 4
40
VOLTAGE
2
CS-SA9BKP5 53.6K 3
( k*) 30
(V) 2
20 IN TAKE AIR temp.
IC1 56 pin
CS-SA12BKP5 31.6K 10
1
PIPE TEMP.
IC1 57 pin
0 0 10 20 30 40 50 60
-10 0 10 20 30 40 50 70
TEMP. ( C )
TEMP. ( C)
R : RED
BL : BLACK
CIRCUIT B : BLUE
BR : BROWN
O : ORANGE
GRY : GREY
Q2 G : GREEN
R14 UN4211
5.1K Y : YELLOW
C19
0.022* W : WHITE
C12
0.1* R19
R1 Y/G : YELLOW/GREEN
10K
5.1K
RECEIVER
5V
PH302C
1 8
0.01*
2 7
330*
3 6
fig.3 RX 137K 0.01*
J2 (KR3) 4 5
R24
CN-RCV
18.2K R20 UPC2800GR
26.1K R16 R12 3 1
IC1 J1
5.1K 1K
2 2 47*
A52D011F062 6.3V
1 3
C14 +
0.01* C7
64 + 10V CN-RCV
POWER C13 100*
63 10V (PH3)
RA1
62 100* 24Kx3
61
60
REMOTE CONTROL TEST 59
C24 4 PIPE SENSOR
58 fig.2 0.01* J3 3 (15K.3950)
57
AN MOTOR INTAKE AIR TEMP. 56 2 IN TAKE AIR SENSOR
+ + R6
55 C6 R7 C15 1 (20K.3950)
16V 20K 16V 15K
54 fig.1
10* 10* CN-TH
53 R18 X1 8MHz
(KR4. W)
LOW FAN 52 150K + - C24
HIGH FAN 51 10V R26
51 100* R13 100K R25 ZD1
BEEPER OCSILLISCOPE 1K
10K Q5 7.5EL1
50 +
GROUND POWER C4 2SC1740S R11
49
R5 10K C22 50V 11K
COMPRESSOR 48
10V 1*
CLOCK 47 100* Q4 (KR5. W) MOTOR(AIR SWING)
REMOTE CONTROL 46 R31 C3
2SC1740S CN-STM
45 6.2K 0.01*
1 1
RESET 43
4 9 13 2
42 2
5 12
STEP MOTOR 41 3 3
6 11 4
SIGNAL (OUT) 40
7 10
4
39
1K 5 5
R9 8 (KR-4)
TEST(IN) 38
IC3
37 CN-DISP
UPA2003C
TEST(OUT) 36 RA2 LED
PUMP 35 10Kx3 1 4
DISPLAY R2 330*
34 2 3 OPERATION (G)
DISPLAY R3 330*
GROUND 33 3 2 TIMER (O)
4 1
CN-DISP
C23 + (PH4)
10V INDICATOR
100*
C17 R10 R8 TEST
C18
0.01* 1K 0.01* 1K
(NH2)
SW1 SW2
AUTO SW PUMP SW CS/CU-SA9BKP5/CS/CU-SA12BKP5
6 7 8 9 10
60
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
61
CS-SA9CKP CU-SA9CKP5 / CS-SA12CKP CU-SA12CKP5
62 Printed in China